SERIES 2000

SERIES 2000 TEMP.

TEMPERATURE REGULATOR
REGULATOR

SIZES 1/2" – 2"


CONTROLS -25 to 400°F
● Self-actuated
● Two and Three Way Valve Bodies
● Single or Double Seat
● Overtemperature Protection
● SpringLoaded Teflon Chevron Type
Packing Assembly
● Double Guided Stainless Steel Monolithic
Disc Assembly
● Stainless Steel Seat Rings and Disc
SERIES 2000 TEMPERATURE REGULATOR
● Adjusting Key Attached
APPLICATION DATA
● Galvanized Iron Union Ends
DIRECT ACTING REVERSE ACTING
● Bottle Washing Machinery ● Induction Furnaces ● Full Ported and Full Flow Bronze Body
● Steam Tables ● Industrial Compressors ● Copper Bulb with 8' Armored Capillary
● Plating Tanks ● Cold Storage Boxes
● Heating Ducts ● Cooling Ducts MODELS
● Fuel Oil Heaters ● Engine Jacket Cooling ● Type 2010 — Single Seat, Direct Acting
● Cooking Vats ● Liquid Chillers ● Type 2020 — Single Seat, Reverse Acting
● Water Heaters GAS SERVICE ● Type 2030 — Double Seat, Direct Acting
● Heat Exchangers ● Oil Treaters ● Type 2040 — Double Seat, Reverse Acting
● Parts Washer ● Line Heaters ● Type 2050 — Three-way Mixing and Diverting
THREE-WAY MIXING ● Separators ● Type 2060 — Gas Service-15 psig maximum. If pressure
● Fire Tube Boiler ● Glycol Dehydrators exceeds 15 psi, a pressure reducing regulator should be
used ahead of the temperature regulator.
● Internal Combustion Engine ● Storage Tanks

VALVE RATINGS OPTIONS


● Dial Temperature Gage (Indicating)
Valve Ends Pressure Temperature
ASME/ANSI PSIG (bar) °F (°C) ● Stainless Steel Bulb
Class 250 NPT 250 (17.2) 400 (204) ● Stainless Steel Armored Capillary
● Capillary lengths greater than 8'
Canadian Registration # OC 0591.9C ● Extra Large Bulb
● Union Bushings & Wells

- 86 -
SERIES 2000

SERIES 2000 TEMP.


TEMPERATURE REGULATOR

REGULATOR
SPECIFICATION
The valve shall be self-operated, requiring no external energy source. It shall have single
or double stainless steel seats with double guided monolithic disc assembly for proper
alignment. The valve shall be direct acting (heating) or reverse acting (cooling) and have
two way or three way operation. The packing assembly shall be spring loaded, self
adjusting with chevron type teflon packing. The thermal system line and bulb assembly
shall be partially filled with a liquid/gas combination and in a range selected for fast
response. The valve rating shall be 250 PSIG at 400°F. Body materials shall be bronze.
MODEL 2060 FOR GAS SERVICE ONLY: The valve shall be self-operated, requiring no
external energy source and designed to control process temperature by regulating gas
flow. It shall be normally open and close with increased temperature. “Bubble tight” dead TYPE 2010-2040 DIRECT
end shutoff shall be provided by Buna-N vulcanized to disc backing. The packing
assembly shall be spring loaded, self adjusting with chevron type teflon packing. The
& REVERSE ACTING
thermal system line and bulb assembly shall be partially filled with a liquid/gas
combination and in a range selected for fast response. The valve rating shall be 15 PSIG.
Body materials shall be nodular iron.
MATERIALS OF CONSTRUCTION
ITEM TYPE 2010-2050 TYPE 2060
Body …………Bronze ASTM B62 C83600 ………Ductile Iron ASTM A536 65-45-12
Trim ……………Stainless Steel ……………………Buna-N
Packing ………Teflon ………………………………Buna-N
Unions…………Iron …………………………………Iron
Yoke …………Steel ………………………………Steel
Cap ……………Aluminum …………………………Aluminum
Bellows ………Bronze ……………………………Bronze
Spring …………Steel ………………………………Steel
Capillary ………Copper ……………………………Copper
Bulb……………Copper ……………………………Copper
Armor …………Bronze ……………………………— TYPE 2050 THREE WAY
Stem …………304 Stainless Steel ………………304 Stainless Steel
Disc ……………304 Stainless Steel ………………Buna-N
Seat……………303 Stainless Steel ………………—
TYPE 2010-2040 DIRECT & REVERSE ACTING
DIMENSIONS inches (mm) AND WEIGHTS pounds (kg)
Dimensions Shipping
Weight
Size Type No. A B C D E F† (Approx.)
1
/2"(A, B, 93/4 81/2 51/2 31/2 213/16 8 Ft. 10
C, D, E) 2010
1/2, 3/4 2020 (248) (216) (140) (89) (71) (4.5)
1
/2" 2030 127/16 93/4 73/16 31/2 213/16 8 Ft. 13
3
/4" 2040 (316) (248) (182) (89) (71) (5.9)
127/16 93/4 73/16 31/2 213/16 8 Ft. 13
1" 2010 (316) (248) (182) (89) (71) (5.9)
1
1 /4" 2020 20 (9.1)
2030 127/8 931/32 815/16 31/2 213/16
11/2" (327) (253) (227) (89) (71) 8 Ft. 25 (11)
2" 2040 30 (14)

TYPE 2050 THREE WAY


TYPE 2060 GAS SERVICE DIMENSIONS inches (mm) AND WEIGHTS pounds (kg)
Dimensions Shipping
TYPE 2060 GAS SERVICE DIMENSIONS Weight
inches (mm) AND WEIGHTS pounds (kg) Size A B D F† K L E (Approx.)
12
/" 12 (5.5)
Dimensions 137/8 93/4 31/2 35/16 35/8
3
Shipping /4" 8 Ft. 12 (5.5)
(352) (248) (89) (84) (92)
Size A B C D F† Weight 1" 13 (5.9)
(Approx.) 11/4" 1421/32 931/32 31/2 41/8 411/16 213/16 27
1
/" 8 Ft. (71)
2
34 93/4 81/2 55/8 31/2 10 Ft. 8 11/2" (372) (253) (89) (105) (119) (12)
/" (248) (216) (143) (89) (3 m.) (3.6)
1" 147/8 931/32 31/2 43/16 47/8 33
2" 8 Ft.
(378) (253) (89) (106) (124) (15)
F†See following pages for standard lengths, ranges, bulb
sizes and maximum line lengths.
- 87 -
SERIES 2000 TEMPERATURE REGULATOR
SERIES 2000 TEMP.

SELECTION
REGULATOR

DIRECT & REVERSE ACTING & THREE WAY FLOW AND PRESSURE RATINGS psig (bar)
Single Seat Double Seat Three Way
Type Number Type Number
Flow Max. Flow Max. Flow Max. Difference
Size
Coefficient Upstream Coefficient Upstream Type Coefficient Between Inlet
Direct Reverse Cv Pressure Direct Reverse Cv Pressure Number Cv Pressures*
1
/2"C .40
1
/2"D 1.00 250
1
/2"E 1.80 (17.2) NOT AVAILABLE IN NOT AVAILABLE IN
1
/2"A 3.29 DOUBLE SEAT THREE WAY
1 200
/2"B 4.29
(13.8)
1 140 140
/2"T 2101 2201 5.22 7.93 5.22
(9.7) (9.7)
3 2010 2020 90 90
/4"T 6.85 (6.2) 10.4 6.85 (6.2)
65 2103 2203 250 65
1"T 9.15 12.9 250 9.15
(4.5) (4.5)
2030 2040 (17.2) 2050
40 40
11/4"T 14.3 20.6 14.3
(2.8) (2.8)
30 30
11/2"T 15.1 24.8 15.1
(2.1) (2.1)
20 20
2"T 17.2 (1.4) 33.0 17.2 (1.4)

SIZING INFO
PAGE 91

RANGES, BULB SIZES & MAXIMUM LINE LENGTHS


How to Select Range & Bulb Size
● Select a temperature range with the Short Ranges Long Ranges †Max. Maximum
control point in the upper half of the (Gold Spring) (Silver Spring) Bulb Line Over-Temperature
temperature range. °F °C °F °C Size Length °F °C
● Determine line length required (8' is 45 to 115 7.2 to 46 45 to 145 7.2 to 63 X Large 40 Ft. 450 232
standard).
65 to 140 18 to 60 65 to 170 18 to 77 450 232
● Use line length and temperature X Large 40 Ft.
range to find correct bulb size in 120 to 200 49 to 93 120 to 230 49 to 110 Small 40 Ft. 300 149
chart at right. 240 to 310 116 to 154 240 to 340 116 to 171 Small 40 Ft. 350 177
EXAMPLE: 280 to 375 138 to 190 280 to 415 138 to 212 Small 40 Ft. 450 232
Control point: 130°F.
Temperature range: 65/140°F.
Line length: 15' †Standard line lengths are 25' and 40'.
SOLUTION:
Bulb size: extra large – G = 155⁄8"

BULB DIMENSIONS* inches (mm)


G I J
Bulb Sizes U
Copper Stain. Stl. Coated Plain Union Well (NPT)
Small 133/8 131/4 113/8 101/2 5
/8 5
/8 3
/4 3
GAS SERVICE BULB & WELL
/4 or 1
(340) (337) (289) (267) (16) (16) (19) DIMENSIONS inches (mm)
Large 155/8 151/8 131/4 121/2 1 1 11/8 I
1 E G U J
(397) (384) (337) (317) (25) (25) (29) Bulb Well (NPT)
Extra Large 19 185/8 19 16 1 1 11/8 81/4 73/8 25
/32 15
/16 711/16
1 1
(483) (473) (483) (406) (25) (25) (29) (210) (187) (20) (24) (195)

- 88 -
SERIES 2000 TEMPERATURE REGULATOR

SERIES 2000 TEMP.


REGULATOR
CODE SELECTION
Line &
CHART Model Orifice Inlet – Bulb Range
Size Size Style Mat’l ºF

2 0 1 0 T C - G Q K
1 2 3 4 5 6 7 8 9
Model - Orifice - Inlet Size - Material† - Range ºF -
Position 1, 2, 3 & 4 Position 5 Position 6 Position 8 Position 9
2010 = Single Seat, A C = 1/2 Q = Copper Bz Armor 8' C = 45/115
Direct Acting B D = 3/4 R = Copper Bz Armor 15' D = 45/145
2020 = Single Seat, C E =1 N = Copper Bz Armor 25’ E = 65/140
Reverse Acting D F = 11⁄4 P = Copper Bz Armor 40’ F = 65/170
2030 = Double Seat, E G = 11⁄2 T = SS Unarmored 8' J = 120/200
Direct Acting T = Standard H =2 V = SS Unarmored 15' K = 120/230
2040 = Double Seat, Line & Bulb Style - W = SS Unarmored 25’ L = 240/310
Reverse Acting Position 7 X = SS Unarmored 40’ M = 240/340
2050 = Three Way G = Indicating Z = Other N = 280/375
N = Non-indicating P = 280/415
Z = Other
† For SS Armored Thermal Assembly Material, add (-TV) at the end of the code (ex.: 2010TC-NTH-TV)
† Small bulb standard for J-1 range and higher.
Extra large bulb standard for D range and lower.
Large bulb standard for E and F range

THERMOWELL UNION BUSHINGS

WELLS UNION BUSHINGS


Cat. Bulb Inches (mm) Cat. Bulb Inches (mm)
No. Size Material Bulb Dia. NPT U Well Dia. No. Size Material Bulb Dia. NPT
S Brass 5/8 (16) 3/4 (19) 101/2 (267) 3/4 (19) 5 3
99A 98A S Brass /8 (16) /4
S Brass 5/8 (55/8/8(16) 1 (25) 1/2 (267)
1010 3/4 3(19) 5/85(16)
99B 1/2 /4 98B S Brass /8 1
99G S 316 St. St. 5/(16)
8 (16) 3/4 (19) 10(267)
1/2 (267) 3/(19)
4 (19) 98C S St. St. 5(16)
/8 (16) 3
/4
99H S 316 St. St. 1 (25) 101/2 (267) 3/4 (19) 98D S St. St. 5/8 (16) 1
99J L Brass 1 (25) 1 (25) 121/2 (318) 11/8 (29) 98E L&X Brass 1 1(25) 1
99K X Brass 1 (25)
1 1 (25)
1 16 (406) 11/18 1(29)/8 98F L&X St. St. 1(25)
(25) 1
99Q L 316 St. St. 1(25) (25) 1(25)
(25) 121/2 (318) 11(29)
/8 (29)
99R X 316 St. St. 1 (25) 1 (25) 16 (406) 11/8 (29)
Thermowells and union bushings are utilized as separate items and should be specified on separate lines.

- 89 -
RATED STEAM CAPACITY TABLE
SERIES 2000 TEMPERATURE REGULATOR
CAPACITY TABLE
SERIES 2000

VALVE SIZE SINGLE SEATED VALVES DOUBLE SEATED VALVES


Inlet Outlet /C
12 /D
12 /E
12 /A
12 /B
12 /
12 /
34 1 11/4 11/2 2 /
12 /
34 1 11/4 11/2 2
Pressure Pressure
PSIG PSIG DRY
DRYSATURATED
SATURATEDSTEAM—LBS.
STEAM—LBS.OF
OFSTEAM/HR.
STEAM/HR
UP to
UP to
5 9"HG.VAC.
9” HG.VAC.
6" HG.VAC.
6” HG.VAC.
12
11
30
29
53
52
97
95
130
125
155
150
200
195
270
265
420
415
450
440
510
500
235
230
305
300
380
375
610
600
735
720
975
960
22 8 21 38 70 90 110 145 195 305 320 365 170 220 275 440 525 700
UP to
UP to
10 3”
3"HG.VAC.
HG.VAC.
3
15
13
35
33
65
60
120
110
160
145
195
175
255
230
340
305
530
480
565
510
635
575
295
265
385
345
480
430
765
690
920
830
1220
1100
7 10 24 44 80 105 125 165 220 345 370 415 190 250 310 500 600 800
UP to 4 21 52 95 170 225 270 355 475 745 790 895 415 540 670 1070 1290 1720
20 10
15
19
15
47
37
85
66
155
120
200
155
245
190
325
250
430
335
675
525
715
555
810
630
375
290
490
380
610
470
970
755
1170
910
1550
1200
UP to 10 27 67 120 220 290 350 460 615 960 1020 530 695 865 1380 1660 2210
30 15
25
25
17
63
42
115
75
210
140
270
180
330
220
435
290
580
385
905
605
960
640
500
335
660
440
815
545
1300
870
1570
1050
2090
1390
UP to 15 33 82 150 270 350 430 560 750 1170 650 885 1060 1690 2030 2710
40 20
30
32
25
79
63
140
115
260
210
340
270
415
330
540
435
725
580
1130
905
625
505
820
660
1020
820
1630
1300
1960
1570
2610
2090
UP to 20 39 97 175 320 415 505 665 890 770 1010 1250 2000 2400 3200
50 30
40
36
28
90
70
160
125
295
230
385
300
470
365
615
480
820
640
710
555
935
730
1150
905
1850
1440
2220
1740
2960
2310
UP to 25 45 112 200 370 480 585 770 1020 890 1160 1440 2310 2780 3700
60 30
50
44
30
110
75
198
135
360
250
470
325
575
400
755
525
1000
700
870
605
1140
795
1410
985
2260
1570
2720
1890
3620
2520
UP to 30 51 127 230 420 545 665 870 1010 1320 1640 2610 3150 4190
70 40
60
49
33
122
82
220
150
400
270
520
350
635
430
830
560
965
650
1260
855
1570
1060
2500
1690
3010
2030
4010
2700
UP to 35 57 140 255 465 610 740 975 1120 1470 1830 2920 3520 4690
80 50
70
53
35
130
85
240
155
435
285
565
375
690
455
905
600
1050
690
1370
910
1705
1120
2720
1800
3280
2160
4360
2880
UP to 41 65 155 285 515 675 820 1070 1240 1630 2020 3230 3890 5180
90 60
90
57
35
140
90
255
165
465
305
610
395
740
480
975
630
1120
730
1470
960
1830
1190
2790
1900
3520
2290
4680
3040
UP to 46 70 170 310 565 740 900 1360 1790 2220 3540 4260 5680
100 60
90
65
40
165
95
295
175
540
320
705
415
855
505
1300
770
1700
1010
2110
1250
3380
2000
4060
2400
5410
3200
UP to 52 75 185 335 615 800 975 1480 1940 2410 3850 4640 6170
110 70
90
70
55
175
135
315
245
575
450
750
590
910
715
1380
1090
1810
1430
2250
1770
3590
2830
4330
3400
5760
4530
UP to 57 80 200 365 665 865 1050 1600 2100 2600 4160 5010 6670
120 80
100
75
55
185
145
330
260
605
475
790
615
965
750
1460
1140
1920
1490
2380
1850
3800
2960
4580
3560
6090
4740
UP to 62 85 215 390 715 930 1130 1720 2250 2800 4470 5380 7160
130 80
110
80
60
205
150
370
270
680
495
885
645
1080
780
1630
1190
2140
1560
2660
1930
4250
3080
5120
3710
6810
4940
UP to 68 95 230 420 765 995 1215 1840 2410 2990 4780 5750 7660
140 90
120
85
60
215
155
390
280
715
510
930
670
1130
815
1720
1230
2250
1620
2800
2010
4470
3210
5380
3860
7160
5140
UP to 72 100 245 445 815 1060 1960 2570 3180 5090 6120 8150
150 90
120
95
75
240
190
430
345
780
625
1020
820
1880
1510
2470
1980
3060
2460
4900
3930
5890
4730
7840
6290

UP to 78 105 260 470 860 1120 2080 2720 3380 5400 6500 8650
160 100
140
100
65
250
165
450
300
820
550
1070
715
1970
1320
2590
1730
3210
2150
5120
3440
6170
4140
8210
5500
UP to 83 110 275 500 810 1190 2190 2880 3570 5700 6870 9140
170 100
140
105
80
270
205
485
370
885
670
1150
875
2130
1620
2790
2120
3470
2630
5540
4210
6660
5070
8870
6740
UP to 89 115 290 525 960 1250 2310 3030 3760 6010 7240 9640
180 120
160
110
70
270
175
485
320
890
585
1150
760
2140
1400
2800
1840
3480
2290
5550
3650
6690
4400
8900
5850
UP to 95 125 305 555 1010 1310 2430 3190 3960 6320 7610 10100
190 120
160
115
85
290
215
525
390
960
715
1250
930
2310
1720
3030
2260
3760
2800
6000
4470
7220
5380
9610
7160
UP to 100 130 320 580 1060 1380 2550 3350 4150 6630 7980 10600
200 120
180
125
75
310
185
560
335
1020
615
1330
805
2470
1480
3240
1940
4010
2410
6410
3850
7720
4640
10300
6180
UP to 105 135 335 605 1110 2670 3500 4350 6940 8360 11100
210 120
180
130
90
330
230
595
415
1080
755
2620
1820
3430
2380
4260
2960
6800
4720
8190
5680
10900
7560
UP to 110 140 350 635 1160 2790 3660 4540 7250 8730 11600
220 140
200
135
80
335
195
600
355
1100
645
2640
1560
3470
2040
4300
2530
6870
4050
8270
4870
11000
6480
UP to 115 145 365 660 1210 2910 3810 4730 7560 9100 12100
230 140
200
140
95
355
240
635
435
1160
790
2800
1910
3680
2500
4560
3100
7290
4960
8780
5970
11700
7940
UP to 120 155 380 690 1250 3030 3970 4930 7870 9470 12600
240 160
200
140
110
355
280
640
500
1160
915
2810
2200
3690
2890
4570
3580
7300
5720
8790
6890
11700
9170
UP to 126 160 395 715 1300 3150 4130 5120 8180 9840 13100
250 160
220
150
100
375
250
675
455
1240
830
2980
1990
3910
2620
4850
3240
7750
5180
9330
6240
12400
8300

- 90 -
SIZING SERIES 2000 TEMPERATURE REGULATORS

SIZING SERIES 2000


REGULATORS
EXAMPLE FOR HEATING SERVICE PERFORMANCE VARIABLE
The maximum anticipated flow requirements for
a regulator on heating service is 500 lbs. of 30°F span from fully open to fully closed
steam per hour. The unit steam pressure is 50
Oversized valve can provide narrower spans–Consult Factory
psig and the downstream pressure is essentially
zero because the steam downstream is dis-
CAPACITY CHART SEE PAGE 90
charged into an open drain.
ANSWER: Locate 50 psi on the inlet pressure
scale on the left side of the Series 2000 Capacity STEAM FLOW REQUIREMENTS
Chart. Choose the outlet pressure line “up to 20” GALLONS OF WATER HEATED PER HOUR
psig because the downstream pressure is Temp.
essentially zero. Follow the “up to 20” outlet Rise 25 50 75 100 150 200 300 400 500 750 1000
pressure line until you come to the value closest °F LBS. OF STEAM PER HOUR
to 500 lbs. of steam per hour (in this case, 505). 10 2 4 6 8 12 17 25 33 42 63 83
Read upward to the valve size and we see that 20 4 8 12 17 25 33 50 67 83 120 167
the 1/2" single seated valve is the correct size. To 30 6 12 19 25 37 50 70 100 120 190 250
size for three-way valves, use single seated 40 9 17 25 33 50 66 100 130 170 250 330
capacities 1/2" through 2" size.
50 11 21 31 42 63 84 125 170 210 310 420
NOTE: FORMULAS FOR EXACT CALCULATIONS.
If the outlet pressure is equal to or less than 60 13 25 37 50 75 100 150 200 250 370 500
53% of the absolute inlet pressure: 80 17 33 50 67 100 130 200 270 330 500 670
Q (lbs steam/hr) = 1.5 x Cv x inlet pressure (psia) 100 21 42 63 83 120 170 250 330 420 630 830
If the outlet pressure is greater than 53% of the 120 25 50 75 100 150 200 300 400 500 750 1000
absolute inlet pressure: 140 29 58 88 117 175 230 350 470 580 880 1170
Q (lbs steam/hr) = 3 x Cv x √ pressure drop (psi) x 160 33 66 100 133 200 270 400 530 660 1000 1330
outlet pressure (psia)
STEAM FLOW REQUIREMENTS RATED WATER CAPACITY TABLE
Use the top chart on this page to determine the SINGLE SEATED VALVES DOUBLE SEATED VALVES
pounds of steam per hour required to raise the PSIG /
12 /
34 1 11/4 11/2 2 /
12 /
34 1 11/4 11/2 2
temperature in tank of known capacity to the
Diff. WATER
WATERFLOW–U.S.
FLOW–U.S.GALLONS
GALLONSPER
PERMINUTE
MINUTE
required temperature. Determine the rise in temp- Press.
erature (control temp. - room temp.) on the left
5 12 15 20 32 34 38 18 23 29 46 55 74
hand column, read the corresponding pounds of
steam per hour under the corresponding gallons 10 17 22 29 45 48 54 25 33 41 65 78 104
of water to be heated. Use the lbs. steam/hr. 15 20 27 35 55 59 67 31 40 50 80 96 128
figure in the chart on the opposite page to deter- 20 23 31 41 64 68 77 35 47 58 92 111 148
mine valve size. 25 26 34 46 72 76 86 40 52 65 103 124 165
Formula for converting the length, width 30 29 38 50 78 83 43 57 71 113 136 181
and depth of solutions (all measured in 40 33 43 58 90 50 66 82 130 157 209
feet) to gallons of solution: Gallons=7.48 x 50 37 48 65 56 74 91 146 175 233
length x width x depth.
60 40 53 71 61 81 100 160 192 256
EXAMPLE FOR COOLING SERVICE 70 44 57 66 87 108 172 207 276
Find the correct regulator valve size that will feed 80 47 61 71 93 115 184 222 295
a compressor intercooler that requires 100 gallons 90 50 65 75 99 122 195 235 313
of water per minute under maximum operating 100 52 79 104 129 206 248 330
conditions. The supply (inlet) pressure (P1) is 60
110 55 83 109 135 216 260 346
psi and the downstream pressure (P2) under
maximum flow conditions is 20 psi. The 20 psi 120 57 87 114 141 226 272 361
pressure is required to force the full flow of water 130 60 90 119 147 235 283 376
through the compressor’s cooling system. Inlet 140 62 94 123 153 244 293 390
pressure must not exceed maximum upstream 150 97 127 158 252 304 404
pressure, per the Series 2000 Temperature Regu- 160 100 132 163 261 314 417
lator Product Pages. 170 103 136 168 269 323 430
ANSWER: The pressure drop permitted across
180 106 140 173 276 333 443
the regulator is P1 minus P2 (40 psi). In the
190 109 143 178 284 342 455
Water Capacity Table (right), locate 40 psi in the
differential pressure column and read across to 200 112 147 182 291 351 467
the required gallons per minute. Read to the 210 115 151 187 299 359 478
highest value (in this case, 130 GPM). The chart 220 118 154 191 306 368 489
indicates that a 11/4" double seated valve is 230 120 158 196 312 376 500
required. To size 3-way valve, use single seated 240 123 161 200 319 384 511
capacities 1/2" through 2" size. 250 125 164 204 326 392 522

- 91 -