Professional Documents
Culture Documents
Faculty of Engineering
Mechanical Engineering Department
HVAC Project
Dr: Salem Nijmeh
1
Introduction………………………………………3-4
Description………………………………
……………5
2
References………………………………………………………34
Introduction
Heating, ventilation, and air conditioning (HVAC)
is an applied science and technology, which studies every aspect
about heating, ventilation and air cooling, trying to provide the best
human comfort, air quality and energy saving for many applications,
including residential buildings, industrial buildings, vehicles and a lot
more
Heating and cooling loads are affected by many factors like heat
transferred from outside to the space by walls, roofs, windows
or/and doors, from that aspect, wall construction components ate
important thing to consider during the calculation and the same for
roof in addition to think about type of system we will design to know
if we need suspended ceiling or not.
3
from calculation to selection of system and then selection of system’s
components till we reach final decision and then simulation on HAP
will be done
The ASHRAE comfort chart indicates the acceptable zones of
selecting the inside operative temperature and the inside relative
humidity for winter heating, summer cooling and year-round air
conditioning
Fig (1)
4
Description
Fig (2)
5
Design The system
We will start to enter the data into the Carrier's Hourly Analysis
Program which is used to calculate the total heating and cooling
loads for each office and all of them. Then we will make a manual
sample of calculation to compare it with HAP results. After that we
will select all the components for the VRF system based on the
Jordanian market
1- Weather
Fig (3)
2-Walls
6
Fig (4)
3-Roof
Fig (5)
4-Windows
7
Fig (6)
Fig (7)
8
Fig (8)
4-Door
Fig (9)
9
5-Space properties for living room
Fig (10)
Fig (11)
10
Fig (12)
Fig (13)
11
6-Air system properties
Fig (14)
12
NOW the calculation from HAP
13
14
15
16
17
NOW Sample hand calculation
1)Cooling load
a. Glass window
A=1.2*1=1.2m2 single glass with aluminum frame
U=5.6 table 5-4
Qwin=A(SHG)*(SC)*(CLF) 9-5
Q=1.2*117*1*0.76=106.7w
F=1 k=1
CLTDcorr=(CLTD+LM) K+(25.5-Ti) +(To, m-29.4) f …. 9.3
18
= 9.1=1* )26.1-29.4(+ )25.5-20(+1* )8-1.1(
Qcon=5.6*1.2*9.1=61.15w
Qtot=61.15+106.7=167.85
b.door
A=2.4m^2
U=2.4
Qdoor=0 ▲Tadj=0
c.Roof
Qroof=U*A*CLTDcorr 9-3
U=0.622
A3.3*3=9.9
CLTDcorr=(18-1.1)+(25.5-20)+(26.1-29.4)=19.1
Qroof=0.715*9.9*19.1=135.8
19
Qcc=n((Qsen*clf)+Qlat)
139.9w=)0.61+30*65(2=
CLTD=6
LM=-1.1
K=0.83 mid color walls
F=1
CLTDcorr=(6-1.1)*0.83+(25.5-20)+(26.1-29.4)=6.3
Qwall=0.64+8.7*6.3=35.1w
Qtot=35.1+139.9+135.2+167.83=478.05w
20
:Heating load )2
a. Infiltration
Vroom=3*3*3.3
N=0.5 from table 6-1
=0.5*(3*3.3*3) =14.85
Q= (1250/360)*14.85*(20-2.4)= 90.2W
b. Door
u=2.4 A=2
Qdoor=2.4*2*(20-2.4) =84.5w
c.window
u=5.6 A=1.2
Window=5.6*1.2*(20-2.4) =118.3w
d.Floor
u=0.15 A=3-3.3=9.9
21
Qfloor=0.15*9.9*(20.2.4) =26.136w
e. Roof
u=0.622 A=9.9
Qroof=0.622*9.9*(20-2.4) =108.4w
Q=0.64*(9.9-1.2)*(20-2.4)=98W
g.Internal wall
Q=0 because ▲Tadj=0
Qtotal=526.2w
22
*Variable Refrigerant Flow system
VRF Systems are equipped with some latest attributes such as variable
speed compressors, inverter-driven fans, and last but not least
simultaneous heating and cooling through their indoor units. The primary
type of VRF System use an outside condenser unit. It is used for
providing both heating or cooling. Furthermore, VRF Systems consists of
two refrigerant lines, one of them is for supplying, and the other one is for
return. Besides, this refrigerant is meant to go through various indoor fan-
coils.
Generally, VRF Systems are known for their energy efficiency and a
great return on your investments. One can think of VRF systems as a
large-scale ductless HVAC system that comes with the capability to work
at higher ranges. The design of these systems is also based on their
application. Opting for VRF Systems will provide you with state-of-the-
art HVAC solution for yourself
23
?How Does a VRF System Work
VRF systems use heat pumps or heat recovery systems to provide
powerful heating and cooling for all indoor and outdoor units without
.the use of air ducts
With a VRF system, your building will have multiple indoor units utilized
by a single outdoor condensing unit, either with a heat pump or heat
recovery system. The main difference between the two is that the latter
can provide simultaneous heating and cooling. The outdoor unit has
compressors with inverter-driven fans, which means their speed varies
by adjusting the frequency of the power supply. The amount of
refrigerant delivered by the compressor is dependent on the rate. When
the indoor unit sends a demand to the outdoor unit, the outdoor unit
delivers the specific amount of refrigerant to the individual indoor units.
VRF technology can perform at a high capacity without the use of ducts,
.which is one of its many advantages
24
2 pipe VRF system provides cooling to the areas that need it by
supplying the refrigerant through refrigerant pipes in a liquid form.
In contrast, the areas that require heating are provided with the
refrigerant through refrigerant pipes in a gaseous form.
These three lines consist of: one is for cooling purpose, one for heating
purpose, and the last one is a return line. Here, each of the indoor units
is diverged using 3 pipes with the use of a solenoid box that is enriched
.with a set of valves
VRF heat recovery systems ditch the branch controllers for delivering
liquid or gaseous refrigerant through VRF refrigerant piping as this
.function is already present in the outdoor condenser unit
Here, the three lines are attached to each indoor fan-coils, and
furthermore, each of the units has a branch selector that works on
diverting the supply based on the specific operating modes – either
.heating or cooling
25
No matter what is the operating mode, the return is the same for each
.fan coil
26
.Figure (16). Branching controller function for three-pipe VRF system
Water-cooling system3-
One of the most commonly used VRF systems are air-cooled systems.
These systems make use of the packaged outdoor condensing units
through copper branch piping, which is connected to several indoor
.units
Water-cooling systems work as an air-cooled unit. These systems use and
plate the heat exchanger that, in result, transfers the energy into the water
.loop instead of opting for a built-in air-cooled heat exchanger
These systems are attached to a cooling tower or a dry cooler that
transfers the heat or energy into the atmosphere. Because of such
operation, the water-cooling systems can be deployed internally in
smaller areas without any stress regarding the vertical risers. They are
.also ideal according to the environmental needs
27
Fig(17)
traffic cop of the refrigerant, based on the demand of the system. See our
article on VRF Single Port versus Multiport Branch Selector Boxes.
28
Fig(18)
29
All INFORMAYION BELOW FROM Carrier Xpower
VRF System brochre
Outdoor units
Fig19
Indoor units
fig20
30
Controler
fig21
Compressor
31
Fig22
32
33
:References
227enterprise.com -3
sciencedirect.com -4
34
Carrier Xpower VRF system -5
.BORCHUR
35