You are on page 1of 22

7 804

ISO 9001

SQN70... / SQN71... SQN74... / SQN75...

Actuators SQN7...
for air dampers and control valves of oil or gas burners

Reversible electromotoric actuators with torques up to 2.5 Nm

• Run times: - SQN70... / SQN71... 4...30 s


- SQN74... / SQN75... 4...60 s
• Versions: - Clockwise or counterclockwise rotation
- With integrated electronic modules
- Choice of drive shafts
• With 2 end and 2...4 auxiliary switches, some with fine adjustment
• Geartrain can be disengaged
• SQN70... / SQN71... - With adapter for direct replacement of actuators
type SQN30... / SQN31...
• SQN74... / SQN75... - Drive shafts, fixing holes and cable entries are
matched to the same type of actuator supplied by
Conectron or Berger
• Versions with UL listing for use in the U.S. and Canada

The SQN7... and this Data Sheet are intended for use by OEMs which integrate
the actuators in their products!

Use

The SQN7... actuators are designed for driving air and gas dampers of oil or gas burn-
ers of small to medium capacity and afford load-dependent control of the amount of
gas, oil or combustion air
• in connection with single- or 2-wire control, or 3-position controllers, or
• directly via the burner control

CC1N7804en Siemens Building Technologies


09.04.2003 HVAC Products
Warning notes

To avoid injury to persons, damage to property or the environment, the following


warning notes should be observed!

Do not interfere with or modify the actuators!

• Before performing any wiring changes in the connection area of the actuator, com-
pletely isolate the equipment from the mains supply (all-polar disconnection)
• Ensure protection against electric shock hazard by providing adequate protection
for the terminals and by securing the housing cover
• Check to ensure that wiring is in an orderly state
• Fall or shock can adversely affect the safety functions. Such units may not be put
into operation, even if they do not exhibit any damage

Mounting notes

• Ensure that the relevant national safety regulations are complied with

Installation notes

• Installation work must be carried out by qualified staff

Commissioning notes

• Commissioning work must be carried out by qualified staff


• Prior to commissioning, ensure that wiring is in an orderly state

Norms and standards

Conformity to EEC directives


- Electromagnetic compatibility EMC (immunity) 89 / 336 EEC
- Low-voltage directive 73 / 23 EEC

Service notes

• Maintenance work must be carried out by qualified staff


• Each time a unit has been replaced, check to ensure that wiring is in an orderly
state

Disposal notes

The actuator contains electrical and electronic components and may not be disposed of
together with household waste.
Local and currently valid legislation must be observed.

2/22

Siemens Building Technologies CC1N7804en


HVAC Products 09.04.2003
Mechanical design

Housing - Made of impact-proof and heat-resistant plastic

Color: SQN70... / SQN71...: Geartrain housing dark-grey,


cover light-grey
SQN74... / SQN75...: Completely black

Drive motor - Reversible and locking-proof synchronous motor

Coupling - Drive shaft can be manually disengaged from geartrain and motor
- Automatic reengagement

Adjustment of - By means of adjustable cams


switching points - Scales beside the cams indicate the angle of the switching point
- Assignment of cams to the end and auxiliary switches is color-coded (refer to
«Connection diagrams»)
- Some of the cam switches feature fine adjustment; they can be changed with a
standard screwdriver
- The other cams can be adjusted manually or with the enclosed hook-spanner or
similar tool

Position indication - Internally:


Scale at the beginning of the camshaft on the geartrain side

Electrical connections - Screw terminals

Geartrain - Maintenance-free

Drive shaft - Made of black-finished steel


- Ready fitted to the front of the geartrain
- Different versions available

Mounting and fixing - Front of the geartrain is used as the mounting surface
- Actuator is secured via through-holes

Printed circuit boards - Made of glass-fiber reinforced epoxy resin


- Metalized through-holes

3/22

Siemens Building Technologies CC1N7804en


HVAC Products 09.04.2003
Type summary
Actuators SQN70... / counterclockwise rotation 9)

Diagram Drive Run time Nominal Holding AS Relays Length of AC 230 V ³) AC 110 V 4) SQN7... replaces
shaft ¹) at 50 Hz 2) torque 6) torque 10) 11) housing ¹) +10 % -15 % +10 % -15 %
for 90° 50...60 Hz 50...60 Hz
8) 7)
no. no. s Nm Nm pcs. pcs. mm Type reference Type reference Type reference
2 0 4 1.5 0.7 2 2 117 SQN70.224A20 --- ---
4 0 4 1.5 0.7 2 3 117 SQN70.244A20 --- SQN30.121A2700
6 0 4 1.5 0.7 2 --- 80 SQN70.264A20 --- SQN30.101A2700
9 0 4 1.5 0.7 2 1 117 SQN70.294A20 --- SQN30.111A2700
2 0 6 1.5 0.7 2 2 117 SQN70.324A20 --- SQN30.151A2700
2 0 12 2.5 1.2 2 2 117 SQN70.424A20 --- ---
5 0 12 2.5 1.2 2 3 117 SQN70.454A20 --- ---
6 0 12 2.5 1.2 2 --- 80 SQN70.464A20 --- ---
6 3 12 2.5 1.2 4 --- 80 SQN70.464A23 --- ---
2 0 30 2.5 1.3 2 2 117 SQN70.624A20 --- ---
6 3 30 2.5 1.3 2 --- 80 SQN70.664A23 --- SQN30.401A2730

Actuators SQN71... / clockwise rotation 9)

Diagram Drive Run time Nominal Holding AS Relays Length of AC 230 V ³) AC 110 V 4) SQN7... replaces
6)
shaft ¹) at 50 Hz ²) torque torque 10) 11) housing ¹) +10 % -15 % +10 % -15 %
for 90° 50...60 Hz 50...60 Hz

8) 7)
no. no. s Nm Nm pcs. pcs. mm Type reference Type reference Type reference
2 0 4 1.5 0.7 2 2 117 SQN71.224A20 --- SQN31.151A2700
6 0 4 1.5 0.7 2 --- 80 SQN71.264A20 --- SQN31.101A2700
2 0 12 2.5 1.2 2 2 117 SQN71.424A20 --- ---
6 0 30 2.5 1.3 2 --- 80 SQN71.664A20 --- SQN31.401A2700

Actuators SQN74... / counterclockwise rotation 9)

Diagram Drive Run time Nominal Holding AS Relays AC 230 V ³) AC 110 V 4)


6)
shaft ¹) at 50 Hz ²) torque torque 10) 11) +10 % -15 % +10 % -15 %
for 90° 50...60 Hz 50...60 Hz

8)
no. no. s Nm Nm pcs. pcs. Type reference Type reference
9 1 4 1.5 0.7 2 1 SQN74.294A21 ---

Actuators SQN75... / clockwise rotation 9)

Diagram Drive Run time Nominal Holding AS Relays AC 230 V ³) AC 110 V 4)


6)
shaft ¹) at 50 Hz ²) torque torque 10) 11) +10 % -15 % +10 % -15 %
for 90° 50...60 Hz 50...60 Hz

8)
no. no. s Nm Nm pcs. pcs. Type reference Type reference
2 1 4 1.5 0.7 2 2 SQN75.224A21 ---
2 6 4 1.5 0.7 4 2 SQN75.224A26 ---
4 1 4 1.5 0.7 2 3 SQN75.244A21 ---
4 6 4 1.5 0.7 4 3 SQN75.244A26 ---
9 1 4 1.5 0.7 2 1 SQN75.294A21 ---
9 1 4 1.5 0.7 4 1 SQN75.294A26 ---
F 1 4 1.5 0.7 4 3 SQN75.2F6A21 ---
2 1 12 2.5 1.2 2 2 SQN75.424A21 ---
2 6 23 2.5 1.2 4 2 SQN75.524A26 ---
K 1 30 2,5 1,3 2 --- SQN75.6K4A21 SQN75.6K4A11
6 3 30 2.5 1.3 4 --- SQN75.664A26 ---
9 1 30 2.5 1.3 2 1 SQN75.694A21 ---

4/22

Siemens Building Technologies CC1N7804en


HVAC Products 09.04.2003
Legend to ¹) Refer to «Dimensions»
«Type summary» ²) At 60 Hz, run times are about 20 % shorter
³) AC 220...240 V +10 % / -15 % possible, but in the case of undervoltage torque is reduced by about 20 %
4) AC 100...120 V +10 % / -15 % possible, but in the case of undervoltage torque is reduced by about 20 %
6) Under nominal conditions; under extreme conditions (e.g. +60 °C, AC 230 V –15 %) approx. –25 %
7) Refer to «Replacement of SQN30... / SQN31...»
8)
Actuator types in normal printing and other types are available on request
9) When facing the drive shaft and when control voltage is present at end switch I
10) Auxiliary switches (in addition to the 2 end switches)
11) Integrated relays

Ordering

When ordering, please give type reference of actuator and accessories according to
«Type summary».

Following item must be ordered separately and is also supplied as a separate item:
• Adapter AGA70.3 for replacing SQN3...

Accessories

Adapter AGA70.3

Not suited for use with SQN74... / SQN75...!

For mounting the SQN70... / SQN71... in place of the SQN3...;


fitted to the SQN70... / SQN71... with a self-tapping screw.

Screw and washer are included in the supply.

5/22

Siemens Building Technologies CC1N7804en


HVAC Products 09.04.2003
Technical data
General actuator data

Actuator Mains voltage AC 230 V –15 % +10 %


AC 110 V –15 % +10 %
Mains frequency 50...60 Hz ±6 %
Safety class
- SQN70... / SQN71... II to VDE 0631
- SQN74... / SQN75... I to VDE 0631
Drive motor synchronous motor
Power consumption 6 VA
On time 60 %, max. 3 min. continuous operation
Angular adjustment max. 160°, scale range 0...130°
Mounting position optional
Degree of protection
- All types IP 40 to DIN 40050, provided adequate
cable entries and fixing screws are used

- SQN74... / SQN75... IP 20 to DIN 40050, provided lateral


knockout hole for cable is used
Cable entry
- SQN70... / SQN71... insertable cable gland holder with thread
for 2 x Pg9, no locknut required

- SQN74... / SQN75... openings for locknut for fixing cable glands


Type of locknut
1 x Pg9 M Pg9 DIN 46320 MS
1 x Pg11 M Pg9 DIN 46320 MS

additional lateral knockout hole for lose


introduction of 2 cables with a max. dia. of
6 mm, cable strain relief to be provided by
the user (also refer to «Degree of protec-
tion»).
Pg glands and locknuts are not part of the
delivery.
Cable connections screw terminals for min. 0.5 mm² and max.
2.5 mm² cross-sectional area
Ferrules matching the dia. of the stranded wire
Direction of rotation refer to «Type summary»
Nominal and holding torque refer to «Type summary»
Run times
- SQN70... / SQN71... 4...30 s for 90°
- SQN74... / SQN75... 4...60 s for 90°
Coupling disengagement of drive shaft / geartrain
with a pin
Backlash between drive motor
and drive shaft
- As supplied ≤ 1.2° ±0.3°
- After 250,000 cycles ≤ 1.5° ±0.3°
Weight (average) approx. 500 g

6/22

Siemens Building Technologies CC1N7804en


HVAC Products 09.04.2003
Technical data (cont’ d)
End and auxiliary Number of end switches 2
switches Number of auxiliary switches
– SQN70... / SQN71... 1...2
– SQN74... / SQN75... 2...4
Actuation via camshaft, color-coded cams (refer to
«Connection diagrams»

switches with fine adjustment


- SQN70... / SQN71... : II and III
- SQN74... / SQN75... : III and IV
Breaking voltage AC 24...250 V

Perm. loading on terminals at cos ϕ = 0.9:


• Connection diagram €
– Terminals 1, 2, 3, 4 < 0.5 A
– Terminals 5, 6, 7 1 A (7 A) ¹)
• Connection diagram •
– Terminals 1, 2, 6, 7 < 0.5 A
– Terminals 3, 4 1 A (7 A) ¹)
• Connection diagram ‚
– Terminals 1, 2, 3 < 0.5 A
– Terminal 4 2 A (14 A) ¹)
– Terminal 5 2 A (14 A) ¹)
– Terminal 6 1 A (7 A) ¹)
– Terminal 7 1 A (7 A) ¹)
– Terminal 8 < 0.5 A
• Connection diagram ƒ
– Terminals 1, 2, 3, 8, 11 < 0.5 A
– Terminals 4, 5, 7, 10 1 A (7 A) ¹)
• Connection diagram „
– Terminals 1, 3 < 0.5 A
– Terminal 4 3 A (14 A) ¹)
– Terminal 5 3 A (14 A) ¹)
– Terminal 6 1 A (7 A) ¹)
– Terminal 7 1 A (7 A) ¹)
– Terminal 8 < 0.5 A
• Connection diagram …
– Terminals 1, 2, 3 < 0.5 A
– Terminal 4 2 A (14 A) ¹)
– Terminal 5 2 A (14 A) ¹)
– Terminal 6 1 A (7 A) ¹)
– Terminal 7 1 A (7 A) ¹)
– Terminal 8 < 0.5 A
• Connection diagram †
– Terminals 1, 2, 3, 4, 5 < 0.5 A
– Terminal 6 1 A (7 A) ¹)
– Terminal 7 1 A (7 A) ¹)
– Terminal 8 1 A (7 A) ¹)
• Connection diagram ‰
– Terminals 1, 2, 3, 4, 5 < 0.5 A
– Terminal 6 1 A (7 A) ¹)
– Terminal 7 1 A (7 A) ¹)
– Terminal 8 < 0.5 A
• Connection diagram F
– Terminals 2...7 < 0.5 A
– Terminals 1, 8, 9 1 A (7 A) ¹)

7/22

Siemens Building Technologies CC1N7804en


HVAC Products 09.04.2003
• Connection diagram K
– Terminals 1, 2 < 0.5 A
– Terminals 3, 4, 5, 6,7 ,8 1 A (7 A) ¹)
¹) Amperages in parentheses are permitted as short-time peak loads for max. 0.5 seconds
Adjustment of cams
- Without fine adjustment 1°
- With fine adjustment infinitely

Norms and standards Environmental conditions


Transport DIN EN 60 721-3-2
Climatic conditions class 2K2
Mechanical conditions class 2M2
Temperature range -50...+60 °C
Humidity < 95 % r.h.
Operation DIN EN 60 721-3-3
Climatic conditions class 3K5
Mechanical conditions class 3M2
Temperature range -20...+60 °C
Humidity < 95 % r.h.

Condensation, formation of ice and ingress of water are not permitted!

Function

The synchronous motor drives the drive shaft which carries the camshaft.

The camshaft actuates the end and auxiliary switches.


Using the associated cam, the switching position of each end and auxiliary switch can
be adjusted within the working range.
Some of the actuator versions are equipped with electronic modules that perform aux-
iliary functions in connection with the end and auxiliary switches or with external de-
vices, such as controllers (refer to «Connection diagrams»).
The functions and technical data of both lines of actuators SQN70... / SQN71... and
SQN74... / SQN75... are nearly identical.

Replacement of Using an adapter (refer to «Accessories»), actuators type SQN30... and SQN31... can
SQN30... / SQN31... be replaced by the SQN70... / SQN71... .

There are no mechanical modifications required.


The different terminal assignments of the 2 types of actuators must be observed, how-
ever.

The «Type summary» contains the SQN3... that can be replaced by SQN7...actuators.

The SQN30... and SQN31... listed in «Type summary»


• refer to the SQN7... AC 230 V versions.
The respective SQN3... AC 110 V versions use the same type reference as the
AC 230 V versions, with one exception: Type suffix ..A27.. is replaced by ..A17.. .
• are versions with no facility for fitting a potentiometer (refer to Data Sheet 7808)

8/22

Siemens Building Technologies CC1N7804en


HVAC Products 09.04.2003
HVAC Products
Nr. 4 LOA24.171.../LOA24.173.../LOA24.174.../LOA24.571.../LOA25.../LOA26... 2-stage operation
LOA28.../LOA36.../LMO24.../LMO44... Prepurge at low-fire position <KL> (see <S5>)
Connection diagrams

3) LOA... / LMO...

Siemens Building Technologies


LOA... / LMO... B C D
SB A
GP
1 2 10 8 3 7 6 4 5 11 12 R/W
1) 2)
QRB OH
t4
OW
OW
tw t1
GP M
OH Z
LR
R AL M BV1

S2) BV1
LR
BV2

FS

I 100 %
BV2 M
SB IV BV2
III min.
HS N 8 4 1 5 3 2 7 6 LK
II 0%
7804d21/1001

I 0 b2 1) Without oil preheater


a1 c1
2) Refer to Data Sheet 7118
N L 3) LOA... / LMO... with oil preheater:
If contakt <OW> opens during operation, there will be a
complete new start
b1 a2
LKP
NL I I
I Red B A C S4) IV IV
M
II Blue I II III IV III S5) III
KL
III Orange 4
7804a01/0502

IV Black
SQN7x.x44xxx zu II
7804d09/1101 t
t1 TSA
t4

09.04.2003
9/22

CC1N7804en
For notes on <S1...S5> refer to <Notes on connection diagrams>
10/22
2-stage operation
Nr. 9 LOA... / LMO24.../LMO44... Prepurge at low-fire position <KL> (see <S5>)

HVAC Products
LOA... / LMO...
LOA... / LMO...
SB A B C D
GP
1 2 10 8 3 7 6 4 5 11 12 R/W t1 t4
2)

Siemens Building Technologies


QRB M
OW 1) 1)
LR
Connection diagrams (cont’ d)

GP BV1
OH Z

M BV2
R AL BV1

S2) FS
LR
I 100 %
M IV BV2
III min.
LK
II 0%
7804d012/1202

BV2
SB
Program sequence without oil preheater
HS N 8 2 1 3 4 5 7 6 1) Voltage at terminal no. 8 of the SQN7...
2) Refer to Data Sheet 7118
I 0

c1
N L LKP
NL I

IV IV
KL III S5) III

C
M
I Red zu*
I II III IV t1 TSA 7804d13/1101 t
II Blue
III Orange t4
9
7804a07/0502

IV Black * When burner is <OFF>, the air damper maintains position <KL>.
SQN7x.x94Axxx No <Damper CLOSED> position, refer to notes on connection
diagrams <S3>.
Connection diagram no. 4 LOA... / LMO... used the
same function with air damper closed when burner is <OFF>.

09.04.2003
CC1N7804en
For notes on <S1...S5> refer to <Notes on connection diagrams>
HVAC Products
2-stage or modulating operation
Nr. 2 LGB22... / LGB32... and LMG22...

Siemens Building Technologies


Prepurge at nominal load position <NL>
Connection diagrams (cont’ d)

LGB 22 / 32... LGB22... / LGB32... / LMG22...


LMG 22... A B C D
GP/SB
12 2 10 8 3 11 9 5 7 4 1
R/W
6
M
tw t1
LP FE LP
Z
GP EK2 S1)
BV2
LR
R 1 2
BV1
AL M
BV1
LR

FS

BV2 9
SB
I 100 %
M
HS N 4 5 1 3 2 8 6 7 IV BV2
III min.
LK
0 I II 0 %
b2
7804d03/1001

a1
N L Program sequence diagrams show 2-stage operation.
For modulating operation, refer to <S1>.
b1 a2
LKP
NL I I
A B
I Red IV IV
II Blue M
KL III III
III Orange I II III IV
2
7804a04/0502

IV Black zu II
SQN7x.x24xxx 7804d07/0901 t
t1 TSA
t4

09.04.2003
11/22

CC1N7804en
For notes on <S1...S5> refer to <Notes on connection diagrams>
12/22

HVAC Products
Siemens Building Technologies
2-stage operation
Nr. 5 LGB22... / LGB32... and LMG22...
Prepurge at nominal load position <NL>
Connection diagrams (cont’ d)

LGB22... / LGB32... / LMG22...


LGB 22 / 32...
SB A B C D
LMG 22...
GP
12 2 10 8 3 6 11 5 9 7 4 1 R/W
M
tw t1
LP LP
Z FE
GP EK2
BV2
LR
R AL BV1
M S2)
BV1 1
LR 2
2 1
FS

BV2
9
SB
I 100 %
M
HS N 5 4 1 3 2 8 6 7 IV BV2
III min.
LK
0 I II 0 %
b2
7804d04/1001

a1 c1
N L
LKP
NL I I

b1 a2 IV IV
KL III III
I Red C A B
II Blue M zu II
III Orange I II III IV 7804d10/0901 t
t1 TSA
IV Black 5
t4
7804a03/0502

SQN7x.x54xxx

09.04.2003
CC1N7804en
For notes on <S1...S5>, refer to <Notes on connection diagrams>
HVAC Products
2-stage operation
Nr. 4 LGB21... / LMG21...
Prepurge at low-fire position <KL> (see <S5>)

Siemens Building Technologies


LGB 21...
LGB21... / LMG21... / LMG22... / LMG25...
A B C D
LMG 21... / 22... / 25... GP/SB
Connection diagrams (cont’ d)

R/W
12 2 10 8 3 6 11 9 7 4 5 1 t1

* M
LP Z
FE LR
EK2
Z
GP BV1
AL M BV1
S2)
LR
BV2
R
FS

I Auf
BV2 M IV BV2
SB
III Zl/Kl
LK II Zu
HS
7804d02/1001

N 8 4 1 5 3 2 7 6

0 I
LKP
b2
NL I I
N L a1 c1
IV IV
KL III S5) III
b1 a2
zu II
t1 TSA 7804d08/1101 t
I Red B A C
M t4
II Blue
III Orange I II III IV
4
7804a02/0502

IV Black
SQN7x.x44xxx
* Required only with LGB21...

09.04.2003
13/22

CC1N7804en
For notes on <S1...S5>, refer to <Notes on connection diagrams>
14/22
2-stage or modulating operation

HVAC Products
Nr. 6 LFL... / LGK16... / LAL... / LOK16...
Prepurge at nominal load position <NL>

LFL... / LGK16... / LAL... / LOK16...


LFL... / LGK16... / LAL... / LOK16... A B C D

Siemens Building Technologies


R
1 2 9 11 20 10 8 18 19 M1
M2
Connection diagrams (cont’ d)

Z
BV1

SB S1) LR*
LR
BV1 RV*
FS
t1
I 100 %
M IV
III min.
LK*
II 0 %
7804d06/0901

S1)
BV2 * Modulating

Program sequence diagrams show modulating operation.


HS N 1 2 3 4 5 7 6 8 For 2-stage operation, refer to <S1>

I 0 LKP
NL I I I
N L

KL III III

zu II
7804d11/0901 t
t1 TSA
M t4
I Red I II III IV
II Blue
III Orange
6
IV Black
7804a06/0502

SQN7x.x64xxx

09.04.2003
CC1N7804en
For notes on <S1...S5>, refer to <Notes on connection diagrams>
2-stage operation
Nr. 9 LFL... / LGK16... / LAL... / LOK16...
Prepurge at nominal load position <NL>

HVAC Products
LFL... / LGK16... / LAL... / LOK16...
LFL... / LGK16... / LAL... / LOK16... A B C D
R
1 2 19 9 20 11 10 8 18 M1

Siemens Building Technologies


M2
Z
Connection diagrams (cont’ d)

BV1

LR
SB
BV2
S2) FS
LR t1
BV1
I 100 %
M
IV BV2
III min.
LK
II 0 %
7804d05/0901

BV2
LKP
NL I I

HS N 8 2 1 3 4 5 7 6 IV IV
KL III III
I 0
zu II
t1 7804d10/0901 t
N L TSA
t4
c1

C
M

I Red I II III IV
II Blue
III Orange 9
7804a05/0502

IV Black
SQN7x.x94xxx

09.04.2003
15/22

CC1N7804en
For notes on <S1...S5>, refer to <Notes on connection diagrams>
16/22

HVAC Products
3-stage operation
Nr. F LAL... / LFL...
Prepurge at stage 3

LFL... / LAL...

Siemens Building Technologies


A B C D
1)
LFL... / LAL...
R
Connection diagrams (cont’ d)

1 2 4 14 13 12 5 9 20 11 10 8 19 18 M1
M
M2
BV1 Z
SB W R ϑ
ST.2 ST.1 ST.1
LP
ST.1

ST.2
ϑ ST.3 BV2

ST.3
C
BV3
c
FS
BV2 BV3
t1
HS N 7 5 6 4 3 8 1 9 2
I
VI
B b1
I 0 IV
LK V
a1
N L III
7804d19/1202

0% II

b2 a2
I Red
II Blue LKP
III Orange
IV Yellow A I ST.3
M VI
V Black IV ST.2
VI Green A S4)
III ST.1 V
7804d20/1202

ST1...3 Stage 1...3

7804a14/0403
F
II ZU**
SQN75.2F6xxx t1 t
BV1 BV2 BV3
Diagram not possible with SQN70... / SQN71...
For notes on <S1...S5>, refer to <Notes on connection diagrams>

09.04.2003
CC1N7804en
HVAC Products
Siemens Building Technologies
Connection diagrams (cont’ d)

2-stage operation
Nr. 1 TMG740 / TMO720
Prepurge at nominal load position <NL>

TMG... / TMO... are devices of other manufacture; they


TMG740 are neither made nor supplied by us.
TMO720 b / 21** The combination with our actuator proposed here
8 13 14 9 15 4 6 12 must be checked with the supplier of the TMG... /
TMO... while taking into consideration safety aspects
and the current version of the burner control.
M
The user assumes full responsibility for this
NL
application.
BV2
L2 Wiring diagram no. 1 corresponds to wiring diagram no. 3
of the SQN3...
N 7 1 6 5 2 3 4 8 Application only possible with SQN74... / SQN75...

B
LKP
NL I I
b a
V V
a1 A a2
IV IV IV
resp. 6°*

KL IV
III
III III III
I Red zu
7804d16e/0403
II Blue I II III IV V II II t
*
M
III Orange
b a b a
IV Orange * Cams III and IV are rigidly connected
1
V Black
7804a09/1202

SQN74.x15xxx
SQN75.x15xxx

** TMO720 terminal no. 6


TMG740 terminal no. 21

09.04.2003
17/22

CC1N7804en
For notes on <S1...S5>, refer to <Notes on connection diagrams>
Connection diagrams (cont´d)

Nr. € → Universal use


N 3 1 2 4 6 5 7
I Red
II Blue
III Orange

I II III

7804a10/1101
M

SQN7x.x03xxx

Nr. K → Universal use

N N 1 2 3 4 5 7 6 8
I Red
II Blue
III Orange
IV Black

I II III IV
7804a11/1101

SQN7x.xK4xxx

For notes on «S1...S5», refer to «Notes on connection diagrams»

18/22

Siemens Building Technologies CC1N7804en


HVAC Products 09.04.2003
Legend No. ‚ Number corresponds to the designation number or letter of the internal cir-
cuit of the SQN7... (second character after the dot in the type code)
AL Remote indication of fault (alarm)
BV1 Fuel valve stage 1
BV2 Fuel valve stage 2
BV3 Fuel valve stage 3
EK2 External remote reset button
FE Ionization probe
FS Flame signal amplifier
GL Air / gas ratio controller
GP Gas pressure switch
HS Main switch
KL Low-fire
L Live
LK Air damper
LKP Air damper position
LP Air pressure switch
LR Load controller (also refer to «S1»)
M Burner or fan motor
M Actuator’s drive motor
M1 Without postpurge
M2 With postpurge
N Neutral conductor
NL Nominal load
OH Oil preheater
OW Oil preheater’s readiness contact
QRB... Photoresistive flame detector
R Temperature or pressure controller
Relay
RV Controller damper
SA Actuator
Fuse
SB Safety limiter
ST... Stage
t... / T... Program time (refer to the Data Sheet of the relevant burner control)
TSA Safety time
R Resistance
Z Ignition transformer
ZU Damper fully closed
s Direction of rotation OPEN
t Direction of rotation CLOSE

Program sequence – diagrams


A Burner ON
A–B Startup of burner
B–C Burner operation / load control operation, modulating or 2-stage
C Burner OFF
C–D Overrun time
D End of program, burner control ready for new start

19/22

Siemens Building Technologies CC1N7804en


HVAC Products 09.04.2003
Notes on connection diagrams
S1) Controller for: • 2-stage operation Thermostat or similar, with changeover
contact (2-wire control).
Burner control

7804a12e/0402 In place of «BV2», it is possible to use a


control damper that is rigidly connected to
the air damper (shown in broken lines).
LR SA RV

BV1 BV2

• Modulating operation 3-position controller for OPEN / CLOSE


positioning pulses with neutral position in
Burner control between (2-wire control).
7804a13e/0402

«BV2» is not used. Air / gas ratio control is


used instead.
LR SA RV
LK This can be accomplished in the form of
• a control damper «RV» that is rigidly
GL connected to the air damper, or
BV1 • an air / gas ratio controller «GL» type
SKP70... (refer to Data Sheet 7651)
that – if combined with safety shutoff –
LR load controller for temperature or is used in place of «BV1» (shown in
pressure control broken lines)
Type RWF40...
Digital PID universal controller for
• temperature or pressure control
• 2-stage or modulating operation, and
with special functions for heat generation plant
(refer to Data Sheet 7865)

S2) Thermostat or similar with N.O. contact (single-wire control).

S3) In heating systems where the air damper does not fully close in the case of burner
OFF, thermal uplift occurs in the flueways (boiler, stack), causing the boiler to cool
down rather quickly, thus giving rise to increased heat losses.

S4) If, during the program sequence, a damper position switch is approached from both
sides, it is not actuated in the same damper position, due to the switching differential.
To ensure that actuation takes place in the same position, the program sequence
makes certain the required damper position will be passed for a short period of time.

S5) The prepurge rate of the heat generation system (boiler, stack, etc.) prior to establish-
ment of the flame must be in compliance with country-specific regulations. As a general
rule, the prepurge rate with oil burners should be 3 times the volume of the heat gen-
eration system, and with gas burners, 5 times that volume. But these are only guide
values. The effective prepurge volume required depends primarily on the type of con-
struction of the heat generation system and is entirely the responsibility of the manu-
facturer of that system. If prepurging is selected for the low-fire position, the prepurge
time is to be appropriately extended (against prepurging for the nominal load) to attain
the required air volume.
• For supplementary connections on the burner controls, refer to the relevant Data Sheets
• For auxiliary switches with fine adjustment, refer to «Technical data»
• In the connection diagrams, the positions of the end and auxiliary switches I...VI in the actuator for the
working range are shown between 0° and the adjusted angular position of the cams, that is, in the start position

20/22

Siemens Building Technologies CC1N7804en


HVAC Products 09.04.2003
Dimensions

Dimensions in mm
SQN70... / SQN71...
R M
36 26
6 AGA70.3 24 24
M,R

16
T

16
ø 5,3

90
1 M,R
ø1

66,5

7804m01e/0502
4) > = 65
2xPg9

1 x 3/8" adapter 18 22 > = 105 21


(connector) 5) 80
2)
33
for U.S. and Canada
2)
117 66

Drive shaft versions Drive shaft versions Drive shaft no.1)


Side view Cross-section

17 8 h9

45°
0

7
0 .05
0
25

+0,05
5 0

3)
10 h9

3
6,5

6
+0,03
0,09

25
8
+0,018

+0,05

3
3 0
-
9,5

9
25

1) Drive shafts are shown in their fully closed position (voltage present at end switch II)
Drive shaft no. is identical with the 6th character after the dot in the type reference
Example: SQN70.664A23 = drive shaft no. 3
2) Length of housing depends on the type of actuator (refer to «Type summary»)
3) Center slot: 6.3 mm deep
Hole dia. 5.1 mm: 16.5 mm deep (including depth of center slot)
4) Not part of the delivery
5) Supplied with types SQN7x.xxxRxx
R Fixing positions matched to SQN3...
(for 1-to-1 replacement by SQN70... / SQN71..., use AGA70.3)
M Through-hole 5.3 mm dia.
T Knockout hole 5.3 mm dia.

21/22

Siemens Building Technologies CC1N7804en


HVAC Products 09.04.2003
Dimensions (cont’ d)

Dimensions in mm

SQN74... / SQN75...
30,5
16 Pg9 19 19,5 Pg11

M M
-0,09

R R
ø14

103,5
A 26 26

104,5
76,5
7804m02e/0402

115 65

> = 100

1)
Drive shaft version Drive shaft version Drive shaft no.
Side view Cross-section 0,05

3,5
0
90°

1
8 h9
25

1) Drive shaft shown in fully closed position (voltage present at end switch II)
A Knockout hole for lose cable entry
R Through-hole 5.3 mm dia.
Fixing positions matched to Conectron LKS 160 and Berger STA
M Pg nuts, not part of the delivery (for type reference, refer to «Technical data»)

2003 Siemens Building Technologies


22/22 Subject to change!

Siemens Building Technologies CC1N7804en


HVAC Products 09.04.2003