EXHAUST SYSTEM

ILX EXHAUST FLAMETRAP

DESCRIPTION

Exhaust flametraps are designed and tested to extinguish explosions created in the exhaust
system.

INSTALLATION

The ILX exhaust flametrap is a heavy item of equipment and this should be taken into account
during installation or removal. Do not run the engine in a hazardous area without an exhaust
flametrap fitted. Ensure that the air flow direction on the ILX exhaust flametrap unit is strictly
adhered to, renew all gaskets and ensure that all fixings are secure.

The entire exhaust system pipework between the outlet from the exhaust cooler and the ILX
exhaust flametrap (including the exhaust outlet box, if applicable) must be pressure tested.
Before testing, ensure that the item under test is completely dry and held clear of any liquids. The
exhaust system pipework must be tested at 10 bar pressure for a period of 30 seconds, followed
by 3 bar pressure for a period of 5 minutes. The assembly is deemed satisfactory if no leakage or
distortion is detected.

MAINTENANCE

A clean ILX exhaust flametrap should be fitted to the exhaust system when necessary. The
cleaning interval may vary on each application but can only be established by monitoring site
operational conditions. Providing idling of the engine is kept to a minimum, the cleaning period
may be extended. Long idling periods result in low exhaust gas temperature and premature
fouling. It is essential that the exhaust flame arrestor is cleaned at the first signs of dirty exhaust
or sluggish engine performances.

To remove the ILX exhaust flametrap, remove the fixings from each of the flanges clean the ILX
exhaust flametrap by soaking in carbon removing solvent ensuring that the flametrap element is
completely covered. Never clean the ILX exhaust flametrap by inserting probes, as the passages
could be enlarged thereby impairing the flametrap performance.

After cleaning, wash the solvent off with water and blow the ILX exhaust flametrap element
through with compressed air. Hold one end of the ILX exhaust flametrap to a light and check
visually that the passages are clear. Before refitting, ensure that the casing and flanges are not
damaged or corroded. When refitting the ILX exhaust flametrap, ensure that the air flow direction
on the ILX exhaust flametrap unit is strictly adhered to, use new gaskets and ensure that all
fixings are secure.