Actuators SQN7...
for air dampers and control valves of oil or gas burners
The SQN7... and this Data Sheet are intended for use by OEMs which integrate
the actuators in their products!
Use
The SQN7... actuators are designed for driving air and gas dampers of oil or gas burn-
ers of small to medium capacity and afford load-dependent control of the amount of
gas, oil or combustion air
• in connection with single- or 2-wire control, or 3-position controllers, or
• directly via the burner control
• Before performing any wiring changes in the connection area of the actuator, com-
pletely isolate the equipment from the mains supply (all-polar disconnection)
• Ensure protection against electric shock hazard by providing adequate protection
for the terminals and by securing the housing cover
• Check to ensure that wiring is in an orderly state
• Fall or shock can adversely affect the safety functions. Such units may not be put
into operation, even if they do not exhibit any damage
Mounting notes
• Ensure that the relevant national safety regulations are complied with
Installation notes
Commissioning notes
Service notes
Disposal notes
The actuator contains electrical and electronic components and may not be disposed of
together with household waste.
Local and currently valid legislation must be observed.
2/22
Coupling - Drive shaft can be manually disengaged from geartrain and motor
- Automatic reengagement
Geartrain - Maintenance-free
Mounting and fixing - Front of the geartrain is used as the mounting surface
- Actuator is secured via through-holes
3/22
Diagram Drive Run time Nominal Holding AS Relays Length of AC 230 V ³) AC 110 V 4) SQN7... replaces
shaft ¹) at 50 Hz 2) torque 6) torque 10) 11) housing ¹) +10 % -15 % +10 % -15 %
for 90° 50...60 Hz 50...60 Hz
8) 7)
no. no. s Nm Nm pcs. pcs. mm Type reference Type reference Type reference
2 0 4 1.5 0.7 2 2 117 SQN70.224A20 --- ---
4 0 4 1.5 0.7 2 3 117 SQN70.244A20 --- SQN30.121A2700
6 0 4 1.5 0.7 2 --- 80 SQN70.264A20 --- SQN30.101A2700
9 0 4 1.5 0.7 2 1 117 SQN70.294A20 --- SQN30.111A2700
2 0 6 1.5 0.7 2 2 117 SQN70.324A20 --- SQN30.151A2700
2 0 12 2.5 1.2 2 2 117 SQN70.424A20 --- ---
5 0 12 2.5 1.2 2 3 117 SQN70.454A20 --- ---
6 0 12 2.5 1.2 2 --- 80 SQN70.464A20 --- ---
6 3 12 2.5 1.2 4 --- 80 SQN70.464A23 --- ---
2 0 30 2.5 1.3 2 2 117 SQN70.624A20 --- ---
6 3 30 2.5 1.3 2 --- 80 SQN70.664A23 --- SQN30.401A2730
Diagram Drive Run time Nominal Holding AS Relays Length of AC 230 V ³) AC 110 V 4) SQN7... replaces
6)
shaft ¹) at 50 Hz ²) torque torque 10) 11) housing ¹) +10 % -15 % +10 % -15 %
for 90° 50...60 Hz 50...60 Hz
8) 7)
no. no. s Nm Nm pcs. pcs. mm Type reference Type reference Type reference
2 0 4 1.5 0.7 2 2 117 SQN71.224A20 --- SQN31.151A2700
6 0 4 1.5 0.7 2 --- 80 SQN71.264A20 --- SQN31.101A2700
2 0 12 2.5 1.2 2 2 117 SQN71.424A20 --- ---
6 0 30 2.5 1.3 2 --- 80 SQN71.664A20 --- SQN31.401A2700
8)
no. no. s Nm Nm pcs. pcs. Type reference Type reference
9 1 4 1.5 0.7 2 1 SQN74.294A21 ---
8)
no. no. s Nm Nm pcs. pcs. Type reference Type reference
2 1 4 1.5 0.7 2 2 SQN75.224A21 ---
2 6 4 1.5 0.7 4 2 SQN75.224A26 ---
4 1 4 1.5 0.7 2 3 SQN75.244A21 ---
4 6 4 1.5 0.7 4 3 SQN75.244A26 ---
9 1 4 1.5 0.7 2 1 SQN75.294A21 ---
9 1 4 1.5 0.7 4 1 SQN75.294A26 ---
F 1 4 1.5 0.7 4 3 SQN75.2F6A21 ---
2 1 12 2.5 1.2 2 2 SQN75.424A21 ---
2 6 23 2.5 1.2 4 2 SQN75.524A26 ---
K 1 30 2,5 1,3 2 --- SQN75.6K4A21 SQN75.6K4A11
6 3 30 2.5 1.3 4 --- SQN75.664A26 ---
9 1 30 2.5 1.3 2 1 SQN75.694A21 ---
4/22
Ordering
When ordering, please give type reference of actuator and accessories according to
«Type summary».
Following item must be ordered separately and is also supplied as a separate item:
• Adapter AGA70.3 for replacing SQN3...
Accessories
Adapter AGA70.3
5/22
6/22
7/22
Function
The synchronous motor drives the drive shaft which carries the camshaft.
Replacement of Using an adapter (refer to «Accessories»), actuators type SQN30... and SQN31... can
SQN30... / SQN31... be replaced by the SQN70... / SQN71... .
The «Type summary» contains the SQN3... that can be replaced by SQN7...actuators.
8/22
3) LOA... / LMO...
S2) BV1
LR
BV2
FS
I 100 %
BV2 M
SB IV BV2
III min.
HS N 8 4 1 5 3 2 7 6 LK
II 0%
7804d21/1001
IV Black
SQN7x.x44xxx zu II
7804d09/1101 t
t1 TSA
t4
09.04.2003
9/22
CC1N7804en
For notes on <S1...S5> refer to <Notes on connection diagrams>
10/22
2-stage operation
Nr. 9 LOA... / LMO24.../LMO44... Prepurge at low-fire position <KL> (see <S5>)
HVAC Products
LOA... / LMO...
LOA... / LMO...
SB A B C D
GP
1 2 10 8 3 7 6 4 5 11 12 R/W t1 t4
2)
GP BV1
OH Z
M BV2
R AL BV1
S2) FS
LR
I 100 %
M IV BV2
III min.
LK
II 0%
7804d012/1202
BV2
SB
Program sequence without oil preheater
HS N 8 2 1 3 4 5 7 6 1) Voltage at terminal no. 8 of the SQN7...
2) Refer to Data Sheet 7118
I 0
c1
N L LKP
NL I
IV IV
KL III S5) III
C
M
I Red zu*
I II III IV t1 TSA 7804d13/1101 t
II Blue
III Orange t4
9
7804a07/0502
IV Black * When burner is <OFF>, the air damper maintains position <KL>.
SQN7x.x94Axxx No <Damper CLOSED> position, refer to notes on connection
diagrams <S3>.
Connection diagram no. 4 LOA... / LMO... used the
same function with air damper closed when burner is <OFF>.
09.04.2003
CC1N7804en
For notes on <S1...S5> refer to <Notes on connection diagrams>
HVAC Products
2-stage or modulating operation
Nr. 2 LGB22... / LGB32... and LMG22...
FS
BV2 9
SB
I 100 %
M
HS N 4 5 1 3 2 8 6 7 IV BV2
III min.
LK
0 I II 0 %
b2
7804d03/1001
a1
N L Program sequence diagrams show 2-stage operation.
For modulating operation, refer to <S1>.
b1 a2
LKP
NL I I
A B
I Red IV IV
II Blue M
KL III III
III Orange I II III IV
2
7804a04/0502
IV Black zu II
SQN7x.x24xxx 7804d07/0901 t
t1 TSA
t4
09.04.2003
11/22
CC1N7804en
For notes on <S1...S5> refer to <Notes on connection diagrams>
12/22
HVAC Products
Siemens Building Technologies
2-stage operation
Nr. 5 LGB22... / LGB32... and LMG22...
Prepurge at nominal load position <NL>
Connection diagrams (cont’ d)
BV2
9
SB
I 100 %
M
HS N 5 4 1 3 2 8 6 7 IV BV2
III min.
LK
0 I II 0 %
b2
7804d04/1001
a1 c1
N L
LKP
NL I I
b1 a2 IV IV
KL III III
I Red C A B
II Blue M zu II
III Orange I II III IV 7804d10/0901 t
t1 TSA
IV Black 5
t4
7804a03/0502
SQN7x.x54xxx
09.04.2003
CC1N7804en
For notes on <S1...S5>, refer to <Notes on connection diagrams>
HVAC Products
2-stage operation
Nr. 4 LGB21... / LMG21...
Prepurge at low-fire position <KL> (see <S5>)
R/W
12 2 10 8 3 6 11 9 7 4 5 1 t1
* M
LP Z
FE LR
EK2
Z
GP BV1
AL M BV1
S2)
LR
BV2
R
FS
I Auf
BV2 M IV BV2
SB
III Zl/Kl
LK II Zu
HS
7804d02/1001
N 8 4 1 5 3 2 7 6
0 I
LKP
b2
NL I I
N L a1 c1
IV IV
KL III S5) III
b1 a2
zu II
t1 TSA 7804d08/1101 t
I Red B A C
M t4
II Blue
III Orange I II III IV
4
7804a02/0502
IV Black
SQN7x.x44xxx
* Required only with LGB21...
09.04.2003
13/22
CC1N7804en
For notes on <S1...S5>, refer to <Notes on connection diagrams>
14/22
2-stage or modulating operation
HVAC Products
Nr. 6 LFL... / LGK16... / LAL... / LOK16...
Prepurge at nominal load position <NL>
Z
BV1
SB S1) LR*
LR
BV1 RV*
FS
t1
I 100 %
M IV
III min.
LK*
II 0 %
7804d06/0901
S1)
BV2 * Modulating
I 0 LKP
NL I I I
N L
KL III III
zu II
7804d11/0901 t
t1 TSA
M t4
I Red I II III IV
II Blue
III Orange
6
IV Black
7804a06/0502
SQN7x.x64xxx
09.04.2003
CC1N7804en
For notes on <S1...S5>, refer to <Notes on connection diagrams>
2-stage operation
Nr. 9 LFL... / LGK16... / LAL... / LOK16...
Prepurge at nominal load position <NL>
HVAC Products
LFL... / LGK16... / LAL... / LOK16...
LFL... / LGK16... / LAL... / LOK16... A B C D
R
1 2 19 9 20 11 10 8 18 M1
BV1
LR
SB
BV2
S2) FS
LR t1
BV1
I 100 %
M
IV BV2
III min.
LK
II 0 %
7804d05/0901
BV2
LKP
NL I I
HS N 8 2 1 3 4 5 7 6 IV IV
KL III III
I 0
zu II
t1 7804d10/0901 t
N L TSA
t4
c1
C
M
I Red I II III IV
II Blue
III Orange 9
7804a05/0502
IV Black
SQN7x.x94xxx
09.04.2003
15/22
CC1N7804en
For notes on <S1...S5>, refer to <Notes on connection diagrams>
16/22
HVAC Products
3-stage operation
Nr. F LAL... / LFL...
Prepurge at stage 3
LFL... / LAL...
1 2 4 14 13 12 5 9 20 11 10 8 19 18 M1
M
M2
BV1 Z
SB W R ϑ
ST.2 ST.1 ST.1
LP
ST.1
ST.2
ϑ ST.3 BV2
ST.3
C
BV3
c
FS
BV2 BV3
t1
HS N 7 5 6 4 3 8 1 9 2
I
VI
B b1
I 0 IV
LK V
a1
N L III
7804d19/1202
0% II
b2 a2
I Red
II Blue LKP
III Orange
IV Yellow A I ST.3
M VI
V Black IV ST.2
VI Green A S4)
III ST.1 V
7804d20/1202
7804a14/0403
F
II ZU**
SQN75.2F6xxx t1 t
BV1 BV2 BV3
Diagram not possible with SQN70... / SQN71...
For notes on <S1...S5>, refer to <Notes on connection diagrams>
09.04.2003
CC1N7804en
HVAC Products
Siemens Building Technologies
Connection diagrams (cont’ d)
2-stage operation
Nr. 1 TMG740 / TMO720
Prepurge at nominal load position <NL>
B
LKP
NL I I
b a
V V
a1 A a2
IV IV IV
resp. 6°*
KL IV
III
III III III
I Red zu
7804d16e/0403
II Blue I II III IV V II II t
*
M
III Orange
b a b a
IV Orange * Cams III and IV are rigidly connected
1
V Black
7804a09/1202
SQN74.x15xxx
SQN75.x15xxx
09.04.2003
17/22
CC1N7804en
For notes on <S1...S5>, refer to <Notes on connection diagrams>
Connection diagrams (cont´d)
I II III
7804a10/1101
M
SQN7x.x03xxx
N N 1 2 3 4 5 7 6 8
I Red
II Blue
III Orange
IV Black
I II III IV
7804a11/1101
SQN7x.xK4xxx
18/22
19/22
BV1 BV2
S3) In heating systems where the air damper does not fully close in the case of burner
OFF, thermal uplift occurs in the flueways (boiler, stack), causing the boiler to cool
down rather quickly, thus giving rise to increased heat losses.
S4) If, during the program sequence, a damper position switch is approached from both
sides, it is not actuated in the same damper position, due to the switching differential.
To ensure that actuation takes place in the same position, the program sequence
makes certain the required damper position will be passed for a short period of time.
S5) The prepurge rate of the heat generation system (boiler, stack, etc.) prior to establish-
ment of the flame must be in compliance with country-specific regulations. As a general
rule, the prepurge rate with oil burners should be 3 times the volume of the heat gen-
eration system, and with gas burners, 5 times that volume. But these are only guide
values. The effective prepurge volume required depends primarily on the type of con-
struction of the heat generation system and is entirely the responsibility of the manu-
facturer of that system. If prepurging is selected for the low-fire position, the prepurge
time is to be appropriately extended (against prepurging for the nominal load) to attain
the required air volume.
• For supplementary connections on the burner controls, refer to the relevant Data Sheets
• For auxiliary switches with fine adjustment, refer to «Technical data»
• In the connection diagrams, the positions of the end and auxiliary switches I...VI in the actuator for the
working range are shown between 0° and the adjusted angular position of the cams, that is, in the start position
20/22
Dimensions in mm
SQN70... / SQN71...
R M
36 26
6 AGA70.3 24 24
M,R
16
T
16
ø 5,3
90
1 M,R
ø1
66,5
7804m01e/0502
4) > = 65
2xPg9
17 8 h9
45°
0
7
0 .05
0
25
+0,05
5 0
3)
10 h9
3
6,5
6
+0,03
0,09
25
8
+0,018
+0,05
3
3 0
-
9,5
9
25
1) Drive shafts are shown in their fully closed position (voltage present at end switch II)
Drive shaft no. is identical with the 6th character after the dot in the type reference
Example: SQN70.664A23 = drive shaft no. 3
2) Length of housing depends on the type of actuator (refer to «Type summary»)
3) Center slot: 6.3 mm deep
Hole dia. 5.1 mm: 16.5 mm deep (including depth of center slot)
4) Not part of the delivery
5) Supplied with types SQN7x.xxxRxx
R Fixing positions matched to SQN3...
(for 1-to-1 replacement by SQN70... / SQN71..., use AGA70.3)
M Through-hole 5.3 mm dia.
T Knockout hole 5.3 mm dia.
21/22
Dimensions in mm
SQN74... / SQN75...
30,5
16 Pg9 19 19,5 Pg11
M M
-0,09
R R
ø14
103,5
A 26 26
104,5
76,5
7804m02e/0402
115 65
> = 100
1)
Drive shaft version Drive shaft version Drive shaft no.
Side view Cross-section 0,05
3,5
0
90°
1
8 h9
25
1) Drive shaft shown in fully closed position (voltage present at end switch II)
A Knockout hole for lose cable entry
R Through-hole 5.3 mm dia.
Fixing positions matched to Conectron LKS 160 and Berger STA
M Pg nuts, not part of the delivery (for type reference, refer to «Technical data»)