Professional Documents
Culture Documents
Description
The Forbes Marshall Compact Module Thermodynamic
Trap, CMTD42M-F, is a compact thermodynamic trap
module designed with an in built bypass valve, a trap
vent valve and a trap test valve for steam applications
upto 42 bar g. Replaceable trap internals and inbuilt
strainer eases inline maintenance. The CMTD42M-F
has an integral upstream and downstream piston valve,
which isolates the upstream piping of the steam trap.
Operating Range
425
400
Temperature ºC
300
200 Steam
saturation
100 curves
0
0 20 40 42 63
Pressure (bar g)
The product must not be used in this region
31
7
5 27
32
11 12
26
2
3 25
9 33
34
4
6 30
10
15
4
3
16 1
14
5
17
36
5 21
8 22
18
20
19
23 28
5
37 24
38 29
Material
3 DV1 Spacer ASTM A276 Gr 410 23 DV2 Bonnet ASTM A276 Gr410
4 DV1 Sealing Stack SS 304 + graphite 24 DV2 Hex Knob SG Iron 400/15 A
13* DV1 Plain Washer SS 304 33 Inner Seat Gasket SS304 + graphite
14 DV1 Stem Piston ASTM A276 Gr 316 34 Outer Seat Gasket SS304 + graphite
600 strainer screen into recess of the cap. A new gasket should
DN 15
be fitted and the cap screwed into the body. The use of a
500
thread lubricant is recommended.
400
To replace the cover studs
300 After removing old cover studs, fit new cover studs. The use
200
of a thread lock (high temperature grade) is recommended.
100
Spares List
0
1 6 11 16 21 26 31 36 41 Description Part No.
Differential pressure (bar g) Spare Isolation Valve Internals Set (Sealing
1 3,4,9
Stack, Spacer, Stem-Piston)
How to Order Spare for trap isolation valve/ trap bypass Refer
Example: 1 No. DN 15 CMTD42M-F Compact Module - 2 valve (DV1) Extractor Tool and Insertor Tool user
manual
Thermodynamic Trap - Full Version (with 3 valves), socket
weld able end connections, IBR DV1 Spare Kit ( Dome Nut, M6 Plain Washer,
3 M6 Hex Nut, Sealing stack,Spacer,Stem- 3,4,5,
Piston) 6,8,9
Installation
Ensure the following for the CMTD42M-F to operate Spare Sealing Stack for isolation valve and
correctly and remove condensate effectively. 4 trap bypass valve (Dv1) 4
1.The CMTD42M-F is installed with flow in the direction of
5 CMTD42M-F Top Cover Stud and Nut Set 30, 31
the arrow. Flow to be horizontal.
6 15NB CMTD42M-F Seat, Disc 25, 26
2.Ensure that there is sufficient access to the hand-wheel to
allow proper operation of both upstream and downstream 7 20NB CMTD42M-F Seat, Disc
25, 26
isolation valves. 8 CMTD42M-F Strainer Screen 28
3.Ensure that there is sufficient access to the strainer to 9 CMTD42M-F Top Cover and Seat Gasket 32,33,34
allow it to be cleaned periodically. 10 Trap vent valve (DV2) and trap test valve 6,8,18,
4.Allow sufficient access for the bypass valve, trap vent and (DV3) Internals Set 19,20,22
trap test valve to operate.
11 Trap vent valve (DV2) and trap test valve Refer
5.Ensure all the valves are either full opened or tightly shut, user
(DV3) Extractor and Insertor Tool manual
and never kept partially open / crack open.
After 24 hours in service the cover nuts should be checked
for tightness. Separate user manual which comes along Recommended Tightening Torques
with the product gives full details.
Description Torque (Nm)
Bypass valve, trap vent valve and trap test valve M8 Nuts (12) 10
Maintenance M6 LH (8) 0.1
Lubricate valve frequently with Molykote M30 oil or 32 A/F (29) 142-158
equivalent. Lubricate the stem piston and bonnet threading
M10x1.5 Studs (30) 20-25
of drain valves DV1. Operate the valves after lubrication.
17 A/F Nuts (19) 45-50
Opp 106th Milestone B-85, Phase II, Chakan Indl Area A-34/35, MIDC H Block
Bombay Poona Road Sawardari, Chakan, Tal. Khed Pimpri, Pune - 411 018. INDIA.
Kasarwadi, Pune - 411 034. INDIA Dist. Pune - 410 501. INDIA Tel : 91(0)20-27442020, 39851199
Forbes Marshall Tel : 91(0)20-27145595, 39858555 Tel : 91(0)2135-393400 Fax : 91(0)20-27442040
Krohne Marshall Fax : 91(0)20-27147413 CIN No.: U28996PN1985PTC037806
Forbes Marshall Arca Email : seg@forbesmarshall.com, ccmidc@forbesmarshall.com www.forbesmarshall.com
Codel International © All rights reserved. Any reproduction or distribution in part or as a whole without written permission of Forbes Marshall Pvt Ltd, its associate companies
Forbes Solar or its subsidiaries (“FM Group”) is prohibited.
Forbes Vyncke Information, designs or specifications in this document are subject to change without notice. Responsibility for suitability, selection, installation, use,
operation or maintenance of the product(s) rests solely with the purchaser and/or user. The contents of this document are presented for informational
Forbes Marshall Steam Systems purposes only. FM Group disclaims liabilities or losses that may be incurred as a consequence of the use of this information.
DOC# FMSS/0317/TIS-CMTD42M-F/R1