Professional Documents
Culture Documents
Underground buildings
van Dronkelaar, C.
Award date:
2013
Link to publication
Disclaimer
This document contains a student thesis (bachelor's or master's), as authored by a student at Eindhoven University of Technology. Student
theses are made available in the TU/e repository upon obtaining the required degree. The grade received is not published on the document
as presented in the repository. The required complexity or quality of research of student theses may vary by program, and the required
minimum study period may vary in duration.
General rights
Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners
and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights.
• Users may download and print one copy of any publication from the public portal for the purpose of private study or research.
• You may not further distribute the material or use it for any profit-making activity or commercial gain
Eindhoven University of Technology
Department of the Built Environment
Master’s thesis
Underground buildings
February 2013
Author: Advisors:
Chris van Dronkelaar prof. dr. ir. J.L.M. Hensen
Building Physics and Services dr. ir. D. Cóstola
R.A. Mangkuto MSc
CONTENT
I. Underground buildings - Comparative analysis using literature
Size: 15 pages
This paper summarizes the many potential benefits and drawbacks associated with underground buildings, while
discussing the effects different functions and underground building concepts have on them. Some design
strategies are identified to alleviate the negative psychological and physiological effects. The main objective of
this literature study is to perform as a fundamental basis for the practical part of the research, which involves
building performance simulation to assess the sunlight penetration and quantification of the thermal advantages
concerned with underground buildings.
Underground buildings are pointed out as an alternative to conventional aboveground buildings for reducing the
total energy requirements, while alleviating land use and location problems. This paper investigates the potential
in reducing the energy demand of underground buildings compared to aboveground buildings. Monthly
calculations based on EN-ISO 13790 are performed to obtain the annual energy demand of an aboveground
building and underground building. By comparing the annual energy demands for different climates, building
functions and underground depths, deductions can be made to quantify the energy reduction potential of
underground buildings. Introducing variable input parameters allows identification of the influence of design
options on the annual energy demand of a building. Results identify that a variety of the underground building
cases can almost be considered to be zero-energy buildings (annual energy demand below 10 kWh/m2a). In
contrast to the aboveground counterpart where the energy demand is up to 100 kWh/m 2a higher. The low annual
energy demand for these underground building cases originates from the balancing energy flows. The
transmission losses of the underground building are at a stable value annually in comparison to the aboveground
situation, where it varies with seasonal weather changes. Underground buildings can help to reduce the energy
demand in comparison to a conventional aboveground building by using beneficial soil temperatures and large
amounts of earth cover as insulation. Energy reduction is achievable for all climates and functions, but the
magnitude is related to the combination of different design elements. Sensitivity analysis shows that building
functions with high internal gains induce an inefficient balance in tropical to warm climates for underground
buildings, but strongly reduce the heating demand in cold climates. Furthermore, ground properties have a small
influence on the energy demand of an underground building.
To verify the energy reduction potential of underground buildings in the former study and to investigate the
daily patterns of the energy performance of the aboveground- and underground building, the BESTEST Case
900 is simulated using the software program TRNSYS.
ABSTRACT: This paper summarizes the many potential benefits and drawbacks associated with underground buildings,
while discussing the effects different functions and underground building concepts have on them. Some design strategies
are identified to alleviate the negative psychological and physiological effects. The main objective of this literature study is
to perform as a fundamental basis for the practical part of the research, which involves building performance simulation to
assess the sunlight penetration and quantification of the thermal advantages concerned with underground buildings.
KEYWORDS: earth scrapers, subterranean, underground, building, architecture, earth sheltered, subsurface, earth-
sheltered.
1
2.2. Submerged spaces penetrates into the earth, the more the structure will
Submerge spaces are those lying just under the benefit in terms of energy conservation [3].
surface of the ground. They can extend deep into the However, for many functions direct access to the
ground but they always have direct contact with the surface and window openings are required for a
aboveground world and with natural light. To admit variety of psychological, physiological, and safety
daylight, the surface of the ground is perforated by reasons. Energy related benefits are therefore
patios, atriums and domes. An atrium can transport constrained by the requirement for these openings,
daylight to great depths, providing not only natural as well as by the structural costs of supporting
light, but also some external views. In any event, a extensive earth loads at greater depths [3]. Some
view of the sky provides contact with the seasons, assumptions and measurements on the energy
the weather and the time of day. consumption can be found in the literature, but are
not coherent and vary in large amounts due to the
2.3. Earth-covered spaces different underground building concepts.
An earth-covered building is not underground, but
rather at grade, with a surface laid over it. This 3.1.2. Reduction of conduction
building type is free of the technical disadvantages A popular misconception about earth is that it is a
of underground building, while enjoying its spatial good insulator. However, earth is a poor insulator,
advantages. Daylight can penetrate normally and particularly when compared to commonly available
views are usually unimpaired. The elevated ground insulating materials used in building constructions.
level can be laid out as a park, landscape, or urban But even a poor insulating material can insulate
environment. In the majority of cases, earth-covered effectively if it is massive enough. The fact that heat
buildings can be constructed in the traditional loss must flow vast distances makes earth a suitable
manner. Only the roofing and cladding of one or blanket in which to wrap a building [4].
more facades is essentially different [2].
Constraints such as a high water table, expansive 3.1.3. Heat storage capacity
clay soils, rock strata, or flat rural sites have often The heat storage capacity of an underground
been overcome with an at grade concept [1]. building, due to the high thermal mass of the
structure and the surrounding earth, is another
In practice, all three types are found in all kinds of important characteristic. The thermal mass of a
combined forms as shown in Figure 1. Underground structure is a function of the density and quantity of
buildings are generally connected in one way or the building materials combined with their ability to
another with aboveground buildings, may it be for store heat. Any building with a large thermal mass
the entrance to the building or a larger part of the absorbs heat from the air or from direct solar
building that is situated aboveground, in the latter radiation and releases it back into space at night,
the underground part is generally referred to as its when there is a net heat loss. In an underground
cellars or basement [2]. building, which has a high thermal mass this process
can be slow enough to “carry” the house for several
As indicated, underground buildings have widely hours without any heating from an additional source.
varying characteristics and are therefore very In contrast, conventional dwellings can store very
dependent on the building type. Some basic little excess heat and lose whatever heat they have
assumptions about the most important characteristics relatively fast when the source is interrupted [5].
of underground buildings must therefore be made
when discussing the advantages and disadvantages. 3.1.4. Stability ground temperatures
They are discussed below, followed with a summary Due to the relatively stable temperature of the soil,
in Table 1, where a division is made between major the underground building in summer loses heat to
issues and is grouped in categories. the cool earth rather than gaining heat from the
surrounding air, and in winter the relatively warm
3. Benefits of underground building soil offers a much better temperature environment
The benefits offered by underground structures are than the subzero air temperatures [5]. Energy is
based on certain specific qualities of underground needed only to overcome the difference between the
space and the fact that they are isolated from the earth temperature and a comfortable temperature,
surface to some extent. thus flattening the peak energy requirements for
space conditioning. In essence, the earth moderates
3.1. Benefits with regard to energy use the environment in which the building is located [4].
In general, the greater the percentage of surface area The potential to save energy depends on the ground
in contact with the earth and the deeper the structure temperatures surrounding a building which is
affected not only by climate, but other factors such recreational facilities, parking, and some offices and
as ground cover, soil moisture content, and heat libraries. An overview of different functions and
from adjacent buildings [3]. The greater the depth their impact on characteristics of underground
the more stable the soil temperatures become, while buildings is given in Table 4. However if heat
peak temperatures occur after a considerable delay transfer through the exterior envelope of a building
[3]. Insulation, which separates the interior space is not large relative to ventilation and internal heat
from the earth, reduces the cooling effect, but also gains, it may still represent a substantial amount of
the effective release of heat to the ground. energy [3]. In addition, as ventilation and lighting
systems become more energy efficient, the relative
3.1.5. Control on air infiltration importance of energy transfer through the exterior
Another factor in saving energy through earth skin will increase.
sheltering is the reduction of infiltrated outside air. Not only the number of people in a space but also
With the earth covering most of the envelope of a the patterns or timing of that occupancy, affect
building, the building can be made more airtight. In energy usage. Some buildings must be operated 100
surface structures, up to 35% of heat loss can often percent of the time, whereas others have sporadic or
be attributed to air infiltration [4], while for building intermittent use.
surfaces in contact with the earth, infiltration is
completely eliminated resulting in both heating and 3.2. Benefits with regards to land use and
cooling load reduction. However, too "tight" location
construction can cause the build-up of indoor air In many cases, underground spaces result from a
pollutants, which some experts say can be far lack of surface space or location problems, several
unhealthier than the worst outdoor urban smog. An benefits are mentioned.
underground building offers greater opportunity to
3.1.1. Limited visual impact
control the rate of outside air supply to the interior
of a building [4]. Partially or completely underground buildings are
less visible than above-grade buildings, which can
3.1.6. Reduction of heat gain be an advantage in a number of situations. For
Earth-covered roofs and walls reduce radiant heat example an underground building can preserve the
gain from the sun. The massive earth can absorb a character of sensitive sites with natural beauty,
considerable amount of radiation before it reaches where man-made structures may be undesirable. Or
the envelope. While window area of most in a similar way, an underground building is often an
underground buildings is minimized by design, a appropriate solution for an area with a special
major source of heat gain in many aboveground historical character where an above ground
buildings is reduced considerably [3]. Another very contemporary building would be disruptive [3].
important component in reducing heat gain from Many other buildings are unwanted above ground
radiation is the use of plant materials. In the process due to their physical appearance and therefore are
of evapotranspiration, plants can effectively cancel necessarily placed underground, for example; public
out most of the incoming radiation from the sun. utilities, storage of less-desirable materials and car
This requires a sufficient level of moisture in the parks.
ground to enable the plants to grow [3].
3.1.2. Preservation of surface space
3.1.7. Impact of occupancy patterns on By placing a building underground and by allowing
energy related benefits the roof to remain as a park or plaza area, no open
Many of the energy related benefits are associated space is lost. This is very beneficial for compact
with heat transfer through the exterior skin of the building areas with limited remaining open space.
building. The relative importance of the exterior Not only is this space desirable for recreation, but it
envelope of the building in terms of heating and can also relieve the feeling of density and allow
cooling loads depends on the occupancy patterns and greater access to sunlight and view for above ground
use of the structure. For functions with a relatively buildings [3].
high number of people, ventilation requirements are
3.1.3. Efficient use of scarce land
greater and usually internal heat gain from lights,
people, and machines are increased as well. Thus, The use of underground space allows a building to
the functions that can benefit to the greatest extent be built in a location where this is not possible on
by being underground are those with low to the surface, either because of lack of space or
moderate occupancy levels. These include because it is not acceptable to the community.
warehouses, cold storage, archives, laboratories, Extensive amounts of space can be created without
3
requiring additional land, while unique and efficient 3.1.7. Protection from surface noise and
functional relationships could be developed, such as vibration
housing on the surface with workplaces in the mined Small amounts of earth cover are very effective at
space below, or commercial uses on the surface with protecting from the transmission of airborne noise.
manufacturing, storage, and service below. Such Similarly, if the vibration sources are at or near the
relationships can create compact, efficient ground surface, levels of vibration will diminish
development patterns within urban areas while rapidly with depth below ground and distance of the
preserving agricultural and recreational land by source [7]. This could be desirable for two reasons.
reversing the trend toward sprawling development First the function to be enclosed may require quiet
[3]. and isolation from the surrounding environment.
Where a second reason is that the function itself
3.1.4. Topographic reasons
creates undesirable noise and the outside
In hilly or mountainous areas, the use of tunnels environment would benefit from any reduction in the
improves or makes feasible various transport options noise. Manufacturing facilities or transit systems are
such as roads, railways, canals, etc. Tunnels are also examples of such undesirable functions [3].
an important option in river, streets and harbor
crossings. Generally speaking, underground space 3.1.8. Provide security
use offers many advantages with regard to the layout Because of its isolation from the surface substantial
of facilities and infrastructures. These advantages fireproof construction, and limited points of access,
derive essentially from the freedom (within underground space can be considered more secure
geological, cost, and land ownership limitations) to than above ground buildings. With limited points of
plan a facility in three dimensions and from the entry, surveillance is easier, resulting in fewer break-
removal of physical barriers on the land [6]. ins. This is a particularly appealing feature for the
storage of important records, manuscripts or critical
3.1.5. Preservation of natural
materials such as emergency food and fuel supplies
vegetation/scenery [3].
A well designed earth sheltered building can blend
with the surrounding earth and become part of the 3.1.9. Protection from natural disasters
natural landscape. In addition to the positive Underground structures are naturally protected from
aesthetic effect on the environment, underground severe weather (hurricanes, tornadoes,
buildings provide the opportunity to improve or thunderstorms, and other natural phenomena).
enhance the natural environment, particularly in Underground structures can also resist structural
urban areas [3]. Another benefit is the revitalization damage due to floodwaters, although special
of the natural landscape that results simply from the isolation provisions are necessary to prevent
increase in the amount of plant and animal habitat in flooding of the structure itself [7]. Moreover,
a given area. Water and air quality are enhanced and underground structures have several intrinsic
the soil is enriched by allowing the natural advantages in resisting earthquake motions; they are
ecological processes to occur within the boundaries less affected by the surface seismic waves. The
of a built environment [3]. structural oscillation effects are limited, since they
are constrained to move with the ground motion.
3.1.6. Fire protection Besides, as they are designed to support important
Underground structures are mostly built of concrete ground loads, they often can better resist earthquake
surrounded by soil or, in the case of mined space, loadings [7].
rock caverns. These fireproof materials provide a
great degree of fire protection and prevent the spread 3.1.10. Protection from cold or hot climates
of any fires to or from other buildings [3]. In spite of Although advantages can be achieved for reducing
the fireproof nature of underground buildings, the energy demand when building underground,
materials within the buildings may still be people may also benefit largely from the fact that do
combustible. Since these structures often have fewer not have to endure extremely high or cold
openings to the surface and the path of exit for temperatures during the day and night, when
occupants is upward rather than downward, some infrastructure and other facilities are also being
unique life safety problems may arise. Careful provided for underground.
design and consultation with building code
authorities is necessary [3].
3.3. Benefits with regards to Life Cycle Costs
7
Table 1: Benefits and drawbacks of underground facilities (adjusted from [15]).
ISSUES CATEGORY POTENTIAL BENEFITS POTENTIAL DRAWBACKS
Relief from severe climate (coolness in Lack of spatial orientation
hot-climates) Negative psychological reactions
PSYCHOLOGICAL &
PSYCHOLOGICAL
claustrophobia, fear of
collapse/entrapment
Lack of public acceptance
Isolation from surface noise and Excessive noise or lack of noise
vibration Lack of fresh air/indoor air pollution
Stable indoor temperatures High humidity/condensation
PHYSIOLOGICAL
Lack of natural daylight and view
Higher radon concentration
Requirement for openings
Reduction conduction Impact ventilation rate
ENERGY
6. Functions
6.1. Living
Underground functions are becoming increasingly
“Habitation is the most difficult function to place
diversified. Spaces for working, shopping, leisure
underground. Contact with the upper world, with
and even living are appearing alongside traditional
light and air is so important that rules concerning
storage and transport functions. The demands made
such aspects are generally specified legally. With a
on the space vary for each individual function,
little ingenuity, submerged buildings are able to
whereby the length of time spent underground plays
comply with such regulations. Underground homes
an important role.
are introverted by definition, and are comparable
with patio homes, which appeal only to a limited
group of consumers. There are more points of
contact with earth-covered homes. The relationship Certain parts of a housing program, such as storage
with the outside world and the quality of life are space, garages and sanitary rooms, can be built
entirely comparable with the accepted manner of underground without much difficulty” [2].
house building, even where views are concerned.
Table 2: Comparison of different underground building concepts and their effect on several benefits and drawbacks.
LEVEL OF IMPACT* BENEFITS DRAWBACKS
REFERENCE
LOW LOW
Provide security
Water leakage
Building type
Visual impact
Maintenance
Above grade
"True" Underground
At grade
Atrium or Courtyard
Berm Elevational
Side Penetrations
"Non-earth" roof
"True" Underground
Below grade
Atrium or Courtyard
Hillside Elevational
Side Penetrations
"Non-earth" roof
*Level of impact scaled from high to low with reference to an conventional above grade building.
Public visibility
Residential Dwelling
Hotel
Industrial Manufacturing
Laboratory
Commercial Office
Restaurant
Shopping mall
Educational Classroom
Library
Medical Hospital room
Operating theatre
Religious Religious building
Leisure Swimming pool
Theatre
Cinema
Disco
Storage Wine cellar
Bank vault
Oil storage
Military Fallout shelter
Prison
Utility Pedestrian transport
Goods transport
Waste water pipes
Agriculture Mushroom growing
Plant nursery
*Major requirement in most or all cases / Only applies in some cases or to a moderate degree / No requirement.
**Rating primarily based on [3].
13
14 C. van Dronkelaar / Underground Building (2012) – Eindhoven University of Technology
ABSTRACT: Underground buildings are pointed out as an alternative to conventional aboveground buildings for reducing
the total energy requirements, while alleviating land use and location problems. This paper investigates the potential in
reducing the energy demand of underground buildings compared to aboveground buildings. Monthly calculations based on
EN-ISO 13790 are performed to obtain the annual energy demand of an aboveground building and underground building.
By comparing the annual energy demands for different climates, building functions and underground depths, deductions
can be made to quantify the energy reduction potential of underground buildings. Introducing variable input parameters
allows identification of the influence of design options on the annual energy demand of a building. Results identify that a
variety of the underground building cases can almost be considered to be zero-energy buildings (annual energy demand
below 10 kWh/m2 a). In contrast to the aboveground counterpart where the energy demand is up to 100 kWh/m 2a higher.
The low annual energy demand for these underground building cases originates from the balancing energy flows. The
transmission losses of the underground building are at a stable value annually in comparison to the aboveground situation,
where it varies with seasonal weather changes. Underground buildings can help to reduce the energy demand in comparison
to a conventional aboveground building by using beneficial soil temperatures and large amounts of earth cover as
insulation. Energy reduction is achievable for all climates and functions, but the magnitude is related to the combination of
different design elements. Sensitivity analysis shows that building functions with high internal gains induce an inefficient
balance in tropical to warm climates for underground buildings, but strongly reduce the heating demand in cold climates.
Furthermore, ground properties have a small influence on the energy demand of an underground building.
KEYWORDS: underground buildings, energy balance, energy conservation, Monte Carlo analysis, sensitivity analysis.
1. INTRODUCTION
Pressing problems that mankind is currently faced with, are the energy crisis and increasing demand for
buildings caused by the continuous growth in the world’s population [1] [2] [3] [4]. Solutions such as building
underground are pointed out as an alternative to conventional aboveground buildings for reducing the total
energy requirements, while alleviating land use and location problems [5] [6] [7] [8]. Although research is done
on various aspects of underground building heat transfer [2], [9], [10], no study has been found that investigates
the relationship between different design elements of an underground building and its regional climate, which
determine its energy performance. A comparative analysis is needed to quantify the difference in the annual
energy demand between an aboveground building and underground building [11]. This study incorporates such
an analysis by including different climates, functions and depths to assess the energy reduction potential of
underground buildings. By applying variable input parameters the influence of design options on the annual
energy demand of a building can be investigated.
This paper presents results of a comparative study on the annual energy demand of an underground- and
aboveground building. The scope of the study includes 15 different climates, 6 building functions and 3
underground depths and the annual energy demand is calculated using 11 variable building input parameters.
2. METHODOLOGY
The building’s energy need for space heating and -cooling is calculated using the monthly method described in
EN-ISO 13790 [12]. The procedure for the investigation is visualized and described in a flowchart (Figure 1)
and follows three steps; pre-processing, calculation and post-processing. In the pre-processing stage, the
building functions, weather data and variable input parameters are defined. The variable input parameters are
obtained from literature and are processed into samples using Latin hypercube sampling (LHS). In the
calculation stage, the annual energy demand for the aboveground- and underground building is calculated with
200 different combinations of input variables. This is done for 15 different climates, 6 building functions and 3
depths, which totals to 540 different cases. In the post-processing stage, the annual energy demand and
influence of the variable input parameters are analyzed using uncertainty and sensitivity analysis.
1
Pre-Processing Calculation Post-processing
Figure 2: Köppen-Geiger climate classification map of the world [13], with the chosen climates and corresponding cities.
The annual energy demand is examined for 6 different building functions (Table 1). Building characteristics for
different functions are obtained from the U.S. building stock [14].
Table 1: Building characteristics for different building functions
Domestic Education Hospital Industrial Offices Sport
2
Occupancy density [m /pp] 60 10 30 20 20 20 [12]
Floor area [m2] 120 19592 22422 5000 46320 1500 [14]
Number of floors 3 2 5 1 12 1 [14]
Height per floor [m] 2.8 4 4.3 8.5 4 7.6 [14]
Aspect ratio [EW / NS] 1.2 1.3 1.3 2.2 1.5 1.2 [14]
Dimensions for the domestic building function are assumed.
Education is based on the size of a secondary school, industrial on a warehouse and offices on a large office.
Sport building function is based on a 33m x 18m x 7.6m four-court hall, with attachments.
2
The variable input parameters evaluated in this study can be divided into uncertainty- and design parameters.
The uncertainty parameters internal gains and ventilation rate are normally distributed around a mean with a
standard deviation (Table 2). The uncertainty parameters infiltration rate, ground properties and design
parameters are uniformly distributed to represent a range of possible values (Table 3). The range of occurrence
is determined by the use of published data or follows from assumed values. The value of the uncertainty
variables and design variable infiltration rate are dependent on the size of the building and occupancy density.
Therefore the size and accordingly the level of impact of these variables are considered during the evaluation of
the results. The variable input parameters are different for the aboveground- and underground building. For the
underground building it is assumed that there are no windows nor is there any infiltration. Calculations for the
aboveground building do not take into account the changing ground properties. A total of 8 input parameters are
therefore used for the annual energy demand calculations of the aboveground building and 9 for the
underground building.
Table 2: Normally distributed uncertainty variables
Domestic Industrial Education Hospital Offices Sport
Internal gains 1
μ 4.6 6.42 15.25 18.66 8.17 27.25 [12], [15]
[W/m2] σ 0.575 1.906 2.332 0.802 1.021 3.406 (25%)
Ventilation rate2 μ 42 14 7 30 14 14 [12], [15]
[m3/h.pp] σ 5.250 0.875 3.750 1.750 1.750 1.750 (25%)
Uncertainty variable distribution: Both uncertainty variables are normally distributed.
1
Gains are dependent of floor area. Internal gains include the combination of metabolic (people), lighting and
appliance gains multiplied by the fraction of time present, which depends on the building function.
2
The total ventilation requirement depends on the occupancy density and floor area of the building.
Table 3: Uniformly distributed variables
Minimum Maximum
1 2
Design Conductivity of walls [W/m K] 0.1 0.3 Assumption
variable Conductivity of windows [W/m2K] 0.5 1.5 Assumption
Solar transmittance (g-value) 0.3 0.7 Assumption
Window to wall ratio 0.3 0.8 Assumption
Internal heat capacity2 80,000 370,000 [12]
Uncertainty Infiltration rate3 [1/h] 0.15 0.25 [15]
variable GP 4: Thermal conductivity [W/mK] 0.9 3 [16]
GP 4: Density [kg/m3] 1500 2700 [16]
GP 4: Specific heat capacity [J/kgK] 700 2200 [16]
Uncertainty and design variable distribution: All variables are uniformly distributed.
1
The U-value of walls excludes the surface heat transfer coefficients, which are included in the calculation.
2
80,000 corresponds to a very light building and 370,000 to a very heavy building.
3
The range for the infiltration rate corresponds to a tight to very tight building.
4
GP stands for ground properties and includes variations of clay and sand soils.
3
2.3. Energy calculation (EN-ISO 13790)
Calculations are made for a single-zone building being fully underground, therefore the assumption is made that
no infiltration or solar gains are existent. The building’s need for space heating and space cooling is calculated
using the monthly method described in EN-ISO 13790 [12]. In principle there is an energy need when the zone
needs heating to raise the internal temperature to the required minimum level (set-point for heating) or when the
zone needs cooling to lower the internal temperature to the required maximum level (set-point for cooling). The
total heat gains (internal- and solar gains) and heat losses (transmission- and ventilation losses) are calculated
for the heating and cooling mode with a corresponding utilization factor. The utilization factor is a function of
the heat balance ratio for both heating and cooling and requires a numerical parameter that depends on the
building’s thermal inertia [12]. The appropriate temperature difference compared to heat transmission to the
external environment, due to the large inertia of the ground, is taken into account by an adjustment factor that
adjusts the heat transfer coefficient instead of the temperature difference. The transmission losses to the ground
are calculated by using this factor in combination with calculated ground temperatures.
Where:
T (x,t) = temperature of soil at depth and on day t of the year in ˚C
Tm = mean annual ground surface temperature ˚C
x = depth below surface in m
t = time of year in days (Jan 1 = 1)
t0 = the phase constant, corresponding to the day of minimum surface temperature (days)
= the thermal diffusivity of the soil (m2/day)
As = amplitude of surface temperature wave
The cosine is expressed in radians.
This analytical equation does not take into account the precipitation and ground properties for every unique
spot, which are dissimilar at different locations and depths. The thermal diffusivity of the soil is based on its
density, thermal conductivity and specific heat capacity. The thermal diffusivity depends on the type of soil and
because this differs per location, it has been chosen to make the ground properties variable to include the range
of probable soil types.
The ground temperature is calculated for 15 climates with different ground properties. The ground temperature
profiles have a sinusoidal diurnal pattern, which follow the same pattern as the air temperature. Larger
amplitudes between the different depths exist in climates where the seasonal temperature difference is larger. In
the tropical climates (Af, Aw), the annual temperature can have a variation of only a few degrees Celsius,
therefore also the ground temperatures have a small fluctuation throughout the year. For the BSh, Cfb and Dfb
4
climates the amplitudes are larger than those of the tropical climates. The sinusoidal pattern of the temperature
dampens with an increase of depth. For the calculation of the energy demand of the underground building, three
depths (2m, 5m and 10m) have been chosen with their corresponding ground temperatures. Underground
temperatures at a depth of 2m have a larger fluctuation than at a depth of 10m, which is almost stable, but still
fluctuates less than the outdoor temperature.
Spearman’s rank correlation [21] is applied to identify whether the input variables and annual energy demand
relate in a monotonic function, meaning that if an input variable increases or decreases, the annual energy
demand increases or decreases. Spearman’s rank correlation coefficient is a non-parametric measure of
correlation as it does not try to make any assumption about the nature of the relationship between two ranks.
Due to the large amount of different cases the mean values of the annual energy demand (kWh/m 2a) are
compared by subtracting the total annual energy demand of the aboveground building with those of the
underground building (Table 5). Summing the values from both tables shows the annual energy demands of the
aboveground building (AB) (= Table 4 + Table 5 or AB = (AB-UB)+UB)). This gives the possibility to quickly
see potential sources of energy reduction by using colors, and it shows the climates and functions that have a
low annual energy demand in Table 5 (green to red – small to large energy demand). In Table 4 a larger
difference induces a higher energy reduction, as is indicated by the colors (green to red – large to small
difference). A negative value indicates that the aboveground situation performs better than the underground
situation and is therefore colored red. A comparison to the actual values is necessary to show the relevance of
the energy reduction.
5
Table 4: Difference between mean annual Table 5: Mean annual energy demand
energy demand (kWh/m2a) of the aboveground (kWh/m2a) of the underground
building and underground building for building for different climates and
different climates and building functions. building functions.
Education
Education
Industrial
Domestic
Industrial
Domestic
Hospital
Hospital
Offices
Offices
Sport
Sport
Singapore Af 122 22 24 56 84
33 46 136 166 246 61 73
Bangkok Aw 143 28 39 64 95
65 56 142 172 255 72 77
Phoenix BWh 138 10 21 71 74
97 13 116 147 206 24 60
San Antonio BSh 106 -1 0 61 53
67 3 101 136 181 8 53
Colorado Springs BSk 61 24 76 74 277 46 57 46 85 76 30 24
Seville Csa 88 -9 -11 46 42
64 1 92 127 163 3 47
Johannesburg Cwb 33 -21 -31 15 27
65 5 78 117 137 0 38
Jacksonville Cfa 95 -4 -9 52 49
47 2 102 134 179 7 52
Amsterdam Cfb 53 -2 43 53 245 14 53 49 87 79 25 24
Great Falls Dsb 80 41 104 81 330 69 73 39 78 59 45 23
Minneapolis Dwb 97 55 118 99 346 95 72 42 81 61 45 26
Kansas City Dfa 107 22 58 96 216 58 27 64 103 108 8 32
Helsinki Dfb 92 48 132 81 410 71 97 31 69 43 71 19
Sodankylae Dfc 123 92 223107 579 124 145 22 54 21 121 22
Inukjuak ET 143 127 314134 732 150 197 30 50 31 174 30
green to red green to red
large to small difference in energy demand small to large energy demand
Results show that a variety of the underground building cases can almost be considered zero-energy buildings as
the annual energy demand is near zero (below 10 kWh/m2a), in contrast to the aboveground counterpart where
the energy demand is up to 100 kWh/m2a higher (Table 4). The low annual energy demand for these
underground building cases, which can be seen in a large range of climates, originates from balancing energy
flows. Due to the building being underground, the transmission losses are stable throughout the year in
comparison to the aboveground situation, where it varies due to the seasonal weather changes.
Table 4 and Table 5 also show that there can be a large difference between the aboveground- and underground
buildings for different functions in the same climate. This difference is largely dependent on the size of the
building in combination with the internal gains. Building functions with low internal gains have a higher energy
demand in colder climates, while building functions with high internal gains have a high energy demand in
warm climates and vice versa. Warm to temperate climates (Af to BSh and Csa to Cfb) show a low energy
reduction (up to 30%) for the education, hospital and sport building functions, and in some cases are even less
efficient (down to -30%) than its aboveground counterpart.
3.2. High potential case
An example of balancing energy flows is given subsequently for a specific climate (Cfa) and building function
(domestic). Figure 3 shows that the underground building (right graph) has an underground temperature (UB
temperature) at the lower level of the set-point temperature interval. The balance of the energy losses and gains
will decide whether a comfortable temperature can be maintained without any requirements for heating or
cooling. On the other hand an aboveground building (left graph) has fluctuating annual outside temperatures
(AB temperature). This causes the temperature to be inside the interval for several months (April, May and
September), but to be outside the interval for the remaining months. Furthermore, the transmission and
ventilation losses are higher in the winter resulting in a larger energy need for heating. In contrast to
underground buildings, aboveground buildings can make use of solar gains. The annual energy demand
difference between the aboveground building and underground building for this specific climate and function is
88 kWh/m2a. However, for the same climate, a hospital building function with higher internal gains causes
overheating in the underground building and subsequently requires more energy for cooling, this result is also
visible in Table 5. In the Cfa climate, a domestic underground building function is much more energy efficient
than the aboveground building, but for a hospital building function it performs worse by a margin of 9
kWh/m2a.
6
(annual energy demand: 95 kWh/m2a) (annual energy demand: 2 kWh/m2a)
30 30 30 30
25 25 25
25
Energy (kWh/m2 )
Temperature (˚C)
20 20
Temperature (˚C)
Energy (kWh/m2)
20 15 20 15
15 10 15 10
10 5 5
10
0 0
5 -5 5 -5
0 -10 0 -10
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12
Month Month
Set-point cooling AB temperature Set-point cooling UB temperature
Set-point heating Transmission losses Set-point heating Transmission losses
Ventilation losses Internal gains Ventilation losses Internal gains
Solar gains
Figure 3: Energy balance of an aboveground building (left) and underground building (right) show the cause of the
difference in annual energy demand, for the Cfa climate and a domestic building function.
Energy (kWh/m2)
120 9
8
100 7
80 6
5
60 4
40 3
20 2
1
0 0
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12
Month Month
Transmission losses Ventilation losses Transmission losses Ventilation losses
Internal gains Solar gains Internal gains Solar gains
Infiltration = 0 Infiltration = 0.05
Infiltration = 0.1 Infiltration = 0.15
Infiltration = 0.2
Figure 4: Energy balance of an aboveground building (left) and underground
building (right) in the ET climate for the office building function.
7
3.4. Rationale of the energy balance of a building
Understanding the energy balance of a building is very important to comprehend the results and their
relationship between different combinations of climates and functions. The rationale for the energy balance is
that the annual energy need of a building depends on the deviation from the interval between the heating and
cooling set-point temperatures. As derived from the presented results, there are some underground building
cases that show an almost zero-energy demand. The prime reason for this is that the underground temperature
maintains a stable value inside the set-point interval throughout the year. This signifies that no energy is
required to maintain the internal temperature at a comfortable level, unless the internal gains cause an
imbalance. Therefore the underground temperature is very important to achieve a high energy reduction. In
contrast, the aboveground building is exposed to outside temperatures with larger daily and seasonal
temperature fluctuations that deviate from the interval and require more energy to maintain a comfortable
internal temperature. Furthermore, certain climates have underground temperatures that are below the heating
set-point. Depending on the range of this deviation, extra energy for heating is required to maintain the
comfortable internal temperature. In these cases it can be advantageous to have a building function with high
internal gains that nullify large amounts of transmission losses to balance the equation. In warm climates (high
underground temperatures) internal gains are therefore superfluous and would only increase the cooling
demand. In contrast to cold climates, internal gains are useful to reduce the heating demand. A sports building
function (high internal gains) is therefore inefficient in a warm climate, but efficient in a cold climate, but for a
domestic building function (low internal gains) the situation is reversed. These results are calculated without
using hourly user schedules (such as for the temperature set-points and occupancy pattern) throughout the day.
This may cause a day and night time fluctuation that could influence the energy demand for a building in certain
climates.
Aboveground
60 0 Underground
0
50
0
40
0 53 kWh/m2a 34.1% 34.1%
30 0
13.6% 13.6%
20 0
2.1% 0.1%
10 0
0 0
20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240
-3σ -2σ -1σ μ 1σ 2σ 3σ
2
Energy (kWh/m a)
Figure 5: Frequency distribution and probability distribution of the annual energy demand for the Af climate and domestic
building function, for 200 different combinations of variable input parameters.
An important observation is made when comparing the best case (lowest energy demand) of the aboveground
building with the worst case (highest energy demand) of the underground building. The mean and standard
deviation values of the annual energy demand for the aboveground- (AB) and underground (UB) buildings in
the previous example are B (μ 1 7 σ 8) and UB (μ 4 σ 7). The best aboveground building is then
167-28 = 139 kWh/m2a, while the worst underground building is 46+7 = 53 kWh/m 2a, this differs by 139-53 =
86 kWh/m2a. For 2 standard deviations, there is therefore a ~95% (0.9762) chance that the difference in the
annual energy demands of the aboveground- and underground building is 53 kWh/m2a or more. The best
aboveground building case will thus perform worse than the worst underground building case by a large margin.
The same comparison is made for every climate and building function. In most cases the worst underground
building performs better than the best aboveground building (positive interval value). Except for the Af to Cfb
and Dfa climates for the education, hospital and sport building functions. In these cases the 2 standard deviation
8
interval value between the worst and best case is negative. In some of these cases this already follows from the
negative difference in the mean and almost equal standard deviation.
Figure 6 shows Spearman’s rank correlation coefficients for the sport building function in a tropical (Af) and
polar climate (ET). It can be seen that in the tropical climate, the internal gains indicate a very strong positive
correlation to the annual energy demand of an aboveground- and underground building. In the polar climate on
the other hand, the internal gains correspond to a negative correlation for both an aboveground- and
underground building.
Spearman's rank correlation coefficient Spearman's rank correlation coefficient
-1 -0,5 0 0,5 1 -1 -0,5 0 0,5 1
U-value walls U-value walls
Internal gains Internal gains
Ventilation rate Ventilation rate
Internal heat capacity Internal heat capacity
Infiltration rate Infiltration rate
U-value glazing U-value glazing
Solar transmittance Solar transmittance
Window to wall ratio Window to wall ratio
GP: Thermal conductivity GP: Thermal conductivity
AB GP: Density AB GP: Density
UB GP: Specific heat capacity UB GP: Specific heat capacity
Figure 6: Spearman’s correlation coefficient on the annual energy demand of an aboveground- (AB) and
underground building (UB) with sport function, for the tropcial climate Af (left) and polar climate ET (right).
The correlation coefficients of the 5 most important variable parameters on the annual energy demand for an
underground- and aboveground building for all building functions and climates are shown in Table 6. The
correlation is visualized by using a color scale, -1 very strong negative correlation (red) to 1 very strong positive
correlation (green), 0 (white) means there is no correlation.
No single parameter seems to have the highest influence in every situation, although there are some parameters
that have a higher influence in most cases. The ground property parameters are not shown for the underground
building as their influence on the annual energy demand is very small, which is also observed in a former study
[22]. Furthermore, 3 parameters for the aboveground building are not shown as they only have a strong
influence for the domestic building function. The U-value of the windows has a strong negative influence in the
colder climates, while solar transmittance and window to wall ratio have a strong negative influence in the
warmer climates.
9
Table 6:Variable parameter analysis on annual energy demand (negative (-1 “green”) to positive (1 “red”) correlation).
Internal heat
U-value walls Internal gains Ventilation rate Infiltration rate
capacity
Education
Education
Education
Education
Education
Industrial
Industrial
Industrial
Industrial
Industrial
Domestic
Domestic
Domestic
Domestic
Domestic
Hospital
Hospital
Hospital
Hospital
Hospital
Office
Office
Office
Office
Office
Sport
Sport
Sport
Sport
Sport
Af
Aw
BWh
BSh
BSk
Aboveground
Csa
Cwb
Cfa
Cfb
Dsb
Dwb
Dfa
Dfb
Dfc
ET
Af 1
Aw 0
BWh -1
BSh
BSk
Underground
Csa
Cwb
Cfa
Cfb
Dsb
Dwb
Dfa
Dfb
Dfc
ET
The annual energy demand is strongly influenced by several parameters, and there exists a large difference in
correlation between the climates and building functions.
An increase in the U-value (lower resistance) will almost always increase the energy demand of an
aboveground building, stronger so in the colder climates. On the contrary, the energy demand of an
aboveground building in the warm climates increases when the U-value is decreased (higher resistance).
Higher internal gains increase the energy demand in warm climates and reduce the energy demand in
cold climates for both the aboveground- and underground building. But for the underground building,
the parameter is much more sensitive and has a larger negative effect in most of the climates. It is the
most important parameter for the underground building.
A decrease in the internal heat capacity of a building has a positive influence on the energy demand in
almost all cases.
For larger aboveground buildings the infiltration rate has a strong negative correlation with the energy
demand, for the remainder of the buildings, the correlation is also existent in the colder climates. Much
energy is saved in the underground building due to the absence of this unwanted air infiltration.
From the sensitivity analysis it follows that the combination of parameters in a certain climate and building
function can have a large influence on the energy demand of both an underground and aboveground building.
Thus to achieve the highest possible energy reduction through optimization, a dissimilar combination of
parameters is required for every different climate and building function.
10
4. CONCLUSION
The energy reduction potential of underground buildings has been investigated by performing monthly
calculations on the annual energy demand. A comparative analysis between aboveground- and underground
buildings is applied for different climates, building functions and depths. This made it possible to quantify the
differences and assess the energy reduction potential. A sensitivity analysis is performed by analyzing variable
input parameters and their correlation on the annual energy demand.
Underground buildings have the potential to reduce the energy demand in comparison to a conventional
aboveground building by using beneficial soil temperatures and large amounts of earth cover as insulation. But
the magnitude of this potential is related to the combination of different design elements. The energy reduction
potential starts with underground buildings that require almost no energy to maintain a comfortable indoor
temperature, as can be seen in several climates. The prime reason for this is that the underground temperature
maintains a stable value inside the set-point interval throughout the year. This signifies that no energy is
required to maintain the internal temperature at a comfortable level, unless the certain parameters, such as the
internal gains cause an imbalance. Therefore the underground temperature is very important to achieve a high
energy reduction. In contrast, the aboveground building is exposed to outside temperatures with larger daily and
seasonal temperature fluctuations that deviate from the interval and require more energy to maintain a
comfortable internal temperature. According to the calculation of different ground depths (2m, 5m and 10m), it
is concluded that their mutual effect on the annual energy demand of an underground building is negligible.
Furthermore, variable ground properties show only a very small influence on the energy demand of an
underground building.
Certain climates have underground temperatures that are below the heating set-point. Depending on the range of
this deviation extra energy for heating is required to maintain a comfortable indoor temperature. In these cases it
can be advantageous to have a building function with high internal gains that nullify large amounts of
transmission losses to balance the equation. In warm climates (high underground temperatures) internal gains
are therefore superfluous and would only increase the cooling demand. In contrast to cold climates, internal
gains are useful to reduce the heating demand.
A high energy demand is perceived for large aboveground buildings in cold climates due to infiltration. This
consequently creates a high potential case for the underground building to reduce the energy demand, due to the
absence of this infiltration.
For every case 200 calculations are made that provide a mean and standard deviation of the annual energy
demand. Uncertainty analysis of the results show that in most cases the worst underground building performs
better than the best aboveground building.
Based on the reviewed results and methodology, some recommendations can be made for future work
concerning identification of the energy reduction potential of underground buildings compared to aboveground
buildings.
A higher accuracy can be obtained by performing calculations using simulation software which contain a
more accurate ground heat transfer calculation. More knowledge can be obtained on the daily pattern by
performing hourly calculations and by providing occupancy schedules. Also, a better understanding of the
local microclimate in underground buildings is necessary to identify whether lower peak heating and cooling
is required.
The method of applying weather data from a location that corresponds with a certain climate should also be
reconsidered, as the difference in weather data between different locations in the same climate can be very
large and therefore one location does not accurately represent a climate. Average values for more locations in
one climate can make a better representation.
More quantitative information on the annual energy demand of semi underground buildings is required, as
these buildings can benefit from the thermal advantages of the ground while also allowing daylight to enter
the building.
11
5. REFERENCES
[1] J. Godard, "Urban underground space and benefits of going underground," in World Tunnel Congress 2004
and 30th ITA General Assembly, Singapore, 2004.
[2] J. Admiraal, "A Bottom-up Approach to the Planning of Underground Space," Gouda.
[3] E. Horvat, "Going beyond the frontier of urban space, use of the subsurface space".
[4] F. Chow, T. Paul, I. Vähäaho, B. Sellberg and L. Lemos, "Hidden Aspects of Urban Planning: Utilisation
of Underground Space," in Conference on Soil Structure Interaction in Urban Civil Engineering, Zurich,
2002.
[5] M. Khair-El-Din and Abd-El-Hamid, "Earth Sheltered Housing: An Approach to Energy Conversation in
Hot Aird Areas," Architecture and Planning, vol. 3, pp. 3-18, 1991.
[6] F. Wang and Y. Liu, "Thermal environment of the courtyard style cave dwelling in winter," Energy and
Buildings, vol. 34, pp. 985-1001, 2002.
[7] L. Boyer, "Earth Sheltered Structures," Ann. Rev. Energy, vol. 7, pp. 201-219, 1982.
[8] R. Sterling and J. Godard, "Geoenengineering considerations in the optimum use of underground space".
[9] B. Todorovic and B. Despotovic, "Development of calculation procedure for heat losses of underground
spaces," in Proceedings of the Transactions of the 30th HVAC Congress, Belgrade, 1999.
[10] A. Anselm, "Passive annual heat storage principles in earth sheltered housing, a supplementary energy
saving system in residential housing," Energy and Buildings, vol. 40, pp. 1214-1219, 2008.
[11] A. Al-Temeemi and D. Harris, "A guideline for assessing the suitability of earth-sheltered mass-housing in
hot-arid climates," Energy and Buildings, vol. 36, pp. 251-260, 2004.
[12] EN-ISO 13790, "Energy performance of buildings - Calculation of energy use for space heating and
cooling (ISO 13790:2008)," European Committee for Standardization, 2008.
[13] M. Peel, B. Finlayson and T. McMahon, "Updated world map of the Köppen-Geiger climate
classification," Hydrol. Earth Syst. Sci., vol. 11, pp. 1633-1644, 2007.
[14] M. Deru, K. Field, D. Studer, K. Benne, B. Griffith and P. Torcellini, U.S. Department of Energy
Commerical Reference Building Models of the National Building Stock, Colorado: National Renewable
Energy Laboratory, 2011.
[15] CIBSE, CIBSE Guide A: Environmental design, Norwich: CIBSE, 2006.
[16] S. Ocaña and I. Guerrero, "Comparison of analytical and on site temperature results on Spanish traditional
wine cellars," Applied Thermal Engineering, vol. 26, pp. 700-708, 2006.
[17] C. Hopfe, "Uncertainty and sensitivity analysis in building performance simulation for decision support and
design optimization," Eindhoven University of Technology, Eindhoven, 2009.
[18] K. J. Lomas and H. Eppel, "Sensitivity analysis techniques for building thermal simulation programs,"
Energy and Building, vol. 19, pp. 21-44, 1992.
[19] K. Labs, "Underground Building Climate," Solar Age, vol. 4, no. 10, 1979.
[20] Solar Energy Laboratory, "TRNSYS 17.1. A transient systems simulation program," Solar Energy
Laboratory, University of Wisconsin-Madison, Madison, 1990.
[21] J. Myers, Research design and statistical analysis, Lawrence Erlbaum Associates, 2003.
[22] M. Staniec and H. Nowak, "Analysis of the earth-sheltered buildings' heating and cooling energy demand
depending on type of soil," Archives of Civil and Mechanical Engineering, vol. XI, no. 1, pp. 221-235,
2011.
[23] T. McKnight and D. Hess, Physical Geography: A Landscape Appreciation, Upper Saddle River, New
Jersey: Prentice Hall, 2000.
12
Appendix A – CLIMATE DESCRIPTIONS
13
14
III. Underground buildings
BESTEST Case study
Underground buildings
BESTEST Case study
C. van Dronkelaar, J.L.M. Hensen, D. Cóstola and R.A. Mangkuto
1. INTRODUCTION
To verify the energy reduction potential of underground buildings in the former study described in Chapter I,
and to investigate the daily patterns of the energy performance of both buildings, the BESTEST Case 900 is
simulated using the software program TRNSYS [2]. The building is simulated for the aboveground situation and
corresponding underground situation.
2. METHODOLOGY
2.2. Climates
Calculations are made for three different climates (Table 2). Ground input parameters for the three climates are
calculated using the Labs equation [4]. A desert climate (BWh, location: Phoenix), maritime temperate climate
(Cfb, Amsterdam) and hemiboreal climate (Dfb, Helsinki) are simulated to show differences in the energy
performance in different climates.
Table 2: Three different climates with corresponding ground characteristics.
BWh Cfb Dfb
Deep earth temperature [˚C] 22.46 9.46 4.44
Amplitude of surface temperature [˚C] 10.97 7.14 11.89
Day of minimum surface temperature 350 16 45
1
Figure 1: Model of the aboveground- and underground building in Google SketchUp.
80 Cooling
70
(kWh/m2a)
60
50
40
30
20
10
0
AB UB AB UB AB UB
BWh (Phoenix) Cfb (Amsterdam) Dfb (Helsinki)
Figure 2: Annual energy demand of the aboveground- and underground situation
of the BESTEST case 900 for three different climates.
In all cases the underground building performs better than the aboveground counterpart. Nonetheless, it can be
seen that there exist large differences in energy demand of the aboveground- and underground building for
different climates. The desert climate (BWh) shows a high potential in the energy reduction of the aboveground
building, by placing it underground. While the maritime temperate climate (Cfb) shows only a small reduction
2
in the annual energy demand. The hemiboreal climate (Dfb) shows a higher energy reduction than the maritime
temperate climate (Cfb), but smaller reduction than in the desert climate (BWh).
The explanation between these differences can be found when investigating the climate characteristics. In
Figure 3 to Figure 5, temperature profiles are shown for the ambient temperature, the zone temperature of the
underground building, and the boundary temperature of the underground wall in three different climates. The
high energy reduction potential of the desert climate follows from the high underground temperature of around
23˚C. The underground temperature lies between the heating- and cooling set points, which causes the
transmission losses to be very low. Therefore little energy is required to keep the building at a comfortable
indoor temperature in comparison to the aboveground building, where cooling is needed due to the high outside
temperatures.
40
30
Temperature (˚C)
20
10
0
226
451
676
901
2251
2476
2701
2926
3151
5401
5626
5851
6076
6301
8551
1126
1351
1576
1801
2026
3376
3601
3826
4051
4276
4501
4726
4951
5176
6526
6751
6976
7201
7426
7651
7876
8101
8326
1
-10
-20 Tambient
Tzone
-30 Tboundary
Hour of the year
Figure 3: Temperature profiles (outside, zone and boundary wall) of the underground building in the desert climate (BWh).
The underground temperatures of the maritime temperate and hemiboreal climates are much lower and therefore
much energy is needed for heating the underground building. This is also true for the aboveground situation,
where even more heating is needed during the winter due to even lower temperatures than the underground
temperatures. While during the summer temperatures are somewhat higher than the underground temperature
and therefore little cooling is also required for the aboveground building.
40
30
Temeprature (˚C)
20
10
0
221
441
661
881
1
1101
1321
1541
1761
1981
2201
2421
2641
2861
3081
3301
3521
3741
3961
4181
4401
4621
4841
5061
5281
5501
5721
5941
6161
6381
6601
6821
7041
7261
7481
7701
7921
8141
8361
8581
-10
-20 Tambient
Tzone
-30 Tboundary
Hour of the year
Figure 4: Temperature profiles (outside, zone and boundary wall) of the underground building in the maritime temperate climate (Cwb).
3
40
30
Temperature (˚C)
20
10
0
221
441
661
881
1
1101
1321
1541
1761
1981
2201
2421
2641
2861
3081
3301
3521
3741
3961
4181
4401
4621
4841
5061
5281
5501
5721
5941
6161
6381
6601
6821
7041
7261
7481
7701
7921
8141
8361
8581
-10
-20 Tambient
-30 Tzone
Hour of the year Tboundary
Figure 5: Temperature profiles (outside, zone and boundary wall) for the underground building in the hemiboreal climate (Dfb).
Although the underground temperature is a very important factor in reducing the energy demand of the
underground building, there are several other energy flows that affect the energy reduction potential. To get a
better understanding of how the energy gains and losses influence the energy performance of an aboveground-
and underground building, the daily pattern of the energy flows is important. In Figure 6 and Figure 7, the
energy flows and temperatures of the aboveground- and underground building are shown for the desert climate
(BWh) on the 22th of July.
3,0 40 3,0 40
2,5 35 2,5 35
2,0 30 2,0 30
Temperature (˚C)
Temperature (˚C)
Energy (kW)
Energy (kW)
1,5 25 1,5 25
1,0 20 1,0 20
0,5 15 0,5 15
0,0 10 0,0 10
5
1
3
7
9
11
17
23
13
15
19
21
1
3
5
7
9
11
13
23
15
17
19
21
-0,5 5 -0,5 5
-1,0 0 -1,0 0
Hour of the day Hour of the day
Qinfiltration Qventilation Qinfiltration Qventilation
Qsolargains Qinternalgains Qsolargains Qinternalgains
Qtransmission Qheating Qtransmission Qheating
Qcooling Tambient Qcooling Tboundary
Tzone Tzone
Figure 6: Energy balance and temperatures of the Figure 7: Energy balance and temperatures of the
aboveground BESTEST case in a desert climate (BWh) on underground BESTEST case in a desert climate (BWh) on
the 22th of July. the 22th of July.
From the graphs it follows that the underground building has a boundary temperature of 23˚C and therefore the
transmission losses are very low. Only due to the ventilation gains and internal gains during the day, the
underground building requires only a small amount of energy for cooling. In comparison, the aboveground
building is adjacent to very high outdoor temperatures during this summer day. To establish and maintain the
maximum set-point temperature of 24˚C, a large amount of cooling is needed. But in this case, not only the high
outdoor temperatures are cause of the large difference in the cooling demand. Although the internal gains and
ventilation gains are equal to the underground building, the solar gains present during the day cause the cooling
demand to be much higher. The infiltration in this case has very little influence on the energy demand. For the
aboveground situation in the desert climate (BWh) the daily profile is almost the same throughout the year,
which means that the increase in energy demand is quite stable.
4
For the hemiboreal climate (Dfb) the outdoor temperatures are below 0˚C for a large time interval, while it is
somewhat warmer during the summer. In Figure 8 and Figure 9 the energy balance and temperatures are shown
of a particular summer day.
3,5 30 3,5 30
2,5 25 2,5 25
Temperature (˚C)
Temperature (˚C)
1,5 20 1,5 20
Energy (kW)
Energy (kW)
0,5 15 0,5 15
7
1
9
11
15
19
23
27
13
17
21
25
3
7
1
13
17
23
27
11
15
19
21
25
-0,5 10 -0,5 10
-1,5 5 -1,5 5
-2,5 0 -2,5 0
Hour of the day Hour of the day
Qinfiltration Qventilation Qinfiltration Qventilation
Qsolargains Qinternalgains Qinternalgains Qsolargains
Qtransmission Qheating Qtransmission Qheating
Qcooling Tambient Qcooling Tboundary
Tzone Tzone
Figure 8: Energy balance and temperatures of the Figure 9: Energy balance and temperatures of the
aboveground BESTEST case in a hemiboreal climate (Dfb) underground BESTEST case in a hemiboreal climate (Dfb)
on the 22th of July. on the 22th of July.
In comparison to the desert climate (BWh), the underground building requires a much larger amount of energy
to maintain a comfortable temperature. This is largely due to the much lower underground temperature of
around 7˚C throughout the year. A building with more internal gains would reduce the energy need for heating
in this case. The aboveground building on the other hand requires cooling during the summer due to the high
solar gains that are present during the afternoon.
The daily profiles of the maritime temperate climate (Cfb) are similar to the daily profiles of the hemiboreal
climate (Dfb). The only difference is that the transmission losses are somewhat larger in the hemiboreal climate
(Dfb) due to the lower outdoor- and ground temperatures.
The energy reduction potential of the hemiboreal climate (Dfb) is somewhat higher than for the maritime
temperate climate (Cfb). The reason for this is the relatively higher energy demand of the aboveground building
in the hemiboreal climate (Dfb). The lower outdoor temperatures during the winter seem to have a larger
negative effect on the energy demand than the lower ground temperature in the hemiboreal climate.
4. CONCLUSION
The energy reduction potential of underground buildings has been verified by simulating the BESTEST Case
900 with the software program TRNSYS. Although several building characteristics and inputs are dissimilar to
the calculations performed in the former study, high energy reduction is perceived between the energy demand
of the aboveground- and underground building. Furthermore, hourly calculations have allowed a better
understanding of the daily pattern of the energy performance of the aboveground- and underground building.
The underground temperature seems to be a very important factor for reducing the energy demand of the
underground building. An underground temperature that is near the heating- and cooling set-points is most
likely to result in a building with low energy requirement. A low energy demand can therefore be achieved in
climates that have beneficial underground temperatures. Nonetheless, the energy reduction potential of
underground buildings compared to aboveground buildings is not based on the low energy demand of
underground buildings, but on the difference between the annual energy demand of the aboveground- and
5
underground building. Therefore, it is not useful to build an underground building when the aboveground
building counterpart is very energy efficient and has a low energy demand.
Simulations should therefore be carried out if considering and underground building instead of an aboveground
building. The energy reduction potential depends on the location (climate) of the building, but also the other
building characteristics, such as internal gains and ventilation can have a large influence on the energy demand.
Some recommendations can be made, which follow from simulating and modeling underground buildings with
the software program TRNSYS.
In the underground situation, it is impossible to model walls that are not perpendicular. This impossibility
causes an inaccuracy in modeling many buildings. The modeling method that is needed in TRNSYS should
therefore be adjusted to include the feature of modeling different angles in a building façade.
The modeling of an underground building is very time consuming and unclear. Every surface of a zone has
to be connected several times throughout different module types. A more efficient way would be to let
TRNSYS do this automatically.
5. REFERENCES
[1] C. van Dronkelaar, J. Hensen, D. Cóstola and R. Mangkuto, "Underground buildings - Potential in terms of
energy reduction," Eindhoven University of Technology, 2013.
[2] Solar Energy Laboratory, "TRNSYS A Transient System Simulation Program," University of Wisconsin-
Madison, 2012.
[3] R. Judkoff and J. Neymark, "International Energy Agency Building Energy Simulation Test (BESTEST) and
Diagnostic Method," National Renewable Energy Laboratory, Golden, Colorado, 1995.
[4] K. Labs, "Underground Building Climate," Solar Age, vol. 4, no. 10, 1979.
[5] Trimble Building, "SketchUp Pro," Trimble Navigation Limited, 2012.
[6] TESS Experts in Energy Modeling & Analysis, "TESS Component Libraries: General Descriptions".
6
IV. Underground buildings
Underground building examples
# Peel, M. C. and Finlayson, B. L. and McMahon, T. A. (2007). "Updated world map of the Köppen–Geiger climate
classification". Hydrol. Earth Syst. Sci. 11: 1633–1644. ISSN 1027‐5606. (direct: Final Revised Paper)
1
%
0
5
10
15
20
25
30
35
40
Leisure
Educational
Office
Residential
Retail
Recreational
Industrial
Religious
Infrastructure
Functions
Storage
Agriculture
Military
Industrial
0
5
10
15
20
25
30
35
40
Atrium or Courtyard
True Underground
Berm Elevational
Nonearth Roof (b)
Nonearth Roof
Hillside Elevational
Building type
%
0
5
10
15
20
25
Australia
Brazil
China
Finland
Germany
Iceland
Italy
Mexico
New Zealand
Peru
Countries
South Korea
Sweden
Tunisia
U.K.
%
0
5
10
15
20
25
30
Aw
BWh
BSh
BSk
Csa
Csb
Cwb
Cfa
Cfb
Dsc
Climates
Dwa
Dwb
Dfa
Dfb
Dfc
ET
2
Architect | Location | Year of completion Kohn Pedersen Fox and LPT Architects|Singapore, Singapore | 2000
Function(s) Climate description Retail Tropical rainforest
(Climate code) (Af)
≤ Disadvantages ≥ CityLink Mall is the unique retail component of the One Raffles Link
development. It provides around 60,000 sq.ft. of retail space in an
Below ground level ≈ % Below ground level ≈ 100%
≥ Advantages air‐conditioned subterranean mall, and links One Raffles Link to the
Surface to ground ≈ % Surface to ground ≈ 40%
City Hall and Esplanade MRT Station.
Depth ≈ m Depth ≈ 300m
≥ The stunning subterranean mall with over 50 shops, offers
international fashion names, exquisite gifts & accessories, home
accessories and some of the best eateries in Singapore.
≥ Daylight is delivered to the space by glazed pavilions sited on the
War Memorial gardens, which creates a bright and cheery feel.
Building type
# http://www.contrib.andrew.cmu.edu/~igaur/
# Reference # http://www.citylinkmall.com/about
3
Oscar Niemeyer | Brasilia, Brazil | 1970 Matmata, Tunisia | knowledge of existence from 1967
Religious Tropical wet Residential Dry Desert
(Aw) (BWh)
≥ The cathedral is a hyperboloid structure constructed from 16 ≥ A large pit is dug, where around the perimeter of this pit artificial
concrete columns, weighing 90 tons each. caves are dug to be used as rooms, with some homes comprising
Below ground level ≈ 20% Below ground level ≈ 100%
≥ The exterior of the cathedral resembles the circular plan and ribbed Surface to ground ≈ 20%
multiple pits, connected by trench‐like passageways.
Surface to ground ≈ 60%
structure of Liverpool Metropolitan Cathedral, but the latter is clad Depth ≈ 2m ≥ A tourist attraction, because filming is done in one such a troglodyte Depth ≈ 6m
in solid material, while the Cathedral of Brasília allows light in and home for the Star Wars movies.
out for almost the full height of the ribs.
4
Longhi Architects | Pachacamac, Lima, Peru| 2012 ‐ | Coober Pedy, Australia | 1800’s
Residential Dry Desert Residential Dry Desert
(BWh) (BWh)
≥ Because it is entirely constructed of stone, it will last thousands of ≥ This small town in the middle of nowhere, Australia, is home to some
years. It’s also almost entirely underground, which will make it able Below ground level ≈ 70% of the strangest houses on Earth. A combination of climactic Below ground level ≈ 100%
to withstand extreme climate change in the meantime. Surface to ground ≈ 70% conditions and the existence of opal mining in the region have Surface to ground ≈ 100%
≥ Locally quarried, smoothed and polished stone also is used inside to Depth ≈ 4m literally driven the residents underground. Everything from Depth ≈ 10m
construct the interior walls and even some shelving. For its longevity, residences to churches are carved out of the ground as the above
it will certainly win LEED points: it’s not going to the landfill any images show. The place is something of a tourist attraction, with
decade soon. Its energy use is moderated by being underground. So underground hotels as well as a golf course above ground – though
it’s green. golf is played at night due to the regional heat!
≥ For what amounts to a 10,000 square foot underground bunker, light
is able to get down into the entirely stone hewn space fairly well.
The dining room table is a huge singular stone set permanently in
place.
# http://www.homedesignfind.com/green/10000‐square‐foot‐underground‐
# http://weburbanist.com/2007/09/30/7‐underground‐wonders‐of‐the‐
bunker‐will‐remain‐forever/
world‐labyrinths‐crypts‐and‐catacombs/
# http://www.longhiarchitect.com/home.html
5
Matthew Fromboluti | Lavender Pit Mine in Bisbee, Arizona, U.S.A. | Concept Tadao Ando | Naoshima, Kagawa, Japan | 1995
Residential, Office, Agriculture, Leisure Dry Steppe Leisure, Residential Dry Steppe
(Bsh) (BSk)
≥ Through use of many simple, passive systems, the entire complex is ≥ The composition of the Museum’s main building consists of three
a sustainable, underground oasis in the desert, with the area above overlapping cubes and a circle, with a rectangular guest wing attached
Below ground level ≈ 95% Below ground level ≈ 100%
reclaimed for nature, and the space below a unique opportunity for at an angle to it. The simple geometrical volumes of the Museum are
Surface to ground ≈ 60% Surface to ground ≈ 60%
human use. built within the hillside so as not to disturb the beauty of the natural
Depth ≈ 50m Depth ≈ 10m
≥ The building is completely self‐sustaining, with its own power landscape but to become a part of it.
source, water recycling system, and mechanisms such as a solar ≥ Connected to this corridor is an oval shaped cut out volume of which
chimney to control the artificial climate. in the center is a pool of still water filled to its edges reflecting the
surrounding volume and the sky above.
# http://www.evolo.us/architecture/skyscraper‐or‐sustainable‐underground‐
# E. von Meijenfeldt, Below Ground Level, 2003
society/
# http://www.galinsky.com/buildings/naoshima/index.htm
# http://www.frombo.com/folio‐Evolo10.html
6
Walker McGough Foltz Lyerla architects | Spokane, Washington, U.S.A. | 1980 Cappadocië, Central Anatolia, Turkey | > 1000 B.C.
Leisure, Office Dry Steppe Residential Dry Steppe
(BSk) (BSk)
≥ The earth is used effectively in this project to achieve energy ≥ Cappadocia contains several underground cities (see Kaymaklı
conservation. Heat transfer by means of infiltration is virtually Underground City), largely used by early Christians as hiding places
Below ground level ≈ 60% Below ground level ≈ 0%
eliminated by the monolithic earth covering before Christianity became an accepted religion.
Surface to ground ≈ 70% Surface to ground ≈ 70%
≥ In Spokane, air temperatures vary between ‐23 and 48°C. Depth ≈ 6m ≥ 260km2 with 200+ underground villages and tunnel towns complete Depth ≈ ?m
Temperatures in the earth at a depth of 2 m vary from 5 to 16°C. with hidden passages, secret rooms and ancient temples
According to the architects
≥ 50% reduction in the amount of energy consumed, compared to a
conventionally constructed façade building of the same size and
function.
# Barker, M., 1986. Using the Earth to Save Energy: Four Underground
Buildings. Tunneling and Underground Space Technology # http://www.turkije‐info‐site.nl/capadocie‐turkije.html
# http://www.cprestress.com/projects/63/
7
‐ | Cortez, Colorado, U.S.A. | 12th Century Mi5 + PKMN | Tereul, Aragón, Spain | 2012
Residential Dry Steppe Leisure Dry Steppe
(BSk) (BSk)
≥ It may be the most significant archeological preserve of Native ≥ Teruel‐Zilla is a three‐story underground leisure and rec center for
American culture in the United States. In the 12th century, the Below ground level ≈ 0% the youth of Teruel, Spain. The spot was once home to a public Below ground level ≈ 95%
Anasazi start building houses in shallow caves and under rock Surface to ground ≈ 30% market building, but it was becoming obsolete, so the town decided Surface to ground ≈ 90%
overhangs along the canyon walls. Some of these houses were as Depth ≈ ?m to make way for something more useful. Mi5 + PKMN designed a Depth ≈ 10m
large as 150 rooms. The most famous of these are called Cliff Palace leisure center to take the place of the market building, but buried it
and Spruce Tree House. By 1300, all of the Anasazi had left the Mesa underground in order to create open space in the public square. The
Verde area, but the ruins remain almost perfectly preserved. landscaped area on the ground floor is a series of stepped planes,
ramps and staircases which creates a new urban topology that
encourages interaction, activity and community. Burying the center
underground protects it from the warm climate and leaves the
ground floor for vegetation, thus helping reduce energy use and heat
island effect.
# http://inhabitat.com/teruel‐zilla‐is‐an‐underground‐leisure‐lair‐inspired‐
# http://www.touropia.com/cave‐dwellings/ by‐dinosaurs‐in‐spain/teruel‐zilla‐mi5‐pkmn‐9/
# http://www.mi5arquitectos.com/mi5‐architects‐plaza‐teruel/
8
‐ | Israel| ‐ Mickey Muennig | Big Sur, California, U.S.A. | 1971
Residential Dry‐summer subtropical Residential Dry‐summer subtropical
(Csa) (Csa)
≥ “Bir al‐Id used to be home to 397 Palestinians. The village residents ≥ The structure of the home is so that it maximizes the views across
maintained a unique way of life, drawing water from wells and pits in Below ground level ≈ 100% the islands. Below ground level ≈ 80%
the area around their huts, tents and cave dwellings. Surface to ground ≈ 95% Surface to ground ≈ 70%
≥ “These people live in caves – some out of poverty, some out of Depth ≈ 4m Depth ≈ 3m
preference. They keep flocks like Bedouin do but they also practice
subsistence agriculture. They split their time between a town called
Yatta and the caves.
# http://www.rhr‐na.org/blog/?p=789 # http://www.hebhide.co.uk/
9
Emilio Ambasz | Sevilla, Spain | 1980 Petra, Jordan, Israel | 6th century B.C.
Residential Dry‐summer subtropical Residential Dry‐summer subtropical
(Csa) (Csa)
≥ An underground "canopy" of fiberglass panels extends horizontally ≥ The site remained unknown to the Western world until 1812, when
as a ten foot cornice from the wall's top to keep water from soaking it was introduced by Swiss explorer Johann Ludwig Burckhardt.
Below ground level ≈ 70% Below ground level ≈ 0%
the ground around the house.
Surface to ground ≈ 60% ≥ The area is visited by flash floods and archaeological evidence Surface to ground ≈ 70%
≥ All practical needs and services (kitchen, baths, storage, etc.) are Depth ≈ 5m demonstrates the Nabataeans controlled these floods by the use of Depth ≈ ?m
satisfied by geometric containers placed into the ground. Sleeping is dams, cisterns and water conduits. These innovations stored water
in either some of the living areas or in the sleeping alcoves for prolonged periods of drought, and enabled the city to prosper
contained within the sides. from its sale.
# http://www.emilioambaszandassociates.com/portfolio/portfolio.cfm?Pid=81
# http://www.pbase.com/bmcmorrow/image/42241331
# http://www.pushpullbar.com/forums/showthread.php?4480‐USA‐Emilio‐
# http://www.aquiziam.com/petra_images2.html
Ambasz
# http://en.wikipedia.org/wiki/Petra
10
decaArchitecture | Antiparos, Paros, Greece| 2008 Emilio Ambasz | Castellaneta all Mare, Puglia, Italy | 2003
Residential Dry‐summer subtropical Residential Dry‐summer subtropical
(Csa) (Csa)
≥ The design of the Aloni House took a cue from these existing ≥ Nuova Concordia is a residential resort community including such
natural‐stone walls. The architectural intervention is located in a amenities as a shopping complex, international hotel, conference
Below ground level ≈ 20% Below ground level ≈ 20%
hollow between two mountain slopes and creates a bridge, so to center, sporting facilities, golf course and health spa.
Surface to ground ≈ 30% Surface to ground ≈ 80%
speak, between two contours. The house's sides disappear into the
Depth ≈ 0m ≥ To preserve the primal beauty of this site, the architect situated the Depth ≈ ?m
ground, blending the structure into the landscape. To the front, the buildings and roadways within landscaped berms and flowering
land falls away, allowing one of the house's long elevations a view of trellises so they appear as undulating hills in the landscape. The
the sea. There are five internal courtyards, which flood the rooms result is a medium density development turned into a park‐by‐the‐
with light and shield windows and doors from stormy rainwater. sea
# http://www.emilioambaszandassociates.com/portfolio/portfolio.cfm?Pid=8
# http://www.architonic.com/ntsht/camouflage‐architecture‐underground‐ 1
buildings/7000497 # http://www.pushpullbar.com/forums/showthread.php?4480‐USA‐Emilio‐
# http://www.deca.gr/#/en/project/265 Ambasz
11
Bacchus caves | Napa, California, U.S.A. | 2007 BNKR Arquitectura|Mexico city, Mexico | Concept
Residential, Leisure Mediterranean Leisure, Retail, Residential, Office Temperate with dry winters
(Csb) (Cwb)
≥ In the hillside directly behind The Meritage Resort lies Spa Terra, a ≤ Would work much better in a dry area in a northern, colder climate,
luxury spa located entirely underground in our 22000 square foot where solid ground keeps you warm, and the glass top acts as a
Below ground level ≈ 100% Below ground level ≈ 100%
Estate Wine Cave. This Napa Valley treasure is experience unto itself. greenhouse. In a hot climate putting a building underground
Surface to ground ≈ 100% Surface to ground ≈ 40%
Spa guests experience the hushed serenity of the cave, with natural removes many ventilation opportunities.
Depth ≈ 3m Depth ≈ 300m
stone and copper water features combined with Florentine
architecture and furnishings. The cave itself took 18 months to bore, ≥ The enormous complex is intended to get round the city’s planning
plumb and construct and houses Spa Terra , an Entertainment Cave laws, which state that buildings can be no more than eight storeys
seating up to 240 guests and the Trinitas high.
≥ One advantage of the unusual structure is that it would create space
in the centre of Mexico City, which is full of historic buildings which
cannot be demolished.
12
Busmann & Haberer | Cologne, Nordrhein‐Westfallen, Germany | 1986 Nikken Sekkei Co | Osaka, Japan | 1996
Leisure Temperate with dry winters Leisure, Office Humid subtropical
(Cwb) (Cfa)
≤ Footstep sounds from pedestrians with high heels or noise from ≥ This gymnasium consists of a main arena with seating for 10,000, a
skateboards or rolling suitcases are transmitted from vibrating sub‐arena, facilities for judo and kendo, conference rooms, and a
Below ground level ≈ 100% Below ground level ≈ 90%
beams inside the concert hall. The reason for this is among other sports information area.
Surface to ground ≈ 70% Surface to ground ≈ 80%
things the defective flooring. For this reason, the place above the
Depth ≈ 30m ≥ For the purpose of environmental preservation and effective use of Depth ≈ 30m
theater is closed during performances. the premises, most of the building including the main arena (30m
high, 110m diameter) was built underground. The roof is covered
≥ The concert hall is build in the building complex of the Ludwig with a 1m‐thick layer of soil and plants, realizing an undulating park
Museum. rich in vegetation. Natural daylight and air circulation in all dry areas
was insured with energy‐saving techniques, such as a ventilation
system that utilizes heat‐insulation and isothermal effects specific to
underground building
# http://www.bhbfh.de/index.php?id=139&tx_kbshop_pi1[folderId]=66&tx_k # http://nett21.gec.jp/ESB_DATA/EN/building/html/esb‐087.html
bshop_pi1[v]=41&cHash=b0502e7b7be691c38c500943d5fae8d2#images|1 # http://www.nikken.co.jp/en/projects/cultural/sports/post‐1.html
# http://de.wikipedia.org/wiki/K%C3%B6lner_Philharmonie
13
Fan Shuning, Zhang Xin| China | Idea Loess Plateau, Shaanxi province, China| from the Han dynasty 206 B.C.
Residential Humid subtropical Residential Humid subtropical
(Cfa) (Cfa)
≥ China extracts an average of 2 billion tons of coal each year to satisfy ≥ Generally carved out of a hillside or excavated horizontally from a
its energy demands. Apart from the environmental concerns, coal central “sunken courtyard”
Below ground level ≈ 100% Below ground level ≈ 100%
mining is an extremely dangerous profession which leads to more Surface to ground ≈ 100% ≥ Little building material is needed, which is scarce in the loess Surface to ground ≈ 60%
than 6000 deaths every year. Depth ≈ 500m plateau. Depth ≈ 8m
≥ The main concept behind this proposal is to make use of the ≥ An estimated 40 million people in northern China live in Yaodongs.
immense coal mines as an underground city where miners will have
access to a better quality of life through modern housing and
recreational areas. This underground metropolis will coexist with
regular cities and will integrate them through an exchange of goods
and services.
# http://chinablog.cc/2009/02/yaodong‐cave‐dwellings‐on‐loess‐plateau/
# http://www.evolo.us/architecture/underground‐metropolis/
# http://en.wikipedia.org/wiki/Yaodong
14
Takashi Yamaguchi | Kyoto, Japan | 1998 Taisei Corporation | Tokyo, Japan
Religious Humid subtropical Residential, Office, Infrastructure, Education Humid subtropical
(Cfa) (Cfa)
≥ To maintain the integrity of the historic building, the new temple ≥ In their infrastructure areas, they plan power generation, regional
was placed underground, if not rendered entirely invisible. heating, waste recycling and sewage treatment facilities. As shown
Below ground level ≈ 80% Below ground level ≈ 80%
in the accompanying pictures such underground space can be
Surface to ground ≈ 70% Surface to ground ≈ 70%
spherical or cylinder‐shaped.
Depth ≈ 6m Depth ≈ 100m
≥ Construction costs have been studied in considerable depth, a
12floor office space (80m deep) would cost about €440 million and a
80‐m diameter and 60m high infrastructure space placed on 110 m
underground would run about €530 million. Total cost for a city of
100,000 is estimated at €3 billion, roughly half the price of one high‐
priced surface acre on Tokyo's Ginza strip!
15
Bohlin Cywinski Jackson | New York, U.S.A.| 2010 Tadao Ando | Naoshima, Kagawa Prefecture, Japan | 2004
Retail Humid subtropical Leisure Humid subtropical
(Cfa) (Cfa)
≥ To ensure that the museum does not affect the beautiful scenery of
Naoshima, the majority of the building is located underground.
Below ground level ≈ 80% Below ground level ≈ 100%
Despite its positioning, it receives an abundance of natural light,
Surface to ground ≈ 80% Surface to ground ≈ 70%
changing the appearance of the artworks and the ambience of the
Depth ≈ 5m Depth ≈ 10m
space itself with the passage of the days and the seasons.
# http://www.benesse‐artsite.jp/en/chichu/index.html
# http://www.apple.com/retail/fifthavenue/gallery/gallery4.html
# http://www.vuw.ac.nz/architecture‐
# http://intransit.blogs.nytimes.com/2010/04/01/apple‐store‐most‐
onlineteaching/courses/arch403/assign1/matthew_colson_chichu.pdf
photographed‐in‐new‐york/
16
Tadao Ando | Tsuna‐gun, Hyogo, Japan | 1991 Emilio Ambasz | Fukuoka, Japan | 1994
Religious Humid subtropical Leisure, Office, Retail, Storage Humid subtropical
(Cfa) (Cfa)
≤ The roof of the building consist of a pool, which has different ≥ Underneath the park's fifteen one‐story terraces lies over one
thermal properties than an earth covered roof. million square feet of multipurpose space containing an exhibition
Below ground level ≈ 40% Below ground level ≈ 30%
hall, a museum, a 2000‐seat proscenium theater, conference
Surface to ground ≈ 50% Surface to ground ≈ 30%
≥ Surprisingly, the lotus pool is actually the roof of the temple, which facilities, governmental and private offices, as well as several
Depth ≈ 7m Depth ≈ 12m
is built partly underground; to reach the sanctuary visitors descend a underground levels of parking and retail space
stairway which cuts the oval shape of the pool in two.
# Barker, M., 1986. Using the Earth to Save Energy: Four Underground
Buildings. Tunneling and Underground Space Technology
# http://www.greenroofs.com/projects/pview.php?id=476
# http://michiganmodern.org/architects‐designers‐firms/architects/gunnar‐
# http://www.archidose.org/Dec00/121100.html
birkerts/
17
Davis Buckley Architects and Planners| Washington, DC, U.S.A. | Concept Beyer Blinder Belle Architects | Shanghai, China | 2011
Leisure Humid subtropical Leisure Humid subtropical
(Cfa) (Cfa)
≥ Two glass garden‐like pavilions invite visitors in to the museum and ≥ The lobby is lit only by sunshine; in the evenings, artist Ding
fill the space below with natural light. Glass pavers set within the Below ground level ≈ 70% Shaoguang’s massive blue‐green rainforest painting will glow with Below ground level ≈ 80%
stone plaza and between the pavilions create a varied pattern of Surface to ground ≈ 70% LED light, echoing the stained‐glass windows of European cathedrals. Surface to ground ≈ 80%
light on the ceiling of the main atrium. Depth ≈ 4m Better still, the building plunges 26 meters underground, providing Depth ≈ 30m
≥ However there is no room for it to fit nicely into the square! At least, natural heating and air conditioning while cutting both its costs and
above ground. Davis Buckley’s proposal for the Museum is for two carbon footprint.
4,000‐square foot, above‐ground glass‐entry pavilions. These are
supposed to symbolize the visibility of law enforcement but also
provide an unobtrusive entrance on the historic square.
# http://www.homedesignfind.com/green/10000‐square‐foot‐underground‐
bunker‐will‐remain‐forever/ # http://www.beyerblinderbelle.com/?ID=196
# http://www.longhiarchitect.com/home.html
18
‐ | Springfield, Missouri, U.S.A. | ‐ Norman Foster | London, United Kingdom | 1999
Storage Humid subtropical Infrastructure, Retail Maritime temperature
(Cfa) (Cfb)
≥ Going underground is an environmentally friendly business decision ≥ The main reason for the station’s enormous dimensions was the
without the added cost of an aboveground green facility. Because great number of passengers predicted; as many as 50.000 daily.
Below ground level ≈ 100% Below ground level ≈ 100%
Springfield Underground is 100 feet below the surface, it is below These predictions have outgrown, with as many as 70.000+ today.
Surface to ground ≈ 100% Surface to ground ≈ 90%
the weather. There is no seasonal temperature variation, meaning Depth ≈ 30m ≥ Above ground there is little sign of the vast interior: two curved Depth ≈ 25m
that you spend a smaller, more uniform amount on utilities. And glass canopies at the east and west ends of the station cover the
there are no worries about weather‐related catastrophes the way entrances and allow daylight into the ticket hall below. A public park
aboveground facilities do. is situated between the two canopies, above the station concourse.
# http://www.greenroofs.com/archives/sg_jan‐apr04.htm
# http://www.springfieldunderground.com/
# http://en.wikipedia.org/wiki/Canary_Wharf_tube_station
19
Reardon Smith Architects | Surrey, London, United Kingdom| Concept Reardon Smith Architects | Surrey, London, UK | ?
Residential Maritime temperature Residential Maritime temperature
(Cfb) (Cfb)
≥ In addition to the green integrated into the building, the proposal ≥ Fridge is cooled by air coming underground through foundations.
includes the addition of extensive on‐site re‐vegetation and re‐
Below ground level ≈ 90% ≥ Skylight in roof lets in natural feeling light. Below ground level ≈ 0%
organization of existing spaces (such as parking) that will actually ≥ Solar panels for lighting, music and computing.
Surface to ground ≈ 70% Surface to ground ≈ 60%
leave the site even more eco‐friendly than it is now.
Depth ≈ 10m Depth ≈ 0m
# http://inhabitat.com/5‐star‐underground‐hotel‐in‐london/ # http://www.simondale.net/house/
20
Bill Lishman | Purple Hill, UK | 1988 J.R.R. Tolkien | New Zealand
Residential Maritime temperature Residential Maritime temperature
(Cfb) (Cfb)
≥ “To pursue building a house such as this the costs are higher than ≥ A fictional place where earth‐sheltered homes are build to house
building conventionally because it involves moving tons of earth and “Hobbits” in the Lord of the Rings trilogy.
Below ground level ≈ 0% Below ground level ≈ 0%
a great deal of work by skilled artisans. The costs will be recouped
Surface to ground ≈ 90% Surface to ground ≈ 90%
during the life of the house and in the long run it will be cheaper and
Depth ≈ 3m Depth ≈ 3m
more rewarding but the initial building takes a great deal of
dedication”.
# http://www.williamlishman.com/underground.htm # http://students.english.ilstu.edu/rwohara/creation/shire.html
21
Henket & Partners architecten| Arnhem, Gelderland | 2004 Marcel Breuer, Piero Nervi and Bernard Zehrfuss | Paris, France | ‐
Educational Maritime temperature Office, Leisure Maritime temperature
(Cfb) (Cfb)
≥ Application of special sun blocking cloths between trusses, to spread ≥ One of the three buildings that completes the headquarters site of
incoming light. The cloths are made of plasticized glass fiber. the UNESCO House in Paris, consisting of two office floors hollowed
Below ground level ≈ 100% Below ground level ≈ 100%
≥ For fire safety use is made of windows that open during a fire to Surface to ground ≈ 80% out below street level, around six small sunken courtyards, Surface to ground ≈ 70%
release smoke and heat out of the building, to create a smokefree Depth ≈ 10m containing many remarkable works of art and are open to the public. Depth ≈ 6m
environment for easier evacuation.
≥ Ventilation grids of 1.2m in height are applied in the glass facades to
release daily heat.
≥ Lowest floor at 10m depth.
# http://www.unesco.org/new/en/unesco/about‐us/who‐we‐
are/history/paris‐headquarters/
# http://www.abt.eu/nl/projecten.asp?projectcatid=4&projectid=68
# http://us.franceguide.com/UNESCO‐IN‐
FRANCE.html?NodeID=1&EditoID=83582
22
I.M. Pei, Macary, Duval | Paris, France | 1993 Foster + Partners | Carmarthenshire, U.K.| 2000
Leisure Maritime temperature Educational, Retail, Leisure Maritime temperature
(Cfb) (Cfb)
≥ Roughly at midpoint, the avenue is interrupted by a small upside‐ ≥ The buildings concrete substructure is banked to the north to
down glass pyramid, a witty reminder of its famous aboveground provide protection from cold northerly winds and is concealed by a
Below ground level ≈ 100% Below ground level ≈ 70%
counterpart. On sunny days, it reflects all the colors of the rainbow. covering of turf so that the three entrances on the northern side
Surface to ground ≈ 80% Surface to ground ≈ 50%
≥ Certain measures create the feeling of being outside: the lighting Depth ≈ 10m
appear to be cut discreetly into the hillside. Within this base are a
Depth ≈ 6m
generates a kind of accelerated perspective, making the space seem public concourse, a café, educational spaces and service installation.
even higher and lighter, while the ventilation has been designed to ≥ To optimize energy usage, conditions inside and outside are
produce an occasional breeze, and even noticeable changes in monitored by a computer‐controlled system. This adjusts the supply
temperature. of heat and opens glazing panels in the roof to achieve desired levels
of temperature, humidity and air movement.
≥ The principal heat source is a biomass boiler, located in the parks
Energy Centre, which burns timber trimmings. This method is
remarkably clean when compared with fossil fuels.
≥ Rainwater collected from the roof supplies grey water for irrigation
and flushing lavatories while waste from the lavatories is treated in
reed beds before release into a watercourse.
23
Make Architects | North West England, UK | 2009 Pattersons | Arrowtown, New Zealand | 2007
Residential Maritime temperature Residential Maritime temperature
(Cfb) (Cfb)
≥ The four‐bedroom, single‐storey family home is deliberately ≥ Each home will be between 367 and 700 square meters, with turf
embedded into the contours of the Pennine hillside to minimize the Below ground level ≈ 80% and pebble roofs. Below ground level ≈ 40%
impact on the surrounding moorland and has a roof of flora and Surface to ground ≈ 70% ≥ Kiwi tycoon Michael Hill wanted to build homes on and around his Surface to ground ≈ 40%
meadow grasses which flows seamlessly over the property and into Depth ≈ 3m golf course, but he didn’t want them to interfere with the views of Depth ≈ 3m
the landscape. the area.
≥ It has been designed to consume less energy than it uses; a ground
source heat pump, photovoltaic panels and a wind turbine will
generate on‐site renewable energy.
# http://www.makearchitects.com/#/projects/9067/
# http://dornob.com/uk‐celebrity‐plans‐on‐building‐huge‐underground‐eco‐ # http://www.pattersons.com/
home/
24
‐ | Holmpton, U.K. | 1954 Future Systems | Druidston, Pembrokeshire, U.K.| 1998
Military Maritime temperature Residential Maritime temperature
(Cfb) (Cfb)
≥ On top of this the bunker was provided with two floors accounting ≥ The basic design of Malator is very simple, with essentially one room
for an internal height of 22ft. Above this a steel shuttered fabrication Below ground level ≈ 100% inside, divided by prefabricated colored pods, while on the outside Below ground level ≈ 80%
to form the ceiling and then the outer shell of 10ft of concrete. Surface to ground ≈ 100% the house melds with the surrounding landscape. Surface to ground ≈ 85%
Depth ≈ 30m Depth ≈ 3m
# http://en.wikipedia.org/wiki/Malator
# http://www.subbrit.org.uk/rsg/sites/h/holmpton/
# http://www.s4c.co.uk/tycymreig/e_p8main.shtml
25
2030 Architects |Appleby, Cumbria, U.K. | ~2010 Denton Corker Marshall| Phillip Island, Victoria, Australia| 1989
Residential Maritime temperature Residential Maritime temperature
(Cfb) (Cfb)
≥ Cumbria's first earth‐sheltered dwelling and the subject of a Channel ≥ Buried into the dunes, the house is visible from the beach as a low
Four "Grand Designs" programme, demonstrated how such Below ground level ≈ 0% black line – the colour of the rocks – with ragged tufts of dune grass Below ground level ≈ 40%
construction methods can achieve a light and airy, zero heat dwelling Surface to ground ≈ 30% above it. It is completely hidden from the landward side. The Surface to ground ≈ 60%
for a similar cost to that of more conventional buildings. A simple Depth ≈ 5m objective was to maintain a low profile and to have an internal focus Depth ≈ 3m
mechanical ventilation and heat recovery system, powered in part by to the house, avoiding engagement with the surrounding context.
a small photovoltaic array aided by a 6kw wind turbine, provides a ≥ The house is a long thin concrete box, black inside and outside, set
healthy interior environment. along one edge of a large square courtyard contained by three metre
high black concrete walls with dune berms ramped up to roof level
on three sides. On the open ocean elevation, windows are sized and
positioned within each room to act as picture frames to the views,
and the proportions and locations of the windows are determined by
these internal considerations. The courtyard offers protection from
winds and is a north facing sun trap in winter.
# http://www.2030architects.co.uk/#!residential/c20x9 # http://www.architonic.com/aisht/marshall‐house‐denton‐corker‐
# http://www.youtube.com/watch?v=lnD7OD2svbI&feature=player_embed marshall/5100501
ded # http://www.dentoncorkermarshall.com/projects/phillip‐island‐house/
26
Gardner Stewart Architects | London, U.K. | 2001 LOM | Devon, U.K. | 2010 (Concept)
Leisure, Retail Maritime temperature Residential Maritime temperature
(Cfb) (Cfb)
≥ At an architectural level, these Passive Annual Heat Storage buildings ≥ An innovative 3,500 ft² low carbon home in the Devon countryside,
are amongst the most ecologically responsible in the country and Below ground level ≈ 80% designed to offer best practice in environmental sustainability. The Below ground level ≈ 50%
have been designed to minimise the demand on all natural Surface to ground ≈ 50% site is located close to an area of outstanding natural beauty, and the Surface to ground ≈ 65%
resources. They have the following key environmental attributes: Depth ≈ 3m house is built into a hillside to reduce visual impact and provide a Depth ≈ 1‐6m
≥ No heat input requirement means a corresponding dramatic high level of insulation.
reduction in emissions. Boreholes provide entire water ≥ The building uses a green roof, a triple glazed primary facade with
requirements, including lakes, irrigation & buildings solar shading, geothermal and waste air heat reclamation, rainwater
≥ Thermal stability across the year, due to entire building acting as storage and grey water recycling systems.
heat sump
≥ Low‐tech a/c with air naturally cooled & filtered by series of
underground pipes
≥ Virtually maintenance free beyond cleaning requirements
≥ Promotion of immense wealth of biodiversity in both the park and
buildings.
# http://inhabitat.com/spiky‐ecology‐pavilion‐sprouts‐in‐east‐london/\
# http://www.lom‐fdp.com/lom/portfolio/private‐client‐earth‐sheltered‐
# http://www.gardnerstewartarchitects.com/portfoliomenu/portfoliomenu.
house/
htm
27
‐ | Saenautasel / Glaumbaer, Iceland| 10th Century ‐ | Samseong‐dong , Gangnam‐gu area of Seoul, South Korea |‐
Residential Subarctic Retail, Infrastructure, Office, Recreation Hot Summer Continental
(Dsc) (Dwa)
≥ The Icelandic turf house was the product of a difficult climate, ≥ Asia's largest underground shopping mall with an area of about
offering superior insulation compared to buildings solely made of 85,000m2.
Below ground level ≈ 0% Below ground level ≈ 80%
wood or stone, and the relative difficulty in obtaining other
Surface to ground ≈ 60% ≥ In it resides hundreds of shops, the mall houses two food courts, a 16‐ Surface to ground ≈ 40%
construction materials in sufficient quantities. screen multi‐cinema complex, an aquarium attraction, a large
Depth ≈ 0m Depth ≈ 15m
≥ The floor of a turf house could be covered with wood, stone or earth bookstore, and the Kimchi Field Museum
depending on the purpose of the building. They contain grass on
their roofs.
# http://www.lifeinkorea.com/travel2//215
# http://en.wikipedia.org/wiki/Icelandic_turf_houses
# http://www.coexmall.com/eng/index.asp
28
Byoungsoo Cho | Yangpyeong‐gun, Gyeonggi‐do, Republic of Korea | 2009 BWBR Architects, Inc. | University of Minnesota, Minneapolis, U.S.A.| 1983
Residential Hot Summer Continental Educational Warm Summer contintental
(Dwa) (Dwb)
≥ The house uses a geothermal cooling system with a radiant floor ≥ Earth‐sheltered building 95% underground
heating system under the rammed clay and concrete floor. Off‐peak
Below ground level ≈ 100% ≥ Winner 1983 ASCE Outstanding Civil Engineering Achievement Below ground level ≈ 40%
electricity is used at night to heat the small gravel under the floor. Award.
Surface to ground ≈ 70% Surface to ground ≈ 50%
≥ A combination of passive cooling and geothermal tubes which are Depth ≈ 3m Depth ≈ 21m
buried in the earth around the buildings keep the temperature cool
in summer and warm in winter.
# http://www.archdaily.com/73831/earth‐house‐bcho‐architects/ # Barker, M., 1986. Using the Earth to Save Energy: Four Underground Buildings.
# http://inhabitat.com/soeul‐gains‐an‐underground‐house‐by‐byoung‐soo‐ Tunneling and Underground Space Technology
cho/tub2/ # http://www.mbjeng.com/home/projects/education/umn‐civil‐engineering
29
Patkau Architects | Fallingwater, Pennysylvania, U.S.A.| 2010 ‐ Mined space | Kansas City, Missouri, U.S.A. | 1940s
Residential Hot Summer Continental Industrial, Storage, Office Hot Summer Continental
(Dfa) (Dfa)
≥ Patkau Architects won a competition run by the Western ≥ 5.060.000 m3, 4.5km2 manmade mines, claimed to be the world’s
Pennsylvania Conservancy, an institute that looks after the largest underground storage facility.
Below ground level ≈ 90% Below ground level ≈ 100%
preservation and maintenance of Fallingwater. Surface to ground ≈ 90% ≥ Currently 460,000 m³ is occupied and 920,000 m³ are "improved." Surface to ground ≈ 98%
≥ The six new units will serve as accommodation for participants in the Depth ≈ 3m About 13,000 m2 of available space are added each year as active Depth ≈ ?m
institute's further‐education programme. mining continues.
≥ The jury praised the subtle, yet progressive, character of the design, ≥ The mine naturally maintains temperatures between 18 to 20˚C
with its minimal impact on the landscape, which also met the criteria year‐round.
of sustainability and energy efficiency that had been set down. ≥ Fully sprinkler installed
≥ Constant relative humidity levels.
# http://www.architonic.com/ntsht/camouflage‐architecture‐underground‐
buildings/7000497 # http://en.wikipedia.org/wiki/SubTropolis
# http://www.patkau.ca/ # http://www.huntmidwest.com/subtropolis/movies/overview.html
30
‐ |Toronto, Ontario, Canada | from 1900 Ushida‐Findlay Partnership | Tokyo, Japan | 1994
Retail, Infrastructure, Office, Recreation Hot Summer Continental Residential Hot Summer Continental
(Dfa) (Dfa)
≥ PATH is the largest underground shopping complex in the world with ≥ The more intimate rooms are enveloped as though within protective
371,600 m² of retail space. capsules, while the house itself folds around an inner courtyard. The
Below ground level ≈ 80% Below ground level ≈ 0%
≥ More than 50 buildings/office towers are connected through PATH. Surface to ground ≈ 70%
height of surrealism is its blue, egg‐shaped bathroom, which is at the
Surface to ground ≈ 40%
Twenty parking garages, five subway stations, two major department home’s center.
Depth ≈ 30m Depth ≈ 3m
stores, six major hotels, and a railway terminal are also accessible
through PATH.
31
‐ | Festus, Missouri, U.S.A.| ‐ Helmut Jahn| Chicago, U.S.A. | 2008
Residential Hot Summer Continental Educational Hot Summer Continental
(Dfa) (Dfa)
≥ This enormous mansion was made in an existing cave in the small ≥ The Mansueto Library houses cutting‐edge facilities for the
town of Festus, Missouri. Before it was a private residence, the cave preservation and digitization of physical books, as well as a high‐
Below ground level ≈ 0% Below ground level ≈ 60%
was used as a concert hall and a skating rink, among other things. density underground storage system with the capacity to hold 3.5
Surface to ground ≈ 80% Surface to ground ≈ 65%
Depth ≈ 0m million volume equivalents. Depth ≈ 10m
# http://webecoist.momtastic.com/2010/01/20/going‐green‐underground‐16‐ # http://www.architonic.com/ntsht/underground‐structures/7000652
subterranean‐eco‐buildings/9‐huge‐cave‐home‐missouri/ # http://www.murphyjahn.com/projects
32
Hyvamaki‐Karhunen Parkkinen | Itäkeskus, Helsinki, Finland | 1993 Timo and Tuomo Suomalainen | Etu‐Töölö, Helsinki, Finland | 1969
Recreational Hemiboreal Religious Hemiboreal
(Dfb) (Dfb)
≥ The entire complex is built within the rocks, and the interior reflects ≥ The interior is excavated an built into the rock, but is bathed in
the contours of the exterior rocks. natural light entering through the glazed dome.
Below ground level ≈ 100% Below ground level ≈ 70%
≥ It is made for 1.000 visitors and can be used as a bomb shelter for Surface to ground ≈ 98% ≥ The church is frequently used as a concert venue due to its excellent Surface to ground ≈ 30%
3.800 people. Depth ≈ ?m acoustics which are ensured by the rough, virtually unworked rock Depth ≈ 5m
surfaces.
# http://en.wikipedia.org/wiki/Temppeliaukio_Church
# http://www.hkp.fi/
# http://www.muuka.com/finnishpumpkin/churches/helsinki/chteh/church_c
# http://www.getunderground.fi/web/printpreview.aspx?printpreview=1&refi
hteh.html
d=148
33
Gunnar Birkert | Ann Arbor, Michigan, U.S.A. | 1982 ‐ | Wieliczka, Poland| 13th century
Educational Hemiboreal Leisure (Tourism) Hemiboreal
(Dfb) (Dfb)
≤ The energy performance of this building has not been superior to an ≥ Several hundreds of years of rock salt exploitation have shaped the
above‐grade building structure of the same size built for the same spatial arrangement of its excavated structure. Lying on nine levels,
Below ground level ≈ 50% Below ground level ≈ 100%
purpose concealed under the town, the mine reaches down to the depth of
Surface to ground ≈ 50% Surface to ground ≈ 100%
Depth ≈ 15m 327 metres. Subterranean Wieliczka consists of nearly 300 Depth ≈ 327m
≥ The legal research building for the University of Michigan is kilometres of corridors and almost 3,000 chambers. The tourist route
designed to protect the existing gothic revival buildings and accessible to visitors includes a 3.5‐kilometres section located from
courtyards. 64 to 135 metres below ground level.
≥ The Wieliczka mine functions also as a sanatorium, for the micro‐
climate in the underground spaces is particularly beneficial in the
treatment of upper respiratory disorders, asthma and allergy. In
1997 the Underground Rehabilitation and Medical Centre was
opened. Owing to the active therapy in the Centre, the patients
breathe in the air rich in sodium, calcium and magnesium chloride,
and thus efficiently get rid of some disorders caused by civilization.
# Barker, M., 1986. Using the Earth to Save Energy: Four Underground
Buildings. Tunneling and Underground Space Technology
# http://michiganmodern.org/architects‐designers‐firms/architects/gunnar‐ # http://www.hotelraider.com/salt‐mine‐wieliczka/
birkerts/
34
John E. Barnard Jr. | Marstons Milss, Massachusetts, U.S.A. | 1972 Claus Bonderup | Jutland, Denmark | ~1970
Residential Hemiboreal Residential Hemiboreal
(Dfb) (Dfb)
≥ One‐fifth normal heating cost, 25% lower building cost, privacy from
neighbors and no unsightly damage to surrounding property
Below ground level ≈ 100% Below ground level ≈ 50%
Surface to ground ≈ 80% Surface to ground ≈ 80%
Depth ≈ 4m Depth ≈ 3m
# http://we‐make‐money‐not‐art.com/archives/2009/08/sorry‐out‐of‐gas‐
architectures.php # http://newspirit‐square1.blogspot.com/2010/06/claus‐bonderups‐vacation‐
# Popular Mechanics, June 1974 house.html
35
Hans hollein | Salzburg, Austria | 1989 (concept) ‐ | Pionen, Stockholm, Sweden | 2008
Leisure Hemiboreal Storage Hemiboreal
(Dfb) (Dfb)
≥ 1989 Hans Hollein’s project was the winner of an international ≥ Originally a nuclear bunker: The data center is housed in what was
invited competition for a museum in the Mönchsberg—a large rock Below ground level ≈ 95% originally a military bunker and nuclear shelter during the Cold War Below ground level ≈ 100%
formation that is one of the principal features in the city of Salzburg. Surface to ground ≈ 90% era. The facility still has the code name from its military days: Pionen Surface to ground ≈ 100%
The singular feature of his design is the fact that the proposed Depth ≈ 50m White Mountains. Depth ≈ 30m
museum is enclosed entirely within the volume of the Mönchsberg ≥ Located in central Stockholm below 30 meters (almost 100 ft) of
rock on three levels. It has no visible façade. The gallery spaces on bedrock: The facility has 1110 sqm (11950 sq ft) of space and is
the upper two levels are covered by a vast system of skylights that located below 30 meters of solid bedrock (granite) right inside the
offer light to the subterranean museum. Building inside the rock city.
allows free, a–tectonic expansion in all directions. The project was ≥ 1.5 megawatt of cooling for the servers: Cooling is handled by
continued as a feasibility study for a “Salzburg Guggenheim” and, Baltimore Aircoil fans producing a cooling effect of 1.5 megawatt,
after optimizing the program in a transformed, reduced condition, enough for several hundred rack‐mounted units.
was being discussed as a location for cooperation between
Kunsthistorisches Museum, Wien, Guggenheim Museum, New York ≥ Work environment with simulated daylight and greenhouses: For a
and Eremitage, Sankt Petersburg. pleasant working environment the data center has simulated
daylight, greenhouses, waterfalls and a huge 2600‐liter salt water
fish tank.
# http://royal.pingdom.com/2008/11/14/the‐worlds‐most‐super‐designed‐
data‐center‐fit‐for‐a‐james‐bond‐villain/
# http://www.subbrit.org.uk/rsg/sites/h/holmpton/
# http://abdtechnology.com/our‐company/data‐centers/swedish‐facility‐
pionen‐stockholm‐sweden/
36
Montreal, Quebec , Canada| from 1962 Peter Vetsch | Dietikon, Switzerland | 1993
Retail, Infrastructure, Office, Leisure, Education Subartic Residential Tundra
(Dfc) (ET)
≥ With over 32 km of tunnels spread over more than 12 km2, ≥ The organic construction consists of shotcrete, with a 25 cm layer of
connected areas include shopping malls, apartment buildings, polymer bitumen and recycled glass foam on top.
Below ground level ≈ 80% Below ground level ≈ 0%
hotels, condominiums, banks, offices, museums, universities, seven
Surface to ground ≈ 70% ≥ Access to the houses is at the sides, entirely out of sight to the Surface to ground ≈ 40%
metro stations, two commuter train stations, a regional bus terminal benefit of their free forms.
Depth ≈ 30m Depth ≈ 0m
and the Bell Centre amphitheater and arena. ≥ Interior room such as kitchens and bathrooms are illuminated by
domed skylights.
37
SeARCH & Christian Müller Architect | Vals, Switzerland | 2008 Moe‐Levorsen | Gjøvik, Oppland, Norway | 1993
Residential Tundra Leisure Tundra
(ET) (ET)
≥ The introduction of a central patio into the steep incline creates a ≥ World’s largest cavern hall for public use.
large façade with considerable potential for window openings.
Below ground level ≈ 100% ≥ An ice hockey rink located within a mountain hall, with a capacity for Below ground level ≈ 100%
≥ The viewing angle from the building is slightly inclined, giving an Surface to ground ≈ 70% 5,500 spectators, the hall also features a 25‐meter swimming pool Surface to ground ≈ 98%
even more dramatic view of the strikingly beautiful mountains on Depth 5m and telecommunications installations. Depth ≈ ?m
the opposite side of the narrow valley.
# http://www.youtube.com/watch?v=u7CWjtM1938
# http://www.treehugger.com/sustainable‐product‐design/underground‐
# http://en.wikipedia.org/wiki/Gj%C3%B8vik_Olympic_Cavern_Hall
houses‐vals‐house‐by‐search‐and‐christian‐ma14ller‐architects.html
# http://www.fjellhallen.no/gammel/engindex.html
# http://www.christian‐muller.com/CMA_Projects‐HVV.html
38