Professional Documents
Culture Documents
net/publication/319930193
CITATIONS READS
0 759
1 author:
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
design and implementing direct torque control of induction motor using TMDSHVMTRPFCKIT dsp View project
All content following this page was uploaded by Engidaw Abel Hailu on 20 September 2017.
Abstract: In this paper, the results of the energy audit of buildings in Arba Minch Institute of Technology (AMIT) are presented. The objective of the study
was to identify the energy lossy applications, activities and traditions and to suggest the least costly energy conservation mechanisms. All functional
lighting systems, office equipment, desktop computers and water fixtures (showerheads, dishwashers, toilet flushers and hand washers) are taken into
consideration for the study. Increased energy consumption due to daytime operation of lighting systems, inactive mode operation office equipment and
desktop computers and poor water management practices were the focus of the study. Based on the audit results, poor water management practice in
the campus contributes the most to the total energy loss followed by the inactive mode energy consumption of desktop computers and daytime operation
of outdoor lighting systems. Therefore, a significant amount of energy can be saved by practicing regular maintenance of water fixtures and pipes in the
campus. Moreover, awareness creation campaign can help a lot in reducing the energy loss, which could be resulted from inactive mode energy
consumption of computers and daytime operation of lamps. Installation of electronic day light control and motion detection systems can be potentially
used to reduce the energy consumption of lighting systems operating in the daytime and in class rooms and halls both in the day and night time
respectively.
Keywords: energy auditing, lighting systems, office equipment, desktop computers, water management, energy conservation measures, awareness
creation
———————————————————
184
IJSTR©2017
www.ijstr.org
INTERNATIONAL JOURNAL OF SCIENTIFIC & TECHNOLOGY RESEARCH VOLUME 6, ISSUE 09, SEPTEMBER 2017 ISSN 2277-8616
colleges and Universities. The energy audit of the IIT- the discharge rate of water leakage from different damaged
Kanpure Hostels area was conducted [2]. They looked water fixtures (dish washer, toilet, shower heads,etc).
forward with optimism that the institute authorities, staff and
students shall ensure the maximum execution of the 2.1 Lighting system energy consumption
recommendations and the success of their work. In IIT The lifetime energy consumption of a lamp with power
Roorke an energy audit has been conducted to seek rating of P and operating for t hours of its lifetime is
opportunities to improve the energy efficiency in the calculated by the expression
campus [3]. Reduction of energy consumption while 𝐸𝐶 = [kWh]………………………….(1)
maintaining or improving human comfort, health and safety
Similarly, the energy loss of the same lamp operating for td
were of primary concern. Moreover, some daily practices
hours/day unintentionally can be calculated by:
relating common appliances have been provided which may
help reducing the energy consumption. A sincere attempt 𝐸𝐿 = [KWh/day] ………………….(2)
has been made to conduct the energy audit at Nandi If in average, n number of the same lamps are operating
Institute of Technology & Management Sciences, unnecessarily for td hours/day, and if this happens for d
Bangalore, to estimate the energy consumed in a day, week days/year, the annual total energy loss can be calculated
and month [4]. Identification of areas of energy wastage as:
and estimation of energy saving potential in the canteen, all 𝐸𝐿𝑇 = [KWh/year] ……… .(3)
departments and institute central facilities has been made
by walk-through energy audit. The steps of an electrical
2.2 Office equipment energy consumption
audit have been shown by investigating the electricity
The energy consumption of an office equipment with active
consumption at University campus [5]. The results showed
power consumption of Pa operating for ta hours/day, being
that significant electricity savings can be achieved if the
idle for ti hours/day, being in sleep mode for ts hours/day
current lighting system is replaced by an energy efficient
and shut down for tsh hours/day is:
light emitting diode (LED) type fixtures. Energy cost meter
is used to measure the standby power for various domestic 𝐸𝐶 = [kWh/day].........(4)
appliances [6]. The energy cost meter is used to determine Where Pi=the power consumption (in watts) of the
how much electricity a household product consumes. equipment when it is idle, Ps= power consumption during
Energy cost meter is a device programmed to measure 24 the sleep mode, Psh=power consumption during shut down
hours and it can also be reprogrammed to measure for 7 or mode( zero if it is unplugged)
30 days or a period by ones choice. However, no one has EC=energy consumption in kwh/day
yet considered the effect of poor water management in the The annual energy consumption of the same equipment
campuses on the energy loss and associated expenditure. working for d days/year will be
Therefore, in this study, in addition to others, the effect of 𝐸𝐶𝑌 = 𝑑 𝑥 𝐸𝐶………………………….(5)
water leakage on the energy consumption of institutes where: ECY is the energy consumption in kwh/year. Out of
having own water pumping system is considered. This the total energy consumption, the contribution of idle, sleep
study can be used as a reference in locating energy and shut down modes is taken as energy loss, which can
wastage areas in public higher institutions of Ethiopia. It is be calculated as follows:
expected to reduce energy losses and energy expenditure 𝐸𝐿𝐴 = 𝑑 𝑥 [𝐸𝐶 − ( )] ………………………….(6)
in Arba Minch Institute of Technology and bring
breakthrough in energy utilization trend. where: ELA is the annual energy loss(kWh/year) by the
office equipment due to the power consumption of the
equipment when it is not operating.
2 METHODOLOGY
Energy auditing is a complex and lengthy process that 2.3 Energy consumption of water pumps
needs to apply a lot of effort and time. To finish the auditing, In simple terms, the energy consumed by a water pump to
the researcher has accomplished the following tasks. deliver 1 million liter (ML) of water at total dynamic head
Audit preparation-selection of major electricity (TDH in meters) can be calculated by:
applications in the campus
𝑘𝑊ℎ 𝑡𝑜 𝑝𝑢𝑚𝑝 1𝑀𝐿 = ………………………….(7)
Survey and collection of data-collect data regarding the
type, location and number of energy consuming where 𝜂 is the efficiency of the pump system.
appliances and problematic water fixtures in the Therefore, the energy consumption of the pump (ECP in
campus. kWh) to pump V(in ML) liters of water by TDH (in meters) is
Data analysis-analysis of collected data to calculate the 𝐸𝐶𝑃 = 2 725 ………………………….(8)
energy losses and related expenses. In this research, the main concern is to calculate the energy
Identification of Energy conservation Measures(ECMs)- loss due to the water management problems. Therefore,
identify least costly ECMs and analyze them how they whenever water leaks unintentionally, it results not only
can contribute for energy saving for the campus water wastage but also energy wastage.
For data collection,the following tools have been used.
Power Quality Analyzer- is used to measuere the power
consumption of appliances at different conditions of the
appliance. Plastic bottles- different sizes like 1 liter, 0.5 liter,
0.25 liter and 0.125 liter plastic bottles are used to measure
185
IJSTR©2017
www.ijstr.org
INTERNATIONAL JOURNAL OF SCIENTIFIC & TECHNOLOGY RESEARCH VOLUME 6, ISSUE 09, SEPTEMBER 2017 ISSN 2277-8616
No. of lamps
loss(kWh/da
loss(kWh/da
switched on
operating in
Description
evening
the late
of lamp
Energy
Energy
y)
TABLE 5 This can be presented with the pie chart for comparison as
INACTIVE MODE ENERGY CONSUMPTION OF COMPUTERS shown on Figure 2
187
IJSTR©2017
www.ijstr.org
INTERNATIONAL JOURNAL OF SCIENTIFIC & TECHNOLOGY RESEARCH VOLUME 6, ISSUE 09, SEPTEMBER 2017 ISSN 2277-8616
4 CONCLUSIONS
In this study, effort has been applied to study the potential
energy lossy activities and traditions in buildings of Arba
Minch Institute of Technology. The audit result shows that
the water leakage contributes about 60% of the total
energy waste in the campus followed by the inactive mode
energy consumption of desktop computers. Therefore, the
campus administration has to focus on regular maintenance
of water fixtures and create awareness among the
employees and students of the institute to practice energy
conservation activities. It is also recommended to
implement technical solutions like day light control and
motion detection systems, which switch off/on the lights in
streets and classrooms when necessary.
5 ACKNOWLEDGEMENT
The study was conducted by the acknowledged support of
Arba Minch University who coversall the the expenses
related to the study. Moreover, my thanks goes to my
friends and colleagues who supported during data
collection.
REFERENCES
[1]. "Framework for Strategy Development on Energy
Efficiency in Industries, Buildings and Appliances,"
The Energy and Resource Institute, Banglore,
2014.
188
IJSTR©2017
www.ijstr.org
View publication stats