You are on page 1of 154

OPERATING PROCEDURES

FOR
EASTERN REGION

(as mandated by the


IEGC clause 5.1(f))

Revision-8: June 2013

Eastern Regional Load Despatch Centre


14,Golf Club Road, Tollygunj
Kolkata – 700033
ERLDC:POSOCO

Table of Contents

Chapter 1…………….. ................................................................................................... ……………….4


1. General .......................................................................................................................................... 4
1.0. Introduction ........................................................................................................................... 4
1.1. Scope ..................................................................................................................................... 4
1.2. Objective................................................................................................................................ 4
1.3. Maintenance of Operating Procedures .................................................................................. 4
1.4. Structure of the Operating Procedure Document .................................................................. 5
1.5. List of Annexure(s) and Reference Documents .................................................................... 5

Chapter 2……………… .......................................................................................................................... 6


2. Frequency Management ................................................................................................................ 6
2.0. Frequency Standard ............................................................................................................... 6
2.1. High Frequency Conditions ................................................................................................... 6
2.2. Low Frequency Conditions ................................................................................................... 7
2.3. Broad Guidelines for Issue of Over drawl messages ............................................................. 8

Chapter 3…………… ............................................................................................................................ 10


3. Voltage Management .................................................................................................................. 10
3.0. Introduction ......................................................................................................................... 10
3.1. AVRs of Generators ............................................................................................................ 10
3.2. VAR Exchange by constituents for Voltage and Reactive Control..................................... 10
3.3. VAR generation / absorption by generating units ............................................................... 10
3.4. Transformer Taps ................................................................................................................ 11
3.5. Control of Voltage at grid substations/generating stations .................................................. 11
3.6. Switching off the line reactors in case of low voltage ......................................................... 12

Chapter 4………….. .............................................................................................................................. 13


4. Outage Planning .......................................................................................................................... 13
4.0. Introduction ......................................................................................................................... 13
4.1. Objective.............................................................................................................................. 13
4.2. Scope ................................................................................................................................... 13
4.3. Outage Planning Procedure: ................................................................................................ 13
4.4. Outage planning not covered in Annual Outage plan.......................................................... 14
4.5. Procedure for Availing the Outage in Real Time ................................................................ 15

Chapter 5…………… ............................................................................................................................ 17


5. Switching Coordination .............................................................................................................. 17
5.1. Introduction ......................................................................................................................... 17
5.2. Switching of System Elements for first time ....................................................................... 17
5.3. Switching of Important Elements ........................................................................................ 17
5.4. Other Precaution to be taken during Switching ................................................................... 18

Chapter 6…………… ............................................................................................................................ 20


6. Periodic Reports and Event Information..................................................................................... 20
6.0. Introduction ......................................................................................................................... 20
6.1. Objective.............................................................................................................................. 20
6.2. Periodic Reports .................................................................................................................. 20
6.3. Event Information ................................................................................................................ 21

_________________________________________________________________________
Operating Procedures for Eastern Region Page 1 28-06-2013
ERLDC:POSOCO

6.4. Reporting system ................................................................................................................. 21


6.5. Grid Incidence/Disturbances and Categorisation ............................................................... 22

Chapter 7………….. .............................................................................................................................. 23


7. Network Security and Congestion Management ........................................................................ 23
7.0. Introduction ......................................................................................................................... 23
7.1. Network Security ................................................................................................................. 23

Chapter 8……….. .................................................................................................................................. 33


8. Scheduling and Despatch Procedure ........................................................................................... 33
8.0. Introduction ......................................................................................................................... 33
8.1. Scope ................................................................................................................................... 33
8.2. Objective.............................................................................................................................. 33
8.3. Description of the procedure ............................................................................................... 33
8.4. Procedure for revising ISGS schedule downwards on account of surrendering of share by
beneficiaries ................................................................................................................................... 34

Chapter 9…………. ............................................................................................................................... 43


9. SCADA System Operation ......................................................................................................... 43
9.0. SCADA / EMS System Operation ...................................................................................... 43
9.1. System Configuration .......................................................................................................... 43
9.2. Starting up an operator console ........................................................................................... 44
9.3. Identifying the failed node ................................................................................................... 45
9.4. Calling up a substation displays .......................................................................................... 47
9.5. Bringing-up Video Projection Display (VPS) ..................................................................... 48
9.6. Configuring data Trends ..................................................................................................... 49
9.7. Manually Defining of Data ( Replace / Not in service ) ...................................................... 50
9.8. Removing Manual Override and Restoring a Value to Service .......................................... 51
9.9. Data Quality flags ................................................................................................................ 51
9.10. Collection and Viewing the Disturbance Data................................................................. 51
9.11. Area of Responsibility (AOR) ......................................................................................... 55
9.12. Saving Layout and Restoring ........................................................................................... 55
9.13. Procedure to run Real Time Network Analysis (RTNET), Study Mode Network Analysis
(STNET) and Contingency Analysis. ............................................................................................ 56
9.14. Transfer of Schedules to SCADA System ....................................................................... 72
9.15. Real-time data availability from other region .................................................................. 72
9.16. Data transfer to NPSD ..................................................................................................... 73
9.17. Uploading Daily Report on ERLDC Website .................................................................. 73
9.18. Data communication with NLDC for PX scheduling ...................................................... 73
9.19. Daily report upload .......................................................................................................... 74
9.20. Operation of DG Set in Auto/Manual Mode.................................................................... 74

Chapter 10…………. ............................................................................................................................. 77


10. Metering and Settlement System............................................................................................. 77
10.0. Introduction ...................................................................................................................... 77
10.1. Metering and Data Collection .......................................................................................... 77
10.2. Data Processing ................................................................................................................ 77
10.3. Energy Accounting .......................................................................................................... 77
10.4. Pool Account Operation ................................................................................................... 78

_________________________________________________________________________
Operating Procedures for Eastern Region Page 2 28-06-2013
ERLDC:POSOCO

Annexure(s)

Annexure: I Generation capacities in Eastern Region...................................................................... 79


Annexure: II List of Generating Units and their Capacities ............................................................. 80
Annexure :III Captive Power Stations in Eastern Region and Their Capacities ............................... 83
Annexure: IV UI Rate at different frequencies ................................................................................... 84
Annexure: V Format for Overdrwal message .................................................................................... 85
Annexure: V(a) Format for Category A Message .......................................................................... 85
Annexure: V (b) Format for Category B Message .......................................................................... 86
Annexure: V(c) Format for Category C message........................................................................... 87
Annexure-VI Format for Overdrawal Message to NLDC/Other RLDCs ........................................ 88
Annexure: VII List of 765/400kV & 400/220kV ICTs and their tap positions .................................... 89
Annexure: VIII Reactive Compensation Details ................................................................................... 90
Annexure: IX Format for message to be issued by ERLDC for Real Time Outage clearance .......... 92
Annexure :X Format for Weekly Reports .......................................................................................... 93
Annexure :XI Format for Quarterly Reports ....................................................................................... 95
Annexure :XII Format for written report for event reporting ............................................................... 99
Annexure: XII (a) Format For Reporting System Disturbances .................................................. 100
Annexure :XIII Categorisation of Grid Incidences/Disturbances ........................................................ 103
Annexure: XIV Flow Gate ................................................................................................................... 104
Annexure : XIV (a) Flow Gate -I ................................................................................................. 104
Annexure :XIV (b) Monsoon Flow Gate -I .................................................................................. 105
Annexure: XIV(c) Winter Flow Gate I ......................................................................................... 106
Annexure :XIV(d) Winter & Summer Flow gate II ...................................................................... 107
Annexure :XV List of Important Elements........................................................................................ 108
Annexure :XVI Automatic UFR load shedding Schemes................................................................ 115
Annexure :XVII Power Demand Override ...................................................................................... 116
Annexure : XVIII Special Protection schemes at Talcher and Kolar ............................................... 117
Annexure :XIX Islanding schemes in ER ........................................................................................... 120
Annexure :XX Scheduling Formats ( Broad guidelines for the Formats) .......................................... 123
Annexure: XXI Meter Locations ........................................................................................................ 126
Annexure :XXII Grid Maps ............................................................................................................. 136
Annexure :XXIV Message for violation of TTC/Flow Gate/System Constraint ............................. 149
Annexure :XXV :- Format for Applying and Withdrawing congestion .............................................. 150

List of Revisions: ................................................................................................................................. 152

_________________________________________________________________________
Operating Procedures for Eastern Region Page 3 28-06-2013
ERLDC:POSOCO

Chapter 1
1. General
1.0. Introduction
In compliance to the IEGC (Indian Elecricity Grid Code) clause no 5.1(f) this internal Operating
Procedure for Eastern Region is developed in consultation with the regional constituents of Eastern
Region. Eastern Region Grid system comprises of the states of Bihar, Jharkhand, Orissa, West
Bengal and Sikkim and has an operating area of 4,25,423 sq km, which is about 13% of the total area
of the country. Damodar Valley Coprporation (DVC) established under sub-section (1) of Section 3 of
the Damodar Valley Corporation Act, 1948 in eastern region is an integrated utility similar to
STU/SEB encompassing part of the states of West Bengal and Jharkhand and has its own generation,
transmission and Distribution facilities in its identified command area. Eastern Region is strategically
located and has interconnections with all the other regions as well as with neighbouring countries like
Bhutan and Nepal.

The IEGC brings together the different terms, encompassing all the utilities connected to / or
using the Inter-State Transmission System (ISTS) and provides documentation in regard to
relationship between various users of the ISTS. It lays down the rules and guidelines for planning,
development, operation and maintenance of the grid in an efficient, reliable and economical
manner.

The internal operating procedure as prepared by ERLDC is to clearly specify the roles of each player
in the grid i.e., Central Sector Generating and Transmission Utilities, State Utilities, Independent
Power Producers, Traders, System Operators and other agencies operating in the power market to
facilitate grid operation in efficient, reliable and economic manner.

1.1. Scope
This document describes the role of all agencies connected in the region in order to operate the grid
in an integrated manner promoting efficiency, reliability and economy in conformation to the desired
security standards and to meet the common interests of all the agencies.

1.2. Objective
Objective of this document is to describe the procedures to be adopted for integrated system
operation and roles of each agency and their responsibilities in the grid in compliance to the various
provisions of IEGC. This document aims at operation, maintenance and development of regional
power system in the most efficient, economic, secure and reliable manner. This document also aims
to facilitate beneficial trading opportunities between utilities within as well as outside the region to
harness bottled up power

1.3. Maintenance of Operating Procedures


The Operating Procedure shall be maintained by ERLDC and reviewed periodically. However, in the
event of any specific operational issues/philosophy requiring urgent revision of the procedure, the
same may be expeditiously carried out in consultation with the Regional constituents. Further,
whenever amendments are made in the IEGC, UI, Open Access, Congestion managment and related
regulations, the operating procedure would be also be amended accordingly.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 4 28-06-2013
ERLDC:POSOCO

1.4. Structure of the Operating Procedure Document


The Operating procedure of the Eastern Region system contains the following chapters .

Chapter 1 General
Chapter 2: Frequency Management
Chapter 3 Voltage Management
Chapter 4 Outage Planning
Chapter 5 Switching Coordination
Chapter 6 Periodic Reporting and Event information
Chapter 7 Network Security and Congestion management
Chapter 8 Scheduling and Despatch
Chapter 9 SCADA system operation
Chapter 10 Metering & Settlement System

1.5. List of Annexure(s) and Reference Documents

For the purpose of understanding the operational aspects and issues, there would be a necessity to
refer to various data, lists and parameters, external and internal documents/lists, Grid Maps etc. A list
of Annexure(s) had been shown at the beginning of this document.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 5 28-06-2013
ERLDC:POSOCO

Chapter 2
2. Frequency Management
2.0. Frequency Standard
IEGC vide its clause 5.2(m) has mandated that all Regional entities shall make all possible efforts to
ensure that the grid frequency always remains within the 49.7-50.2 Hz band,. Frequency is the most
important indicator of the quality of supply and is the global parameter in the grid i.e. it is same
throughout an inter-connected power system. Since frequency is a function of the load-
generation balance, it is subject to variation on a continuous basis as either of the two viz.
generation or load may vary from time to time. Whenever, the frequency approaches upper/lower
limits of the above range, advance action needs to be initiated in order to arrest further rise/fall in
frequency; as it takes some time for remedial measures to give desired result. Therefore, in
practice, whenever frequency exceeds 50.1Hz. and is in rising trend, action shall be initiated to
contain the same. Similarly when frequency touches 49.8 Hz. and is in falling trend, action shall
be initiated to improve the same.

2.1. High Frequency Conditions


In case the frequency is high (above 50.1Hz) and is in increasing trend then the following actions
may be initiated:

2.1.1 ERLDC shall check whether the high frequency condition is due to the heavy under-
drawal by any entity within the region or by neighbouring regions. In the latter case, the
matter has to be brought to the notice of the concerned region as well as NLDC for
necessary remedial action
2.1.2 ERLDC shall advise the regional entities within ER to lift load shedding if any.
2.1.3 If the frequency of the Southern region is lower than ER frequency, ERLDC shall explore
the possibility of increasing UI export after due checking of voltage conditions and network
loading. In case any major network constraint is envisaged while exporting UI to Southern
Region through ER-SR HVDC links, ERLDC may in consultation with WRLDC, NRLDC
and NLDC explore the possibility of exporting UI through WR-SR HVDC link to SR.
2.1.4 However, before taking up with other regions / NLDC, ERLDC would check the possibility
of any backing down of the reservoir based hydro stations within state system .
2.1.5 ERLDC before advising any generation reduction at the hydro stations, in consultation
with concerned SLDC, would check back whether such reduction would cause any
adverse change in voltage levels or network loading in the ISTS. Similarly, the concerned
SLDC would also assess the impact on its intra-state network. In case any problem is
envisaged due to such generation reduction, the same shall be avoided.
2.1.6 Explore the possibility of running of Purulia Pump storage hydro units in pump mode, in
consultation with SLDC, West Bengal.
2.1.7 Advise/remind the states to back down costly generation as per merit order by taking
adequate support from SCADA. The applicable UI rate as revised by CERC (w.e.f 17-09-12)
is shown at Annexure IV.
2.1.8 If any ISGS (other than must run) is generating more than their schedule, advise the ISGS
to reduce the over injection.
2.1.9 The Hydro stations of Bhutan power system exporting power to India are not covered
commercially under ABT mechanism. Backing down advice on account of high frequency
conditions may be issued to stations at Tala, Chukha and Kiruchu of Bhutan system only

_________________________________________________________________________
Operating Procedures for Eastern Region Page 6 28-06-2013
ERLDC:POSOCO

after all possible remedial measures are exhausted. However, in case the stations are
noticed generating extra with respect to schedule issued , ERLDC shall attempt revising
the generation schedule with due revision of constituents drawal schedule.
2.1.10 At a frequency above 50.0 Hz, any regional entity / control area that is in need of power,
should have enough incentive to draw UI, subject to volume restrictions as provided in UI
regulations, which requires no prior agreement.
2.1.11 In case any regional entity is underdrawing/overinjecting, ERLDC may advice to maintain
net exchange as per schedule.
2.1.12 In case any regional entity is under-drawing, ERLDC may advice concerned SLDC for
considering surrendering of its share from ISGS, based on merit order
2.1.13 If the frequency is still high, and action from underdrawing beneficiaries is not
forthcoming, ERLDC shall suo-motto reduce the generation schedule of ISGS with
corresponding downward revision of schedule of the concerned beneficiary
2.1.14 Backing down of the spilling hydro units or the run-off-the-river units for short duration may
also be considered if all other options are exhausted.

2.2. Low Frequency Conditions


If the frequency is less than 49.8 Hz. and has a decreasing trend, the following actions may be
taken:

2.2.1 ERLDC shall check whether the low frequency condition is due to the heavy over-drawal
by regional entities or by the neighbouring regions. In the event of overdrawal by
neighbouring regions, matter may be brought to the notice of NLDC through written
messages with a copy/ies to the RLDC of the over drawing region/s Sample message
format to be issued to NLDC/Other RLDCs is at Annexure VI.
2.2.2 Alternately, if the frequency of Southern Region is high, ERLDC operator would attempt
importing UI from Southern region using the ER-SR HVDC link. If any major network
constraint is envisaged because of such UI import ERLDC in consultation with WRLDC
may explore importing of UI in the NEW Grid from southern region through SR-WR HVDC
link.
2.2.3 If any unit of Purulia Pump storage is operating in pump mode and if the concerned STU
is over drawing, ERLDC shall advise the concerned SLDC for discontinuing the pump
operation.
2.2.4 ERLDC may advise all regional entities / control areas, through their respective SLDCs to
maximize their internal generation viz. hydro, thermal, IPP etc. in case margins are
available.
2.2.5 The UI (Amendment) regulations 2012 already lays down appropriate financial and legal
penalties for under-generation / over-drawal at low frequency. Nevertheless, if any ISGS
is under-generating, it may be reminded to generate as per schedule. If such generation
increase is not possible due to any technical constraints, the concerned ISGS may be
advised to reduce its Declared Capability. ERLDC would then correspondingly reduce the
drawal schedules of all concerned beneficiaries (including outside regions) and advise
them to maintain their net exchanges as per their respective revised schedules.
2.2.6 The Actual receipt from the Hydro stations from Bhutan may be closely monitored under
low frequency conditions. In case such receipt is less than the schedule, because of some
technical reasons like low inflow etc., ERLDC may suo motto revise the generation
schedule downwards with corresponding downward revision of drawal schedules of the
respective constituents who have share on such stations. Such downward revision shall
be duly informed to the concerned beneficiaries with an advise to curtail their drawal from
the grid.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 7 28-06-2013
ERLDC:POSOCO

2.2.7 If the frequency is less than 49.8Hz. and has a falling trend, remind the SLDC(s) of
overdrawing regional entity /entities telephonically to maintain frequency by picking up
internal generation/ curtailing overdrawal. The estimation of over-drawal has to be done
corresponding to nominal frequency (50.0 Hz) after applying requisite frequency bias
correction on the exchange at the prevailing off-nominal frequency.
2.2.8 Issue caution messages Category A, violation message Category B & Category C to
overdrawing constituent/s within region as per the guidelines. If no relief is forthcoming,
request them to take self regulatory measures by opening the radial feeders if possible.
The broad guidelines for issuance of Category A, Category B and Category C messages
are detailed below at 2.3 of this chapter.
2.2.9 If the frequency is less than 49.7 Hz and it may appear that practically no control area is
as such overdrawing, a general message may be issued to all regional entities requesting
to estimate their respective actual net exchanges at 50.0 Hz (after applying necessary
frequency correction factor on the existing interchange) and improve internal generation/
shed loads wherever the estimated actual drawal corresponding to 50.0 Hz exceeds the
net scheduled drawal. Before issuing above messages, it is to be ensured that SCADA
data of the drawls is in order and there is no UI export to other region.
2.2.10 ERLDC may further examine the latest status of thermal units under outage (forced) and
find out when the units are expected to be on bar and take up for expediting the same.
2.2.11 As a long term measure, It may be examined that whether a planned maintenance of any
unit can be postponed without much affecting the AMP of other units.

2.3. Broad Guidelines for Issue of Over drawl messages


While issuing any messages, ensure that SCADA data for the drawls and injections of ISGS is in
order.
1. Category A Message( Vide Annexure V(a))
Message ‘A’ would be issued to an overdrawing state(s) if the frequency is less than 49.8
Hz and the UI is more than 150 MW or above 12%, of schedule, whichever is less, and
there is a downward trend in frequency.
And/Or
There are repeated instances of high overdrawal, irrespective of the frequency.
For this purpose, if more than one State is overdrawing, a single message addressing one
or more overdrawing state/s can be issued.
2. Category B Message( Vide Annexure V(b))
Message ‘B’ would be issued under following conditions:

Frequency is less than 49.70 Hz


And/or
UI is more than 150 MW or above 12% of schedule whichever is less under the
conditions when the frequency is less than 49.80 Hz for more than the last 10 minutes
And/or
There are repeated instances of high overdrawal, irrespective of the frequency
Though not mandatory, it would however be attempted that the ‘Message A’ is generally
issued prior to the issuance of ‘Message B’. However, in case of sudden increase in
overdrawal by a state and/or sharp fall in frequency and/or there are repeated instances of
high overdrawal by the given utility, ‘Message B’ may be issued independent of ‘Message A’,
without waiting for the given time period.
For this purpose, if more than one regional entity is overdrawing, separate message shall be
given to each of them, as it is a violation message and each entity is to be dealt with
separately before CERC. While issuing such message the schedule and actual drawal may

_________________________________________________________________________
Operating Procedures for Eastern Region Page 8 28-06-2013
ERLDC:POSOCO

be clearly indicated. The Message must a clear number with date and time. The message
along with the print out shall be preserved as record for all future actions such as producing
them before the CERC etc. In case there is overdrawal by synchronously connected
neighbouring region(s) a message indicating the schedule and actual drawal by such region(s)
may be mentioned. It is to be noted that post synchronous interconnection between Northern
and Western Regions one of them may be underdrawing while the other may be overdrawing.
Under such circumstances ERLDC Operator may cross verify the net UI (as a whole) of each
of these regions before bringing the matter to NLDC.

3. Category C Message( Vide Annexure V(c))

Message ‘C’ would be issued under following conditions:

Overdrawal when frequency is less than 49.70 Hz;


And/Or
Overdrawal is more than 150 MW or above 12% schedule whichever is less, when
frequency is less than 49.80 Hz for more than the last 15 minutes;
And/Or
There are repeated instances of high overdrawal, irrespective of the frequency

Like ‘B’ message, in case of ‘C’ message also, generally it would be issued after a ‘B’ message.
However, in case of sudden increase in the overdrawal by a state and/or sharp fall in frequency
and/or repeated instances of high overdrawal by the given utility, ‘Message C’ may be issued
independent of ‘Message B’, without waiting for the given time period.

4. Feeder disconnection in case of over drawl at 49.7 Hz or below


As per provisions 5.4.2 (a) & 5.4.2 (b) of the Grid Code all constituents are required to
reduce their overdrawal moment the frequency falls to 49.8 Hz and start demand
disconnection when the frequency falls below 49.7 Hz. In case repeated warning massages
from ERLDC to curb over drawal does not yield any results, ERLDC will instruct the
defaulting constituents to disconnect identified radial feeders within their respective systems
for reduction of over drawl. Concerned constituents should send compliance report to
ERLDC in this regard after taking necessary action. .

5. General Message when no state is overdrawing more than 100 MW but frequency is
running low:
At times, the over drawal by the regional entities may be less than 100 MW but frequency is less
than 49.7 Hz. In such occasions, when expected relief is not forthcoming, a general message
may be issued indicating the real time values of frequency, frequency corrected drawl /frequency
corrected UI( MW restriction needed), highlighting the urgency of the matter and informing the
amount of load shedding to be carried out by the constituents to improve the frequency.
The above stated actions for controlling high / low frequency are of a general nature and
applicable so long as there is no incident / disturbance in the regional grid. In case of sudden
outage of multiple elements and / or partial separation / collapse of the regional grid, ERLDC may
direct any regional entity to increase / decrease its net interchange by a certain amount at the
earliest. Such instructions have to be forthwith complied with by the concerned regional entity /
entities.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 9 28-06-2013
ERLDC:POSOCO

Chapter 3
3. Voltage Management
3.0. Introduction
In compliance to the IEGC (Indian Electricity Grid Code) clause no 5.2(s) all regional constituents
shall make all possible efforts to ensure that the grid voltage always remains within the following
operating range

Nominal Maximum Minimum


(KV –Rms) (KV –Rms) (KV –Rms)
765 800 728
400 420 380
220 245 198
132 145 122

Eastern Region Grid has a very good spatial distribution of generation rendering a better voltage
profile across 400 kV and 220kV network. However, in some pockets of 132kV system where radial
loads are fed, occasional low voltage is experienced. Post commissioning of Tala Transmission
system exhaustive 400kV networks have been laid. This part of the network is essentially used to
evacuate the hydro power from Bhutan system, generation of Teesta-V HPS and surplus hydro power
of North Eastern Grid during monsoon. During non-monsoon season, with receding hydro, the Tala
Transmission system experiences high voltage during lean hours. Although adequate reactive
compensation has been provided yet resorting to opening of lines are not uncommon during the
months of winter. Rest of the 400kV system usually operates within the prescribed voltage limit as
specified in the IEGC. 400kV stations at Jeypore occasionally experience low or high voltages due
to the low fault MVA of these stations. As the HVDC station Gajuwaka is also connected to Jeypore
having low fault MVA, any power flow change associated with switching of filter banks operation
render at times wide fluctuations in voltage at 400kV level.
3.1. AVRs of Generators

As per the provisions of clause 5,2(k) of IEGC, all generating units shall keep their Automatic Voltage
Regulators (AVRs) in operation and power system stabilizers (PSS) in AVRs be appropriately tuned.

3.2. VAR Exchange by constituents for Voltage and Reactive Control

In line with clause 4.6.1(a) of IEGC each agency shall provide adequate compensation of its reactive
requirements including appropriate reactive reserves, to support safe and secure power transfer on
interconnecting transmission circuits. The agencies shall take action in regard to VAR exchange with
the grid looking at the topology and voltage profile of the exchange point. In general, the regional
entities shall endeavour to minimize the VAR drawl at interchange point when the voltage at that point
is below the nominal value and shall not inject VARs when the voltage above the nominal value. In
fact, the regional entities are expected to provide local VAR compensation so that they do not draw
any VARs from the grid during low voltage conditions and do not inject any VARs to the grid during
high voltage conditions.

3.3. VAR generation / absorption by generating units


In order to improve the overall voltage profile, the generators shall run in a manner so as to have
counter balancing action corresponding to low/high backbone grid voltage and to bring it towards the
nominal value. In order to achieve the same, all generators shall generate reactive power during low
voltage conditions and absorb reactive power during high voltage conditions as per the capability limit

_________________________________________________________________________
Operating Procedures for Eastern Region Page 10 28-06-2013
ERLDC:POSOCO

of the respecting generating units. The online tap changers (OLTC) on the generator transformer
wherever possible should also be used to achieve this. Off load tap changes should be used to take
care of the seasonal variations in the voltage profile.

3.4. Transformer Taps


In line with IEGC clause 6.6.4, the transformer tap positions on different 400kV class ICTs shall
be changed as per requirements in order to improve the grid voltage. ERLDC shall coordinate
and advise the settings of different tap position and any change in their positions shall be carried
out after consultation with ERLDC. A list of tap positions for 400/220kV ICTs as on 30.04.12 is
enclosed at AnnexureVII . ERLDC operator shall maintain this list and incorporate due changes
and reasons for change of 400/220kV ICT tap positions. Frequent on line tap changing may be
avoided to the extent possible. Any measure to maintain the voltage profile within the operating
range by way of change of ICT taps may be resorted to through detailed study and observing
the real time voltage profile of the concerned station/s. As a part of such study, ERLDC shall duly
examine from the weekly special energy meter data the pattern of VARh drawal by regional
entities at various ISTS interconnection points at HIGH/LOW voltage. Effort shall be made to
identify such ISTS points where regular VARh charge payment to regional pool takes place.
Necessary measure shall be initiated to set optimum ICT taps so as to minimise such payment to
pool.

3.5. Control of Voltage at grid substations/generating stations


Following corrective measures in order of priority shall be taken by ERLDC and for ISTS system
and by SLDC for regional entities in the event of voltage going beyond the operating limits as
stipulated in IEGC.

3.5.1 High Voltage:


In the event of high voltage (e.g. 400 kV voltage going beyond 415 kV and having a rising
trend) following specific steps would be taken by the respective grid substation/generating
station at their own, with intimation to ERLDC, unless specifically mentioned by
ERLDC/SLDCs. Before taking any voltage control action the reason for high voltage as
observed /reported be carefully studied The network adjoining to the substation/s
experiencing high voltage be also carefully studied and areas/substations /generating
stations be identified where voltage control measures need to be taken in the following
order of priority
a) The bus reactor be switched in
b) The switchable line/tertiary reactor are taken in ( a list of Bus reactors /line reactors
and tertiary reactors available at ER grid is enclosed at Annexure VIII
c) Optimization of the filter banks at HVDC terminal (provided high voltage is being
experienced in the vicinity of the terminal)
d) The Generating units on bar at the stations in proximity to high voltage areas, absorb
reactive power within the limits of their capability curves.
e) Check the possibility of changing the transformer Tap if one side of ICT is witnessing
High voltage while other side is having low voltage.
f) Checking possibility of rerouting /change of power flow on HVDC terminals so that
loading on parallel EHV network can be altered that may result in reduction in voltage.
g) ERLDC/SLDCs shall consider opening one circuit of lightly loaded multi circuit lines
around the area /substation where high voltage is reported, ensuring security of the
balance network. In case it becomes essential to switch out one of the circuits of inter-
regional lines to mitigate high voltage at one or more inter-regional sub-stations, due
consent would be obtained from the concerned neighbouring RLDC (s) and NLDC.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 11 28-06-2013
ERLDC:POSOCO

3.5.2 Low Voltage Condition


In the event of low voltage(e.g. 400 kV voltage going below 390 kV and have a declining
trend), following specific steps would be taken by the respective grid
substation/generating station at their own, with intimation to ERLDC, unless specifically
mentioned otherwise by ERLDC/SLDCs. However, before taking any voltage control
action, the reason for low voltage as observed /reported be carefully studied. The
network adjoining the substation/s experiencing low voltage be also carefully studied and
areas/substations /generating stations be identified where voltage control measures need
to be taken in the following order of priority

a) Close the lines which were opened to control high voltage after obtaining due
permission from ERLDC/SLDCs.
b) The bus reactor be switched out
c) The switchable line/tertiary reactor be taken out
d) Optimization of the filter banks at HVDC terminal
e) Check the possibility of changing the transformer Tap if one side of ICT is
witnessing Low voltage while other side is having High voltage
f) All generating units on bar shall generate reactive power upto the limits of their
respective capability curves.
g) Operate hydro generator for VAR generation i.e. at lagging p.f.
h) Check possibility of altering HVDC power flow settings on HVDC terminals so that
loading on parallel EHV network goes down resulting in rise in voltage.

3.6. Switching off the line reactors in case of low voltage


In the event of persistent low voltage conditions, some of the line reactors are to be selected on the
basis of line length, grid conditions, network topology etc., which can be switched off in order to
improve the system voltage profile. The details of such reactors in ER Grid are listed at Annexure V
of this document. The switching off of such line reactors and reviving them back would be carried out
as per the instructions issued by ERLDC.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 12 28-06-2013
ERLDC:POSOCO

Chapter 4
4. Outage Planning
4.0. Introduction
In reference to the clause 5.7.1 of IEGC, this chapter sets out the procedure for preparation of outage
schedule for generating units and transmission elements of the region in a coordinated and optimal
manner keeping in view the regional system operating conditions and maintaining load generation
balance in the system. Adequate security margins shall be ensured while preparation of the
generation and transmission outage programme. ERPC secretariat shall be responsible for
preparation of the annual outage plan in advance for the financial year and be reviewed on monthly
basis.

4.1. Objective
4.1.1 To formulate a coordinated outage programme of transmission lines and generating units for
the regional grid considering all the available regional resources and taking into account
transmission constraints as well as other requirements.

4.1.2 To minimise surplus or deficit, if any, in the requirement of power and energy and help to
operate system within the grid standards.

4.1.3 To optimise the transmission outages of the elements of the Eastern Regional grid that should
not affect adversely the regional grid operation but take into account the generation outage
schedules, outage of SEB/STU systems thereby maintaining security standards.

4.2. Scope
The scope of this chapter is applicable to all agencies viz. SEBs/STUs, ISGSs, IPPs. MPPs and CTU
as well as RLDC, SLDCs, (vide clause 5.7.3 of IEGC). For the purpose of a coordinated maintenance
programme, outage programme for the generating stations at Bhutan viz. Tala HEP, Chukha HEP
and Kiruchu HEP and its associated transmission system shall also be covered within the scope of
outage planning procedure of Eastern Regional Grid system.

4.3. Outage Planning Procedure:


4.3.1 For the purpose of Load Generation Balance (LGB)/ Outage planning process, OCC
(Operation Coordination Committee) of ERPC shall, in general, be the forum for reviewing and
deciding the outage planning.

4.3.2 It shall be the responsibility of the ERPC secretariat to analyse the outage programmes
proposed by various agencies and, prepare a draft annual outage schedule for finalization of
the annual outage plan for the following financial year by 30th November of each year.

4.3.3 All SLDCs/STUs, CTU, ISGS, IPPs, MPPs shall provide RPC Secretariat their proposed
outage programmes in writing for the next financial year by 31st October of each year. These
shall contain identification of each generating unit/line/ICT, the preferred date for each outage
and its duration and where there is flexibility, the earliest start date and latest finishing date.

4.3.4 Each load serving control area shall be responsible to match its demand with the anticipated
availability from its own plant(s) and availability from ISGS / other purchase / sale contracts.
The SLDC/STUs along with the proposed outage programme, therefore, shall also furnish
details of the anticipated load generation balance report(LGBR) to ERPC secretariat in order
to facilitate preparation of the annual outage plan

_________________________________________________________________________
Operating Procedures for Eastern Region Page 13 28-06-2013
ERLDC:POSOCO

4.3.5 ERPC Secretariat after receiving the outage programme will study the following :-
i) Total power and energy availability( for peak and off-peak condition)
ii) Monthwise availability and requirement
iii) In case of both surplus and deficit, proper staggering of generation outage to
reduce/ eliminate the deficit.
iv) In case of only deficit efforts to be taken to even out high and low deficit by
staggering of generation outage.
v) The anticipated programme for bilateral transaction under STOA or otherwise by
state beneficiaries

4.3.6 ERPC Secretariat shall then come out with a draft load generation balance report (LGBR) and
draft outage programme for the next financial year by 31st December of each year for the
Regional grid taking into account the available resources in an optimal manner and to
maintain security standards. This will be done after carrying out necessary system studies and,
if necessary, the outage programmes shall be rescheduled. Adequate balance between
generation and load requirement shall be ensured while finalising outage programmes.

4.3.7 The final outage plan alongwith the Load Generation Balance report(LGBR) shall be prepared
in consultation with NLDC and RLDC and intimated to NLDC, Users, STUs, CTU, other
generating stations connected to ISTS and the RLDC for implementation latest by 31st
January of each year as mutually decided in ERPC forum.

4.3.8 The above annual outage plan shall be reviewed by ERPC Secretariat on quarterly and
monthly basis in coordination with all parties concerned, and adjustments made wherever
found to be necessary.

4.4. Outage planning not covered in Annual Outage plan


4.4.1 Some of the outages not foreseen while finalising annual outage plan will be considered in
monthly OCC meeting of ERPC.

4.4.2 Indenting Agency: The agency which gives the requisition for outage of any transmission
element shall be called Indenting Agency. Any of the following may request for outage of any
transmission elements:
4.4.2.1 Transmission Licensees / State Transmission Utilities
4.4.2.2 Generating Companies

4.4.3 Indenting Agency shall submit the proposed shutdown for the next calendar month latest by
3rd day of the current month to the RPC Secretariat as per Format IA / Format IB.

4.4.4 In case of shutdown of inter-regional lines and intra-regional lines affecting the transfer
capability of any inter regional corridor, the Indenting agency shall submit the shutdown
proposal in both the concerned RPCs. To facilitate this broad list of such lines is indicated at
Annexure II which will be reviewed and updated by NLDC from time to time. The indenting
agency may do an internal screening of its outage plan centrally to avoid multiple outages in
the same corridor simultaneously. Bilateral discussion between the agencies involved may
also be done to minimize outage duration before submitting the outage plan to RPCs.

4.4.5 ERPC Secretariat shall compile all the received proposals and put up the same on its website
by 5th day of the month as per Format IIA / Format IIB.

4.4.6 System Study sub-committee of ERPC shall study the impact of these outages and based on
its recommendations, ERPC shall discuss proposed outages in the OCC meeting and prepare
a list of approved transmission outages with the precautions to be taken. ERPC would attempt
to schedule all their OCC meetings between 10th to 15th day of the month so that sufficient

_________________________________________________________________________
Operating Procedures for Eastern Region Page 14 28-06-2013
ERLDC:POSOCO

time is available both to the Study Committee before the OCC meetings as well as for
ELDC/NLDC (mainly to take care of further changes in the network topology and/or in load
generation) after the OCC meeting.

4.4.7 While approving the shutdowns it shall be ensured that outages in the same corridor shall not
be approved simultaneously. It also need to be ensured that all other concerned entities
should also complete their work during the shutdown period so as multiple shutdown of same
element for work by multiple agencies are avoided. The multiple outages of the transmission
element for the same work during the year may also be avoided.

4.4.8 ERPC shall send the list of approved transmission outages to SLDCs/ELDC/NLDC within 3
days of the OCC meeting and preferably latest by 18th of the month as per Format IIIA /
Format IIIB. The same shall also be displayed on ERPC websites.

4.4.9 Any shutdown proposal which requires approval of two RPCs shall be considered approved
only if it is approved in both the RPCs.

4.4.10 After the receipt of Format IIIA / Format IIIB from each RPC, NLDC in consultation with
RLDCs may prepare a tentative readjusted timings/dates of transmission element outages for
next month considering the principles set out in this procedure

4.4.11 In case of emergency in the system, viz., loss of generation, break down of transmission line
affecting the system, grid disturbances, system isolation, RLDC may conduct studies again
before clearance of the planned outage.

4.4.12 Vide clause 4.7(g) of IEGC ERLDC is authorised to defer any planned outage in case of any
of the following taking into account the statutory requirements:
i) Major grid disturbances (Total black out in Region)
ii) System isolation / separation
iii) Black out in a control area
iv) Any other event in the system that may have an adverse impact on the system
security by the proposed outage.

4.5. Procedure for Availing the Outage in Real Time


4.5.1 The agencies involved shall ensure availing of outages as per the approved schedule time.

4.5.2 On the day of outage, the outage availing agency shall seek the code for availing outage from
ERLDC/NLDC (wherever applicable). The agencies involved shall endeavour to avail the
outage with in 15mintues of availing the code but not later than 30 minutes. In case, due to
any contingency, the outage could not be availed within 30 minutes, a fresh code needs to be
obtained by all concerned agencies stating the reason there of Record of scheduled and
actual time of outage and restoration shall be maintained at ERLDC/NLDC.

4.5.3 ERLDC shall prepare a monthly statement of scheduled and actual time of outage and
restoration and forward the same to ERPC latest by 05th day of the next month with a copy to
NLDC.

4.5.4 SLDCs shall prepare a monthly statement of scheduled and actual time of outage and
restoration and forward the same to ERPC latest by 05th day of the next month with a copy to
ERLDC..

4.5.5 As any deviation in the outage from the schedule can affect other planned outages as well as
affect reliability and electricity markets, indenting agency must strictly adhere to the shutdown
timings

_________________________________________________________________________
Operating Procedures for Eastern Region Page 15 28-06-2013
ERLDC:POSOCO

4.5.6 RLDC if required shall conduct further system studies based on the system condition and
approve the shutdown at least two day in advance.

4.5.7 While issuing clearance of the shutdown ERLDC shall clearly mention the following( vide
format at Annexure IX)
i) Message no.
ii) Name of the element /elements which shall remain under outage.
iii) Name of the agency /agencies availing the outage.
iv) Date and duration of the outage
v) Nature of the outage
vi) Reason for availing the shutdown
vii) Specific network /system conditions to be maintained including impact of the outage
viii) Sequence of switching instruction if any

_________________________________________________________________________
Operating Procedures for Eastern Region Page 16 28-06-2013
ERLDC:POSOCO

Chapter 5
5. Switching Coordination
5.1. Introduction
Coordination of switching operations in the grid is important for ensuring safety of personnel and
equipment as well as for ensuring adequacy and security of the grid. Before any operation of
important elements of the Eastern Regional Grid is carried out on a User/STU system, the Users,
SLDC, STU, CTU, licensee shall inform ERLDC, in case the Eastern Regional grid may, or will
experience an operational effect.

5.2. Switching of System Elements for first time


In line with Regulation 6 (1) of the Central Electricity Authority (Grid Standards) regulations 2010, no
entity shall introduce an element in the ISTS of Eastern Grid without the concurrence of ERLDC in the
form of an operation code. In case a new power system element in Eastern Regional grid is likely to
be connected with the Inter-State Transmission System or is to be energized for the first time, from
the ISTS, the applicant User/STU/CTU/licensee shall send a separate request in advance along (at
least one week) with the confirmation of the following:
 Acceptance of ERLDC with regards to registration as regional entity
 Signed Connection Agreement if applicable
 Availability of telemetry of station/Element at the ERLDC/SLDC
 Availability of voice communication with the station at ERLDC/SLDC
 Interface meter installed and tested by downloading data and forwarding it to ERLDC
 Single Line Diagram
 Healthiness of Protection System/Protection Setting
 Statutory clearance has already been obtained

5.3. Switching of Important Elements


In line with regulation 5.2 (a, b, c), of the IEGC no part of the Eastern Regional grid shall be
deliberately isolated from the rest of the National/Regional grid except under an emergency
conditions in which such isolation would prevent a total grid collapse and would enable early
restoration of power supply or safety of human life; when serious damage to a costly equipment is
imminent and such isolation would prevent it; when such isolation is specifically instructed by ERLDC.
Important elements of the regional grid, which have a bearing on the network security, is
compiled and issued by ERLDC as a separate document [IEGC 5.2 (c)]. The regional entities, users,
STU, CTU, licensee shall obtain ‘operation code’ from ERLDC before carrying out any switching
operation on any of the important elements of the Northern Regional grid. Shut down of any 400 kV
bus at substation needs approval of ERLDC.
In respect of double main and transfer switching scheme at 400 kV substations, ERLDC shall
be informed whenever the 400 kV transfer bus at any substation is utilized for switching any line/ICT.
In a 400 kV substation/power station switchyard having breaker and a half switching scheme, outage
within the substation (say main or tie circuit breaker) not affecting power flow on any line/ICT can be
availed by the constituents under intimation to ERLDC. However, while availing such shutdowns or
carrying out switching operations it must be ensured that at least two Dias are complete even after
such outage from the view point of network reliability. Any outage not fulfilling the above conditions
needs the approval of ERLDC.
Whenever any protection system such as Bus Bar protection, LBB protection, Auto reclose
etc. at generating station or grid substation is required to be taken out of service for any maintenance
work, an operational code would be taken from SLDC/ERLDC.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 17 28-06-2013
ERLDC:POSOCO

5.4. Other Precaution to be taken during Switching


In addition to the above, it is necessary that special attention be paid to maintaining the reliability of
the system. The following areas need careful implementation by the concerned constituents / stations

i. In case of a two-bus system at any substation it must be ensured that the segregation of
feeders on the different buses is uniform. This would help in minimizing the number of
elements lost in case of a bus fault. This is assuming the availability of bus-bar protection at
such substation(s).

ii. In 400 kV substations having a breaker and a half scheme, it must be ensured that the two
buses at such substation remain connected at least by two parallel paths so that any line / bus
fault does not result in inadvertent multiple outages. In case any element, say a line or an ICT
or a bus reactor, is expected to remain out for a period say beyond two hours at such
substation, the main & tie breakers of such elements should be closed after opening the line
side isolator. This should be done after taking all suitable precautions to avert inadvertent
tripping. This of course assumes that no maintenance is planned on such breakers / isolators.

iii. In case when circuit breaker controlling the line is under lockout it is not advisable to interrupt
the changing current through an isolator the following practice to be adopted in such cases:-

a. De-energise the bus connecting the line with lockout CB and then open the isolator

b. If due to some reason it is not possible to open the isolator in above mentioned way,
and then open the isolator so that no charging current is interrupted through the
isolator and the charging current is diverted to other parallel path. Such switching
sequence could be possible in case of breaker and half scheme or Double breaker
Scheme, which is as follows:

i. Open the line from remote end first with direct trip (DT) disabled. With this now
line remains charged from the end where CB has problem.
ii. In case of breaker and half scheme open the isolator so that charging current is
diverted to the parallel path and after that open the CB of parallel path.
iii. In case of double breaker scheme open the isolator of the lockout breaker
diverting the charging current to other CB and then open the CB.
iv. In case of double main and transfer scheme open the isolator of lockout
breaker so that divert the charging current through transfer bus coupler and
then open the line through TBC circuit breaker.

It is also recommended that while vacating a bus in such cases, the operators
need to check the switching arrangement for individual feeders so as to avoid
unintended loss of any feeder.

iv. The substation operators must ensure the above condition even when any lightly loaded
line is opened to control overvoltage. Such opening of lines is generally superimposed
over other line outages on account of faults created by adverse weather conditions
resulting in reduced security of the system.

v. Single pole auto-reclose facility on 400 kV / 220 kV lines should always be in service.
ERLDC’s approval would be required for taking this facility out of service. Likewise, in
case any transfer breaker at any 400 kV substations having two main and transfer bus
scheme is engaged, the same would be informed to ERLDC.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 18 28-06-2013
ERLDC:POSOCO

vi. All precautions should be taken to avoid switching on to fault particularly in case of
Interconnecting Transformers. In order to avoid fault current through costly equipment
generally the line shall be charged from the far end, wherever possible.

vii. A transmission line side shall preferably be charged from the grid substation. Dead line
charging by a generator shall normally be avoided except during system restoration, black
start, or in case where both ends of the transmission line are terminating at a generating
station.

viii. During test charging of transmission line for the first time, all safety precautions shall be
taken and the transmission utility owning/operating the line shall satisfy the substation
utility at either ends with regards to statutory/safety clearances. During test charging if the
line does not hold even after two attempts, thorough checking of protection settings and
line patrolling shall be carried out.

ix. Operation code issued by ERLDC for switching shall become invalid if the switching is not
completed within half an hour of issue of code. In case the switching operation is not
completed within half an hour of the issue of operation code from ERLDC, and if there is a
probability of further delay same code could be revalidated by ERLDC within that half an
hour. The utility obtaining at one end shall intimate the other end utility.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 19 28-06-2013
ERLDC:POSOCO

Chapter 6
6. Periodic Reports and Event Information
6.0. Introduction
Timely and accurate reporting and exchange of information plays an important role in grid operation.
This assumes more importance during an occurrence/ a disturbance or in crisis. Timely and accurate
information flow under such conditions would help operators in making an informed decision and
reduces uncertainty. This chapter describes the event information and reporting procedure in writing
to all Regional entities, ERPC Secretariat/ERLDC/SLDC in accordance with the provisions of clause
5.9 of IEGC. This section in accordance with clause 5.5 describes the different periodic reports to be
prepared by RLDC to be sent to all entities of the region and ERPC Secretariat

6.1. Objective
The objective of this chapter is to define the incidents to be reported, the reporting route to be
followed and information to be supplied to ensure a consistent approach to the reporting of
incidents/events. The Objective of the periodic reports are to highlight performance of the Regional
Grid, bring out the system constraints, reasons for not meeting the requirements, if any, of security
standards and actions taken.

6.2. Periodic Reports


5.2.1 Weekly Report
As per clause 5.5.1 (C) of IEGC, ERLDC shall be responsible for issuance of weekly report
that shall cover the performance of the Regional Grid for the previous week. ERLDC shall
ensure that such weekly report be available at its website. The report shall be sent to all
Regional entities and ERPC Secretariat and shall contain the following -
i. Frequency Profile
ii. Voltage profile for selected substations
iii. Major Generation and Transmission Outage
iv. Transmission Constraints
v. Instances of persistent/significance non compliance of IEGC
vi. Instances of congestion in transmission system.
vii. Instances of inordinate delays in restoration of transmission elements and
generating units
The format for weekly report is shown at Annexure X

5.2.2 Quarterly Reports


A Quarterly report ( vide clause 5.5.2 of IEGC)shall be issued by ERLDC to all Regional
entities detailing the power supply positions during the last quarter, quality of supply, the
system constraints being faced and the agencies responsible causing constraints.
The format for quarterly report is shown at Annexure XI

5.2.3 Exceptional Reports


In case of any contingency such as industrial unrest, natural calamity etc., there could be
additional reporting requirements not covered in the above schedule. ERLDC shall inform all
regional entities of any such exceptional requirements and the entities would extend all
necessary cooperation in this regard.

5.2.4 Under frequency Relay(UFR) Operation Report

In accordance with clause 5.2(n) of IEGC , all distribution licensees / STUs shall provide automatic

_________________________________________________________________________
Operating Procedures for Eastern Region Page 20 28-06-2013
ERLDC:POSOCO

under-frequency and df/dt relays for load shedding in their respective systems, to arrest frequency
decline that could result in a collapse/disintegration of the grid, as per the plan separately finalized by
the concerned RPC and shall ensure its effective application to prevent cascade tripping of
generating units in case of any contingency. They shall inform (through their respective SLDCs) any
UFR operation that has taken place in their system and the areas affected with approximate quantum
of load relief obtained

6.3. Event Information


5.3.1 Vide clause 5.9.5 any of the following events require reporting by ERLDC/ Regional
entity

i) Violation of security standards


ii) Grid indiscipline
iii) Non compliance of RLDC’s instructions
iv) System islanding / system split
v) Regional blackout / partial system blackout
vi) Protection failure on any element of ISTS and or any item on the agreed list of the
intra-state systems
vii) Power system instability
viii) Tripping of any element of the regional grid
ix) Sudden load rejection in regional entity’s control area

5.3.2 Any tripping of an element under the list of important elements of regional grid, whether
manual or automatic, shall be intimated by the control centre of the regional entity to ERLDC
in a reasonable time say within 10 minutes of the incident. Along with the tripping intimation,
the reasons for tripping (to the extent known) and the likely time of restoration shall also be
intimated. Such information can be on telephone, fax or e-mail.

5.3.3 Any operation planned to be carried by a regional entity which may have an impact on the
regional grid or on any of the important element, shall be reported by the concerned SLDC to
ERLDC in advance.

5.3.4 Any operation planned to be carried out on the instructions of ERLDC which may have an
impact on the system of a regional entity shall be reported by ERLDC to the concerned SLDC
in advance.

5.3.5 The intimation and the exact time of revival of any element under the category of important
events will be furnished to ERLDC as early as possible.

6.4. Reporting system


The details of event reports and periodic reports to be prepared and issued by regional entities /
ERLDC are as follows:

5.4.1 In the event of tripping of any important elements, the preliminary event report with possible
details shall be sent by the SLDC of the concerned regional entity to ERLDC within a period of
three hours of the occurrence of the event and the detailed event report in the form detailed
under the section 5.9.6(C) of IEGC (contents vide Annexure XII) shall be sent within the
next day.
5.4.2 Such report shall follow the telephonic / flash reporting by the concerned SLDC say within a
reasonable time say within 10 minutes of the occurrence of the event as stated under Para
5.2(d)

_________________________________________________________________________
Operating Procedures for Eastern Region Page 21 28-06-2013
ERLDC:POSOCO

6.5. Grid Incidence/Disturbances and Categorisation


As per the severity of any events/incidences CEA has formulated the guidelines for categorisation of
Grid incidences and disturbances. Any event to be reported may therefore need to be categorised as
detailed below

5.5.1 Grid Incident

A Grid incident is tripping of one or more power system elements of the Grid like a generator,
Transmission line, Transformer, Shunt Reactor, Series capacitor, Static VAR Compensator (SVC) etc,
with no loss of grid supply or integrity of the grid at 220kV and above.

Categorisation of Grid incidents based in increasing order of severity

Category: 1 Tripping of one or more power system elements of the grid like a generator ,
transmission line, transformer, shunt reactor, series capacitor, Static VAR
Compensator(SVC) etc which requires rescheduling of generation or load
without total loss of supply at a sub-station or loss of integrity of the grid at
220kV (132kV in case of NER)

Category:2 Tripping of one or more power system elements of the grid like a generator ,
transmission line, transformer, shunt reactor, series capacitor, Static VAR
Compensator(SVC) etc which requires rescheduling of generation or load
without total loss of supply at a sub-station or loss of integrity of the grid at
400kV and above (220kV in case of NER)

5.5.2 Grid Disturbance


Grid disturbance is defined as tripping of one or more power system elements resulting in total failure
of supply at a sub-station or loss of integrity of the grid, at the level of 220kV and above (132kV and
above in case of NER)

Categorisation of Grid Disturbance in increasing order of severity is described as under.


Category 1: When less than 10% of the antecedent generation or load in a Regional Grid is
lost
Category 2: When 10% to less than 20% of the antecedent generation or load in a Regional
Grid is lost.
Category 3: When 20% to less than 30% of the antecedent generation or load in a Regional
Grid is lost
Category 4: When 30% to less than 40% of the antecedent generation or load in a Regional
Grid is lost
Category 5: When 40% or more of the antecedent generation or load in a Regional Grid is
lost.

ERLDC shall maintain a log (Vide Annexure XIII) of such incidences/disturbances and whenever
such incidences/disturbances occur shall report in writing (vide Annexure XII) as enumerated at para
5.4

Note: i) Any forced outage of ISGS generator would cause rescheduling of generation and
corresponding revision of drawal. Therefore, this should be treated as Grid incidence.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 22 28-06-2013
ERLDC:POSOCO

Chapter 7
7. Network Security and Congestion Management
7.0. Introduction
This chapter describes the actions required to be undertaken by system operators to maintain the
security of the network at all times against any plausible contingencies /outages within the ER
network as well as from any contingencies arising out due to incidences occurring in the rest of the
National grid that may have an adverse effect on ER system.

7.1. Network Security


7.1.1. Background
The Indian power grid has two synchronous grids viz (i) “NEW” Grid comprising of Northern , Eastern,
North Eastern and Western region and (ii) the Southern Region grid. With formation of the New Grid,
there has been sea change in the operational philosophy in system operation that has already yielded
various benefits like peak/off peak demand management through diversity of time, surplus/deficit
management due to seasonal resource variations, demand forecast errors, weather variations
besides increased economic transactions, improvement in overall system security due to increased
stability margin and a higher stiffness to the tune of 2200-2400MW /Hz. Eastern Region is
strategically located with synchronised interconnections with all the other regions of the NEW Grid
besides having synchronous integrated operation with Bhutan Power system. Eastern Grid is also
connected to Southern Region through two no HVDC interconnections having a total capacity of
3500MW capacity. The large number of synchronous interconnections of Eastern Region with other
regions/neighbouring country (Bhutan), however has also resulted in evolution of contingencies of
critical nature under different despatch/demand scenarios.

In addition, system may operate at times beyond the assumptions of the planner in line with various
transmission security standards and associated criteria mentioned in section 3.5 of IEGC due to
following reasons:

a) Planned maintenance programme of the generators and transmission lines. It is imperative to


ensure that such maintenance programmes are properly coordinated and do not result in reduced
redundancy not envisaged during planning.

b) The events beyond the control of operators such as extreme weather conditions affecting the
reliability of transmission system, uneven demand growth or delay in commissioning of
generators/transmission elements.

7.1.2. Measures to ensure Network Security and Reliability

In order to maintain the security of the Regional power system, it is important that the planned outage
of generation and transmission system particularly in the important flow-gates are properly
coordinated. The important flow-gates of Eastern region with the limits of flow gates are shown at
Annexure XIV. A list of important Regional Grid elements (vide clause 5.2(c) of IEGC) of the Eastern
regional grid which have a bearing on the network security are shown at Anneure-XV. It is therefore
necessary to carry out operational studies in order to assess the grid security and network stability
while finalizing the annual outage plan of these important elements. The outage planning should be
reviewed during the quarterly and monthly review of ERPC OCC forum.

Additionally, any opening of the important elements have to be carried out only after prior Intimation
to ERLDC as enumerated in the ‘Outage planning Procedure’. In the event of tripping of any of the

_________________________________________________________________________
Operating Procedures for Eastern Region Page 23 28-06-2013
ERLDC:POSOCO

important elements, ERLDC need to be informed at the earliest time indicating the likely time of
restoration. It is necessary that special attention is paid for maintaining the reliability of the system.

7.1.2.1. Assessment of Transfer Capability (Total Transfer Capability(TTC) and


Available Transfer Capability(ATC))

While a Transmission system is built, inherent design margins are kept in order to take care of
reliability and security issues, future generation growth, ROW issues, cost optimisation etc. The
interregional interconnections as have been planned and over the years had also taken care of
such margins. However, since power flow takes place as per the laws of physics and with more and
more AC interconnections between Areas/Regions the transfer between two or more regions gets
restricted because of factors like generation despatch conditions, loop flows between regions,
upstream or down stream network limitations, voltage and angular differences between critical buses
etc. Thus the Total transfer capability between areas is equal to or less than the aggregated design
capacity of interconnection/s and therefore need to be assessed through power system studies well in
advance considering the load / generation balance forecast to a fair degree of accuracy.

Available Transfer Capability (ATC) is a measure of the transfer capability remaining in the physical
transmission network for further commercial activity over and above already committed uses. It is
derived from the Total Transfer Capability (TTC) after discounting the total existing transmission
commitments and reliability margins. Thus ATC = TTC – Existing Transmission Commitments (viz.
Long Term) - Reliability Margins. This ATC is for scheduling short term bilateral and collective
transactions on the interregional links. In other words the simultaneous net total import or
export of a particular region taken together with the reliability margins must not exceed the
TTC in the respective direction. Reliability margins are also required to take care of the inherent
uncertainties in projecting transfer capability over longer time periods. These margins are necessary
for reliable transmission services to all transmission system users under a broad range of potential
system conditions. Margins in the form of Transmission Reliability Margin (TRM) and Capacity
Benefit Margin (CBM) must be kept aside to provide operating flexibility in real time.

STOA- Bilateral+Collective ATC

Long Term Open Access TTC

Reliability margin

Transmission Reliability Margin (TRM)


Transmission Reliability Margin(TRM) is the amount of transmission transfer capability necessary to
provide a reasonable level of assurance that the interconnected transmission network will be secure.
TRM accounts for the inherent uncertainty in system conditions and its associated effects on ATC
calculations, and the need for operating flexibility to ensure reliable system operation as system
conditions change.

It is therefore imperative that the exchanges between regions are contained to a level of ATC
and in no case exceed the TTC between the regions. All the regional entities of Eastern Region
and / or neighbouring region(s) will adhere to their levels of net interchanges as advised by

_________________________________________________________________________
Operating Procedures for Eastern Region Page 24 28-06-2013
ERLDC:POSOCO

ERLDC whenever such breach in TTC level among the regions takes place to ensure the grid
security irrespective of frequency and schedule .

Assessment of Total Transfer Capability (TTC), Transmission Reliability Margin (TRM) and Available
Transfer Capability (ATC) for import and export of power within Eastern region as required for reliable
system operation and for facilitating non-discriminatory open access in transmission shall be carried
out by ERLDC in coordination with National Load Despatch Centre and other RLDCs. The ‘Detailed
Procedure for Relieving Congestion in Real Time Operation’ as approved by the CERC vide order
dated 22.04.2013 may be referred for further details. The assessed TTC, TRM and ATC shall be
posted on ERLDC/NLDC website.

The detailed procedure for assessment of TTC, monitoring and invoking congestion
conditions in real-time, application of Congestion Charge and Congestion Charge accounting
and settlement shall be as per the regulation / procedure issued / approved by CERC

7.1.2.2. Flow gates and Congestion Management

Eastern Region being strategically located, it is connected to all the other regions. The typical
generation dispatch pattern during monsoon and winter, demand scenarios within the region as well
as of the other regions results in congestion in some corridors of the Eastern Network. These
congestions are well identified. The anticipated power flow pattern along these flow gates has a direct
impact on the Total Transfer Capability in different seasons. While carrying out the system studies for
arriving at the TTC and ATC figures anticipated flow pattern along these flow gates need to be
checked under and in real time require to be monitored for a secured operation. The various flow
gates and their characteristics and actions required to be taken by ERLDC operators during
congestions in these flow gates are described below:

7.1.2.2(a) Flow gate –I ( allowable limit≈ 4000MW) ( vide Annexure XIV(a))

400kV Kahalgaon-Banka-Biharsariff D/C


400 kV Kahalgaon-Biharsariff D/C
400kV Kahalgaon-Barh D/C

Scenarios:
 High drawl by NR
 Injection from WR and SR

Northern region imports power through ER-NR tie links throughout the year. Around
50-60% of this power flows through 400 kV Kahalgaon-Biharsariff D/C, Kahalgaon-
Banka-Biharsariff D/C and 400kV Kahalgaon-Barh D/C. the loading of 400 kV
Kahalgaon-Biharsariff D/C, Kahalgaon-Banka-Biharsariff D/C and remains around
2000 MW throughout the year while that of the 400kV Kahalgaon-Barh D/C remains
around 1500 MW. In case the summation of flow of above six lines remains under
4000 MW then n-1 security criteria is satisfied, but in case the loading goes above
4000 MW then n-1 security criteria may not be satisfied.

Congestion Management:
In the event loading across this flow gates exceeding beyond allowable limit following
actions may be initiated:

1. Request NRLDC to maintain their schedules if they are overdrawing with respect to
schedule.
2. Request W.Bengal and DVC SLDCs to maintain drawal as per schedule in case
they are underdrawing with respect to schedule

_________________________________________________________________________
Operating Procedures for Eastern Region Page 25 28-06-2013
ERLDC:POSOCO

3. Request Bihar to maintain its schedule if it is overdrawing with respect to schedule.


4. Request BSEB to reduce its drawl at Biharsariff and Patna.
5. In case ER is availing UI power from SR/WR check whether reduction in UI
quantum ease out the congestion or not. Check whether UI transactions to SR over
HVDC links is possible or not
6. Request curtailment of drawal by NR on account of congestion
7. Request NLDC to invoke the congestion charge if curtailment of drawal is not
forthcoming.
8. Monitor the congestion and inform NLDC immediately as soon as the congestion is
removed

7.1.2.2(b) Monsoon Flow gate –I ( allowable limit≈ 1900MW) ( vide Annexure XIV(b))

400kV Purnea-Muzaffarpur D/C ( with TCSC at Purnea)

Scenarios:
 Monsoon ( period Mid July to Sept)
 High Availability at Binaguri 400kV S/S (≈ 2000MW and more) due high generation
at the following stations
 Teesta = 510 MW
 Import from Tala HEP/Chukha HEP ≈ 1100 MW
 Import from North Eastern Region ( surplus hydro) ≈400-500MW
 High Demand in Northern Region

During peak monsoon, the power of the order of 2000 MW available from Bhutan,
Teesta and NER on the round the clock basis is essentially pooled Binaguri 400kV S/S.
Northern Region having higher demand during these periods most of the hydro power
as above is evacuated to Northern Region along Tala Transmission System. The
series compensated 400kV Purnea – Muzaffarpur D/C because of its lower impedance
gets loaded at times beyond 900 MW per ckt. Any outage of one of the circuit of
Purnea-Muzaffarpur might therefore lead to overloading of other circuit beyond
permissible limit.

Congestion Management:
In the event loading across this flow gates exceeding beyond allowable limit( As
notified separately during TTC calculation( generally around 1900MW ) following
actions may be initiated :
.
(i) In case ER is availing UI power from SR check whether reduction in UI
quantum ease out the congestion or not. Check whether UI transactions to
SR over HVDC links is possible or not
(ii) Request West Bengal and DVC SLDC to maintain drawal as per schedule in
case they are underdrawing with respect to schedule
(iii) Request NERLDC to maintain curtail overinjection
(iv) Request curtailment of drawal to NR on account of congestion
(v) Request NLDC to invoke the congestion charge if curtailment of drawal is not
forthcoming.
(vi) Monitor the congestion and inform NLDC immediately as soon as the
congestion is removed.

7.1.2.2 (c) Winter Flow gate –I ( allowable limit≈ 1200 MW or less) (vide Annexure XIV(c))

400kV Farakka-Malda D/C

_________________________________________________________________________
Operating Procedures for Eastern Region Page 26 28-06-2013
ERLDC:POSOCO

Scenarios:
 Winter ( period Dec to Mid Feb)
 Low Hydro Availability at Bhutan( Tala and Chukha), Teesta, and NE Region
 High winter Demand in Northern Region

The high demand in Northern Region during winter results in higher drawal from
Eastern Grid. As hydro availability in North Eastern Region also gets depleted,
overdrawal by NE Region is also a frequent phenomenon. The scarce Hydro
availability within Bhutan and Teesta cause power to flow northwards along Farakka-
Malda 400kV D/C corridor. Frequent congestion is noticed along this corridor as the
power in Farakka-Malda 400kV D/C often exceeds 1200MW. Although at 1200 MW
load, n-1 security criteria is not satisfied for Farraka-Malda D/C (twin moose), it is
estimated that an (n-1) -1 contigency upto this order of power flow can be sustained by
ER grid. However beyond 1200 MW such a contingency may not be tolerable.
Although TCSC at Purnea provides desired stability margin along Tala
Transmission system, yet during winter, the FSC at Purnea is required to be kept open
as the lower impedance across Purnea-Muzaffarpur section aggravates the congestion
at Farakka – Malda D/C. Therefore, before onset of high winter demand in NR, ERLDC
may review the various corridor loading and consider keeping FSC at Purnea under
switched off condition during winter.

Congestion Management

(i) Request NR/NER to maintain their schedules if they are overdrawing


with respect to schedule.
(ii) Check whether any UI transaction over HVDC link to SR is possible or
not.
(iii) Request ER constituents to maintain schedule if it is under drawing.
(iv) Check whether any available hydro generation at Teesta ,Tala or
Chukha can be increased
(v) Request NLDC to invoke the congestion charge if the violation of
schedules leading to the congestion is continuing.

7.1.2.2 (d) Winter & Summer Flow gate –II (vide Annexure XIV(d))

 400kV Rourkella-Talcher D/C


 400kV Kharagpur-Baripada S/C
 400 kV Jamsedpur-TISCO-Baripada S/C

Scenarios:
 Winter-Summer ( period Nov to May)
 High Drawl by Orissa.
 High export to Southern Region
 Less generation at Talcher St-I (2x500 MW)

The high demand in Southern Region during winter and summer results in higher
Power export to SR through HVDC links at Gazuwaka and Talcher. As hydro
availability in South Odisha also gets depleted, Odisha resort to high drawl from Grid
to meet its load. These two condition along with less generation at Talcher St-I leads to
sever loading of 400 kV Rourkela-Talcher D/C. Although the recently constructed 400
kV Jamsedpur-Baripada LILOed at TISCO eases out loading of 400 kV Rourkeal-
Talcher to some extent. It is expected that construction of second 400 kV Jamsedpur-

_________________________________________________________________________
Operating Procedures for Eastern Region Page 27 28-06-2013
ERLDC:POSOCO

Baripada(direct circuit) will further reduce its flow. However as these lines are new and
we have yet to witness a summer and winter with these new lines. So this flow gate is
kept under consideration.

Congestion Management

(i) Request Odisha to maintain it schedules if they are overdrawing with


respect to schedule.
(ii) It should be insured that no power to SR should be exported under UI .
(iii) Request West Bengal to maintain its schedule if Over drawing. .
(iv) Request WRLDC/NLDC to limit WR-ER flow if Western region is
injecting power in ER beyond its schedule.

Message for controlling congestion


In case of violation of TTC/Flow Gate limit/ overloading of any line / ICT a message is to be issued to
the SLDC of the concerned regional entity(ies) / RLDC of the concerned region(s) for immediate
remedial action. Format of the message is given at Annexure XXIV

7.1.2.3. Monitoring of Congestion


Real time data for monitoring Congestion shall be displayed on the ERLDC website in the formats as
enclosed in Annexure-XXV.

7.1.2.4. Generation Rescheduling


ERLDC may revise the interchange schedule as allowed by IEGC regulation 6.4.12, 6.5.5, and 6.5.16.
Further details may be seen in the chapter on scheduling.

7.1.2.5. Curtailment of Scheduled Transactions


The transactions already scheduled may be curtailed by ERLDC in the event of transmission
constraints; congestion in the grid, or in the interest of grid security. In line with regulations 6.4.12,
6.5.28, 6.5.30 and 6.5.31 of IEGC the transactions shall generally be curtailed in the following
sequence
a. Unscheduled Interchanges
b. Short term bilateral transactions
c. Short term collective transactions
d. Medium term transactions
e. Long-term transactions
Amongst the customers of a particular category, curtailment shall be carried out on pro rata basis.
ERLDC would curtail a transaction at the periphery of the Regional entities. SLDC (s) shall further
incorporate the inter-se curtailment of intra State entities to implement the curtailment.

7.1.2.6. Procedure for Relieving Congestion


Congestion Management shall be as per the detailed procedure for relieving congestion in real time
operationas approved by CERC vide its order dated 22.04.2013. It is important to note that the
congestion charge could be applied both upstream and downstream of the congested corridor
irrespective of the frequency. Whenever actual flow on inter/ intra regional link/ corridor exceeds
Available Transfer Capability and security criteria are violated for continuously two time blocks, the
National Load Despatch Centre may issue a warning notice. In case SLDC observes congestion
within the Intra State grid it shall take appropriate action and inform the respective RLDC which in
turn shall inform the NLDC. The notice for congestion shall be communicated to all the Regional
entities telephonically or through fax/voice message/ e-mail and through postings on website and
making the same available on the common screen at NLDC/ RLDCs/ SLDCs. The various formats

_________________________________________________________________________
Operating Procedures for Eastern Region Page 28 28-06-2013
ERLDC:POSOCO

may be referred in the detailed procedure for relieving congestion in real time operation under
regulation 4 (2) of the Central Electricity Regulatory Commission (Measures to relieve congestion in
real time operation) Regulations, 2009.
7.1.2.7. Defence Mechanism
Despite utmost caution exercised during operational planning and implementing all the above
steps to improve the network security and reliability, the possibility of a contingent situation
cannot be totally ruled out. It calls for suitable defence mechanism to be available in the system
to take care of such contingencies. Following are the minimum schemes which should be
operational in Eastern Region to ensure safe and secure grid operation.

i) Automatic Under Frequency Load Shedding Scheme.


In line with clause 5.2(n) of IEGC, all regional entities shall provide Automatic Under Frequency
Load Shedding in their respective system to arrest frequency decline that could result in a
collapse / disintegration of the grid as per the scheme formulated by ERPC forum and shall
ensure its effective application and functionality at all times to prevent cascade tripping of
generating units in case of any contingency. ERLDC shall inform ERPC Secretariat about
instances when the desired load relief is not obtained through these relays in real time operation.
ERPC Secretariat shall carry out periodic inspection of U/F relays and maintain proper records of
the inspection. It is extremely important that there should be no overlapping between the areas
covered by under frequency load shedding and that included in the manual load shedding plan
as part of demand control. The approved Automatic Under Frequency Load Shedding Scheme at
Annexure XVI

ii) Special Protection scheme


Such schemes are required to take care of some special contingencies and operate under
specific contingency conditions.

Power Demand Over (PDO) ride at Gazuwaka and Talcher

The Power Demand Override at HVDC stations control systems provide the features when power
flow through HVDC System gets automatically changed to preset value when declared
contingencies such as tripping/overloading of elements or tripping of generators take place.
The HVDC back to back station at Gazuwaka having a transfer capacity of 1000 MW( 500 MW
per pole block) is utilised for transfer of power from Eastern Region to Southern region. The
station is connected to Jaypore 400kv substation of CTU in Eastern Region. Jeypore substation
is in turn connected to Indravati (PowerGrid) and Meramundali(OPTCL) thro S/C 400kV lines.
However, Jeypore has further connectivity to 220kV system of OPTCL via 2x 315MVA ICTs.
However under heavy power transfer to Gazuwaka(SR) from Jeypore tripping of any of the
element as mentioned above might give rise to a contingent condition leading to cascade tripping
of one or more elements within south Orissa network. In order to circumvent this contingency
condition following special protection system of power demand override has been implemented
at Gazuwaka HVDC station
Similarly PDO at Talcher and Kolar is also designed to a preset value under certain
contingencies. These PDOs are described at Annexure XVII

Special protection system at HVDC Talcher( SPS 450 and SPS 1000)

Talcher Super thermal power station having a capacity of 3000MW( 6x500 MW) is located in
Orissa of Eastern Region. The station was commissioned with 2x500MW capacity and
subsequently its second stage was commissioned and station capacity was augmented to

_________________________________________________________________________
Operating Procedures for Eastern Region Page 29 28-06-2013
ERLDC:POSOCO

3000MW with commissioning of its further 4x 500MW machines. The station is the largest
capacity station in the region. However, the capacity of the entire stage II ( 4x500 MW) was
allocated to the beneficiaries of southern region. Subsequently, 10% of the capacity was
allocated to the Orissa, in Eastern region. For evacuaton of Talcher STPS –II generation to
Southern Region, +/- 500kV HVDC bipole transmission system was commissioned right upto the
load centre of Southern Region at Kolar. The HVDC substation at Talcher has two pole blocks
1000MW capacity each( subsequently augmented to 1250MW ).
The very basic design of the evacuation system of Talcher stage II to SR poses a major threat to
Eastern Region and subsequently to the New Grid as any sudden forced outage of one or both
the poles would mean that Eastern Grid has to initially absorb a jerk of load throw off to the tune
of 1800-2000MW . The surplus power would get wheeled through Talcher-Rourkella 400kV D/C
and Rengali –Baripada-Kolaghat S/C. During monsoon as such these corridors remain heavily
loaded and such contingency of pole block at Talcher would lead to a definite cascade tripping
leading to isolation /possible collapse of Orissa system including TSTPP station. In order to avoid
such contingency two automatic special protection schemes were envisaged and have been
implemented at Talcher Super Thermal power station. The 1st scheme as commonly known as
SPS 450 was first implemented and subsequently a further improvised 2nd scheme was devised
as known as SPS 1000 scheme. Both the schemes and their modalities of arming and disarming
is described below:
SPS 450: This scheme was originally implemented with a view that Eastern and Western Region
would absorb a jerk of 450 MW therefore rest of the generation as available at Talcher stage II
generation must be shed in order avoid a cascade tripping of the network. However, during
monsoon, from Eastern Regional point of view at times absorbing even 450MW under N-1
contingency criteria of Talcher-Rourkella 400kV D/C Line becomes critical when major
generation at Talcher stage II must be shed in order to avoid further criticality of the Grid. Further
under any critical outage condition in the rest of the New Grid outage of HVDC bipole might pose
a serious threat when it might necessitate arming of SPS -450 scheme with due coordination
with NLDC. The Scheme is described below

SPS 1000: Post formation of the NEW Grid this scheme was subsequently envisaged in order to
minimise shedding of generation at Talcher STPP. The basic philosophy of this scheme is to
absorb 1000MW in place of 450 MW as the Grid size increased. However, as one of the
prerequisites for arming this scheme Eastern Regional operator has to ensure that sufficient
evacuation margin( approx 1000 MW) is available at the AC evacuation system of TSTPP. The
scheme is described below:

Both SPS 450 and SPS 1000 schemes are described at Annexure XVIII

Special protection system at SEL (Sterlite Energy Limited)


SEL have a total installed capacity of 2400 MW ( 4 x 600 MW) is located in Odisha. Out of these
four units second unit (Unit-2) is dedicated to Odisha and is connected at separate 400 kV Bus
(400 kV OPTCL bus) which also have 2 x 315 MVA 400/220 KV ICT installed. The 220 kV side of
this SEL bus is connected with 220 kV VAL (Vedanta Aluminium limited) through 220 kV SEL-
VAL D/C.
The remaining three unit at SEL (Unit 1, 3 & 4) is connected to other 400 kV Bus at SEL (400 kV
PGCIL bus) which further have four outgoing lines connected to it, two to Rourkela and two to
Raigarh. In turn these four lines i.e 400 kV SEL-Raigarh D/C and 400 kV SEL-Rourkela D/C is
used to evacuate power from SEL.
SPS at SEL continuously monitor flow of all 400 kV lines and it gets actuated whenever flow of
any line touches 650 MW. In case flow of any line exceeds 650 MW, generation reduction at SEL
took place to bring the line loading under limit.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 30 28-06-2013
ERLDC:POSOCO

iii) Islanding Scheme


To avoid total black out of the grid during system disturbances and for early normalisation, the
procedure for islanding of systems and major generating stations with associated loads need to be
developed constituent wise/system wise. The islanding schemes as in operation in Eastern Region is
shown at Annexure XIX

7.1.2.8. Switching Diagram


The switching diagrams of all generating stations (100 MW and above), 400kV, important 220kV
and 132kV substations especially those involved in the evacuation of generation shall be made
available to ERLDC system operator at SCADA Desk. The selection of such diagrams is
described at Chapter 8. The same shall be updated from time to time.

7.1.2.9. Operational Areas of Importance


The following areas needs careful implementation by the concerned constituents / stations:-
i) In case of a 2 main & transfer bus system at any sub-station, it must be ensured that the
segregation of feeders on the different buses is uniform. It would help in minimizing the
effect on the system in case of a bus fault.
ii) In 400kV substations having one and half breaker scheme, it must be ensured that each
feeder remains connected to both the buses so that any bus fault does not result in
inadvertent outage of feeders. In case any element, say a line or an ICT or a bus reactor,
is expected to remain out for a prolonged period at such substation, the main and tie
breakers of such elements should be closed after opening the line side isolator. This
should be done after taking all suitable precautions to avert inadvertent tripping.
iii) The substation operators must ensure the above condition even when any lightly loaded
line is opened to control over voltage. Such opening of lines is generally superimposed
over other line outages on account of faults created by adverse weather conditions
resulting in reduced security of the system.
iv) Single pole auto reclose facility on 400kV lines should always be in service. Approval of
ERLDC would be required for taking this facility out of service. Likewise, in case any
transfer breaker at any 400kV substations having two main and transfer bus scheme is
engaged, the same would be informed to ERLDC.
v) In order to damp out the low frequency oscillations in the system, the power system
stabilizers on the generating units would be tuned as per the programme drawn at ERPC
forum. in consultation with the constituents.
vi) All regional entities would endeavor to operate the connected generation and reactive
power management devices such as Capacitors, Reactors, Synchronous Condensers,
Fixed Series Capacitors (FSCs), Static Var Compensators (SVCs) etc in a manner which
enables stable voltage behavior at various points of the grid under different operating
conditions.
vii) All regional entities would also maintain in good operating conditions of all control
measures such as defence mechanism, SPS, U/F & U/V load shedding, AVRs, PSS,
FGMO, Operating reserves, emergency back-up power supplies etc., and ensure that the
operational security standards are maintained for reliable and secured operation of the
interconnected
system.
viii) In line with sections 5.2(f) of the IEGC, the generating units should ensure free governor
operation.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 31 28-06-2013
ERLDC:POSOCO

7.1.2.10. Recording Instruments, Voice and Communication Facilities


i) The recording instruments such data acquisition system, disturbance recorder event logger,
fault locator, time synchronization equipment voice recorder and any other such equipment in
each generating station / sub-station / control centre / SLDCs / ERLDC shall be kept in good
working condition in order to record the events and sequence. All such places shall have a
common time reference whose authenticity shall be ensured by periodic verification and
validation procedure to be developed and monitored by ERPC Secretariat.
ii) Each regional entity shall provide adequate and reliable communication facility internally and
with other constituents / RLDC to ensure exchange of data / information necessary to
maintain reliability and security of the grid. All the agencies shall provide systems to telemeter
power system parameters such as power flow, voltage and status of switches/transformer
taps etc., in line with interface requirements and other guidelines made available to RLDC /
SLDCs atleast before the date of commercial operation of the generating stations or
substation/line being connected to the ISTS.
iii) In line with Central Electricity Authority (Technical Standards for Connectivity to Grid)
Regulations 2007, the requester and user shall provide necessary facilities for voice and data
communication and transfer of online operational data such as voltage, frequency, line flows
and status of breaker and isolator position and other parameters as prescribed by the
appropriate Load Despatch Centre and agree to maintain the communication system in good
condition.
iv) In line with Central Electricity Authority (Technical Standards for Connectivity to Grid)
Regulations 2007, every generating station and substation connected to the grid at 220kV or
above shall be provided with disturbance recording (DR) and event logging facilities. All such
equipment shall be provided with time synchronization facility for common time reference.
v) For a high degree of service reliability under normal and emergency operation, at least one
main telecommunication channel with an alternate backup channel shall be provided

7.1.2.11. Monitoring of System States (Grid Health)


As a corollary to the provisions laid down in the IEGC chapter on Operating Code for Regional
Grids, ERLDC has the responsibility of monitoring the state of the regional grid at all times.
The state of the grid has been classified as either NORMAL or ALERT or EMERGENCY,
depending on whether certain security criteria are violated or not, as stated below. The display
system in control room has been accordingly modified to alert the operator, in case the state
of the grid passes to either to ALERT mode or EMERGENCY mode. The Boolean conditions
for various modes are as follows:

NORMAL mode – (Grid frequency  49.9 Hz) AND (No Flowgate limit, as specified by
operator violated)

ALERT mode – Actual flow through Flowgate-1  Limit specified by operator


OR
Actual flow through Flowgate-2  Limit specified by operator
OR
Actual flow through Flowgate-3  Limit specified by operator
OR
Actual flow through Flowgate-4  Limit specified by operator
OR
Grid Frequency  49.9 Hz & > 49.7 Hz

EMERGENCY mode – (Resultant output of ALERT mode) AND (Grid Frequency  49.7 Hz)

_________________________________________________________________________
Operating Procedures for Eastern Region Page 32 28-06-2013
ERLDC:POSOCO

Chapter 8
8. Scheduling and Despatch Procedure
8.0. Introduction
The broad principles and guidelines to be followed for scheduling and dispatch of power in the
regional ISTS and the demarcation of responsibilities for this purpose are in accordance with Part 6 of
the IEGC.
8.1. Scope
This procedure is applicable to ERLDC and other RLDCs, all the thermal and hydro ISGSs on which
beneficiary constituents have shares, the beneficiary constituents of Eastern Region and any regional
entity. For the purpose of implementation of the schedules for import of power from Hydro stations in
Bhutan, this procedure shall also be applicable to the hydro stations of Bhutan
8.2. Objective
This chapter deals with the procedures to be adopted for scheduling of the inter-State generating
stations (ISGS) and net exchange of regional entities on a daily basis with the modality of the flow of
information among the ISGS/RLDCs/entities of the Region. The procedure for submission of
capability declaration by each ISGS and submission of exchange schedule by each beneficiary is
intended to enable RLDCs to prepare the dispatch schedule for each ISGS and exchange schedule
for each beneficiary. It also provides methodology of issuing real time dispatch/drawal instructions
and rescheduling, if required, to ISGS and beneficiaries.
8.3. Description of the procedure
The Regional grids shall be operated as power pools (with decentralized scheduling and dispatch), in
which the States shall have operational autonomy, and SLDCs shall have the total responsibility for (i)
scheduling /dispatching their own generation (including generation of their embedded licensees), (ii)
regulating the demand of their customers, (iii) scheduling their drawal from the ISGS (within their
share in the respective plant’s expected capability), (iv) arranging any bilateral interchanges, and (v)
regulating their net drawal from the regional grid. The system of each State shall be treated and
operated as a notional control area. The algebraic summation of scheduled drawal from ISGS , long-
term access , medium term and short-term open access arrangements shall provide the drawal
schedule of each State, and this shall be determined in advance on daily basis. The regional entities
shall regulate their generation and / or consumers’ loads so as to maintain their actual drawal from
the regional grid close to the above schedule. The regional entities, through their SLDCs shall always
endeavour to restrict their net drawal from the grid within their respective schedules, whenever the
system frequency is below 49.8 Hz or the loading of any important transmission element is beyond
the acceptable limit. Below 49.7 Hz, regional entities shall carry out requisite load shedding to ensure
that there is no overdrawal.
The introduction of the scheduling and despatch mechanism as mandated in IEGC, has further
evolved the framework for developing other power markets such as Short term open access
transactions and collective transactions that can fit in with the scheduling and despatch procedures
as mandated in IEGC. Further CERC has also issued regulation on Short Term and and Collective
transactions and procedure for short term and collective transactions have been duly issued by CTU
and approved by CERC. Therefore procedure as issued by CTU on Short term and Collective may
be referred separately as a part of this procedure. In order to understand the procedure and bring in
more clarity the scheduling and despatch procedure has been prepared in the form of flow chart as
described below:
The entire activities are broadly divided into three parts namely
(i) Day ahead scheduling
(ii) Revision of schedules
(iii) Implementation of Final schedules

_________________________________________________________________________
Operating Procedures for Eastern Region Page 33 28-06-2013
ERLDC:POSOCO

All the relevant formats are enclosed at Annexure XX

Under fuel shortage conditions, thermal ISGSs may face constraints in adhering to the usual
scheduling procedure. They may propose to deliver a higher MW during peak-load hours by saving
fuel during off-peak hours, in pursuance to Clause 21(4) of the CERC Terms and Conditions of Tariff
2009-14. The broad guidelines to be followed for scheduling ISGSs under such conditions are as
follows:

 Fuel shortage would be declared by the generating stations on a day ahead basis only and
status cannot be changed during the day of operation even if fuel supply status changes,
except in case of unit tripping.

 The concerned plant shall declare its energy capability (MWh), maximum ex-bus
generation (MW) and minimum possible ex-bus generation (MW) that can be maintained.

 Utilities may requisition based on their requirements either as average MW in all time
blocks or different MW in different time blocks upto the entitled maximum MW remaining
within the total energy entitlement for the day. The default would be average MW during all
blocks for those beneficiaries whose time-block wise requisition is not received by RLDC.

 Peak hours shall be of minimum three hours duration as decided on a regional basis
through Operational Coordination sub Committee (OCC) meetings of the RPC. In between
the month changes could also be done by RLDC with advance declaration of two days.
The OCC can also decide peak hours as more than 3 hrs based on regional load curves
either in one continuous spell or two spells for covering morning and evening peak hours.
[e.g. one and half hour continuous or 1 hour and 2 hour continuous in each spell].

 DC for the day in such an event shall be taken to be equal to the maximum peak-hour ex-
power plant MW schedule specified by the concerned Load Despatch Centre for that day.

8.4. Procedure for revising ISGS schedule downwards on account of surrendering of


share by beneficiaries
As already mentioned in this chapter, the beneficiaries of an ISGS have full autonomy in deciding
their respective requisitions from the ISGS. Thus, in the event of low demand as well as high
availability from own generating stations, a beneficiary may either not requisition its full share or even
prefer to forgo its full share from the ISGS. Such surrendering by multiple beneficiaries of a thermal
ISGS for a particular time period , may cause the despatch schedule of the station to become less
than the minimum level of generation technically achievable by the thermal units. Under such
circumstances ERLDC will moderate the requisitions of the under-requisitioning beneficiaries in a
manner so that unrealistic backing down or shutting down of thermal unit can be avoided. The
general philosophy to be adopted is as follows:

8.4.1. Before issuance of revision 0 schedule (at 17:00 Hrs) for the next day
If the generation schedule on certain time blocks determined by summing the requisitions of its
beneficiaries is found to be less than the technical minimum level of the station, ERLDC shall pro-rata
reduce the requisitions of the under-requisitioning beneficiaries as per their entitlement in order to
maintain the dispatch schedule of the plant at the technical minimum level.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 34 28-06-2013
ERLDC:POSOCO

8.4.2. Before issuance of revision 1 schedule (at 23:00 hrs) for the next day
(a) If the dispatch schedule of the station on certain time blocks is already below the declared
capability and further surrendering of share by any beneficiary leads to a schedule that is
below the technical minimum level of the station, then the revision in requisition will be
accommodated to the extent that does not result in a schedule below the minimum feasible
level.

(b) In case of surrendering of share by multiple beneficiaries received between 17:00 hrs to
22:30hrs, pro-rata approach will be adopted.

8.4.3. On the day of operation:


Surrendering of share will be considered on first-come-first-serve basis. At any stage, if the dispatch
schedule is already at the technical minimum level, no further request for surrendering of share will be
entertained by ERLDC.

8.4.4. Status of requisition


Requisition for revision received at ERLDC will remain valid till the revision of corresponding schedule
is carried out and published. Thereafter validity of the same requisition will expire and no reference of
any earlier requisition can be drawn at a later time/date.

8.4.5. Revision of schedule for upward revision of entitlement


As per present practice agreed by all constituents, in case of upward revision of entitlement, full
entitlement will be scheduled to those constituents who have already requisitioned full entitlement
previously.
In case there is already less requisition by any constituent from ISGS/s for some block, no revision of
schedule will be carried out for upward revision of entitlement for those blocks for that constituent
provided technical minimum limit criteria is satisfied. If technical minimum limit criteria is/are not
satisfied, then ERLDC shall increase requisition of that constituent to the extent to give technical
minimum schedule of that ISGS. However, for those blocks where full entitlement is requisitioned the
same constituents, ERLDC will schedule full entitlement for that constituent.

8.4.6. Revision of schedule for downward revision of entitlement


In case downward revision of entitlement, revision of schedule will be carried out subject to restricted
entitlement. No revision will be carried out for that constituent, whose requisition is already below
entitlement previously till technical minimum limit criteria is/are satisfied and requisition is less than
revised entitlement. If technical minimum limit criteria is/are not satisfied, then ERLDC shall increase
requisition of that constituent to the extent to give technical minimum schedule of that ISGS.
In case of subsequent upward revision of entitlement, same methodology as followed in case
of upward revision of entitlement will be followed.
For those constituents, who have given less requisition from any ISGS earlier and due to
subsequent downward revision of entitlement from same ISGS which is less than the
requisition(specially when unit trips), schedule from that ISGS will be restricted to entitlement for that
constituent and validity of earlier requisition of that constituent will expire. In case of subsequent
upward revision of entitlement from same ISGS (specially when unit returns), ERLDC will schedule
full entitlement from that ISGS to the same constituent.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 35 28-06-2013
ERLDC:POSOCO

8.4.7. Scheduling of LTA and MTOA:

1. Constituent/Generator would only furnish to ERLDC the mutually agreed schedules by 17:00 Hrs
for the next day. Endorsement of the concerned SLDC/RLDC (when one of party is from outside
region) will be required.
2. ERLDC would incorporate the schedules and release the schedule for next day by 18:00 hrs.
3. SLDCs/Generators can inform of any mutually agreed changes duly endorsed by concerned
SLDC/RLDC (when one of party is from outside region) by 22:00 hrs of previous day to ERLDC.
4. Schedules for next day to be frozen by 23:00 hrs
5. Revision of the schedule during course of the day would be permitted, depending upon intimation
of the revised mutually agreed schedules duly endorsed by concerned SLDC/RLDC (when one of
party is from outside region) to ERLDC. The concerned SLDCs/RLDCs (when one of party is from
outside region) may also give standing instructions to ERLDC in advance to accommodate all day
ahead requisition/revision on the day of operation, on behalf of constituents under their jurisdiction
so that schedule furnished by other constituent/s/generator/s will be construed as mutually agreed
schedule and will be revised accordingly.
6. In case of tripping of unit of Generating station/s having LTA, schedule will be revised with
intimation to concerned SLDCs/RLDCs. The revised schedules shall become effective from the
4th time block, counting the time block in which the forced outage is declared and revision sought
in MW quantum from the generator to be the first one.
7. Revised schedules for other revision shall become effective from the 6th time block, counting the
time block in which revised mutually agreed schedule duly endorsed by concerned
SLDC/RLDC(when one of party is from outside region)has been received by ERLDC to be the first
one.

Procedure, priority, timeline etc. for scheduling for all types of transactions shall be
guided by IEGC and other regulations of CERC amended time to time

_________________________________________________________________________
Operating Procedures for Eastern Region Page 36 28-06-2013
ERLDC:POSOCO

Name of the Activity: SCHEDULING FOR DAY AHEAD

START

Receive from each


ISGS Capacity ISGS Ex-pp Declare
Availability in Form - A Capacity Availability for
format at 09:00hrs the following day

No
Is all applicable
DCs Received ?

Yes

% Weekly Send Form - B to all the


Loss & Prepare ISGS Entitlement beneficiary constituents at
Share of all constituents in 10:00hrs (R0) & then
Allocation % 15min time blocks for the Subsequent revisions.
following day - Form - B

Yes

Is there any change


DC_ in ISGS DC?
Rev

No
Receive STOA
Data from OA Check and configure
Dept. the Advance
Approved STOAs

Receive requisition ISGS & STOA


from each (Advance Appd)
constituent in Form - requisitions of
C format at 15:00hrs Constituents

No
Are Requisitions of all
constituents
received?

Yes

Cont..2

_________________________________________________________________________
Operating Procedures for Eastern Region Page 37 28-06-2013
ERLDC:POSOCO

From 1

PX Transaction
Receive Data from Wheeling
NLDC at 15:00hrs Diversiion
Inter Regional Trx

Preparation of Constituent's Drawal


Req_ Schedule & ISGS Despatch
Rev Schedule

Not OK Send Drawal Schedule to


OK Check for Tr SLDCs & Despatch Schedule
Constraint, Tech to ISGS -(Form - D) for the
Min & Ramping following day at 17:00hrs

Yes
Broadcast the URS Details to
Is there any All the Constituents & Upload
URS to RLDC Website

No

Receive Check / configure


Data from the Day Ahead
Grid Mgmt Approved STOAs

Req_
Rev
DC_Rev
Is there any change in
ISGS DC or
Constituent’s
Requisition Requisition? DC Change
Change

No

Preparation of Send final Drawal Schedule to


Constituent's Drawal SLDCs & Despatch Schedule
Schedule & ISGS to ISGS -(Form - D) for the
Despatch Schedule following day at 23:00hrs

Is there any URS Power?

END

_________________________________________________________________________
Operating Procedures for Eastern Region Page 38 28-06-2013
ERLDC:POSOCO

Activity: REVISION OF CURRENT DAY SCHEDULE

START

Is there any No
Change in DC of RR
ISGS?

Yes

Receive the revised Receive Revised


of ISGS Capacity Declaration of
Availability in Form - Available Capacity
A format of ISGS

Prepare ISGS No Yes Prepare ISGS


Entitlement of Entitlement of
all constituents Is it due to all constituents
in 15min time forced in 15min time
blocks w.e.f 6th outage of blocks w.e.f 4th
time block - Unit? time block -
Form - B Form - B

Send From - B to
Send From - B all the beneficiary
to all the constituents
Receive Revised
beneficiary Requisition from the
constituents Beneficiary
Constituents

Receive
requisition from Preparation of
constituent in Constituent's Drawal
Form - C format Schedule & ISGS
Despatch Schedule

Not
OK OK

Check for Tr Send Drawal Schedule to SLDCs


Constraint, Tech & Despatch Schedule to ISGS.
Min & Ramping (Form - D)& upload to web

Yes
Broadcast the URS Details to All the
Is there any Constituents and Upload to RLDC
URS Power? website

END

_________________________________________________________________________
Operating Procedures for Eastern Region Page 39 28-06-2013
ERLDC:POSOCO

Activity: Procedure flow chart for current day schedule revision…contd

RR

Yes
Is it NEW Approval of Same Day STOA?

No
Yes
Is there any System Constraint?

No

Is SLDC Changed
END its Requisition?
No
Yes

Receive the revised Receive Revised


Requisition of the Requisition of
Beneficiary Constituent Beneficiary
in Form - C format Constituent

Preparation of Constituent's
Drawal Schedule & ISGS Preparation of Constituent's
Despatch Schedule w.e.f 6th Drawal Schedule & ISGS
time block or latter as approved Despatch Schedule w.e.f 4th
/ requisitioned time block

Send Drawal Schedule to


Yes SLDCs & Despatch Schedule
to ISGS -(Form - D) Yes
Check for Tr Check for Tr
Constraint, Tech Constraint, Tech
Min & Ramping Min & Ramping

No No

Is there any URS Power? Yes

No Broadcast the URS Details to All the


constituents & Upload to RLDC website

END

_________________________________________________________________________
Operating Procedures for Eastern Region Page 40 28-06-2013
ERLDC:POSOCO

Activity: IMPLEMENTED SCHEDULE

START

Regional Weekly Loss % Are Loss % Values Correct the values as applicable
State System Loss % entered correctly? for the particular day
No
Yes

No
Share Allocation % Are Loss % Values Correct the values as applicable
entered correctly? for the particular day

Yes

STOA Details No
(Advance Approved & Are STOAs Correct the values as applicable
Day Ahead Approvals) Configured correctly? for the particular day

Yes

Details of Grid Incidents No


and Grid Disturbance if Was the Schedule Correct the values as per
any. Revision done Declaration in line to IEGC
correctly? provisions

Yes

Details of Transmission Was the No Incorporate the curtailment


Constraints, if any. curtailment done with correct values as per
correctly? IEGC guidelines / provisions

Yes

Details of Revisions in No
Was all the Check for the Constituent's Drawal
Declared Capacity of
Revisions Schedule & ISGS Despatch Schedule
ISGS & Requirements of
scheduled & co-ordinate for rectification of errors
Constituents
correctly? if any.

Yes

Cont..2

_________________________________________________________________________
Operating Procedures for Eastern Region Page 41 28-06-2013
ERLDC:POSOCO

From
1

Inter Regional Link


Schedules Check for matching of the Inter Regional
(STOA & Wheeling / Schedules for each link.
Diversion Details)

Co-ordinate with
Are the Inter Regional No respective RLDCs &
Link Schedules are
eliminate the
matching with other
discrepancy.
Region?

Yes

Communicate to
respective RLDC

Release the Final Implemented


Schedule and Upload in to Web.

Is there any
Receive from SLDC /
dispute on
ISGS / Traders / Go to Start
discrepancy of
RLDCs
the Schedule, Yes
with in 5 days?

No

Release weekly schedules to commercial


dept for Energy Accounting

END

_________________________________________________________________________
Operating Procedures for Eastern Region Page 42 28-06-2013
ERLDC:POSOCO

Chapter 9
9. SCADA System Operation
9.0. SCADA / EMS System Operation

This manual prepared for the use of them who intend to operate the SCADA / EMS system installed
at ERLDC to help them with real time information pertaining to ER power system grid and to facilitate
system study with information available from the real time system.

9.1. System Configuration

This section gives only a brief description of the hardware. The intent is to have an idea about the
type of hardware components available not the quantity and the detailed technical specifications.

The RSCC system hardware architecture is represented below :

RSCC Hardware Architecture

SCADA/EMS ISR ICCP DTS Operator Development


Servers Servers Servers Server Consoles Console
(EA0DS1 & EA0DS2) (EA0HS1 & (EA0IC1 & ( EA0DS3 ) ( EA0OC[1 - 9] ) ( EA0PC1 )
EA0HS2) EA0IC2)

Communication Operation Network WAN Peripheral


Scheduling Managemnt Routers
Front-end Equipment
Consoles Console
(EA0FE1 & ( EA0VP1 )
EA0FE2) (EA0CO1 & ( EA0CN1 )
EA0CO2)

To SLDCs Remote
To RTUs To CPCC VDUs

The equipment Ids are marked as blue in the above mentioned diagram. The details of networking
equipments and printers / loggers are not included.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 43 28-06-2013
ERLDC:POSOCO

9.2. Starting up an operator console

Before starting a operator console check the availability of power to the monitor and the server
machine. On switching on the power supply, the machine will start up and the login prompt shall be
displayed for operator login :

Username for operator console : supervis


Password : supervis

The following display shall be available to the user for interacting with the SCADA/EMS system :

_________________________________________________________________________
Operating Procedures for Eastern Region Page 44 28-06-2013
ERLDC:POSOCO

9.3. Identifying the failed node

The status of the equipment connected in the network is available on the following display. The
colour of a the healthy node is green. The colour code used for the display is given below :

Green : Available
Red : unavailable / out of date
Brown : Ready for recovery

_________________________________________________________________________
Operating Procedures for Eastern Region Page 45 28-06-2013
ERLDC:POSOCO

There are ten different displays are available for showing the status of all the nodes available on the
SCADA LAN. To call the displays from EMS panel, follow the following navigation path :

Click on “SYSTEM MGMT “ button to call up “System Management Display”


Click on “Displays” button against “COMPUTER STATE AND CONTROL”
Click on “SITE OVERVIEW : DATA SERVERS” BUTTON

The status of Data Server nodes shall be available.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 46 28-06-2013
ERLDC:POSOCO

For other displays : from related display pull down menu call up the displays.

9.4. Calling up a substation displays

Individual substation displays are available for all the stations for which telemetry is available. The
displays are arranged control center-wise which may be called up using pull down menu as follows:

Navigate => Master Menu : to call up system displays menu

Click on “ONLINE” button to call up E SC&C ONE-LINE displays

_________________________________________________________________________
Operating Procedures for Eastern Region Page 47 28-06-2013
ERLDC:POSOCO

The corresponding displays are available on the respective “Displays” button.

9.5. Bringing-up Video Projection Display (VPS)

The VPS is driven by a P-III window based machine connected to on-line network. This is machine is
communicating to the dataservers through “Exceed” software. A station for VPS has been configured
on both the data servers which is called through a “PC-Rapport” program.

A desktop icon “PCRAPPORT.BAT” is available on the desktop of the VPS machine. On double
clicking on this icon, VPS station will be started with the pre-defined room. Subsequently, the required
rooms may be called from the PC-Rapport menu

_________________________________________________________________________
Operating Procedures for Eastern Region Page 48 28-06-2013
ERLDC:POSOCO

It may be mentioned here that the trending displays cannot be saved as a room and the trend
displays are to be called up separately through separate desktop icon “trend_ea0ds2”

9.6. Configuring data Trends

Any analog value ( telemetered or calculated ) can be plotted against time in real time to see the
trend of the selected value. To call up a trend display go to session manager

Go to pull down menu ER SC&C tab and select Start prograf. The trend display shall be started with
the default trend.

To add particular point on the trend display, first select the point and then click on the value. A pop-
window shall be available. Select trend & display and then done button. The point shall be added to
the trend. Then to configure the trend navigate

Master menu => SCADA =>Trend => Point Assignment

Then in the point assignment window, Select Track / Add New Track and assign point from available
point list.
The scale, zoom, history can be configured from the PM pull down memu.

NOTE : In case the value is available in the available point list, the same point should not be added
additionally to save buffer space.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 49 28-06-2013
ERLDC:POSOCO

9.7. Manually Defining of Data ( Replace / Not in service )

The following sections describe procedures that relate to modifying data values for analogs and
status points. If a modified value is rejected after completing any of the procedures in this section, it
may be for one of the following reasons:
 The value might need to be put in the “not in service” state.
 The value is normally supplied by the State Estimator.
 You attempted to enter a null value.
 You entered a value outside of the reasonability limits.

9.7.1.1. Manually Overriding Point Values From a Oneline


This procedure is used to remove a point from service and enter an operator override:
a. On a Oneline, select the device symbol.
A popup box appears.
b. Select the Remove button.
The "not in service" symbol appears next to the button.
c. Select the Select button, and the toggle button on the popup becomes
available for use.
d. Select the toggle button.
If the device status is currently OPEN it changes to CLOSED; if the
device status is currently CLOSED it changes to OPEN.
e. Select the Done button.
The popup disappears. Note that the manually replaced symbol appears next
to the device on the Oneline, indicating that the status has been manually
overridden.
9.7.1.2. Manually Overriding Analog and Count Values From a Oneline
This procedure is used to remove an analog or count from service and override its value.
a. On the Oneline, select the analog field.
A popup box appears.
b. Select the Remove button.
The field containing the analog value becomes enterable.
c. Position the cursor on the field containing the value, type in the new value and
press the Enter key.
The entry is accepted if you have permission for entry and the value is within
the reasonability limits. If not, the entry is rejected.
d. Select the Done button.
The popup disappears. Note that the analog's value has changed on the
Oneline, and that it is accompanied by a “manually replaced” symbol.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 50 28-06-2013
ERLDC:POSOCO

9.8. Removing Manual Override and Restoring a Value to Service


As the previous sections indicate, when a value is manually overridden, both the "manually
replaced" and "not in service" flags are set for the point, analog, or count involved. The following
procedure removes both flags from the point, analog, or count, and causes its value to be
replaced with the next scanned value. If the point, analog or count has simply been removed from
service without having its value manually overridden, the following procedure simply returns it to
service.
a. On the Substation Tabular display, select the point, analog, or count's
depressed Not In Service button.
The point, analog, or count is restored to scan. On the tabular display, the
point, analog, or count's Data Quality field no longer reads Replaced, and its
"not in service" flag is removed (as can be seen by selecting the Flags button).

9.9. Data Quality flags

Composite data quality flags flags indicate a measurement's reliability. However, composite flags
provide a quicker way for the operator to judge reliability which are available on the display along
with real time value. There are four composite flagsGOOD, REPLACED, SUSPECT, and
GARBAGEwhich are defined below.
 GARBAGE: Data is unreliable. This flag appears when the measurement point is
uninitialized.
 SUSPECT: Data is labeled with one or more of these flags: OLD, BAD, OVER, REMSUSP,
and QUEST.
 REPLACED: Data is labeled with MANREP, ESTREP, or REMREPL
 GOOD: Data is not labeled as GARBAGE, SUSPECT, or REPLACED.

9.10. Collection and Viewing the Disturbance Data

The data available in SCADA is stored in a file called HDR file. These files can be used for viewing
the data and playback.
The following steps are to be followed to reconstruct the database as it existed during a particular
date and time, and to follow it through subsequent scans.
1. Call up the Historical Data Recording display and select the HDR Reconstruction Control
display from the Related Displays menu.
Navigate => SCADA => HDR Reconstruction Control
The HDR Reconstruction Control display appears.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 51 28-06-2013
ERLDC:POSOCO

2. Select the Start button.


The Reconstruction function is started and the Reconstruction File Directory is created. This
directory lists the HDR historical files from which data can be reconstructed.
a. In the box underneath Reconstruct To Time, type the date and time for which
you want SCADAMOM to be reconstructed, then press Enter.
b. Select the Reconstruct To Time button.
HDR takes data out of the historical files and reconstructs SCADAMOM as it
existed during the desired time.
9.10.1. Playing Back a Reconstructed Database
HDR has a "playback" feature that enables to follow the progress of a reconstructed database
over time. The number of seconds between database reconstructions, and the time interval
between advances in the playback need to be specified.
To "play back" a reconstructed database, do the following:
a. Reconstruct the database to a given date and time (see steps 1-4 under Error!
Reference source not found.).
b. In the RATE field on the HDR Reconstruction Control display, type the number
of seconds between database reconstructions, then press Enter.
c. In the Every field, type the number of seconds between advances to the next
database reconstruction, then press Enter.
d. Select the Playback button.
Automatic playback begins, based on the time values entered.
e. If you want to pause the playback, select the Pause button.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 52 28-06-2013
ERLDC:POSOCO

The current database reconstruction remains in place, without advancing to the


next one.
f. To resume the playback, select Playback again.
Playback resumes, advancing to the next reconstruction at the prescribed
interval.
g. When finished, select the Exit button.
HDR exits the reconstruction function.
Note: Once Playback is completed, select the Reconstruct To Time button to start
another Playback.
9.10.2. Viewing SOE data

To view the SOE data dump of the previous days follow the following steps

Go to session manager
Go to pull down menu => ER SC&C
Select the start SOE dump viewer, the program will ask for the host computer name. Enter :
EA0OC2 ( The program shall run on EA0OC2 ) A notepad editor will open along with a file
open pop-up window.

9.10.2.1. PICTURE
Navigate to select the date and the file from ( DK0:[pan25.bp.data] )
Double click on BP folder ( LEFT pane )
Select DATA folder ( LEFT pane )
Select the file by scrolling ( from the right pane )
Double click on the selected file, the file is available on the notepad.

9.10.2.2. Transferring SOE data to a PC ( EA0CO1 )

Double click on “get SOE” shortcut icon available on Desktop.


Select the SOE file to be copied to pc.
Observe the directory selected on PC for transferring the file
Select the SOE file and drag the same to the PC.
Close the copy application
Open the file using notepad / Excel from the directory.

9.10.3. Alarms and Notepad

SCADA detects and notifies operators of events and conditions in the monitored system that can
lead to operational problems. For example, SCADA can detect when a normally closed circuit
breaker trips, and can take action. SCADA can detect problems that occur for status, analog, and
count points, RTUs and other equipment in the communications system, and intersite
communications equipment and software. Individual analog or status points may optionally be
configured to suppress the alarm until the analog or status has remained in the abnormal state for
a specified period of time. In addition, SCADA can detect when control operations fail.
Some of the common conditions and events that SCADA considers abnormal, and therefore
alarmable, are as follows:
 Abnormal and illegal conditions for analog, status, and count points in the monitored system.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 53 28-06-2013
ERLDC:POSOCO

 An analog or status point's return to normal operation after being in an abnormal or illegal
state.
 Problems in the communications system, in particular with RTUs and scan groups.

These alarms are logged separately and can be viewed based on requirement. To view the
current list of analog and status alarms go to EMS panel and click on “EXCEPTIONS” button.

The time ordered alarms will be listed.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 54 28-06-2013
ERLDC:POSOCO

9.11. Area of Responsibility (AOR)

In the SCADA database the entire system (including all of the SCADA control sites) is divided
into areas and each area is named. Each area is referred to as an area of responsibility.
Dividing the control system into areas serves two purposes:
 It restricts the control of monitored devices to specific control sites and to individual operator
consoles within each site.
 It limits which control sites, and which operator consoles within each site, can respond to
alarmed conditions and events.
An area of responsibility is assigned to each device type in the monitored system and to each
RTU in the communications system. For a control operation (such as remove/restore) to be
carried out from a control site and operator console, the area of responsibility of the device
type or RTU must match the area of responsibility of the operator's console.
Similarly, an area of responsibility is assigned to RTUs, SCADA sites participating in intersite data
transfer, and substation voltage for the purpose of limiting which operator console can respond
to alarms.
Again, the console's area of responsibility must match the area name of the alarmed RTU, remote
site, or substation, in order for the alarm to be heard or seen at the console.

9.12. Saving Layout and Restoring

The user can choose to save desired set displays in a work station for his convenience of use.

8.12.1 Arranging a layout


Open the desired displays and arrange them properly. This becomes a layout.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 55 28-06-2013
ERLDC:POSOCO

8.12.2 Saving a Layout


Open RFG station Manager.

Then type the following command in the command window


room /save <name>

New room will be saved with the layout selected. The same will be available in the room directory for
calling up the display.

9.13. Procedure to run Real Time Network Analysis (RTNET), Study Mode Network
Analysis (STNET) and Contingency Analysis.

Login in any operator console under supervise mode. Click on Navigate -> Master Menu->Net
_Security

_________________________________________________________________________
Operating Procedures for Eastern Region Page 56 28-06-2013
ERLDC:POSOCO

Now click on “On-Line Network sequence-> Network Online Sequence”

In the opened display click on Run Sequence button. Wait for the sequence to complete and check
the program status. It must be either VALID SOLUTION or SOLVED WITH EXCESS MISMATCH or
INVALID SOLUTION

_________________________________________________________________________
Operating Procedures for Eastern Region Page 57 28-06-2013
ERLDC:POSOCO

In SE Controls view the following Options are selected and these settings are no need to be change by
the User
1. Preferred LTC Tap
2. Auto enables of Auto dis Measurements
3. Globally include all buses
Disable quality code transfer to SCADA (If this is not selected the SCADA data may get warning flag
for the data whose SE result is not consistent with SCADA)
The remaining Options as mentioned below may need to be set by the Operator some times for
initializing the State Estimator. This needs to be done as State estimator accumulates the error while in
periodic trigger. It is a good indication that if you need to less frequently reset the error deviations of
State Estimator; your solution is that much consistent
COLD INIT
FLAT START
RECALCULATE WEIGHTS
REPEAT (ITERATION TYPE) -> this is to be chosen as FACTOR
RESET STDEV and BIAS

_________________________________________________________________________
Operating Procedures for Eastern Region Page 58 28-06-2013
ERLDC:POSOCO

With the help of Process Parameters View we can change the Maximum real Power mismatch,
reactive Power mismatch, voltage angle convergence requirement etc.
(Generally these options are not need to change)

Accuracy classes are select and fixed at Net model level only

_________________________________________________________________________
Operating Procedures for Eastern Region Page 59 28-06-2013
ERLDC:POSOCO

If the solution state is Invalid -> In order to identify on which last Bus the program unable to
converge -> go to Real time Network solution sequence display (From Network Online sequence->
Related displays->selecting Real time Network Solution Analysis).

_________________________________________________________________________
Operating Procedures for Eastern Region Page 60 28-06-2013
ERLDC:POSOCO

In this display See on which last bus it was unable to converge (At Bus xxx) -> now click on Related
displays-> Network Components -> Network Bus summary -> Select Bus Symbolic View-

>

Enter the Bus Number xxx in the field besides to Position to Bus -> Now click on the button Position
to Bus-> You will be placed at that particular Bus No:xxx->

_________________________________________________________________________
Operating Procedures for Eastern Region Page 61 28-06-2013
ERLDC:POSOCO

On the Bus symbolic view, for each device you have two flows are showing for MW and MVAR. The
bottom value is SCADA Value and the Top value is estimated value. Now compare this SCADA and
Estimated values, locate the problem rectify it accordingly either by enabling that measurement ( For
this go to Telemetered Network data display (on the Network online sequence display-> click on
Related Displays-> select Telemetered Network Data-> click on All Analog Measurements View-
>Click on Directory Button->

_________________________________________________________________________
Operating Procedures for Eastern Region Page 62 28-06-2013
ERLDC:POSOCO

Select the particular station which was unable to converge.->enable the particular measurement from
this telemetered Network data display. Some times scada value might have wrong in that case rectify
the scada value by replacing both MW and MVAR of particular device and enable this value in the
telemetered network display may help to resolve the problem. Run the sequence again from the
Network Online sequence display. See if the solution converges or not. If not remove that particular
device (temporarily) from the network and run the sequence .

Note : some times you have to reset the errors which have been accumulated in the Network
applications by going to Network Online Sequence main display -> click on the button SE Initial
Conditions -> SE Controls View - > Select the buttons COLD INIT, FLAT START, Iteration Type to
REFACTOR, reset Standard Deviation (STDEV)and Bias. By doing this you are making the algorithm
to initialize. This will help to improve your Network convergence.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 63 28-06-2013
ERLDC:POSOCO

If the solution state is Solved with excess mismatch:


We have to identify on which Bus the excess mismatch has come. Not that here the mismatch we are
talking is the algebraic sum of estimated values on the given Bus. go to Real time Network solution
sequence display (From Network Online sequence-> Related displays->selecting Real time Network
Solution Analysis). In this display select the view Bus Mismatch -> see the Buses which are having
highest MW and MVAR Mismatch. Note down the Bus number -> now click on Related displays->
Network Components -> Network Bus summary -> Select Bus Symbolic View->Enter the Bus Number
xxx in the field besides to Position to Bus -> Now click on the button Position to Bus-> You will be
placed at that particular Bus No:xxx->Locate on which device the excess estimation is happening by
comparing with SCADA and rectify it accordingly as explained above.
Once your state estimator getting VALID solution, increase your network by enabling more
and more SCADA data in to RTNET. Converge the solution. Check on the One-Line display for all the
Central station and then for other constituents how SCADA and estimator values are matching.
Rectify the problems if found as explained in the above.

Running Powerflow/Load flow with Realtime Snap-shot:


Once your network started converging and giving the good quality solution, with SCADA and
Estimator values are matching in more and more places you can run the Powerflow program on
STUDY mode. For this login in Engineer mode in any of the operator console go to NET_STUDY->
NETWORK STUDY button-> NETWORK STUDY display.
On this display click on the DATA RETRIEVAL button-> In the opened window, click on Copy Real
time Application Data -> Done. This will copy the RTNET database of Last run in to study clone.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 64 28-06-2013
ERLDC:POSOCO

Wait for 5 minutes to copy the Real time data in to study family and once you get the message in the
Solution state: Completed Database copy, you click on Input Setup button.
In the opened window two buttons are present. One is Update Network Topology and the other one is
Evaluate Time Depend Data. Click on both the buttons, one by one. Now click on the Run Solution
Sequence button and see whether the POWERFLOW program is converged or not by checking the
field PROCESS STATUS:. If the solution converges it shows the status as UN LOSS DONE. In case
of Non convergence it will show as either INVALID solution or Max Iteration or case Diverged. In
that case you go to the display POWERFLOW SOLUTION ITERATION from the Network STUDY
display -> Related Displays-> Powerflow displays -> Powerflow Study -> Now again click on Related
displays from this display -> click on Powerflow Solution Iteration. On this display you can find what
are the substations having error values giving problem to Powerflow program. To rectify this you have
to again tune your RTNET application for these problematic substations and then you run
POWERFLOW as explained above.
Please note that Converging Powerflow will come with experience.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 65 28-06-2013
ERLDC:POSOCO

Running Powerflow and comparing the Results:


Some times you need to analyze what will happen if you take a Bus shutdown or a Line trip and also
the possible effects on the other lines. To do this in Powerflow program we have total 3 study clones
are provided.we can copy the Real –time data from RTNET in to these clones and run the powerflow
with and with out the disturbance. Then we can compare the results.
That is first we will work in Study1 clone -> Run the Powerflow as explained in the above section.
Now click on the Compare Results and other Studies button -> In the opened window-> click on Go
To Study2 Button-> It will give the message “Areas have been assigned correctly .In this clone also
you copy the Basecase from RTNET. Now create some disturbance like tripping a Generator or
removing line etc by Related Displays ->Network Components -> Network Bus summary. Go to that
particular Bus , Then remove the component.
Next come to the Main Network Study display by clicking Study Button. Click on Input setup-> Update
the Network Topology. Now run the Power flow program by clicking on Run solution sequence. After
solution converges, click on the button Compare Results & Other Studies button ->Click on the
button Compare with Study1 button. Wait for comparing to finish Next you can see the results by
clicking on Comparison Results. Select various views such as Line ,Gen etc and see how the effect of
removing this component.
Contingency Analysis
Real time Contingency Analysis is a tool to study the effect of Outage of particular Network elements
in the real time scenario. To get the correct report on Violations, the Alarm limits of the elements
(MVA) in the Network to be set as per actual scenario.
Step by step procedure for creating Contingency and to see the results on that contingency as shown
below

_________________________________________________________________________
Operating Procedures for Eastern Region Page 66 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 67 28-06-2013
ERLDC:POSOCO

Click on start button and then give the contingency ID in the field mentioned in Define/Update
contingency and then follow the Arrow path as shown in the display i.e. first click on Define New
contingency -> Update Primary components ->Outage Selection-> save /Update Outage selection

_________________________________________________________________________
Operating Procedures for Eastern Region Page 68 28-06-2013
ERLDC:POSOCO

Click on save /Update Outage selection after this

SAVE ->VALIDATE ->STOP.


DIRECTORY ->select your contingency (to see your contingency description)
Now click on RUN Sequence with RTCA option selected as shown in the figure below

_________________________________________________________________________
Operating Procedures for Eastern Region Page 69 28-06-2013
ERLDC:POSOCO

The RTCA should completed


Check state estimator output in SCADA display for the given lines, Check in the same line flows how
RTCA calculated i.e. both STATE ESTIMATOR and RTCA should have same results

_________________________________________________________________________
Operating Procedures for Eastern Region Page 70 28-06-2013
ERLDC:POSOCO

For getting correct violations in contingency you need to have the MVA alarm limits to be set
correctly. For this you have to set the SCADA (MVA limits), they will be copied while running
RTNET .
Some times you won’t get any violations even after running RTCA, the possible reasons
The Operating area which should be monitored is not enabled To see this go to Network Monitored
Groups as shown below.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 71 28-06-2013
ERLDC:POSOCO

We can change the violations reporting area from Monitored element definition
.
9.14. Transfer of Schedules to SCADA System
Daily schedules are being prepared in Excel platform. One sheet, “online” has been prepared to copy
the data to SCADA system, An macro on VB has been prepared, which copies the data to a realtime
machine “EA0CO2” as when the schedule is revised. The operator has to be click on the button
“schedule upload” button made on Excel after the schedule is revised.

A separate macro on VB has been prepared which updates the data in the respective cell of the file
“current schedule.xls” in each 15 mins and the data of the respective cells are pumped back to
SCADA server through “HABCONNECT” utility.

9.15. Real-time data availability from other region


The following text file containing real time data of the other regions are sent through ftp protocol in
each 1 minute interval to one of our machine “LOADCURVE”. The files are kept in the folder
c:\usr\viswanadh \region

1. NR.txt
2. SR.txt
3. NER.txt
4. WR.txt

_________________________________________________________________________
Operating Procedures for Eastern Region Page 72 28-06-2013
ERLDC:POSOCO

One macro on VB project which is running of “EA0CO2” in “external update.xls” file which is opening
the above files sequentially and prepares the data for pumping back to SCADA through
“HABCONNECT” utility.

9.16. Data transfer to NPSD


The real time data is being sent to NPSD in a text file through ftp protocol. The remote system is
collecting the data logging in to our machine “LOADCURVE”. The file is being transferred is
erdisplay1.txt. The location of the file is c:\online.

The file is getting updated in one minute interval through a macro on VB available in MOPdata.xls
through “HABCONNECT” utility.

9.17. Uploading Daily Report on ERLDC Website


The real time data has been made available to ERLDC website utilizing the same text file being sent
to NPSD. The text file is also transferred to ERLDC web server and aspx page has been developed
to display the data fro the text file. The file is transferred to web server through ftp protocol.

9.18. Data communication with NLDC for PX scheduling


The data communication with NLDC in respect of PX transactions is being done through a dedicated
network with NRLDC. The text files are exchanged through ftp protocol for sending the ATC to SLDC
and schedule implementation.

9.18.1. ATC Declaration : By 09:00 Hrs.


ATC for STOA for the following day
= TTC – RM – LTOA ( following day ) – STOA ( advanced )

To achieve the STOA quantum the following configurations have been made.
One <calculation file.xls> ( Location : C:\ px_files on shift in charges machine ) has been prepared in
which the above calculations are done.

The entries of the above file is taken through a program from <Form- D> sheet & <Share table>
sheet of the same file for LTOA transaction and <OPEN ACCESS MMMYY> file for advance STOA
transaction. The file is being updated by Open access group.

The following checks are carried out before sending the ATC file to NLDC.
1. Share table in calculation.xls file as when it is revised for the schedule file
2. LTOA transactions ( excl. ISGS ) in the <Form – D> sheet.
3. DC to be revised in case of confirmed outage on the following day.
4. TTC and ATC figures in all the regional sheets ( available in the <calculation file.xls > file
to be changed in case of contingency. Normally this is being taken care off by Open
access group based on TTC / ATC declared on monthly basis.
5. Percentage loss on the calculation sheet should also be checked on Sunday ( as the
loss % age is changed on Monday). Normally this is being taken care off through a
program. However for confirmation this may be checked after sending the file.

Information sent for ATC is being stored as 00ERATC<mmddyy>.xls under c:\px_files\daily files.

The file is sent to NLDC server ( IP :192.168.55.74 ) through ftp.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 73 28-06-2013
ERLDC:POSOCO

9.18.2. Receipt of PX transaction from NLDC after 16:00 Hrs


NLDC shall finalise the PX transaction by 16:00 hrs and the shall be made available at the NLDC
server which needs to be download to the schedule machine for incorporation in the daily schedule of
ERLDC. A program has been prepared <PX DOWN>for downloading the file on excel. The file ( .csv
format ) shall be downloaded at c:\px_files\px_data. The name of the files are

1. <01ERIEXddmmyy.csv> for IEX


2. <01ERPXIddmmyy.csv> for PXI

9.18.3. Incorporation in the schedule


The required transaction ( Utility code given ) available row wise ( 96 block ) to be incorporated in the
schedule file <PX> sheet of the relevant schedule file. ( A program shall be made available )

9.18.4. Confirmation of the schedule to NLDC to be done by 18:00 Hrs


A file is to be sent to NLDC server after incorporation of the PX transaction. A program has been
prepared <PX UPLOAD> which shall send the file to NLDC server. The program at the same time
changes the ATC file available in the shift in-charge machine for releasing the day ahead and
contingency transactions. The application received for day ahead/contingency to be approved /
consented based on the available ATC.

8.18.5 Uploading of schedules to the web by 18:00 Hrs

The daily schedules ( rev – 0 ) after incorporating the LTOA, advanced bilateral transactions and PX
transaction is to be uploaded to the web through <SCHD UPLOAD> button available on excel in
Schedule machine.

9.19. Daily report upload


The daily reports are prepared on .xls format. The same is converted to .pdf file <ddmmyy.pdf>. The
same is uploaded along with frequency plot to the web through ftp protocol.

9.20. Operation of DG Set in Auto/Manual Mode

ERLDC is having two DG sets, 400 KVA and 125 KVA. The higher capacity unit caters all the load
like ac plant, lift including ERPC load, the smaller unit caters only the load of technical block of
ERLDC. The old unit i.e. 400 KVA unit does not have automatic start facility however auto start
facility has been provided with the smaller unit.

9.20.1. Starting sequence of 400 KVA unit


In case of main supply failure, the toggle switch is kept to “ENGINE” side. The start button of S.D.
valve is pressed for a duration of 30 secs. Subsequently, the self start button is pressed to start the
engine.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 74 28-06-2013
ERLDC:POSOCO

ENGIN

START ON START RAISE LOWER


(SELF) ( S. D. Valve )

VOLT FREQ AMP

KWH

The voltage builds up and frequency meter starts showing the frequency of the generator power.
“RAISE” and “LOWER” button is used to bring the frequency to near 51 Hz. Then the outgoing switch
is switched to extend supply to the main switch gear panel. The capacitor bank should be switched off
before starting the DG set.

In the main switchgear panel, incoming switch of the main supply (CESC) is switched off and the
incoming switch of the 400KVA (marked as F)is switched on to extend power supply to the common
bus.

9.20.2. Operation of 125 KVA set


The machines are generally kept on manual mode (1) as most of the time 400 KVA set is in operation
in case of main supply failure. To start the engine, the start button is pressed. The engine starts and
the supply is extended to the ac panel technical block.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 75 28-06-2013
ERLDC:POSOCO

HOOTER
ON

OFF
DG SUPPLY DG LOAD ON BAT CHARGER LOW FUEL BAT
ON ON LEVEL CHARGER
ON

OFF

ENGINE ENGINE ALT CONN. ALT. CONN FAULT


START STOP CLOSE TRIP RESET

1. MANUAL
2. AUTO 1.TICKLE
3. TEST 2. BOOST

3
1

2
2
1

Control panel of new DG Set (125 KVA)

The following indicator displays are available for operators checking :

1. DG Supply on
2. DG load on
3. Battery Charger on
4. Low fuel level

Toggle switches have been provided to make battery charger on / off and to reset hooter. Further
operator buttons have been provided for tripping and closing the alternator and fault reset ( relays )

_________________________________________________________________________
Operating Procedures for Eastern Region Page 76 28-06-2013
ERLDC:POSOCO

Chapter 10
10. Metering and Settlement System
10.0. Introduction
The settlement system is an important part in implementation of Availability Based Tariff (ABT) . The
system involves metering, data collection and processing, energy accounting and raising of bills by
the constituents. This chapter indicates the roles and responsibilities of the different regional entities
in making the settlement system operative in most efficient manner.

10.1. Metering and Data Collection


9.1.1 As per Chapter-6 clause 6.4.21 of IEGC, the CTU shall install Special Energy Meters on all
inter connections between the regional entities and other identified points for recording of
actual net MWh inter-changes, average frequency on 15-minute time block and MVARh
drawls under low/high voltage conditions.
9.1.2 The type of meters to be installed, metering scheme, metering capability, testing and
calibration requirements and scheme for collection and dissemination of meter data shall be
as per Annexure-2 of IEGC.
9.1.3 All concerned entities having SEMs installed in their premises shall fully cooperate and extend
necessary assistance by taking weekly meter reading and transmitting them to ERLDC in time.
9.1.4 All concerned entities having SEMs shall also carry out necessary time adjustments in the
meter as per the procedure already in vogue/advice of
9.1.5 In the event of any reported problem of SEMs as by ERLDC during processing in the matter
shall be reported to concerned / to the owner of the meter for necessary replacement /repair.

10.2. Data Processing


9.2.1 As mentioned in section 6.4.21, all the energy meter data would reach ERLDC by every
Tuesday afternoon via email. The CTU/STU, ISGSs and regional entities shall be responsible
for sending of data of sending of data to ERLDC. ERLDC would carry out data validation and
in case of any problem, request any entity to send the data again. Each entity would therefore
have necessary backup of data at their local PC level.
9.2.2 The computation of the net injection of each ISGS and actual net drawl of each beneficiary
shall be carried out in line with clause 6.4.22 of IEGC based on the above meter readings
received at ERLDC. The preparation and issue of REA to the constituents shall be done by
ERPC Secretariat on the basis of meter data and implemented schedule forwarded by ERLDC.
9.2.3 Data related to the reactive energy exchange between two STU systems and between STU
and ISTS points would also be forwarded by ERLDC for preparation of reactive energy
accounts and communication to all constituent and ERLDC by ERPC Secretariat.
9.2.4 The final schedule implemented by ERLDC shall be open to all regional entities for checking /
verification for a period of five days and mistakes/omissions ,if any ,would be rectified.

10.3. Energy Accounting


ERPC Secretariat would process the information provided by ERLDC and other utilities to determine
the following energy accounts:
10.3.1. Monthly Regional Energy Account for the purpose of billing
a) Capacity charges payable by each beneficiary to each ISGS.
b) Energy charges payable by each beneficiary to each ISGS
c) ISGS energy scheduled for each regional beneficiaries.
In case of utilities outside Eastern regions are having shares on ISGSs, ERLDC shall be
furnishing consolidated schedule drawal at the concerned regional boundary/ies only.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 77 28-06-2013
ERLDC:POSOCO

10.3.2. Weekly UI( Unscheduled Interchange) Account


` Weekly UI charges shall be settled as per UI calculation for each 15 minute block. The UI
charges payable/receivable shall be calculated with respect to UI Pool. The Pool Account
shall be maintained by ERLDC. The UI account as prepared by ERPC Secretariat shall have
the following components
a) UI charges payable by beneficiaries/ISGSs to Pool
b) UI charges receivable by the beneficiaries/ISGSs from the pool
c) Pool balance amount due to capping of UI rate for Thermal ISGSs.
Since the hydro stations within Bhutan System is not covered under UI mechanism of
settlement, the accounting for drawal from these stations shall be as per the Monthly energy
account as per the agreed principles. However, deviations of injections from these stations
shall be accounted for and duly apportioning the deviations amongst its beneficiaries.

10.3.3. Weekly VARh Account


The VARh account as prepared by ERPC Secretariat shall have two distinct components.
a) VARh charges payable/receivable for VARh exchange between STU systems
b) VARh charges payable by Beneficiaries for low VARh drawal or High VARh injection
between STU and ISTS points.
The VARh account low VARh drawal and High VARh injection between STU ans ISTSs shall
be maintained by ERLDC. Any payment to be made from VARh account shall be discussed
beforehand in ERPC forum.

10.3.4. Congestion Charge Account


The Congestion Charge account is prepared by ERPC secretariat. There is a congestion
imposed on real time Grid Operation, Congestion Charge shall be applicable to Regional entities as
per the CERC (Measures to relieve congestion in real time operation) Regulations and orders on rate
of congestion charge as applicable from time to time. Congestion charge would be levied for over
drawal or under-injection in the importing control area and, Congestion charge would also be levied
for under drawal or over-injection in the exporting control area.

10.4. Pool Account Operation


In line with Annexure-I of IEGC, from the date of issue of weekly UI and Reactive Energy Charge
Account by ERPC Secretariat, within 10-days, the concerned regional entity shall pay on priority the
indicated amount into regional UI, Reactive Energy and Congestion charges accounts operated by
ERLDC. The agencies that have to receive the money from pool accounts would then be paid within
3-working days. These pool accounts are to be reconciled once in periodic intervals.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 78 28-06-2013
ERLDC:POSOCO

Annexure: I Generation capacities in Eastern Region

EFFECTIVE/INSTALLED CAPACITY
(AS ON 31.05.2013)

INSTALLED CAPACITY EFFECTIVE CAPACITY

CONST. THERMAL HYDEL GT TOTAL THERMAL HYDEL GT TOTAL

BSEB 554 45 0 598 536 45 0 581

JSEB 1260 130 0 1390 1190 130 0 1320

DVC 6100 144 90 6334 6070 144 90 6304

TTPS(NTPC) 470 0 0 470 460 0 0 460

OHPC 0 2069 0 2069 0 2069 0 2069

OPGC 420 0 0 420 420 0 0 420

WBSEDCL 0 1196 100 1164 0 1195 100 1163

WBPDCL ~ 3950 0 0 3950 3860 0 0 3860

CESC 1285 0 0 1285 1225 0 0 1225

DPL 695 0 0 695 690 0 0 690

SIKKIM 5 33 0 38 5 33 0 38

NTPC * 7440 0 0 7440 7440 0 0 7440

NHPC 0 570 0 570 0 570 0 570

IPP 4800 0 0 4800 4800 0 0 4800

REGION $ 26979 4186 190 31223 26696 4185 190 30939

CHPC 0 336 0 336 0 336 0 336


KHPC 0 60 0 60 0 60 0 60
THPC 0 1020 0 1020 0 1020 0 1020
Thermal capacity of Sikkim refers to diesel generators only
* Including 2000MW TSTPS Stage-II, geographically located in ER and synchronized with
ER grid but dedicated entirely to SR
~STPS #1 to 4 (4x120 MW) units decommissioned (intimated by WBPDCL vide letter no.
84-PO/O/VI/55-17/2006 dated 16/05/2011)

_________________________________________________________________________
Operating Procedures for Eastern Region Page 79 28-06-2013
ERLDC:POSOCO

Annexure: II List of Generating Units and their Capacities


(As on 31.05.13)

_________________________________________________________________________
Operating Procedures for Eastern Region Page 80 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 81 28-06-2013
ERLDC:POSOCO

CAPACITY DETAILS

SIKKIM SYSTEM
ALL FIGURES IN MW
SYSTEM STATION INS CAP EFF CAP
UNITS TOTAL UNITS TOTAL

SIKKIM HYDRO 32.89 32.89


DIESEL 5 5

TOTAL 37.89 37.89

CENTRAL SECTOR

SYSTEM STATION INS CAP EFF CAP


UNITS TOTAL UNITS TOTAL
NTPC FARAKKA STG-I & II 3x200+2x500 1600 3x200+2x500 1600
FARAKKA STG-III 1x500 500 1x500 500

KAHALGAON STG-I 4X210 840 4X210 840


KAHALGAON STG-II 3x500 1500 3x500 1500

TALCHAR NTPC 2X500 1000 2X500 1000


TALCHAR STG-II 4X500 2000 4X500 2000
TOTAL NTPC 7440 7440

NHPC RANGIT NHPC 3 x 20 60 3 x 20 60


TEESTA V 3 x 170 510 3 x 170 510

CHPC CHUKHA CHPC 4x84 336 4x84 336


KHPC KURICHU HEP 4 x 15 60 4 x 15 60
TALA THPS 6 x 170 1020 6 x 170 1020

IPP/MPP
SYSTEM STATION INS CAP EFF CAP
UNITS TOTAL UNITS TOTAL
VEDANTA STERLITE 4x600 2400 4x600 2400
APNRL ADHUNIK 2 X270 540 2 X270 540
GMR GMR 2X350 700 2X350 700
TATA MPL 2x525 1050 2x525 1050
GATI CHUJACHEN 2X55 110 2X55 110

EASTERN REGION
SYSTEM STATION INS CAP EFF CAP
TOTAL TOTAL
THERMAL 24684 24401
DIESEL 5 5
E.REGION HYDRO 4186 4185
GT 190 190
TOTAL 29065 28781
Talcher Stage-II ( I.C 2000 MW) is dedicated to SR. Only 10% share is allocated to GRIDCO.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 82 28-06-2013
ERLDC:POSOCO

Annexure :III Captive Power Stations in Eastern Region and Their Capacities
CAPTIVE POWER STATIONS IN EASTERN REGION
AS ON 30.04.2013
31.10.2011

POWER SATION INSTALLED CAPACITY TOTAL


SYSTEM (MW) (MW)
1 VENDANTA (JHARSUGUDA) 9X135 1215
2 NALCO (ANGUL) 10 X120 1200
3 JINDAL STEEL & POWER LTD. 4X135 540
4 BHUSAN STEEL & STRIPS (M'MUNDALI) 1X33+1X77+2X150 410
5 BHUSAN STEEL, JHARSUGUDA 1X40+1X60+2X130+2X8 376
6 HPCL(HINDALCO), HIRAKUD 3 X 100+1X67.5 367.5
7 JINDAL STAINLESS LTD. 2X125 250
8 RSP(ROURKELA) 4X25+2X60 220
9 ICCL (CHOUDWAR) 2X54+1X30 138
10 IFFCO (PARADEEP) 2 X 55 110
11 NBVL (MERAMUNDALI) 1X30+1X65 95
12 VEDANTA (LANJIGARH) 3 X 30 90
13 VISA STEEL LTD. (NEW DUBURI) 3X25 75
ORISSA 14 KMCL(NINL), Duburi 2X19.25+1X24 62.5
15 M/S FACOR POWER LIMITED 1x45 45
16 ARATI STEEL (GHANTIKHAL, CUTTACK) 1X40 40
17 ACTION ISPAT & POWER PVT. LTD. 1X25+1X12 37
18 SMC POWER GEN. LTD. 1X8+1X25 33
19 SREE GANESH 1X32 32
20 SHYAM DRI( PANDOL, SAMBALPUR) 1X30 30
21 ACC, BARGARH 1X30 30
22 MAITHON ISPAT NIGAM LTD., JAIPUR RD. 1X30 30
23 TATA SPONGEIRON( JODA ) 1X18.5+1X7.5 26
24 MSP METALLICS LTD. 1X25 25
25 MAHESWARI ISPAT PVT. LTD. 2X12 24
26 ORISSA SPONGE IRON & STEEL LTD 1X24 24
27 EMAMI PAPER MILLS LTD. 1X15+1X5 20
28 RSPL (KATAPALLI) 1X20 20
29 ARYAN ISPAT & POWER PVT. LTD. 1X18 18
30 PATTANAIK STEEL (KEONJHAR) 1X15 15
31 MAHAVIR FERRO ALLOYS PVT. LTD. 1X12 12
32 DINABANDHU / YAZDANI STEEL & POWE 1X10 10
33 NARBHERAM POWER & STEEL PVT. LTD 1X8 8
TOTAL 5628.00
1 FCI 80 80
BIHAR 2 USHA MARTIN 25 25
3 BCCL REHLA 1X30 30
TOTAL 135
1 JOJOBERA 2X120 + 67.5 307.5
2 BSL 2X55+3X60+1X12 302
3 TISCO 1X67.5+3X30+1X25
215
JHARKHAND 4 (EXCL. DG SETS) 1X12.5+1X20
5 BIHAR CAUSTIC & CHICAL LTD 30
TOTAL 855
1 DSP 2X60+4X5 140
2 TATA POWER HALDIA (2X45+1X30) 120
3 HALDIA REFINERY (IOC ) 84.5
W.BENGAL 4 HALDIA PETROCHEMICALS LTD. 75.5
5 IISCO 2X10+2X20 60
6 CRESCENT POWER ( 2X20) 40
7 BEL (1x40) 40
8 PCBL ( 1X30) 30
9 RAM SWARUP LOHIA UDYOG 20
10 RENUKA SUGAR ( 1X15) 15
11 DPSCO 14.2
12 ELECTRO STEEL GREEN POWER. (4x3) 12
13 HIMADRI CHEMICAL (1x12) 12
14 CORPORATE ISPAT ALLOY (1X10) 10
15 AMRITA BIO-ENERGY & IND. LTD. 10 10
16 KESORAM REYON 6
17 KAMARHATI BIOGAS LTD ( 1X6) 6
TOTAL 695.2
1 ECL 20
COAL 2 BCCL 49.6
INDIA LTD 3 CCL 70.3
4 NEC 1
TOTAL 140.9
REGION TOTAL 7454

_________________________________________________________________________
Operating Procedures for Eastern Region Page 83 28-06-2013
ERLDC:POSOCO

Annexure: IV UI Rate at different frequencies

2000.00
UI Rate VS Frequency (w.e.f 17.09.2012)
1800 Paisa/KWH
1800.00
(Payment Side)
FREQ Normal Range(50.20 ‐ 49.50 HZ)

ADDL UI for OD (in the range < 49.70 HZ & < 49.50 HZ & < 49.20
1600.00 HZ)

49.20 HZ ADDL UI for APM (in the range < 49.70 HZ & < 49.50 HZ & <
49.20 HZ)
1400.00
Addl UI for O/D ADDL UI for UI (in the range < 49.70 HZ & < 49.50 HZ & < 49.20
1260 Paisa/KWH 49.50 HZ HZ)
1200.00

1051.88 Paisa/KWH
1000.00
900 Paisa/KWH

800.00
49.70 HZ
28.12 Paisa/0.02 HZ
590.10 Paisa/KWH 49.80 HZ
600.00

505.80 Paisa/KWH 28.50 Paisa/0.02 HZ


400.00
49.50 HZ
50.00 HZ
200.00
16.50 Paisa/0.02 HZ

0.00
49.00

49.04

49.08

49.12

49.16

49.20

49.24

49.28

49.32

49.36

49.40

49.44

49.48

49.52

49.56

49.60

49.64

49.68

49.72

49.76

49.80

49.84

49.88

49.92

49.96

50.00

50.04

50.08

50.12

50.16

50.20

50.24

50.28
Frequency (HZ)

1200.00

UI Rate VS Frequency (w.e.f 17.09.2012)


1100.00
(Receipt Side) FREQ Normal Range

1000.00
900 Paisa/KWH Buyer/Bef UD>10 % of sch or 250 MW whichever is less &
900.00 Seller/Gen >120 % of sch subject to 105 % of inst Cap in a
block or 101 % of Inst cap over a day
800.00 APM for OG > 105% DC in a block or 101 % over Avg DC
49. 48 HZ 28.12 Paisa/0.02 HZ

700.00
UI CAP RATE GEN/SELLER

600.00
49.80 HZ
500.00 450 Paisa/KWH

400.00
421.50 Paisa/KWH
28.50 Paisa/0.02 HZ
300.00
49.80 HZ 49.82 HZ
200.00 165 paisa/KWH 50.00 HZ

100.00 16.50 Paisa/0.02 HZ

0.00
49.00

49.04

49.08

49.12

49.16

49.20

49.24

49.28

49.32

49.36

49.40

49.44

49.48

49.52

49.56

49.60

49.64

49.68

49.72

49.76

49.80

49.84

49.88

49.92

49.96

50.00

50.04

50.08

50.12

50.16

50.20

50.24

50.28

Frequency (HZ)

_________________________________________________________________________
Operating Procedures for Eastern Region Page 84 28-06-2013
ERLDC:POSOCO

Annexure: V Format for Overdrwal message


Annexure: V(a) Format for Category A Message

POWER SYSTEM OPERATION CORPORATION LIMITED


EASTERN REGIONAL LOAD DESPATCH CENTRE

Message A

Reference: RLDC/OD/A/ Date : Time :

FROM: SHIFT INCHARGE, ERLDC

TO: SHIFT INCHARGE, SLDC, BSEB / JSEB / DVC /OPTCL /WBSETCL


CC : SE / PC / Director / DGM, SLDC/STU< BSEB/JSEB/DVC/OPTCL/WBSETCL >

Sub : Request to restrict the drawl within schedule.


At present the system frequency is below 49.8 Hz and overdrawl is being observed by your state. The present position of
over drawl by < BSEB/JSEB/DVC/OPTCL/WBSETCL > state control area is as follows:

Quantum of overdrawl in MW Frequency in Hz

Under these conditions, your specific reference is invited to Regulation 5.4.2(a), 5.4.2(b) and 6.4.7 of CERC (Indian
Electricity Grid Code) (First Amendment) Regulations 2012. The Regulation 5.4.2 (a) states that SLDC/SEB/Distribution
licensee and bulk consumers shall initiate action to restrict the drawl of its control area, from the grid, within the net
drawl schedule, whenever the system frequency falls to 49.80 Hz and Regulation 5.4.2 (b) states that the
SLDC/SEB/Distribution licensee and bulk consumers shall ensure that requisite load shedding is carried out in its control
area so that there is no overdrawl when frequency is 49.7 Hz or below. The Regulation 6.4.7 of IEGC also reiterates the
above actions to be taken by the SLDC/SEB/Distribution licensee and bulk consumers under different conditions so as to
ensure zero over‐drawl when frequency is 49.7 Hz. or below.

Alternatively

High value of overdrawl is being carried out by < BSEB/JSEB/DVC/OPTCL/WBSETCL > state control area. Under the
conditions of such high overdrawl, in the event of frequency falling down due to any event, difficulty may be expressed
by < BSEB/JSEB/DVC/OPTCL/WBSETCL > state control area in instant control of the drawls and the regulations as stated
in the above para may be violated, and network security may also be endangered.
You are, therefore, requested to take necessary measures so that there is no overdrawl by <
BSEB/JSEB/DVC/OPTCL/WBSETCL> state control area and system frequency always remains within the 49.7 Hz – 50.2 Hz
band as provided in Regulation 5.2 (m) of the CERC (Indian Electricity Grid Code) (First Amendment) Regulations 2012.

SHIFT INCHARGE
ERLDC

_________________________________________________________________________
Operating Procedures for Eastern Region Page 85 28-06-2013
ERLDC:POSOCO

Annexure: V (b) Format for Category B Message

POWER SYSTEM OPERATION CORPORATION LIMITED


EASTERN REGIONAL LOAD DESPATCH CENTRE

Message B
Reference: RLDC/OD/B/ Date : Time :

FROM : SHIFT INCHARGE , ERLDC , KOLKATA

TO: SHIFT INCHARGE, SLDC < BSEB/JSEB/DVC/OPTCL/WBSETCL >


CC : CE / CGM / GM, SLDC/STU < BSEB/JSEB/DVC/OPTCL/WBSETCL>
Member Secretary (RPC), CEO (POSOCO)
Sub: Intimation regarding violation of Regulation 5.4.2 (a), 5.4.2(b) and 6.4.7 of the CERC (Indian Electricity Grid Code)
(First amendment) Regulations 2012 and/or repeated instances of high overdrawl, and directions under regulation
5.4.2 (e) of IEGC and section 29(1) of the Electricity Act 2003 for immediate action for curtailment of overdrawl to
avoid system operation outside stipulated frequency band and for ensuring stability of the grid operation.
This has reference to earlier communications on the low frequency operation and/or overdrawl by <
BSEB/JSEB/DVC/OPTCL/WBSETCL > state control area in high range. In spite of above situations(s) the overdrawl by <
BSEB/JSEB/DVC/OPTCL/WBSETCL > state control area has not been sufficiently curtailed and at present the overdrawl is
as follows:
Quantum of overdrawl in MW Frequency in Hz

In this regard please refer to the regulation 5.4.2 (b) and 6.4.7 of the CERC (Indian Electricity Grid Code) First
Amendment) Regulations 2012 which states that when the frequency is 49.7 Hz, or below requisite load shedding would
be carried out by the concerned SLDC/SEB/Distribution licensee and Bulk Consumers in its control area so that there is no
overdrawl. It is therefore; pointed out that overdrawl at frequency below 49.7 Hz is violation of the regulation 5.4.2 (b)
and 6.4.7 of the IEGC.
Alternatively
In the event of consistent high overdrawal by < Name of State Control Area> state control area, in the event of frequency
falling down due to any event , difficulty may be expressed by your control area in instant control of drawal and grid
security may be endangered .
It is a matter of serious concern that the overdrawal by < BSEB/JSEB/DVC/OPTCL/WBSETCL > state control area is
continuing despite above conditions. RLDC is issuing directions under regulation 5.4.2(e) of the IEGC and Section 29(1) of
the Electricity Act 2003, to increase the generation and/or carry out automatic/manual load shedding by a quantum
equivalent to its overdrawal as per schemes prepared in compliance of regulation 5.4.2 (c) and 5.4.2 (d), so that its
overdrawal from grid becomes zero and details of the action taken be informed. Please note that the non‐compliance of
these directions would be construed as violation of IEGC and the Electricity Act 2003 and would be brought to the notice
of the Hon’ble Central Electricity Regulatory Commission (CERC).
Further, in the event of continued overdrawal by < BSEB/JSEB/DVC/OPTCL/WBSETCL > state control area, RLDC may also
be constrained to disconnect the feeders in < BSEB/JSEB/DVC/OPTCL/WBSETCL > state control area which may result in
the loss of load / network security in a particular area of < BSEB/JSEB/DVC/OPTCL/WBSETCL > state system. The
responsibility for the same would solely be on the inadequate action from < BSEB/JSEB/DVC/OPTCL/WBSETCL > SLDC
due to inadequate actions taken in the matter. Besides the above, your state’s full entitlement in all Inter State
Generating Stations (ISGS) including the liquid backed generation may also be scheduled.
Please treat this message as ‘most urgent’ and act immediately. Kindly also report the compliance.
SHIFT INCHARGE
ERLDC

_________________________________________________________________________
Operating Procedures for Eastern Region Page 86 28-06-2013
ERLDC:POSOCO

Annexure: V(c) Format for Category C message

POWER SYSTEM OPERATION CORPORATION LIMITED


EASTERN REGIONAL LOAD DESPATCH CENTRE
Message C

Reference: RLDC/OD/C/ Date : Time:

FROM : SHIFT INCHARGE, ERLDC, KOLKATA

TO: SHIFT INCHARGE, SLDC< BSEB/JSEB/DVC/OPTCL/WBSETCL >


CC : Member / Dev.Commissioner /Director / Secretary (Engg), SLDC/STU < BSEB/JSEB/DVC/OPTCL/WBSETCL >
Member Secretary (RPC), CEO, POSOCO

Sub: Intimation of violation of regulation 5.4.2(e) of the CERC (Indian Electricity Grid Code) First Amendment)
Regulations 2012 and Section 29(2)/29(3) of the Electricity Act 2003 and request for immediate action for curtailing the
overdrawl.

Please refer RLDC directions issued earlier to increase the generation and/or carry out automatic/manual load shedding
in < BSEB/JSEB/DVC/OPTCL/WBSETCL > state control area in order to maintain the grid frequency within the IEGC
stipulated frequency band given at clause 5.2(m) of the IEGC and/or to avert overdrawls in high range. These directions
were issued under Clause 5.4.2 (e) of IEGC and Section 29 (1) of the Electricity Act 2003.

However, the over drawl by < BSEB/JSEB/DVC/OPTCL/WBSETCL > state control area is continuing, in spite of above
situations. It is informed that by not complying with RLDC’s instructions, the Clause 5.4.2(e) of IEGC and Sections
29(2)/29(3) of the Electricity Act 2003 are being violated. It is also informed that apart from the violation of clauses 5.4.2
(a), 5.4.2 (b) of the IEGC, the clauses 5.4.2 (c) and 5.4.2 (d) of the IEGC which requires functioning of specific schemes for
affecting such demand management, have also been violated. The above violation of the RLDC directions as well as the
IEGC would be reported to the Hon’ble Central Electricity Regulatory Commission (CERC).

At this moment the overdrawl by < BSEB/JSEB/DVC/OPTCL/WBSETCL > state control area is as follows:

Quantum of overdrawl in MW Frequency in Hz

RLDC once again requests < BSEB/JSEB/DVC/OPTCL/WBSETCL > state control area to curtail the overdrawl so that the
grid operates with adequate safety and security. It is also pointed out that under such conditions of operating of the grid,
without the desired security/reliability margins, it may result in to disintegration / disturbance in the grid and the
responsibility of such an eventuality would rest solely on < BSEB/JSEB/DVC/OPTCL/WBSETCL > state control area.
Please treat this message as ‘Most urgent’ and act immediately. Kindly also report compliance.

SHIFT INCHARGE
ERLDC

_________________________________________________________________________
Operating Procedures for Eastern Region Page 87 28-06-2013
ERLDC:POSOCO

Annexure-VI Format for Overdrawal Message to NLDC/Other RLDCs

Eastern Regional Load Despatch Centre


POWER SYSTEM OPERATION CORPORATION
14 Golf Club Road, Tollygunje, Kolkata 700033
Tel.: 033-24235435, FAX: 033-24235809 web:www.erldc.com

FAX MESSAGE
Reference: ERLDC/OD/NLDC/_____ Date :_________ TOO :______

FROM : SCE , ERLDC, KOLKATA


TO: SCE : NLDC

Copy To: 1. SCE : NRLDC/WRLDC/NERLDC

Sub: Curtailment of overdrawal / Request for load shedding to avoid


low frequency operation

The system frequency of the NEW Grid is below 49.8 Hz. The present net exchange of Eastern system at
all its AC tie lines with other regions is as below:

Scheduled interchange (MW) at all Actual Interchange (MW) at all Quantum of overdrawal
AC interconnections with other AC interconnections with other (MW)
regions regions

It is observed that following regions are overdrawing as below at the AC interconnections of ER at a


frequency below 49.8 Hz .

Region Schedule Drawal Actual Drawal (MW) Quantum of


(MW) overdrawal(MW)

In view of secured system operation request kindly take up the matter with concerned RLDC/s for
curtailment of overdrawal as per the provision of clause 6.4.4 of IEGC .

Matter may kindly be treated as most urgent

Shift Charge Engineer


ERLDC, Kolkata

_________________________________________________________________________
Operating Procedures for Eastern Region Page 88 28-06-2013
ERLDC:POSOCO

Annexure: VII List of 765/400kV & 400/220kV ICTs and their tap positions

ICT TAP POSITION


TAP POSITION OF 765/400 kV & 400/220 kV ICTS IN EASTERN REGION AS ON 31.05.13

SUBSTATION CAPACITY TAP

BINAGURI 2X315 10
NEW PURNEA 2X315 11
MUZAFFARPUR 2X315 10
MALDA 2X315 12
SASARAM 400/220kV 2X315 12
SASARAM 765/400 kV 1x1500 12
BIHARSHARIF 3X315 12
BIDHANNAGAR 1X315 14
PATNA 2X315 11
FARAKKA STPS 2X315 11
MAITHON 2X315 9B
RANCHI 2X315 9B
JAMSHEDPUR 2X315 15
PARULIA 2X315 11
BAKRESWAR 2X315 11
ARAMBAGH 3X315 15
JEERAT 3X315 13
KHARAGPUR 2X315 7
SUBHASGRAM 2X315 11
KOLAGHAT 2X315 12
BARIPADA 2X315 9
RENGALI 2X315 12
ROURKELA 2X315 10
TALCHER STPS 2X315 13
MERAMUNDALI 2X315 10
UIHEP 2X315 9B
JEYPORE 2X315 16
MENDASAL 2X315 9
BOLANGIR 2X315 9B
GAYA 765/400 kV 2x1500 12
GAYA 400/220 kV 1X315 + 1x500 9
FOR 765/400 kV TAP 1:807/400, 12:765/400, 23: 723/400
FOR 400/220 KV ICT TAP 1: 440/220, 9:400/220, 17:360/220

_________________________________________________________________________
Operating Procedures for Eastern Region Page 89 28-06-2013
ERLDC:POSOCO

Annexure: VIII Reactive Compensation Details


REACTIVE COMPENSATION DETAILS
FOR 400 KV AND ABOVE LINES / SUB-STATIONS
SL LENGTH REACTORS CAPACITY
NO LINE/SUB-STN ( KM ) IN MVAR REMARKS
BUS LINE END
1 BEHRAMPUR-JEERAT 144 1X50 JEERAT
2 SAGARDIGHI-SUBASHGRAM 256.3 1X63 SAGARDIGHI
1X50 SUBHASGRM
3 FARAKKA-PARULIA-I 150 1X50 FARAKKA
4 BIDHANAGAR-PARULIA 11 1X50 PARULIA
5 K'GAON-B'SHARIFF-I 201 1X50 B'SHARIFF
6 K'GAON-B'SHARIFF-II 201 1X50 B'SHARIFF
7 K'GAON-MAITHON-I 172 1X50 MAITHON
8 K'GAON-MAITHON-II 172 1X50 MAITHON
9 JAMSHEDPUR-R'KELA-I 174 1X50 ROURKELA SWITCHABLE
10 JAMSHEDPUR-R'KELA-II 174 1x50 ROURKELA
11 ROURKELA-TALCHER I 175 1X50 TSTPP
12 ROURKELA-TALCHER II 175 1X50 TSTPP
13 KEONJHAR-BARIPADA 156 1X50 BARIPADA
14 BARIPADA-MENDASAL-I 273 1 X 63 MENDASAL
15 BARIPADA-MENDASAL-II 273 1 X 63 MENDASAL
1 X 63 BARIPADA
16 BAKRESWAR-ARAMBAGH 132 1X50 BAKRESWAR
17 BAKRESWAR-JEERAT 162 1X63 JEERAT
18 RENGALI-INDRAVATI(S/C) 356 1x50 RENGALI
1x50 INDRAVATI
19 B'SHARIFF-TENUGHAT(S/C) 180 1x50 TENUGHAT NOW AT 220 KV
20 MALDA-PURNEA D/C 167 2x63 MALDA
21 BINAGURI-BONGAIGAON-I 216 1X63 BONGAIGAON IN NER
22 BINAGURI-BONGAIGAON-III @ 224 1X80 BINAGURI SWITCHABLE
23 BINAGURI-BONGAIGAON-IV @ 224 1X80 BINAGURI SWITCHABLE
24 BINAGURI-TALA-I 115 1X63 BINAGURI
25 BINAGURI-TALA-II 115 1X63 BINAGURI
26 BINAGURI-TALA-IV 98 1X63 BINAGURI
27 PURNEA-BINAGURI-I 168 1x63 PURNEA
28 PURNEA-BINAGURI-III 160 1X63 PURNEA
28 PURNEA-MUZAFFARPUR-I 240 1x63 PURNEA SWITCHABLE
1x63 MZFRPR SWITCHABLE
27 PURNEA-MUZAFFARPUR-II 240 1x63 PURNEA SWITCHABLE
1x63 MZFRPR SWITCHABLE
28 ROURKELA-RAIGARH - I 212.4 1x63 ROURKELA
29 ROURKELA-STERLITE-I 113 1X63 ROURKELA
30 MERAMUNDALI-ANGUL 20.8 1x80 MERAMUNDALI
31 ANGUL-BOLANGIR 199 1x50 BOLANGIR
32 BOLANGIR-JEYPORE 288 1x50 BOLANGIR
1x80 JEYPORE
33 B'SHARIFF-PUSAULI D/C 195 2x63 PUSAULI SWITCHABLE
34 PUSAULI-ALLAHABAD 271 1X63 PUSAULI SWITCHABLE
35 PUSAULI-SARNATH 1X63 PUSAULI SWITCHABLE
36 MUZAFFARPUR-GRKPR-I 260 1X63 MUZAFFARPUR SWITCHABLE
37 MUZAFFARPUR-GRKPR-II 260 1X63 MUZAFFARPUR SWITCHABLE
38 B'SHARIFF-BALIA -I 242 1X50 BALIA IN NR
39 B'SHARIFF-BALIA -II 242 1X50 BALIA IN NR
40 BARH-PATNA-I 93 1X50 PATNA
41 BARH-PATNA-II 93 1X50 PATNA
RANCHI-SIPAT-I 405 1X80 RANCHI
42 RANCHI-SIPAT-II 405 1X80 RANCHI
43 JEYPORE-GAJUWAKA-I 220 1X80 GAJUWAKA IN SR (SWITCH)
44 JEYPORE-GAJUWAKA-II 220 1X80 GAJUWAKA IN SR (SWITCH)
43 MPL-RANCHI -I 188 1 X50 MPL
1 X50 RANCHI
44 MPL-RANCHI -II 188 1 X50 MPL
1 X50 RANCHI
45 PUSAULI-BIHARSHARIFF-III 198 1 X50 BIHARSARIFF
1 X50 PUSAULI
46 PUSAULI-BALIA 237 1 X50 PUSAULI LINE IS PART 400kV & PART 765 kV
47 BIHARSARIFF-GAYA 189 1 X50 BIHARSARIFF LINE IS PART 400kV & PART 765 kV
48 765 kV GAYA-PUSAULI-FATEHPUR 482 1 X 240 # GAYA 765 kV LINE
(145 & 337) 1 X 330 # PUSAULI MID POINT REACT OR
1 X 330 # FATEHPUR IN NR
49 765 kV PUSAULI-FATHEPUR 356 1 X 330 # PUSAULI 765 kV LINE
50 MAITHON-GAYA-I @ 235 1 X 50 GAYA SWITCHABLE
51 MAITHON-GAYA-II @ 235 1 X 50 GAYA SWITCHABLE
52 MAITHON-KODERMA-I 260 1 X 50 MAITHON SWITCHABLE
53 MAITHON-KODERMA-II 260 1 X 50 MAITHON SWITCHABLE
54 BANKA-BIHARSARIFF I & II 185 2 X 50 BANKA
55 BARIPADA-KEONJHAR 156 1 X 50 BARIPADA
56 BIHARSARIFF-PURNEA I @ 232 1 X 80 BIHARSARIFF SWITCHABLE
TOTAL 4692
# three single phase units, whose combined capacity is indicated
@ Only Reactors are commisioned without line

_________________________________________________________________________
Operating Procedures for Eastern Region Page 90 28-06-2013
ERLDC:POSOCO

REACTIVE COMPENSATION DETAILS


FOR 400 KV AND ABOVE LINES / SUB-STATIONS

57 FARAKKA 2X50
58 BIHARSHARIFF 1X50+1X80
59 KAHALGAON 2X50
60 BARH 1X80
61 MAITHON RIGHT BANK 2 X 50
62 MAITHON 1X50
63 JAMSHEDPUR 2X50
64 ROURKELA 1X50
65 BANKA 1X80
66 KEONJHAR 1X80
67 BOLANGIR 1X80
68 PURNEA 2X125
69 PARULIA 1X50
70 BINAGURI 2X125
71 MUZAFFARPUR 1X63
72 PATNA 1X80+1x125
73 GAYA 2 X125
70 765 kV GAYA 1 x 240 # 765 kV
71 PUSAULI 2 X 125
72 765 kV PUSAULI 1 x 330 # 765 kV
73 RANCHI 1X80+1x125 * TERTIARY
74 RENGALI 31.5* WINDING OF
75 JEYPORE 31.5* +1 x 63 400/220KV ICTs
76 BOLANGIR 1X80
77 ANGUL 1X125
78 JHARSUGUDA 1X125
79 BAKRESWAR 1X50
80 KHARAGPUR 1 X80
81 KODERMA 1X50
82 JEERAT 1X50
83 ARAMBAGH 1X50
84 RAGHUNATHPUR 2X50
TOTAL 3879
# three single phase units, whose combined capacity is indicated
@ Only Reactors are commisioned without line

_________________________________________________________________________
Operating Procedures for Eastern Region Page 91 28-06-2013
ERLDC:POSOCO

Annexure: IX Format for message to be issued by ERLDC for Real Time Outage
clearance

Eastern Regional Load Despatch Centre


POWER SYSTEM OPERATION CORPORATION
14 Golf Club Road, Tollygunje, Kolkata 700033
Tel.: 033-24235435, FAX: 033-24235809 web: www.erldc.com

Reference: ERLDC/SD/_____ Date :_________ TOO :______

FROM : SCE , ERLDC, KOLKATA


TO: SCE : SLDC BSEB/JSEB/DVC/ OPTCL/WBSETCL/SIKKIM
SCE : NLDC/NRLDC/WRLDC/SRLDC/NERLDC

Copy To: 1. Chief Engineer: SLDC/POWER Depatrment


BSEB/JSEB/DVC/ OPTCL/WBSETCL/SIKKIM
2. SE , ERPC, Kolkata

Sub: Shut down clearance Message

Refer your request for shut down message no___________ dated ________.
The shut down of the following element is cleared as detailed below.

1. Shutdown and duration:

Sl Name of the From From To To Remarks


No Element Date Time Date Time
On daily
basis(ODB)/
Continuous

2. Purpose:

3. Nature of Shutdown: Planned(OCC cleared)/Emergency/


High Voltage / Other.

4. Conditions of shutdown:

a) Before actually switching off of the element prior clearance may be availed from
ERLDC.
b) ERLDC may defer/postpone the shutdown if the system condition does not permit
opening of the element/s
c) The shutdown must be normalised within the approved period
d) …………………………………………………………….............................
e) …………………………………………………………………………………
f) …………………………………………………………................................

SHIFT CHARGE ENGINEER


ERLDC/KOLKATA

_________________________________________________________________________
Operating Procedures for Eastern Region Page 92 28-06-2013
ERLDC:POSOCO

Annexure :X Format for Weekly Reports

EASTERN REGIONAL LOAD DESPATCH CENTRE


POWER SYSTEM OPERATION CORPORATION
WEEKLY REPORT
(As per IEGC Clause No.5.5)
File No: Date:
Year: 2013-2014 / Week No: Period: From To
FREQUENCY PROFILE: dd/mm/yy dd/mm/yy
A)
DATE MAXIM MINIMUM AVERAGE
INSTANTANT. FREQ FREQ. REMARKS
(Hz) (Hz) (Hz)

During LSF During HSF


O/D-overdrawl O/G - over generation
U/G-under generation U/D-under-drawl

B) VOLTAGE (kV) :
DATE ROURKELA BIHARSHARIFF DURGAPUR MAITHON JEYPORE
MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN

C) MAJOR GENERATION OUTAGE.


SL PLANT & UNIT NO. MW CONSTI- OUTAGE RESTORATION REASON/
NO. CAPACITY-TUENT Date Time Date Time REMARKS
1
2
3
4
5
6
7

_________________________________________________________________________
Operating Procedures for Eastern Region Page 93 28-06-2013
ERLDC:POSOCO

D) MAJOR TRANSMISSION OUTAGE :


SL LINE / ICT KV/ OWNER OUTAGE RESTORATION REASON/
NO MVA Date Time Date Time REMARKS
1
2

E)TRANSMISSION CONSTRAINTS (if any):

F)Following elements are under breakdown :-

G)GRID DISTURBANCES (if any):


H)Messages issued by ERLDC, regarding violation of schedule,when frequency was beyond the band of 49.7-
50.2 Hz:

I) REGULATORY MEASURES (if any) :

J) SPECIAL MENTION:

Distribution:
1. C.E. TRANS.(O&M),BSEB,PATNA (D.K.Srivastava)
2. C.E.,CLD,DVC,MAITHON AGM, ERLDC
3. SR. G.M.(PS),GRIDCO,BHUBANESWAR
4. G.M. cum C.E.,JSEB,JHARKHAND,RANCHI
5. C.E,CLD,WBSEB,HOWRAH
6. G.M.,FSTPS,NTPC,FARAKKA
7. G.M., KhSTPS, NTPC, KAHALGAON
8. G.M., TSTPS, NTPC KANIHA
9. G.M., ERTS-I, POWERGRID, PATNA
10. G.M., ERTS-II, POWERGRID, KOLKATA
11. C.E., (TRANS), POWER DEPTT., GOVT. OF SIKKIM
12. C.E., RANGIT HPS, NHPC, RANGIT NAGAR, SOUTH SIKKIM
13. C.E, Teesta-V, DIPUDARA, SIKKIM
RPT:
1. Member Secretary, ERPC , KOLKATA
2. AGM (SO), POWERGRID, CC, NEWDELHI

_________________________________________________________________________
Operating Procedures for Eastern Region Page 94 28-06-2013
ERLDC:POSOCO

Annexure :XI Format for Quarterly Reports


POWER SYSTEM OPERATION CORPORATION
EASTERN REGIONAL LOAD DESPATCH CENTRE
QUARTERLY REPORT
(AS PER IEGC CLAUSE 6.5.2 a)

Quarter No. (1,2,3or 4) Period from: Month’yy to Month’yy

Brief report on Regional Power System / Performance of the grid is given below:

1. POWER SUPPLY POSITION

a) Peak Demand Met and Unrestricted Demand (MW)

MONTH STATE PK DMD MET PK REQ SHORTGE %


BSEB
JSEB
Month-yy DVC
OPTCL
WBSETCL
REGION
BSEB
JSEB
Month-yy DVC
OPTCL
WBSETCL
REGION
BSEB
JSEB
Month-yy DVC
OPTCL
WBSETCL
REGION

b) Energy Met and Requirement (MU)

MONTH STATE ENERGY ENERGY AVAILABILITY


SHORTGE
REQ OWN SCHD UI ENERGY %
SOURCE DRWL MET
BSEB
JSEB
Month-yy DVC
OPTCL
WBSETCL

REGION

_________________________________________________________________________
Operating Procedures for Eastern Region Page 95 28-06-2013
ERLDC:POSOCO

MONTH STATE ENERGY ENERGY AVAILABILITY


REQ OWN SCHD UI ENERGY SHORTGE
SOURCE DRWL MET %
BSEB
JSEB
Month-yy DVC
OPTCL
WBSETCL

REGION
BSEB
JSEB
Month-yy DVC
OPTCL
WBSETCL

REGION

2. REPORT ON SYSTEM CONSTRAINT ON REGIONAL GRID

The details of the system constraint in Eastern Region is given in Annexure-I.

3. QUALITY OF SERVICE

a) Frequency Profile (% time)

% of time of the month frequency remained


Month <49.2 49.2-49.5 49.5-49.7 49.7-50.2 > 50.2
Month’yy
Month’yy
Month’yy

Following curves are enclosed:


Annexure II - Frequency duration curve for Month’yy
Annexure III - Frequency duration curve for Month’yy
Annexure IV - Frequency duration curve for Month’yy

b) Voltage Profile

All figures in KV

JEERAT BINAGURI BIHARSHARIFF DURGAPUR PATNA


MONTH MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN
Month’yy
Month’yy
Month’yy

_________________________________________________________________________
Operating Procedures for Eastern Region Page 96 28-06-2013
ERLDC:POSOCO

c) Inter-regional exchanges during the quarter Month-yy to Month-yy


ALL FIG ARE IN MWH
Birpar-Salakati D/C Salakati-Gelyphu Binaguri-Bon'gaon D/C Budipadar-Korba T/C Raipur-Raigarh D/C Ranchi-Sipat D/C
MONTH ( 220 KV ) ( 132 KV ) ( 220 KV ) ( 220 KV ) ( 400 KV ) ( 400 KV )
IMPORT EXPORT IMPORT EXPORT IMPORT EXPORT IMPORT EXPORT IMPORT EXPORT IMPORT EXPORT
Month'yy
Month'yy
Month'yy

Pusauli HVDC/ Bypass Export / Import to NR Pusauli-Sahupuri S/C Muz'pur-Gorokhpur D/C Patna-Balia D/C Biharshariff-Balia D/C
Through 132KV ( 220 KV ) ( 400 KV ) ( 400 KV ) ( 400 KV )
MONTH IMPORT EXPORT IMPORT EXPORT IMPORT EXPORT IMPORT EXPORT IMPORT EXPORT IMPORT EXPORT

Month'yy
Month'yy
Month'yy

Jeypore-Gaz'ka D/C Talcher Interconnector


( 400 KV )
MONTH IMPORT EXPORT IMPORT EXPORT

Month'yy
Month'yy
Month'yy

4. OUTAGE OF IMPORTANT TRANSMISSION ELEMENTS

During Month’yy to Month’yy the following lines/elements in ER system were under


outage:

Name Date of Outage Reason Remarks


.
.
.

5. IMPORTANT EVENTS

6. TOTAL NUMBER OF MESSAGES ISSUED TO RESTRICT OVERDRAWAL

MONTH STATE MSG 'A' MSG 'B' MSG 'C’


BSEB
JSEB
Month-yy DVC
OPTCL
WBSETCL
REGION
BSEB
JSEB
Month-yy DVC
OPTCL
WBSETCL
REGION
BSEB

_________________________________________________________________________
Operating Procedures for Eastern Region Page 97 28-06-2013
ERLDC:POSOCO

JSEB
Month-yy DVC
OPTCL
WBSETCL
REGION

7. GENERATION OF CENTRAL SECTOR THERMAL POWER STATIONS AND


THEIR DECLARED CAPACITY

PLANT Month-yy Month-yy Month-yy


GEN(MU) AVG DC GEN(MU) AVG DC GEN(MU) AVG DC
(%) (%) (%)
FSTPP
KhSTPP-I
KhSTPP-II
TSTPP

Event-Reporting (Clause 6.9.6):

8. GRID INCIDENCES IN ER SYSTEM

_________________________________________________________________________
Operating Procedures for Eastern Region Page 98 28-06-2013
ERLDC:POSOCO

Annexure :XII Format for written report for event reporting


(vide IEGC Clause 5.3.1)

(i) Time and date of event


(ii) Location
(iii) Plant and/or Equipment directly involved
(iv) Description and cause of event
(v) Antecedent conditions
(vi) Demand and/or Generation (in MW) interrupted and duration of
interruption
(vii) All Relevant system data including copies of records of all recording
instruments including Disturbance Recorder, Event Logger, DAS etc.
(viii) Sequence of trippings with time.
(ix) Details of Relay Flags.
(x) Remedial measure

_________________________________________________________________________
Operating Procedures for Eastern Region Page 99 28-06-2013
ERLDC:POSOCO

Annexure: XII (a) Format For Reporting System Disturbances


(Detailed Report by the Constituents, as finalised by Protection Coordination Committee)

OCCURRENCE REPORT

(1) Date & Time of Occurrence :

(2) Name of the Sub Station / Generating Station :

(3) Details of Occurrence :

At the time of occurrence the disposition of the feeders was as below

Bus A Bus B

BUS COUPLER BREAKER STATUS (WHETHER “ON” / “OFF”)

For one and half breaker scheme

Feeder I Feeder II Tie-breaker (On/Off )


Diameter 1
Diameter 2
Diameter 3

(4) Sequence of Trippings :


Event
Time

(hh mm ss )
_________________________________________________________________________
Operating Procedures for Eastern Region Page 100 28-06-2013
ERLDC:POSOCO

(5) Relay Indication for Faulted Line/Transformer/Bus :

(A) Relay Indication Relay Indication

Sl. Name of Bay / Line Local End Remote End


No. Relay type / Make Relay type / Make
And Indications And Indications
1.

2.

3.

4.

(6) Location and nature of Fault :

(7) PLCC counter readings :

Local end Remote end


Before After Before After
CH I

CH II

(8) Analysis:-

(9) Restoration:-

Sl.No. From To Duration

_________________________________________________________________________
Operating Procedures for Eastern Region Page 101 28-06-2013
ERLDC:POSOCO

Remedial Measures / Lesson Learnt

Enclosure:-

1. Schematic Diagram showing position of (ON/OFF) breakers, Isolators and Relay


Indications.
2. DR Charts.
3. Event Logger outputs.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 102 28-06-2013
ERLDC:POSOCO

Annexure :XIII Categorisation of Grid Incidences/Disturbances

Annexure XIV (a) Categorisation of Grid Incidents

Sl No Date Name of Element/Elements Voltage Level Frequency(Hz) Rescheduling Category of Incidence Remarks if any
220kV 400kV Before After Required ?(Y/N) (1/2)

Annexure XIV (b) Categorisation of Grid Disturbance

Sl No Date Name of Element/Elements Voltage Level Frequency(Hz) Antecedant Generation % age Antecedant Lost %age Category Remarks
Tripped 220kV 400kV Before After Generation(MW) Lost (MW) Loss of Gen Load(MW) Load(MW) Load Loss (1/2/3/4/5)

_________________________________________________________________________
Operating Procedures for Eastern Region Page 103 28-06-2013
ERLDC:POSOCO

Annexure: XIV Flow Gate


Annexure : XIV (a) Flow Gate ‐I

_________________________________________________________________________
Operating Procedures for Eastern Region Page 104 28-06-2013
ERLDC:POSOCO

Annexure :XIV (b) Monsoon Flow Gate ‐I

_________________________________________________________________________
Operating Procedures for Eastern Region Page 105 28-06-2013
ERLDC:POSOCO

Annexure: XIV(c) Winter Flow Gate I

_________________________________________________________________________
Operating Procedures for Eastern Region Page 106 28-06-2013
ERLDC:POSOCO

Annexure :XIV(d) Winter & Summer Flow gate II

_________________________________________________________________________
Operating Procedures for Eastern Region Page 107 28-06-2013
ERLDC:POSOCO

Annexure :XV List of Important Elements

Tie Lines (as on 31.05.2013)


SL TIE-LINE OWNED BY CONNECTED SYSTEMS LENGTH COND. VOLTS NO.OF
NO END-1 END-2 (KM) (TYPE) (KV) CKTS.
1 FARAKKA-BEHRAMPUR POWERGRID NTPC POWERGRID 110 TW.MOOSE 400 S/C
2 BEHRAMPUR-JEERAT POWERGRID POWERGRID WBSETCL 200 TW.MOOSE 400 S/C
3 BEHRAMPUR-BEHRAMARA POWERGRID POWERGRID BANGLADESH 85* TW.MOOSE 400 D/C
4 FARAKKA-SAGARDIGHI POWERGRID NTPC WBPDCL 67 TW.MOOSE 400 S/C
5 SAGARDIGHI-SUBHASGRAM POWERGRID WBPDCL POWERGRID 246 TW.MOOSE 400 S/C
6 JEERAT-SUBHASGRAM POWERGRID WBSETCL POWERGRID 80 TW.MOOSE 400 S/C
7 PARULIA-BIDHANAGAR WBSETCL POWERGRID WBSETCL 11 TW.MOOSE 400 S/C
8 BINAGURI-BONGAIGAON POWERGRID POWERGRID(ER) POWERGRID(NER) 216 TW.MOOSE 400 D/C
9 JEYPORE-GAZUWAKA POWERGRID POWERGRID(ER) POWERGRID(SR) 220 TW.MOOSE 400 D/C
10 ANGUL-MERAMANDALI POWERGRID POWERGRID OPTCL 25 TW.MOOSE 400 S/C
11 INDRAVATI-INDRAVATI OPTCL POWERGRID(ER) OPTCL 3 TW.MOOSE 400 S/C
12 KHARAGPUR-BARIPADA WBSETCL & OPTCL WBSETCL POWERGRID(ER) 98 TW.MOOSE 400 S/C
13 TSTPP-MERAMUNDALI POWERGRID NTPC OPTCL 51 TW.MOOSE 400 S/C
14 TSTPP-GMR POWERGRID NTPC GMR 46 TW.MOOSE 400 S/C
15 GMR-MERAMUNDALI POWERGRID GMR OPTCL 8 TW.MOOSE 400 S/C
16 BINAGURI-TALA I & II POWERGRID POWERGRID THEP 115* TW.MOOSE 400 D/C
17 BINAGURI-TALA IV POWERGRID POWERGRID THEP 98* TW.MOOSE 400 S/C
18 JAMSEDPUR-MEJIA-B POWERGRID POWERGRID DVC 168 TW.MOOSE 400 S/C
19 MAITHON - MEJIA B POWERGRID POWERGRID DVC 84 TW.MOOSE 400 D/C
20 MAITHON - MEJIA B POWERGRID POWERGRID DVC 97 TW. MOOSE 400 S/C
21 DSTPS - JAMSHEDPUR POWERGRID DVC POWERGRID 156 TW. MOOSE 400 D/C
22 MAITHON-MAITHON RIGHT BANK POWERGRID POWERGRID MPL 30 TW.MOOSE 400 D/C
23 RANCHI-MAITHON RIGHT BANK POWERGRID POWERGRID MPL 188 TW.MOOSE 400 D/C
24 BINAGURI-MALBASE POWERGRID POWERGRID THEP 121* TW.MOOSE 400 S/C
25 MUZZFARPUR-GOROKHPUR POWERLINKS POWERGRID(ER) POWERGRID(NR) 261 QUAD-MOOSE 400 D/C
26 GAYA-PUSAULI-FATEHPUR POWERGRID POWERGRID(ER) POWERGRID(NR) 482 Qd BERSIMIS 765 S/C
27 PUSAULI-FATEHPUR POWERGRID POWERGRID(ER) POWERGRID(NR) 356 Qd BERSIMIS 765 S/C
28 PUSUALI-BALIA POWERGRID POWERGRID(ER) POWERGRID(NR) 237 Qd MOOSE & Qd BERSI. 400 S/C
29 PATNA-BALIA POWERGRID POWERGRID(ER) POWERGRID(NR) 195 QUAD-MOOSE 400 Q/C
30 RANCHI -SIPAT POWERGRID POWERGRID(ER) POWERGRID(WR) 405 TW.MOOSE 400 D/C
31 SASARAM -SARNATH POWERGRID POWERGRID(ER) POWERGRID(NR) 76 TW.MOOSE 400 S/C
32 SASARAM -ALLAHABAD POWERGRID POWERGRID(ER) POWERGRID(NR) 271 TW.MOOSE 400 S/C
33 JHRASUGUDA-RAIGARH POWERGRID POWERGRID(ER) POWERGRID(WR) 110 TW.MOOSE 400 D/C
34 ROURKELA-SEL POWERGRID & SEL POWERGRID SEL 114 TW.MOOSE 400 D/C
35 SEL-RAIGARH POWERGRID & SEL SEL POWERGRID(WR) 147 TW.MOOSE 400 D/C
36 KODERMA-BIHARSARIFF POWERGRID DVC POWERGRID(ER) 111 QUAD-MOOSE 400 D/C
37 MAITHON-KODERMA POWERGRID POWERGRID DVC 260 QUAD-MOOSE 400 D/C
38 BARIPADA-MENDASAL OPTCL POWERGRID(ER) OPTCL 273 TW.MOOSE 400 D/C
39 SAGARDIGHI-PARULIA WBSETCL WBPDCL POWERGRID(ER) 171 TW.MOOSE 400 S/C
40 SASARAM-NAVINAGAR POWERGRID POWERGRID NTPC 81 TW.MOOSE 400 D/C
41 JAMSEDPUR-AHUNIK APNRL POWERGRID APNRL 0.3 QUAD-MOOSE 400 D/C
42 TESSTA-BINAGURI POWERGRID NHPC POWERGRID 115 TW.MOOSE 400 D/C
43 BARIPADA-TISCO POWERGRID POWERGRID DVC 116 TW.MOOSE 400 D/C
44 PATNA-SIPARA BSPHCL POWEGRID BSPHCL 0.5 ZEBRA 220 D/C
45 DEHRI--PUSUALI BSPHCL BSPHCL POWERGRID 64 ZEBRA 220 S/C
46 PUSUALI-SAHUPURI BSPHCL & UPPCL POWERGRID UPPCL 72 ZEBRA 220 S/C
47 ARRAHA-KAHAGAUL POWERGRID POWERGRID BSPHCL 50 ZEBRA 220 D/C
48 WARIA-BIDHANNAGAR DVC & WBSETCL DVC WBSETCL 17 ZEBRA 220 D/C
49 BALIMELA-U.SILLERU OPTCL & APTRANSCO OPTCL APTRASCO 24 ZEBRA 220 S/C
50 JINDAL-JAMSHEDPUR OPTCL & DVC OPTCL DVC 130 ZEBRA 220 S/C
51 JODA-RAMCHANDRAPUR OPTCL & JSEB OPTCL JSEB 127 ZEBRA 220 S/C
52 BUDHIPADAR-KORBA II & III OPTCL & CSEB OPTCL CHATTISGARH 180 ZEBRA 220 D/C
53 BUDHIPADAR-RAIGARH I POWERGRID OPTCL CHATTISGARH 81 ZEBRA 220 S/C
54 PATRATU-BODHGAYA BSPHCL & JSEB JSEB BSPHCL 136 ZEBRA 220 T/C
55 PATNA-KHAGUAL BSPHCL POWERGRID BSPHCL 25 ZEBRA 220 S/C
56 TENUGHAT-BIHARSHARIFF BSPHCL & JSEB JSEB BSPHCL 182 TW.MOOSE 220 S/C
57 CHANDIL-SANTALDIH WBSETCL & JSEB JSEB WBSETCL 105 ZEBRA 220 S/C
58 TSTPP-MERAMUNDALI OPTCL NTPC OPTCL 40 ZEBRA 220 D/C
59 TSTPP-RENGALI HPS OPTCL NTPC OPTCL 40 ZEBRA 220 S/C

_________________________________________________________________________
Operating Procedures for Eastern Region Page 108 28-06-2013
ERLDC:POSOCO

Annexure XV … contd
Tie lines cont…

SL TIE-LINE OWNED BY CONNECTED SYSTEMS LENGTH COND. VOLTS NO.OF


NO END-1 END-2 (KM) (TYPE) (KV) CKTS.
60 TSTPP-TALCHER OPTCL NTPC OPTCL 30 ZEBRA 220 S/C
61 FARAKKA-LALMATIA POWERGRID NTPC JSEB 79 ZEBRA 220 S/C
62 B'SHARIF(PG)-B'SHARIF(BSPHCL) POWERGRID POWERGRID BSPHCL 0 ZEBRA 220 T/C
63 MAITHON(PG)-K'SWARI(DVC) DVC POWERGRID DVC 7 ZEBRA 220 D/C
64 DHALKHOLA-DHALKHOLA(WB) POWERGRID POWERGRID WBSETCL 3 ZEBRA & CABLE 220 S/C
65 MAITHON(PG)-DHANBAD(DVC) DVC POWERGRID DVC 28 ZEBRA 220 D/C
66 PARULIA(PG)-PARULIA(DVC) DVC POWERGRID DVC 1 ZEBRA 220 D/C
67 BISRA(PG)-TARKERA(OPTCL) OPTCL POWERGRID OPTCL 15 ZEBRA 220 D/C
68 JEYPORE(PG)-JAYNAGAR(OPTCL) OPTCL POWERGRID OPTCL 6 ZEBRA 220 D/C
69 RENGALI-RENGALI OPTCL POWERGRID OPTCL 1 ZEBRA 220 D/C
70 BARIPADA-BALASORE OPTCL POWERGRID OPTCL 77 ZEBRA 220 D/C
71 JAMSHEDPUR-RAMCHANDRAPUR DVC & JSEB POWERGRID JSEB 0.5 ZEBRA 220 D/C
72 PARULIA-BIDHANNAGAR WBSETCL POWERGRID WBSETCL 11 TW.MOOSE 220 S/C
73 BINAGURI-NJP POWERGRID POWERGRID WBSETCL 0.2 ZEBRA 220 S/C
74 SUBH'GRM(PG) - SUBH'GRM (WB) WBSETCL POWERGRID WBSETCL 0.5 ZEBRA 220 D/C
75 BIRPARA- CHUKHA POWERGRID POWERGRID POWERGRID 38 ZEBRA 220 D/C
76 BIRPARA-MALBASE POWERGRID POWERGRID POWERGRID 40 ZEBRA 220 S/C
77 MUZZFARPUR-KANTI POWERLINKS POWERGRID BSPHCL 22 ZEBRA 220 D/C
78 RANCHI-HATIA JSEB POWERGRID JSEB 34 ZEBRA 220 S/C
79 DEHRI-GAYA(PG) BSPHCL & PG BSPHCL POWERGRID 16 ZEBRA 220 D/C
80 BODHGAYA-GAYA(PG) BSPHCL & PG BSPHCL POWERGRID 96 ZEBRA 220 D/C
81 CHANDIL-RANCHI JSEB JSEB POWERGRID 42 ZEBRA 220 S/C
82 BIRPARA-SALAKATI POWERGRID POWERGRID(ER) POWERGRID(NER) 160 ZEBRA 220 D/C
83 BARHI - B'SHARIFF BSPHCL & DVC DVC BSPHCL 170 LARK 132 S/C
84 BARHI-RAJGIR BSPHCL & DVC DVC BSPHCL 125 LARK 132 S/C
85 DEOGHAR-SULTANGANJ DVC & JSEB JSEB BSPHCL 93 PANTHER 132 S/C
86 KAHALGAON-KAHALGAON POWERGRID BSPHCL NTPC 2 PANTHER 132 S/C
87 ARRAH-ARRAH POWERGRID BSPHCL POWERGRID 3 PANTHER 132 S/C
88 DUMRAON-ARRAH POWERGRID BSPHCL POWERGRID 61 PANTHER 132 S/C
89 PURNEA(PG)-PURNEA(BS) BSPHCL BSPHCL POWERGRID 1 LARK 132 T/C
90 PURNEA(PG)-KISANGANJ BSPHCL BSPHCL POWERGRID 70 PANTHER 132 S/C
91 DEHRI--PUSUALI POWERGRID BSPHCL POWERGRID 63 PANTHER 132 S/C
92 KARMANASA--PUSUALI POWERGRID BSPHCL POWERGRID 29 PANTHER 132 S/C
93 KARMANASA-SAHUPURI BSPHCL & UPPCL BSPHCL UPPCL 27 PANTHER 132 S/C
94 KARMANASA-CHANDAULI BSPHCL & UPPCL BSPHCL UPPCL 25 PANTHER 132 S/C
95 SONENAGAR - RIHAND BSPHCL & UPPCL BSPHCL UPPCL 139 PANTHER 132 S/C
96 MAITHON-JAMTARA DVC & JSEB DVC JSEB 100 PANTHER 132 S/C
97 KHARAGPUR-KHARAGPUR DVC DVC WBSETCL 1 PANTHER 132 S/C
98 KOLAGHAT-KOLAGHAT DVC DVC WBSETCL 1 PANTHER 132 S/C
99 MACHKUND-VIZAG OPTCL & APTRANSCO OPTCL APTRANSCO 160 LARK 132 S/C
100 JODA-KENDPOSI OPTCL & JSEB OPTCL JSEB 48 PANTHER 132 S/C
101 BARIPADA-RAIRANGPUR OPTCL POWERGRID OPTCL 70 PANTHER 132 S/C
102 BARIPADA-BARIPADA OPTCL POWERGRID OPTCL 11 PANTHER 132 S/C
103 GARWA-SONENAGAR BSPHCL & JSEB JSEB BSPHCL 104 PANTHER 132 S/C
104 LALMATIA-SABOUR BSPHCL & JSEB JSEB BSPHCL 72 PANTHER 132 S/C
105 CHANDIL-MANIQUE JSEB & DVC JSEB DVC 1 PANTHER 132 D/C
106 PATRATU-PATRATU JSEB & DVC JSEB DVC 3 LARK 132 S/C
107 GARWA-RIHAND JSEB & UPPCL JSEB UPPCL 30 PANTHER 132 S/C
108 RANGIT-RAMMAM POWERGRID NHPC WBSETCL 27 ZEBRA 132 S/C
109 KAHALGAON-SABOUR POWERGRID NTPC BSPHCL 37 PANTHER 132 S/C
110 KAHALGAON-LALMATIA POWERGRID NTPC JSEB 34 PANTHER 132 S/C
111 BIRPARA-BIRPARA WBSETCL POWERGRID WBSETCL 1 PANTHER 132 D/C
112 MALDA-MALDA WBSETCL POWERGRID WBSETCL 6 PANTHER 132 D/C
113 NJP-NBU WBSETCL POWERGRID WBSETCL 8 PANTHER 132 D/C
115 RANGIT - MELLI SIKKIM NHPC SIKKIM 32.5 PANTHER 132 D/C
116 ARHA-JAGDISHPUR BSPHCL POWERGRID BSPHCL 30 PANTHER 132 S/C
117 RANGIT - RABANGLA POWERGRID NHPC SIKKIM 25 LARK 66 S/C
118 GANGTOK - CHUJACHEN POWERGRID POWERGRID CHUJACHEN 49.6 PANTHER+ ZEBRA 132 S/C
119 CHUJACHEN-MELLI POWERGRID CHUJACHEN SIKKIM 66.3 PANTHER+ ZEBRA 132 S/C
120 GANGTOK - GANGTOK POWERGRID POWERGRID SIKKIM 0 PANTHER 132 D/C
121 KALINGPONG-MELLI WBSETCL & SIKKIM WBSETCL SIKKIM 15 DOG 66 D/C
122 NJP-MELLI POWERGRID POWERGRID SIKKIM 90 PANTHER 132 S/C

_________________________________________________________________________
Operating Procedures for Eastern Region Page 109 28-06-2013
ERLDC:POSOCO

Other Important Lines


LINE OWNED BY CONNECTED SYSTEMS LENGTH COND. VOLTS NO.OF
END-1 END-2 (KM) (TYPE) (KV) CKTS.
PTPS -TENUGHAT JSEB JSEB TVNL 53 TW. MOOSE 220 1
MERAMUNDALI - BIDANASI OPTCL OPTCL OPTCL 90 TW. MOOSE 220 2
MERAMUNDALI - MENDASAL OPTCL OPTCL OPTCL 99 TW. MOOSE 400 1
KEONJHAR- BARIPADA OPTCL POWERGRID POWERGRID 156 TW. MOOSE 400 1
KTPS - JEERAT WBSETCL WBPDCL WBSETCL 130 TW. MOOSE 400 1
BAKRESWAR - JEERAT WBSETCL WBPDCL WBSETCL 162 TW. MOOSE 400 1
BAKRESWAR - ARAMBAGH WBSETCL WBPDCL WBSETCL 130 TW. MOOSE 400 1
PPSP - ARAMBAGH WBSEDCL WBPDCL WBSETCL 210 TW. MOOSE 400 2
PPSP - BIDHANAGAR WBSEDCL WBPDCL WBSETCL 185 TW. MOOSE 400 2
KTPS - ARAMBAGH WBSETCL WBPDCL WBSETCL 75 TW. MOOSE 400 1
KTPS-KHARGPUR WBSETCL WBPDCL WBSETCL 80 TW. MOOSE 400 1
JEYPORE - INDRAVATI POWERGRID POWERGRID POWERGRID 72 TW. MOOSE 400 1
INDRAVATI - RENGALI POWERGRID POWERGRID POWERGRID 356 TW. MOOSE 400 1
FARAKKA - KAHALGAON I & II POWERGRID NTPC NTPC 95 TW. MOOSE 400 2
PARULIA - JAMSHEDPUR POWERGRID POWERGRID POWERGRID 177 TW. MOOSE 400 1
MAITHON - JAMSHEDPUR POWERGRID POWERGRID POWERGRID 153 TW. MOOSE 400 1
BIHARSHARIFF-GAYA POWERGRID POWERGRID(ER) POWERGRID(ER) 189 Qd MOOSE & Qd BERSI. 400 1
MAITHON - KAHALGAON POWERGRID POWERGRID NTPC 172 TW. MOOSE 400 2
MAITHON - RANCHI POWERGRID POWERGRID POWERGRID 200 TW. MOOSE 400 2
FARAKKA - MALDA POWERGRID NTPC POWERGRID 40 TW. MOOSE 400 2
KAHALGAON BIHARSARIFF I & II POWERGRID NTPC POWERGRID 201 TW. MOOSE 400 2
KAHALGAON-BANKA POWERGRID NTPC POWERGRID 47 TW. MOOSE 400 2
BANKA-BIHARSARIFF POWERGRID POWERGRID POWERGRID 184 TW. MOOSE 400 2
KAHALGAON -BARH POWERGRID NTPC NTPC 217 QD. MOOSE 400 2
BARH -PATNA POWERGRID NTPC POWERGRID 94 QD. MOOSE 400 4
TSTPP - ROURKELA POWERGRID NTPC POWERGRID 171 TW. MOOSE 400 2
FARAKKA - PARULIA POWERGRID NTPC POWERGRID 150 TW. MOOSE 400 2
TSTPP - RENGALI POWERGRID NTPC POWERGRID 24 TW. MOOSE 400 2
JAMSHEDPUR - ROURKELA POWERGRID POWERGRID POWERGRID 174 TW. MOOSE 400 2
MALDA - PURNEA POWERGRID POWERGRID POWERGRID 167 TW. MOOSE 400 2
PURNEA - BINAGURI I & II POWERGRID POWERGRID POWERGRID 168 TW. MOOSE 400 2
PURNEA - BINAGURI III & IV POWERGRID POWERGRID POWERGRID 160 QD. MOOSE 400 2
PURNEA - MUZAFFARPUR POWERLINKS POWERGRID POWERGRID 240 QD. MOOSE 400 2
BIHARSHARIFF-MUZAFFARPUR POWERGRID POWERGRID POWERGRID 130 TW. MOOSE 400 2
BIHARSHARIFF- PUSAULI POWERGRID POWERGRID POWERGRID 195 TW. MOOSE 400 2
BIHARSHARIFF- PUSAULI III POWERGRID POWERGRID POWERGRID 195 QD. MOOSE 400 1
BIHARSHARIFF-FATUAH BSPHCL BSPHCL BSPHCL 40 ZEBRA 220 2
BIHARSHARIFF-BODHAGYA BSPHCL BSPHCL BSPHCL 85 ZEBRA 220 2
KASBA-EMBYPASS WBSETCL WBSETCL CESC 1 ZEBRA 220 1
FATUAH-MTPS BSPHCL BSPHCL BSPHCL 92 ZEBRA 220 1
WARIA-PARULIA DVC DVC DVC 21 ZEBRA 220 2
WARIA-MEJIA DVC DVC DVC 34 ZEBRA 220 2
CTPS A-DHANBAD DVC DVC DVC 63 ZEBRA 220 1
CTPS B-DHANBAD DVC DVC DVC 63 ZEBRA 220 1
BOKARO-JAMSHEDPUR DVC DVC DVC 150 ZEBRA 220 2
BOKARO-CTPS DVC DVC DVC 41 ZEBRA 220 1
BOKARO-CTPS B DVC DVC DVC 42 ZEBRA 220 1
KALYANESHWARI-MEJIA DVC DVC DVC 55 ZEBRA 220 3
KALYANESHWARI-BURNPUR DVC DVC DVC 18 ZEBRA 220 1
BURNPUR-MEJIA DVC DVC DVC 70 ZEBRA 220 1
BOKARO-RAMGARH DVC DVC DVC 55 ZEBRA 220 2
PATRATU-HATIA JSEB JSEB JSEB 51 ZEBRA 220 1

_________________________________________________________________________
Operating Procedures for Eastern Region Page 110 28-06-2013
ERLDC:POSOCO

Other Important Lines cont..


LINE OWNED BY CONNECTED SYSTEMS LENGTH COND. VOLTS NO.OF
END-1 END-2 (KM) (TYPE) (KV) CKTS.
JEYANAGAR-U.KOLAB OPTCL OPTCL OHPC 6 ZEBRA 220 2
MERAMANDALI-NALCO OPTCL NTPC NALCO 10 ZEBRA 220 2
BALIMELA-JEYNAGAR OPTCL OHPC OPTCL 93 ZEBRA 220 3
IBTPS - BUDHIPADAR OPTCL OPGC OPTCL 25 ZEBRA 220 4
TARKERA-BUDHIPADAR OPTCL OPTCL OPTCL 120 ZEBRA 220 2
U. KOLAB-THERUVALI OPTCL OHPC OPTCL 136 ZEBRA 220 1
TALCHER-MERAMUNDALI OPTCL NTPC OPTCL 20 ZEBRA 220 2
UIHEP-THERUVALI OPTCL OHPC OPTCL 90 ZEBRA 220 4
KTPS-HOWRAH WBSETCL WBPDCL WBSETCL 71 ZEBRA 220 2
BISHNUPUR-SANTALDIH WBSETCL WBSETCL WBPDCL 92 ZEBRA 220 2
SANTALDIH-BIDHANNAGR WBSETCL WBDPCL WBSETCL 100 ZEBRA 220 1
BIDHANNAGAR-DPL WBSETCL WBSETCL DPL 5 ZEBRA 220 1
BIDHANNAGAR-BAKRESWAR WBSETCL WBSETCL WBPDCL 47 ZEBRA 220 2
BAKRESWAR-GOKARNO WBSETCL WBPDCL WBSETCL 82 ZEBRA 220 2
GOKARNO-SAGARDIGHI WBSETCL WBSETCL WBPDCL 39 ZEBRA 200 2
DALKHOLA-PURNEA POWERGRID POWERGRID POWERGRID 41 ZEBRA 220 2
BIRPARA-BINAGURI POWERGRID POWERGRID POWERGRID 80 ZEBRA 220 2
NJP-BINAGURI POWERGRID POWERGRID POWERGRID 6 ZEBRA 220 2
NJP-DALKHOLA POWERGRID POWERGRID POWERGRID 119 ZEBRA 220 2
DALKHOLA-MALDA POWERGRID POWERGRID POWERGRID 116 ZEBRA 220 2
FARAKKA-KAHALGAON III & IV POWERGRID NTPC NTPC 95 TW. MOOSE 400 2
RANCHI-ROURKELA-I&II POWERGRID POWERGRID POWERGRID 143 TW. MOOSE 400 2
SASARAM-ARRAH POWERGRID POWERGRID POWERGRID 112 ZEBRA 220 2

_________________________________________________________________________
Operating Procedures for Eastern Region Page 111 28-06-2013
ERLDC:POSOCO

Annexure XV …. contd
List of important Transformers
LOCATION VOLTAGE RATIO CAPACITY (MVA) OWNERSHIP
GAYA 765/400 3X1500 POWERGRID
GAYA 400/220 1X315 + 1X500 POWERGRID
JAMSHEDPUR 400/220 2X315 POWERGRID
FARAKKA 400/220 1X315 POWERGRID
PARULIA 400/220 2X315 POWERGRID
MALDA 400/220 2X315 POWERGRID
BIHARSHARIF 400/220 3X315 POWERGRID
JEYPORE 400/220 2X315 POWERGRID
RENGALI 400/220 2X315 POWERGRID
KAHALGAON 400/132 2X200 NTPC
MAITHON 400/220 2X315 POWERGRID
ROURKELA 400/220 2X315 POWERGRID
SASARAM 400/220 2X315 POWERGRID
SASARAM 765/400 1X1500 POWERGRID
TSTPP 400/220 2X315 NTPC
BINAGURI 400/220 2X315 POWERGRID
NEW PURNEA 400/220 2X315 POWERGRID
MUZAFFARPUR 400/220 2X315 POWERGRID
BARIPADA 400/220 2X315 POWERGRID
INDRAVATI ICT-I 400/220 1X315 OHPC
INDRAVATI ICT-II 400/220 1X315 POWERGRID
SUBHASGRAM 400/220 4X315 POWERGRID
PATNA 400/220 2X315 POWERGRID
BANKA 400/132 2X200 POWERGRID
KEONJHAR 400/220 1X315 POWERGRID
BOLANGIR 400/220 2X315 POWERGRID
RANCHI 400/220 2X315 POWERGRID
TALCHER HVDC CONV. XMER 400/(210/√3)/210 6X(397/198.5/198.5) POWERGRID
SSRM HVDC CONV. XFER (EAST) 400/(93/√3)/93 3X(234/117/117) POWERGRID
SSRM HVDC CONV. XFER (NORTH) 400/(93/√3)/93 3X(234/117/117) POWERGRID
BIRPARA 220/132 1x160+1x100 POWERGRID
NJP 220/132 1X100+1X160 POWERGRID
PURNEA 220/132 3X100 POWERGRID
MALDA 220/132 2X160 +1X50 POWERGRID
BARIPADA 220/132 2X160 POWERGRID
ARRAHA 220/132 2X100 POWERGRID
GANGTOK 132/66 2X50 POWERGRID
KHAGAUL 220/132 2X100 BSPHCL
SIPARA 220/132 2X160 BSPHCL
PATRATU 220/132 2X150 JSEB
TISCO 400/132 2X315 DVC
BOKARO 220/132 2X150 DVC
CHANDRAPURA 220/132 2x100+2x150 DVC
WARIA 220/132 2X150 DVC
UIHEP 400/220 1x315 OHPC
MERAMUNDALI 400/220 2X315 OPTCL
MENDHASAL 400/220 2X315 OPTCL
JODA 220/132 2X100 OPTCL
TALCHER 220/132 2X160 NTPC
BUDHIPADAR 220/132 2X160 OPTCL
KOLAGHAT TPS 400/220 2X315 WBPDCL
BAKRESWAR 400/220 2X315 WBPDCL
SAGARDIGHI 400/220 1X315 WBPDCL
JEERAT 400/220 4X315 WBSETCL
KHARGPUR 400/220 1X315 WBSETCL
DALKOHLA 220/132 2X160 WBSETCL
ARAMBAGH 400/220 4X315 WBSETCL
BIDHANNAGAR 400/220 2X315 WBSETCL
BARH 400/132 2X200 NTPC
KODERMA 400/220 2X315 DVC
KODERMA 220/132 2X160 DVC
SANTALDIH 220/132 1X100 WBPDCL

_________________________________________________________________________
Operating Procedures for Eastern Region Page 112 28-06-2013
ERLDC:POSOCO

Annexure XV (contd)
List of Reactors and Harmonic Filters
REACTIVE COMPENSATION DETAILS
FOR 400 KV AND ABOVE LINES / SUB-STATIONS
SL LENGTH REACTORS CAPACITY
NO LINE/SUB-STN ( KM ) IN MVAR REMARKS
BUS LINE END
1 BEHRAMPUR-JEERAT 144 1X50 JEERAT
2 SAGARDIGHI-SUBASHGRAM 256.3 1X63 SAGARDIGHI
1X50 SUBHASGRM
3 FARAKKA-PARULIA-I 150 1X50 FARAKKA
4 BIDHANAGAR-PARULIA 11 1X50 PARULIA
5 K'GAON-B'SHARIFF-I 201 1X50 B'SHARIFF
6 K'GAON-B'SHARIFF-II 201 1X50 B'SHARIFF
7 K'GAON-MAITHON-I 172 1X50 MAITHON
8 K'GAON-MAITHON-II 172 1X50 MAITHON
9 JAMSHEDPUR-R'KELA-I 174 1X50 ROURKELA SWITCHABLE
10 JAMSHEDPUR-R'KELA-II 174 1x50 ROURKELA
11 ROURKELA-TALCHER I 175 1X50 TSTPP
12 ROURKELA-TALCHER II 175 1X50 TSTPP
13 KEONJHAR-BARIPADA 156 1X50 BARIPADA
14 BARIPADA-MENDASAL-I 273 1 X 63 MENDASAL
15 BARIPADA-MENDASAL-II 273 1 X 63 MENDASAL
1 X 63 BARIPADA
16 BAKRESWAR-ARAMBAGH 132 1X50 BAKRESWAR
17 BAKRESWAR-JEERAT 162 1X63 JEERAT
18 RENGALI-INDRAVATI(S/C) 356 1x50 RENGALI
1x50 INDRAVATI
19 B'SHARIFF-TENUGHAT(S/C) 180 1x50 TENUGHAT NOW AT 220 KV
20 MALDA-PURNEA D/C 167 2x63 MALDA
21 BINAGURI-BONGAIGAON-I 216 1X63 BONGAIGAON IN NER
22 BINAGURI-BONGAIGAON-III @ 224 1X80 BINAGURI SWITCHABLE
23 BINAGURI-BONGAIGAON-IV @ 224 1X80 BINAGURI SWITCHABLE
24 BINAGURI-TALA-I 115 1X63 BINAGURI
25 BINAGURI-TALA-II 115 1X63 BINAGURI
26 BINAGURI-TALA-IV 98 1X63 BINAGURI
27 PURNEA-BINAGURI-I 168 1x63 PURNEA
28 PURNEA-BINAGURI-III 160 1X63 PURNEA
28 PURNEA-MUZAFFARPUR-I 240 1x63 PURNEA SWITCHABLE
1x63 MZFRPR SWITCHABLE
27 PURNEA-MUZAFFARPUR-II 240 1x63 PURNEA SWITCHABLE
1x63 MZFRPR SWITCHABLE
28 ROURKELA-RAIGARH - I 212.4 1x63 ROURKELA
29 ROURKELA-STERLITE-I 113 1X63 ROURKELA
30 MERAMUNDALI-ANGUL 20.8 1x80 MERAMUNDALI
31 ANGUL-BOLANGIR 199 1x50 BOLANGIR
32 BOLANGIR-JEYPORE 288 1x50 BOLANGIR
1x80 JEYPORE
33 B'SHARIFF-PUSAULI D/C 195 2x63 PUSAULI SWITCHABLE
34 PUSAULI-ALLAHABAD 271 1X63 PUSAULI SWITCHABLE
35 PUSAULI-SARNATH 1X63 PUSAULI SWITCHABLE
36 MUZAFFARPUR-GRKPR-I 260 1X63 MUZAFFARPUR SWITCHABLE
37 MUZAFFARPUR-GRKPR-II 260 1X63 MUZAFFARPUR SWITCHABLE
38 B'SHARIFF-BALIA -I 242 1X50 BALIA IN NR
39 B'SHARIFF-BALIA -II 242 1X50 BALIA IN NR
40 BARH-PATNA-I 93 1X50 PATNA
41 BARH-PATNA-II 93 1X50 PATNA
RANCHI-SIPAT-I 405 1X80 RANCHI
42 RANCHI-SIPAT-II 405 1X80 RANCHI
43 JEYPORE-GAJUWAKA-I 220 1X80 GAJUWAKA IN SR (SWITCH)
44 JEYPORE-GAJUWAKA-II 220 1X80 GAJUWAKA IN SR (SWITCH)
43 MPL-RANCHI -I 188 1 X50 MPL
1 X50 RANCHI
44 MPL-RANCHI -II 188 1 X50 MPL
1 X50 RANCHI
45 PUSAULI-BIHARSHARIFF-III 198 1 X50 BIHARSARIFF
1 X50 PUSAULI
46 PUSAULI-BALIA 237 1 X50 PUSAULI LINE IS PART 400kV & PART 765 kV
47 BIHARSARIFF-GAYA 189 1 X50 BIHARSARIFF LINE IS PART 400kV & PART 765 kV
48 765 kV GAYA-PUSAULI-FATEHPUR 482 1 X 240 # GAYA 765 k V LINE
(145 & 337) 1 X 330 # PUSAULI MID P OINT REACT OR
1 X 330 # FATEHPUR IN NR
49 765 kV PUSAULI-FATHEPUR 356 1 X 330 # PUSAULI 765 k V LINE
50 MAITHON-GAYA-I @ 235 1 X 50 GAYA SWITCHABLE
51 MAITHON-GAYA-II @ 235 1 X 50 GAYA SWITCHABLE
52 MAITHON-KODERMA-I 260 1 X 50 MAITHON SWITCHABLE
53 MAITHON-KODERMA-II 260 1 X 50 MAITHON SWITCHABLE
54 BANKA-BIHARSARIFF I & II 185 2 X 50 BANKA
55 BARIPADA-KEONJHAR 156 1 X 50 BARIPADA
56 BIHARSARIFF-PURNEA I @ 232 1 X 80 BIHARSARIFF SWITCHABLE
57 FARAKKA 2X50
58 BIHARSHARIFF 1X50+1X80
59 KAHALGAON 2X50
60 BARH 1X80
61 MAITHON RIGHT BANK 2 X 50
62 MAITHON 1X50
63 JAMSHEDPUR 2X50
64 ROURKELA 1X50
65 BANKA 1X80
66 KEONJHAR 1X80
67 BOLANGIR 1X80
68 PURNEA 2X125
69 PARULIA 1X50
70 BINAGURI 2X125
71 MUZAFFARPUR 1X63
72 PATNA 1X80+1x125
73 GAYA 2 X125
70 765 kV GAYA 1 x 240 # 765 kV
71 PUSAULI 2 X 125
72 765 kV PUSAULI 1 x 330 # 765 kV
73 RANCHI 1X80+1x125 * TERTIARY
74 RENGALI 31.5* WINDING OF
75 JEYPORE 31.5* +1 x 63 400/220KV ICTs
76 BOLANGIR 1X80
77 ANGUL 1X125
78 JHARSUGUDA 1X125
79 BAKRESWAR 1X50
80 KHARAGPUR 1 X80
81 KODERMA 1X50
82 JEERAT 1X50
83 ARAMBAGH 1X50
84 RAGHUNATHPUR 2X50

_________________________________________________________________________
Operating Procedures for Eastern Region Page 113 28-06-2013
ERLDC:POSOCO

Annexure XV.. contd


SERIES COMPENSATION ELEMENTS & HVDC CONVERTERS

1 FSC + TCSC AT PURNEA END OF 400KV PURNEA - MUZAFFARPUR I & II


2 FSC AT JEYPORE END OF 400KV MERAMUNDALI-JEYPORE LINE
3 FSC AT JEYPORE END OF 400KV JEYPORE - GAJUWAKA I& II
4 FSC AT RENGALI END OF 400KV RENGALI - INDRAVATI LINE
5 FSC AT RANCHI END OF 400 KV RANCHI-SIPAT I & II
5 500MW HVDC BACK-TO-BACK CONVERTER AT SASARAM

Filters at Gazuwaka East Number


106 MVAR Doubled Damped Filter 1
106 MVAR 3rd Harmonic/Doubled Damped Filter 2
50 MVAR Bus Reactor 2
Filters at Talcher Number
Doubled Damped filter
120 MVAR (Switchable) 6
97 MVAR 3
66 MVAR Shunt Capacitor 1
72.6 MVAR Shunt Capacitor 2
Filters at Pusauli Number
112 MVAR at North Bus 4
112 MVAR at East Bus 4

List of Important Generators


Control Area Station Type Owner Capacity(MW)
Farakka Farakka STPS Stage I & II ISGS Thermal NTPC 3x200+2x500
Farakka STPS Stage III ISGS Thermal NTPC 1x500
Kahalgaon Kahalgaon STPS Stage I ISGS Thermal NTPC 4x210
Kahalgaon STPS Stage II ISGS Thermal NTPC 3x500
Talcher Stg I Talcher STPS Stage I ISGS Thermal NTPC 2x500
Talcher Stg II Talcher STPS Stage II ISGS Thermal NTPC 4x500
Teesta -V Teesta ISGS Hydro NHPC 3x170
Rangit Rangit ISGS Hydro NHPC 3x20
Bhutan Tala ISGS Hydro DGPC(Bhutan) 6x170
Bhutan Chukha ISGS Hydro DGPC(Bhutan) 4x84
Bhutan Kurichu ISGS Hydro DGPC(Bhutan) 4x15
Jharkhand Tenughat Thermal TVNL(JSEB) 2x210
Subarnarekha Hydro JSEB 2X65
Waria Thermal DVC (U#4) 210
DVC Mejia Thermal DVC 4X210+2X250
CTPS B Thermal DVC 2 X 250
Mejia-B Thermal DVC 2 X 500
Koderma TPS Thermal DVC 1 x 500
Bokaro"B" Thermal DVC 3x210
DSTPS Thermal DVC 2 X 500
Kolaghat Thermal WBPDCL 6x210
Sagardighi Thermal WBPDCL 2x300
Bakreswar Thermal WBPDCL 5x210
West Bengal Santaldih Thermal WBPDCL 2 X 250
Bandel Thermal WBPDCL U#5 (210)
TLDP Hydro WBSEDCL 4x33
PPSP Hydro WBSEDCL 4X225
DPL Thermal DPL (U#7) 300
Budge-Budge Thermal CESC 3X250
IB Thermal OPGC 2x210
Balimela Hydro OHPC 6x60+2x75
GMR Thermal IPP 1x350
Orissa U-Kolab Hydro OHPC 4x80
U-Indravati Hydro OHPC 4x150
Rengali Hydro OHPC 4x50
MPL Thermal MPL 2 x 525
ADHUNIK Thermal APNRL 2X270
Sterlite* Thermal SEL 4X600
GMR** Thermal IPP 2x350
IPP CHJACHEN Hydro GATI 2 X 55
* one unit of Sterlite is decdicated to Odisha
** one unit of GMR is decdicated to Odisha

_________________________________________________________________________
Operating Procedures for Eastern Region Page 114 28-06-2013
ERLDC:POSOCO

Annexure :XVI Automatic UFR load shedding Schemes

ALL FIG ARE IN MW.


Constituents Stage-I (48.8 Hz, Inst. .) Stage-II (48.6 Hz, Inst. .) Stage-III (48.2 Hz, Inst. .) Emergency
Agreed Actual Agreed Actual Agreed Actual (47.6 Hz, Inst.)
BSEB 80 88 80 82 115 122.5 Nil
JSEB 50 58 50 51 70 70 Nil
DVC 110 132.4 110 142.7 155 166.1 213
OPTCL 150 160.5 150 158.5 208 209.5 Nil
WB( Incl CESC) 285 313 285 285 397 430 220
TOTAL 675 751.9 675 719.2 945 998.1 433

_________________________________________________________________________
Operating Procedures for Eastern Region Page 115 28-06-2013
ERLDC:POSOCO

Annexure :XVII Power Demand Override

PDOs at Talcher

Sl No Number of Connected generators /AC DC Power Limit in MW


lines
1 6 No Limit
2 5 No Limit
3 4 No Limit
4 3 1500 MW
5 2 1000 MW
6 1 500 MW
7 0 Controlled Shut down /ESOF

PDOs at Kolar

Sl No Number of Connected generators /AC DC Power Limit in MW


lines
1 6 No Limit
2 5 2000 MW
3 4 1500 MW
4 3 1000 MW
5 2 500 MW
6 1 Controlled Shut down
7 0 Controlled Shut Down/ ESOF

PDO (Run Back) at HVDC Gajuwaka

Totally 16 PDO’s can be programmed at HVDC Gajuwaka .Presently only 4 PDO’s have been used and they
are detailed below

PDO’s at HVDC Gajuwaka Poles

SL NO Type of PDO Contingency DC Powerlimit

1 PDO-2 East Bus AC U/V Relay set at Vs – 87.5 V or 500 MW


318 kV ( on 400 kV side on any phase- phase)

2 PDO-4 Tripping of 500 MW


 Jeypore –Indravati 400kV S/C
 Jeypore-meramundali 400kV S/C
 One ckt of Jeypore-Gazuwaka 400kV
D/C
 Both 400/220kV Jeypore ICTs
 Jeypore-Jeynagar 220kV D/C
3 PDO-5 East Bus frequency at 49.0 Hz and below. 150 MW
Rate of fall of frequency df/dt – 0.3 Hz./sec
4 PDO-6 Overload Trip contact of Gajuwaka S/s ICT 250MW
on southern side

_________________________________________________________________________
Operating Procedures for Eastern Region Page 116 28-06-2013
ERLDC:POSOCO

Annexure : XVIII Special Protection schemes at Talcher and Kolar

SPS 450
Under this mode of SPS the power injection to N-E-W grid is limited to 450 MW.
The actual generation by the generators is considered for building the logic.

Logic for single pole tripping:


This logic is based on the assumption that during the tripping of one pole of HVDC the other
available pole will automatically ramp up to 1250 MW. The logic is built using power relays
and the logic adopted is detailed below.
One pole trips
AND
Total Power injected by generators is more than 1700 MW
THEN
Tripp one of the selected unit (Presently unit six selected) instantly
Logic for Bipole tripping
Presently this logic is built using power relays and the logic adopted is
detailed below.

If Both Poles trip


AND
Power injected by Generators is more than 1100 MW
THEN
Trip two nos of selected units( presently unit six and three are selected)
IF
The total power injected by the generators is still more than 550 MW for more than 250
milliseconds
THEN
Trip Unit 4

SPS 1000

Under this mode of SPS the power injection to N-E-W grid is limited to 1000 MW. The actual
injection to the HVDC system (by measuring the flow on four a/c lines between TSTPS and
Talcher HVDC station) is considered for building the logic. Under SPS 1000 scheme no
generation shedding is required for a single pole tripping. For contingencies of both pole
tripping and for single pole tripping with the HVDC system going to ground return mode,
generation shedding will be done. Extent of generation shedding depends on the actual
power flow through the HVDC link and to limit the actual injection to N-E-W grid to 1000 MW

_________________________________________________________________________
Operating Procedures for Eastern Region Page 117 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 118 28-06-2013
ERLDC:POSOCO

HVDC INTER TRIP SCHEME (SPS 1000)

Sl number Condition Action


IF THE HVDC POWER FLOW IS Unit 6 Trip
1 MORE THAN 1600 MW & BOTH Unit 5 Unload by 150 MW
POLE BLOCKED Unit 4 Unload by 150 MW

IF THE HVDC POWER FLOW IS Unit 6 Trip


2 BETWEEN 1450 MW TO 1600 MW Unit 5 Unload by 150 MW
& BOTH POLE BLOCKED Unit 4 No effect

IF THE HVDC POWER FLOW IS Unit 6 Trip


MORE THAN 1600 MW & ONE
3 POLE BLOCKED WITH REMAINING Unit 5 Unload by 150 MW
POLE ON GROUND RETURN
Unit 4 No effect
MODE

IF THE HVDC POWER FLOW IS Unit 6 Unload by 150 MW


4 BETWEEN 1300 MW TO 1450 MW Unit 5 Unload by 150 MW
& BOTH POLE BLOCKED Unit 4 Unload by 150 MW

IF THE HVDC POWER FLOW IS


Unit 6 Unload by 150 MW
MORE BETWEEN 1450 MW TO
5 1600 MW & ONE POLE BLOCKED Unit 5 Unload by 150 MW
WITH REMAINING POLE ON
Unit 4 Unload by 150 MW
GROUND RETURN MODE

IF THE HVDC POWER FLOW IS Unit 6 Unload by 150 MW


6 BETWEEN 1150 MW TO 1300 MW Unit 5 No effect
& BOTH POLE BLOCKED Unit 4 Unload by 150 MW

IF THE HVDC POWER FLOW IS


Unit 6 Unload by 150 MW
MORE BETWEEN 1300 MW TO
7 1450 MW & ONE POLE BLOCKED Unit 5 No effect
WITH REMAINING POLE ON
Unit 4 Unload by 150 MW
GROUND RETURN MODE

IF THE HVDC POWER FLOW IS Unit 6 Unload by 150 MW


8 BETWEEN 1000 MW TO 1150 MW Unit 5 No effect
& BOTH POLE BLOCKED Unit 4 No effect

IF THE HVDC POWER FLOW IS Unit 6 Unload by 150 MW


MORE BETWEEN 1000 MW TO
9 Unit 5 No effect
1150 MW & ONE POLE BLOCKED
WITH REMAINING POLE ON Unit 4 No effect

_________________________________________________________________________
Operating Procedures for Eastern Region Page 119 28-06-2013
ERLDC:POSOCO

Annexure :XIX Islanding schemes in ER

Station/System Islanding scheme Criteria


CHPC (Bhutan) One machine (84 MW) alongwith Low
Thimpu Load gets islande with opening Frequency( 47.0Hz)
of bus coupler breaker
CESC The entire system gets islanded at Low frequency (47.8
Kasba ( the synchronising point) Hz)
Or
High frequency (52.5
Hz)
NALCO(CPP in Main –I bus connects all lines Low Freq( 47.4 Hz)
Orissa system) connecting OPTCL Network
Main –II bus connects plant load and
generators
Bus coupler breaker opens to isolate
plant with generators from rest of the
system
ICCL(CPP within The plant gets connected to OPTCL Low Freq ( 47.5 Hz)
Orissa system) network at 132kV.
The 132/33 kV Transformer gets
isolated from 132kV system
RSP (CPP in Orissa CP2 has 2 units 60MW each generating Low frequency(Both
system) at 11kV and connected to 132 bus the schemes operate at
through 132/33 transformer 47.6 Hz)
CP1 has 3 units, 45 MW each,
generating at 6.6 kV and connected to
33 kV bus through 33/6/6kV
Transformer
Scheme I : All units gets islanded by
opening of 132kV lines
Scheme II: One unit may reamin with
Grid and get islanded by opening of
132kV and 33kV Bus coupler CBs
Bhushan Power & 130MW TG#1 & TG#2 will get
Steel (CPP in Orissa islanding status in Governor, AVR and
system) Siprotect Relays through PLC Logic.
For this all status of breaker in MRSS
(220kV Main breaker# 1,220kV Main
breaker#2, and Bus coupler) and 220kV
cable feeder #1 at 130MW power plant
wired up to PLC in 130MW
Arya ISPAT and Whenever the 18 MW TG set is running Under frequency 47.5
power Ltd. (CPP in in synchronization condition with OPTCL Hz for 2.5 Sec
Orissa system) Grid following relays have been nvisaged Over Frequency 52.6 Hz
for islanding purpose of 18 MW TG set: for 2.5 Sec
1)MICOM-P341, Areva make
2)6RW 6000, Siemens make
MICOM-P341 shall sense any rate of
changed of frequency and the variation of
voltages between Grid supply and
generation. Accordingly, it shall give trip
command to Grid incomer breaker.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 120 28-06-2013
ERLDC:POSOCO

Instead of above, the electrical quantities


like U/V, O/V, U/F, O/F are measured by
MICOM-P341 as well as 6RW 6000 and
give trip command to Grid incomer
breaker
Maithon Ispat In the scheme, Micom P 341 Relay, Areva
Limited (CPP in Make, operates during Grid Disturbance
Orissa system) and it gives Trips command to SMS TIE
2 breaker and 220 kV incomer breaker
and consequently incomer breaker gives
trip command to 20/25 and 28/35 MVA
transformer 220 kV incomer breaker
and 11 kV ALONE Breaker through
interlocks
IFFCO (CPP in Whenever there is a disturbance in the Under frequency 48.0
Orissa system) system, the relay calculates the current & Hz for 0 Sec
voltage parameters and evaluates the type Over Frequency 52.0 Hz
of fault. Then the relay gives the alarm/ for 1.0 Sec
trip command. When a trip command
actuates by the relay, it operates the
master trip relay and subsequently trips
the corresponding 132KV Grid incomer
breaker. This results in clearing the fault
and isolating the TG set from feeding the
fault current. Also there is a provision for
tripping of downstream 33KV Grid
Hindalco(CPP in The power system of CGP of Hindalco Under frequency 48.0
Orissa system) Industries Ltd is connected to grid at 132 Hz
kV level through two number of Alco Over Frequency 51.5 Hz
feeders from Burla Power House to their
132 kV main receiving substation. They
have got grid islanding scheme in order to
survive during grid disturbance. The
disturbance in the grid is sensed by the
Numerical Relay Micom P 341 through
following four criteria and it opens the
grid connecting breakers in their main
receiving substation.
IMFA (CPP in Orissa Islanding of 108 MW captive Power Plant Under frequency 48.0
system) is done by sensing frequency Hz
Rate of fall of frequency
0.8Hz/Sec
IBTPS Islanding of IBTPS is done using LADR
(Load Accessed Directional Relay)
technique.
From every feeder, lock out tripping pulse
is extended to LADR relay at BC panel.
Continuously the dI/dt on the system due
to the available of target loads and
enerators are monitored by the relay and
as per the
allowable load limit, this relay sends
command for shedding.

_________________________________________________________________________
Operating Procedures for Eastern Region Page 121 28-06-2013
ERLDC:POSOCO

Different proposed islanding scheme:-


Islanding Scheme:-
Bus-1:- IB (1,3), AT1&2, Korba-2,
Bhusan-(1,2), SPS
Bus-2:- IB (2,4), Vedanta(1,2), Korba-
3,Katapali (1,2) Tarkera(1,2), Raigarh
VAL (CPP in Orissa VAL is a captive power plant having Under frequency 48.5Hz
system) generation of 9 x 135 MW and Rate of fall of frequency
connected to the grid at 220 kV level 1.2 Hz/Sec 0.2 Sec
via 220 kV VAL-Budhipadar D/C line. delay.
It has a facility to island itself from grid Under frequency 48.0
in case of any sever disturbance in Hz 0.5 Sec delay.
grid

_________________________________________________________________________
Operating Procedures for Eastern Region Page 122 28-06-2013
ERLDC:POSOCO

Annexure :XX Scheduling Formats ( Broad guidelines for the Formats)

Form A:

1. DC Declaration by ISGS Thermal For Date:

Time Block Station 1 Ex(PP) DC MW Station 2 Ex(PP) DC MW Station N Ex(PP)DC MW


1
2
3
.
.
.
.
.
96

2. Technical Minimum Limit (MW) upto which station can be backed down
without restoring to oil support
3. Ramp up Rate MW/min or steps of load raising in avg MW
4. Ramp Down Rate MW/min steps of load lowering in Avg MW
5. Remarks : Unit under Maintenance/Overhauling/Other constarints

Form A for ISGS Hydro

C A P A C IT Y D E C L A R A T IO N (E X -B U S )

F R O M : S H IF T IN C H A R G E … … … … … . P O W E R S T A T IO IN TO : S C E , E R L D C , K O L K ATA

D E C L A R E D C A P A C IT Y (E X - B U S ) O F … … ... P O W E R
FO R D ATE
S T A T IO N
D ATE O F
M SG. NO. REV . N o.
IS S U E
T IM E
C A P A B IL IT Y E x- T IM E (h h :m m )
(A ) D E C L A R E D C A P A B IL IT Y U N IT N o s .
B U S (M W )
1 0 :0 0 T O 2 4 :0 0
(i) C a p a b ility a t 0 0 :0 0 H rs . o f n e x t d a y 2 0 :0 0 T O 2 4 :0 0
3 0 :0 0 T O 2 4 :0 0
U n its to g o u n d e r p la n n e d s h u td o w n d u rin g n e xt
(ii) day
N IL

U n its lik e ly to re tu rn fro m p la n n e d s h u td o w n d u rin g


(iii) n e xt d a y N IL

T IM E D U R A T IO N D E C L A R E D C A P A B IL IT Y O F E X B U S
(iv ) D e c la re d c a p a b ility b a s e d o n A -(i), (ii) & (iii) a b o v e (M W )
FROM TO
0 0 :0 0 2 4 :0 0 :0 0

(v ) SU G G ES TE D SC HED ULE

F ro m
To (h h :m m ) D C E x-b u s (M W )
(h h :m m )
0 0 :0 0 2 4 :0 0
E x- B us M W H
(v i) N H P C D AT A F O R TH E D AT E
A d ju s te d p ro p o s e d to b e m a d e in
A c tu a l E x- b u s (A ) (M W H ) s c h e d u le
D C (E ) (M W H ) REV NO MSG NO
(A -E ) (M W H )

( v ii) D e c la re d C a p a c ity ( T h e m a x im u m M W a v a ila b le fo r 3 h rs . o r m o re D u rin g p e a k in g ) MW


( v iii) M a xim u m a v a ila b le c a p a c ity o f E x- b u s u n d e r n o rm a l v o lta g e a n d fre q u e n c y MW
( ix ) C a p a c ity In d e x [(v ii) / (v iii)*1 0 0 ] %
(B ) R E S E R V O IR L E V E L A N D IN F L O W S S T A T U S
( i) R e s e rv o ir le v e l (C u rre n t) m tr.
( ii) A v e ra g e In flo w s o n p re v io u s d a y C um ecs
( iii) _ A n tic ip a te d a v e ra g e in flo w s fo r th e n e x t d a y C um ecs
( iv ) O v e rlo a d C a p a c ity
G e n e ra tio n T IM E (h h :m m )
T im e d u ra tio n fo r w h ic h m a x im u m g e n e ra tio n c a n b e s u s ta in e d a t a (M W )
(v ) s tre tc h (D e p e n d in g U p o n A n tic ip a te d in flo w )

( v i) M in im u m 'm u s t ru n ' g e n e ra tio n (if a n y ) a lo n g w ith tim e p e rio d

( v ii) A n y o th e r c o n s tra in ts
R E M A R K S :-

S H IF T IN C H A R G E

Form B

_________________________________________________________________________
Operating Procedures for Eastern Region Page 123 28-06-2013
ERLDC:POSOCO

Statement of Entitlement for beneficiaries

Constituent : For Date

Time Ex(PP) DC Declared by ISGSs Ex(PP) Entitlement from


Block Stn 1 Stn 2 . . Stn N Stn 1 Stn 2 . . Stn N
1
2
3

Time Block DC

96
Fig : in MW

Form C:

Statement of Requisitions from Beneficiaries For Date:

Time Ex(PP) Requisitions from ISGSs Bilaterals & PXs


Block Stn 1 Stn 2 . . Stn N Utility 1 Utility 2 . . Stn N
1
2
3

96
Figure in MW

Form D : Format for Schedule of drawal by Constituents For Date

Stn 1 Stn 2 . . Stn N LOSS DEBIT BILAT IEX PXI NET


EX-PP EX-PP EX-PP EX-PP EX-PP FOR TOTAL TOT. TOT. DRAWAL
Tm Pt. Blk ISGS SCHD.
WHEEL

1
2
.
.
.
.
.
.
96

_________________________________________________________________________
Operating Procedures for Eastern Region Page 124 28-06-2013
ERLDC:POSOCO

Format for Schedule of Ex PP Generation For Date:


AVL SCHD AVL SCHD AVL SCHD AVL SCHD AVL SCHD UnReq UnReq
StN1 Stn1 Stn2 Stn2 . . . . StnN StnN SurplusStn1 SurplusStnN
TmPt. Blk (Ex-PP) (Ex-PP) . . . . ( Ex-PP) (Ex-PP) ( Ex-Bhu) (Ex-Bhu) (Ex-PP) (Ex-PP)

1
2

96

_________________________________________________________________________
Operating Procedures for Eastern Region Page 125 28-06-2013
ERLDC:POSOCO

Annexure: XXI Meter Locations

_________________________________________________________________________
Operating Procedures for Eastern Region Page 126 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 127 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 128 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 129 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 130 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 131 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 132 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 133 28-06-2013
ERLDC:POSOCO

METER LOCATIONS IN CENTRAL SECTOR TRANSMISSION SYSTEM


PART-I
CU05 CU06 CU 07 CU 08
RG 01 RG02 RG03
TALA
SINGHIGAON CU 03 CU02 CU 01
RANGIT
RG06 RG 04 RG 09 RG10 RG11

RG 07 BT34
BT38 BT37 BT36 BT35 BT33
RAMAM RG08 EM02 GANGTOK
BT 39 BT40
EM01 EM 03 EM 05 ER 44
BIR.(W)
EM 04 EM 06
ER 46 ER 41 ER 40 ER 39
ER 47
BIRPARA
ER 22 ER 43 ER 42 SALAKATI
66 kV SM04 SM03
TS01 TS01 TS03 1 1
MELLI
NE 85 BONGAIGAON
NE 86

ER 37
EM 7 EM 7 EM 10 EM 9

BINAGURI ER 23
BINAGURI
TEESTA

NJP (WBSEB)
ER50
SILIGURI ER 51

ER76

NR ER52 ER 53 ER54

NBU
EM26 EM25 EM27 EM28 ER 33
PURNEA
MUZAFFARPUR EM23 EM24
EM29
EM30 ER 09 / 4153A

ER 65 ER 64
389A 415A

ER 63 ER 62
KANTI (BS) ER 49
411A
415A DALKHOLA
PUR(B)

BALIA
SARNATH
SASARAM (N) MALDA(W)
ALLAHABAD
DEHRI ER 78
ER 58 ER 59
KARMANASA SASARAM (E)
ER 79
ER 61 ER 60
ER 83 ER 82
SAHUPURI
ER 56
ER 14 ER 13 ER 88
DEHRI ER 55
ER 90/2375A ER 89/2374A BSF MALDA
ARRAH ER 02
ER 03 ER 01

ER 9 ER 10
BI 14 BI 13 B’SHARIFF(BSEB)
KHAGAUL
ARRAH DUMRAO
KH 35 KH 36 KH 31 KH 32 KH 12 KH 11 KAHALGAON KAHALGAON(B)

KH 10 KH 09 KH 07 KH 15 KH 16
FATUA KH 08
KH 19
EM 56
KG 03 KG 02 KG 01 KH 01 KH 02 KH 03 KH04 KH 14
KH 13
KH 17 KH 18
EM 55 EM 54 KH 05 KH 06

EM 57 EM 53 PATNA
NR 01 LALMATIA
BALIA
SABOUR BS 09
NR 02
MAITHON FARAKKA

_________________________________________________________________________
Operating Procedures for Eastern Region Page 134 28-06-2013
ERLDC:POSOCO

PART-II
KAHALGAON
MALDA
MPL RB FK14
HATIA CHANDIL 559A

EM 44 EM 45 FK 08 FK17 FARAKKA
FK 09 FK12 FK 13
EM 43 FK 11 FK 10 FK 16 TIE
FK15
KAHALGAON TRA
RANCHI EM 42
FK 06 FK 07 FK 18
EM 46 EM 41 FK 05
FK 01 FK 02 FK 03 FK 04

EM-82 EM-83
MAITHON
ER 15 ER16 ER69 ER70 ER 68
DURGAPUR
B’NAGAR(WB)
ER 11 ER 12 EM 80 EM 81 ER 66 ER 67
MEJIA

ER 06 ER 07
ER 05
K’SWARI
PARULIA BIDHAN’NGR

WB 08/397A

JEERAT WB 09
JAMSHEDPUR
ER 08

ER18
ER 17
BS 06 BS1 05
EM 17 WB 09/471A
KOLAGHAT
EM 15 EM 16
RAIGARH WB 10/476A
EM 18
RAMCHANDAR PUR
EM 19
SUBHASGRAM

ER 81 ER 80 ER 26 ER 25 ROURKELA
ER 71
SUBHASGRAM
ER 72
ER 27 BARIPADA

EM 69
ER 24 ER 23

BALASORE(GR)
TARKERA RENGALI(G)
ER 30 ER 31 BARIPADA(GR)

RAIRANGPUR(GR
ER 73 ER 74/556A ER 28 / 600A / 1000
BALASORE(GR)
ER29 RENGALI
469A

RENGALI PS

TL05 TL06 TL07 TL08

TL 27 TL 28 TL 03
ER 86 TL 04
INDRAVATI PG TL 10 TL 09 TTPS
INDRAVATI PG TL 02 TL 01 TL 13 TL 11 TL 12 TALCHER STPP

ER 36 JEYPORE
TL 38

ER75
ER 85 ER 84 MERAMUNDALI 400 KV
ER77 220 KV
ER 34 ER 35
GAJUWAKA(S)
132 KV
DC-3 SR

DC-4 SR
GAJUWAKA(E)

JEYNAGAR

_________________________________________________________________________
Operating Procedures for Eastern Region Page 135 28-06-2013
ERLDC:POSOCO

Annexure :XXII Grid Maps

_________________________________________________________________________
Operating Procedures for Eastern Region Page 136 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 137 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 138 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 139 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 140 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 141 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 142 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 143 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 144 28-06-2013
ERLDC:POSOCO

Annexure :XXIII Schedule Of Transmission Assets Of Eastern Regional Grid


(in compliance with clause 4.8 of IEGC)
LINES
SL LINE OWNED BY CONNECTED SYSTEMS LENGTH COND. VOLTS NO.OF
NO END-1 END-2 (KM) (TYPE) (KV) CKTS.
1 GAYA-PUSAULI-FATEHPUR POWERGRID POWERGRID POWERGRID 482 QD. BERSIMIS 765 1
1 PUSAULI-FATEHPUR POWERGRID POWERGRID POWERGRID 356 QD. BERSIMIS 765 1
2 FARAKKA-BEHRAMPUR POWERGRID POWERGRID POWERGRID 110 TW.MOOSE 400 1
3 BEHRAMPUR-JEERAT POWERGID POWERGRID WBSETCL 200 TW.MOOSE 400 1
4 FARAKKA-SAGARDIGHI POWERGRID NTPC WBPDCL 67 TW.MOOSE 400 1
5 SAGARDIGHI-SUBHASGRAM POWERGRID WBPDCL POWERGRID 256.3 TW.MOOSE 400 1
6 JEERAT-SUBHASGRAM POWERGRID WBSETCL POWERGRID 80 TW.MOOSE 400 1
7 JEYPORE-ANGUL-BOLANGIR-MERAMUNDAL POWERGRID POWERGRID(ER) OPTCL 516 TW.MOOSE 400 1
8 TSTPP-MERAMUNDALI POWERGRID NTPC OPTCL 51 TW.MOOSE 400 2
9 JEYPORE - INDRAVATI POWERGRID POWERGRID POWERGRID 72 TW. MOOSE 400 1
10 INDRAVATI - RENGALI POWERGRID POWERGRID POWERGRID 356 TW. MOOSE 400 1
11 FARAKKA - KAHALGAON POWERGRID NTPC NTPC 95 TW. MOOSE 400 4
12 PARULIA - JAMSHEDPUR POWERGRID POWERGRID POWERGRID 177 TW. MOOSE 400 1
13 MAITHON - JAMSHEDPUR POWERGRID POWERGRID POWERGRID 153 TW. MOOSE 400 1
14 MAITHON - DSTPS POWERGRID POWERGRID DVC 97 TW. MOOSE 400 1
15 DSTPS - MEJIA-B POWERGRID DVC DVC 32 TW. MOOSE 400 1
16 MEJIA-B - JAMSHEDPUR POWERGRID DVC POWERGRID 168 TW. MOOSE 400 1
17 MAITHON - KAHALGAON POWERGRID POWERGRID NTPC 172 TW. MOOSE 400 2
18 MAITHON - RANCHI POWERGRID POWERGRID POWERGRID 200 TW. MOOSE 400 2
19 FARAKKA - MALDA POWERGRID NTPC POWERGRID 40 TW. MOOSE 400 2
20 KAHALGAON BIHARSARIFF I & II POWERGRID NTPC POWERGRID 201 TW. MOOSE 400 2
21 KAHALGAON- BANKA-BIHARSARIFF I & II POWERGRID NTPC POWERGRID 232 TW. MOOSE 400 2
22 KAHALGAON -BRAH POWERGRID NTPC NTPC 217 QD. MOOSE 400 2
23 BARH -PATNA POWERGRID NTPC POWERGRID 94 QD. MOOSE 400 4
24 TSTPP - ROURKELA POWERGRID NTPC POWERGRID 171 TW. MOOSE 400 2
25 FARAKKA - PARULIA POWERGRID NTPC POWERGRID 150 TW. MOOSE 400 1
26 TSTPP - RENGALI POWERGRID NTPC POWERGRID 24 TW. MOOSE 400 2
27 JAMSHEDPUR - ROURKELA POWERGRID POWERGRID POWERGRID 174 TW. MOOSE 400 2
28 RANCHI - ROURKELA POWERGRID POWERGRID POWERGRID 145 TW. MOOSE 400 2
29 MALDA - PURNEA POWERGRID POWERGRID POWERGRID 167 TW. MOOSE 400 2
30 PURNEA - BINAGURI I & II POWERGRID POWERGRID POWERGRID 168 TW. MOOSE 400 2
31 PURNEA - BINAGURI III & IV POWERGRID POWERGRID POWERGRID 160 QD. MOOSE 400 2
32 PURNEA - MUZAFFARPUR POWERLINKS POWERGRID POWERGRID 240 QD. MOOSE 400 2
33 BIHARSHARIFF-MUZAFFARPUR POWERGRID POWERGRID POWERGRID 130 TW. MOOSE 400 2
34 BIHARSHARIFF- PUSAULI POWERGRID POWERGRID POWERGRID 195 TW. MOOSE 400 2
35 BIHARSHARIFF- PUSAULI -III POWERGRID POWERGRID POWERGRID 198 QD. MOOSE 400 1
36 BIHARSHARIFF- GAYA POWERGRID POWERGRID POWERGRID 189 QD. MOOSE & QD. BERSIMIS 400 1
37 PUSAULI - BALIA POWERGRID POWERGRID POWERGRID 257 QD. MOOSE & QD. BERSIMIS 400 1
38 MAITHON-PARULIA POWERGRID POWERGRID POWERGRID 73 TW. MOOSE 400 2
39 TALA - BINAGURI I & II (Indian part) POWERGRID THEP POWERGRID 115 TW. MOOSE 400 2
40 TALA - BINAGURI IV (Indian part) POWERGRID THEP POWERGRID 98 TW. MOOSE 400 1
41 MALBASE-BINAGURI (Indian part) POWERGRID BPC POWERGRID 125.1 TW. MOOSE 400 1
42 BINAGURI-BONGAIGAON POWERGRID POWERGRID(ER) POWERGRID(NER) 216 TW.MOOSE 400 2
43 JEYPORE-GAZUWAKA POWERGRID POWERGRID(ER) POWERGRID(SR) 220 TW.MOOSE 400 2
44 MUZZFARPUR-GORAKHPUR POWERLINKS POWERGRID(ER) POWERGRID(NR) 261 QUAD-MOOSE 400 2
45 PATNA-BALIA POWERGRID POWERGRID(ER) POWERGRID(NR) 195 QUAD-MOOSE 400 4
46 BIHARSHARIFF-BALIA POWERGRID POWERGRID(ER) POWERGRID(NR) 242 QUAD-MOOSE 400 2
47 BARH-BALIA POWERGRID NTPC POWERGRID(NR) 244 QUAD-MOOSE 400 4
48 ROURKELA-RAIGARH POWERGRID POWERGRID(ER) POWERGRID(WR) 212 TW.MOOSE 400 2
49 TEESTA-V - BINAGURI POWERGRID NHPC POWERGRID 115 TW. MOOSE 400 2
50 MAITHON -MAITHON RIGHT BANK POWERGRID POWERGRID MPL 30 TW. MOOSE 400 2
51 MENDASAL-BARIPADA OPTCL OPTCL POWERGRID 273 TW. MOOSE 400 2
52 ARRAHA-KAHAGAUL POWERGRID POWERGRID BSPHCL 50 ZEBRA 220 2
53 FARAKKA-LALMATIA POWERGRID NTPC JSEB 79 ZEBRA 220 1
54 BINAGURI-NJP POWERGRID POWERGRID WBSETCL 0.2 ZEBRA 220 2
55 BIRPARA- CHUKHA (Indian part) POWERGRID POWERGRID POWERGRID 76 ZEBRA 220 2
56 BIRPARA-MALBASE (Indian part) POWERGRID POWERGRID POWERGRID 40 ZEBRA 220 1
57 BIRPARA-SALAKATI POWERGRID POWERGRID(ER) POWERGRID(NER) 160 ZEBRA 220 2
58 DALKHOLA-PURNEA POWERGRID POWERGRID POWERGRID 41 ZEBRA 220 2
59 BIRPARA-BINAGURI POWERGRID POWERGRID POWERGRID 80 ZEBRA 220 2
60 NJP-BINAGURI POWERGRID POWERGRID POWERGRID 6 ZEBRA 220 2
61 NJP-DALKHOLA POWERGRID POWERGRID POWERGRID 119 ZEBRA 220 2
62 DALKHOLA-MALDA POWERGRID POWERGRID POWERGRID 116 ZEBRA 220 2
63 SASARAM-ARRAH POWERGRID POWERGRID POWERGRID 112 ZEBRA 220 2
64 MUZZFARPUR-KANTI POWERLINKS POWERGRID BSPHCL 22 ZEBRA 220 2
65 PUSUALI-SAHUPURI BSPHCL & UPPCL POWERGRID UPPCL 72 ZEBRA 220 1
66 BUDHIPADAR-RAIGARH POWERGRID OPTCL CHATTISGARH 81 ZEBRA 220 1
67 GAYA-BODHGAYA POWERGRID POWERGRID BSPHCL 16 ZEBRA 220 2
68 GAYA-DEHRI POWERGRID POWERGRID BSPHCL 96 ZEBRA 220 2
69 KAHALGAON-KAHALGAON POWERGRID BSPHCL NTPC 2 PANTHER 132 1
70 DEHRI--PUSUALI POWERGRID BSPHCL POWERGRID 63 PANTHER 132 1
71 KARMANASA--PUSUALI POWERGRID BSPHCL POWERGRID 29 PANTHER 132 1
72 RANGIT-RAMMAM POWERGRID NHPC WBSETCL 27 PANTHER 132 1
73 KAHALGAON-SABOUR POWERGRID NTPC BSPHCL 37 PANTHER 132 1
74 KAHALGAON-LALMATIA POWERGRID NTPC JSEB 34 PANTHER 132 1
75 RANGIT - MELLI POWERGRID NHPC SIKKIM 37 LARK 66 1
75 GANGTAOK-CHJACHEN POWERGRID POWERGRID CHUJACHEN 49.5 PANTHER 132 1
77 CHUJACHEN- MELLI POWERGRID CHJACHEN SIKKIM 63.6 PANTHER 132 1
78 NJP-MELLI POWERGRID POWERGRID SIKKIM 90 PANTHER 132 1

_________________________________________________________________________
Operating Procedures for Eastern Region Page 145 28-06-2013
ERLDC:POSOCO

TRANSFORMERS
LOCATION VOLTAGE RATIO CAPACITY (MVA) OWNERSHIP
GAYA 765/400 3X1500 POWERGRID
GAYA 400/220 1X315 + 1X500 POWERGRID
JAMSHEDPUR 400/220 2X315 POWERGRID
FARAKKA 400/220 1X315 POWERGRID
PARULIA 400/220 2X315 POWERGRID
MALDA 400/220 2X315 POWERGRID
BIHARSHARIF 400/220 3X315 POWERGRID
JEYPORE 400/220 2X315 POWERGRID
RENGALI 400/220 2X315 POWERGRID
KAHALGAON 400/132 2X200 NTPC
MAITHON 400/220 2X315 POWERGRID
ROURKELA 400/220 2X315 POWERGRID
SASARAM 400/220 2X315 POWERGRID
SASARAM 765/400 1X1500 POWERGRID
TSTPP 400/220 2X315 NTPC
BINAGURI 400/220 2X315 POWERGRID
NEW PURNEA 400/220 2X315 POWERGRID
MUZAFFARPUR 400/220 2X315 POWERGRID
BARIPADA 400/220 2X315 POWERGRID
INDRAVATI ICT-I 400/220 1X315 OHPC
INDRAVATI ICT-II 400/220 1X315 POWERGRID
SUBHASGRAM 400/220 4X315 POWERGRID
PATNA 400/220 2X315 POWERGRID
BANKA 400/132 2X200 POWERGRID
KEONJHAR 400/220 1X315 POWERGRID
BOLANGIR 400/220 2X315 POWERGRID
RANCHI 400/220 2X315 POWERGRID
TALCHER HVDC CONV. XMER 400/(210/√3)/210 6X(397/198.5/198.5) POWERGRID
SSRM HVDC CONV. XFER (EAST) 400/(93/√3)/93 3X(234/117/117) POWERGRID
SSRM HVDC CONV. XFER (NORTH) 400/(93/√3)/93 3X(234/117/117) POWERGRID
BIRPARA 220/132 1x160+1x100 POWERGRID
NJP 220/132 1X100+1X160 POWERGRID
PURNEA 220/132 3X100 POWERGRID
MALDA 220/132 2X160 +1X50 POWERGRID
BARIPADA 220/132 2X160 POWERGRID
ARRAHA 220/132 2X100 POWERGRID
GANGTOK 132/66 2X50 POWERGRID
KHAGAUL 220/132 2X100 BSPHCL
SIPARA 220/132 2X160 BSPHCL
PATRATU 220/132 2X150 JSEB
TISCO 400/132 2X315 DVC
BOKARO 220/132 2X150 DVC
CHANDRAPURA 220/132 2x100+2x150 DVC
WARIA 220/132 2X150 DVC
UIHEP 400/220 1x315 OHPC
MERAMUNDALI 400/220 2X315 OPTCL
MENDHASAL 400/220 2X315 OPTCL
JODA 220/132 2X100 OPTCL
TALCHER 220/132 2X160 NTPC
BUDHIPADAR 220/132 2X160 OPTCL
KOLAGHAT TPS 400/220 2X315 WBPDCL
BAKRESWAR 400/220 2X315 WBPDCL
SAGARDIGHI 400/220 1X315 WBPDCL
JEERAT 400/220 4X315 WBSETCL
KHARGPUR 400/220 1X315 WBSETCL
DALKOHLA 220/132 2X160 WBSETCL
ARAMBAGH 400/220 4X315 WBSETCL
BIDHANNAGAR 400/220 2X315 WBSETCL
BARH 400/132 2X200 NTPC
KODERMA 400/220 2X315 DVC
KODERMA 220/132 2X160 DVC
SANTALDIH 220/132 1X100 WBPDCL

SERIES COMPENSATION ELEMENTS & HVDC CONVERTERS


REACTORS & HARMONIC FILTERS
1 FSC + TCSC AT PURNEA END OF 400KV PURNEA - MUZAFFARPUR I & II
2 FSC AT JEYPORE END OF 400KV MERAMUNDALI-JEYPORE LINE
3 FSC AT JEYPORE END OF 400KV JEYPORE - GAJUWAKA I& II
4 FSC AT RENGALI END OF 400KV RENGALI - INDRAVATI LINE
5 FSC AT RANCHI END OF 400 KV RANCHI-SIPAT I & II
5 500MW HVDC BACK-TO-BACK CONVERTER AT SASARAM

_________________________________________________________________________
Operating Procedures for Eastern Region Page 146 28-06-2013
ERLDC:POSOCO

REACTIVE COMPENSATION DETAILS


FOR 400 KV AND ABOVE LINES / SUB-STATIONS
SL LENGTH REACTORS CAPACITY
NO LINE/SUB-STN ( KM ) IN MVAR REMARKS
BUS LINE END
1 BEHRAMPUR-JEERAT 144 1X50 JEERAT
2 SAGARDIGHI-SUBASHGRAM 256.3 1X63 SAGARDIGHI
1X50 SUBHASGRM
3 FARAKKA-PARULIA-I 150 1X50 FARAKKA
4 BIDHANAGAR-PARULIA 11 1X50 PARULIA
5 K'GAON-B'SHARIFF-I 201 1X50 B'SHARIFF
6 K'GAON-B'SHARIFF-II 201 1X50 B'SHARIFF
7 K'GAON-MAITHON-I 172 1X50 MAITHON
8 K'GAON-MAITHON-II 172 1X50 MAITHON
9 JAMSHEDPUR-R'KELA-I 174 1X50 ROURKELA SWITCHABLE
10 JAMSHEDPUR-R'KELA-II 174 1x50 ROURKELA
11 ROURKELA-TALCHER I 175 1X50 TSTPP
12 ROURKELA-TALCHER II 175 1X50 TSTPP
13 KEONJHAR-BARIPADA 156 1X50 BARIPADA
14 BARIPADA-MENDASAL-I 273 1 X 63 MENDASAL
15 BARIPADA-MENDASAL-II 273 1 X 63 MENDASAL
1 X 63 BARIPADA
16 BAKRESWAR-ARAMBAGH 132 1X50 BAKRESWAR
17 BAKRESWAR-JEERAT 162 1X63 JEERAT
18 RENGALI-INDRAVATI(S/C) 356 1x50 RENGALI
1x50 INDRAVATI
19 B'SHARIFF-TENUGHAT(S/C) 180 1x50 TENUGHAT NOW AT 220 KV
20 MALDA-PURNEA D/C 167 2x63 MALDA
21 BINAGURI-BONGAIGAON-I 216 1X63 BONGAIGAON IN NER
22 BINAGURI-BONGAIGAON-III @ 224 1X80 BINAGURI SWITCHABLE
23 BINAGURI-BONGAIGAON-IV @ 224 1X80 BINAGURI SWITCHABLE
24 BINAGURI-TALA-I 115 1X63 BINAGURI
25 BINAGURI-TALA-II 115 1X63 BINAGURI
26 BINAGURI-TALA-IV 98 1X63 BINAGURI
27 PURNEA-BINAGURI-I 168 1x63 PURNEA
28 PURNEA-BINAGURI-III 160 1X63 PURNEA
28 PURNEA-MUZAFFARPUR-I 240 1x63 PURNEA SWITCHABLE
1x63 MZFRPR SWITCHABLE
27 PURNEA-MUZAFFARPUR-II 240 1x63 PURNEA SWITCHABLE
1x63 MZFRPR SWITCHABLE
28 ROURKELA-RAIGARH - I 212.4 1x63 ROURKELA
29 ROURKELA-STERLITE-I 113 1X63 ROURKELA
30 MERAMUNDALI-ANGUL 20.8 1x80 MERAMUNDALI
31 ANGUL-BOLANGIR 199 1x50 BOLANGIR
32 BOLANGIR-JEYPORE 288 1x50 BOLANGIR
1x80 JEYPORE
33 B'SHARIFF-PUSAULI D/C 195 2x63 PUSAULI SWITCHABLE
34 PUSAULI-ALLAHABAD 271 1X63 PUSAULI SWITCHABLE
35 PUSAULI-SARNATH 1X63 PUSAULI SWITCHABLE
36 MUZAFFARPUR-GRKPR-I 260 1X63 MUZAFFARPUR SWITCHABLE
37 MUZAFFARPUR-GRKPR-II 260 1X63 MUZAFFARPUR SWITCHABLE
38 B'SHARIFF-BALIA -I 242 1X50 BALIA IN NR
39 B'SHARIFF-BALIA -II 242 1X50 BALIA IN NR
40 BARH-PATNA-I 93 1X50 PATNA
41 BARH-PATNA-II 93 1X50 PATNA
RANCHI-SIPAT-I 405 1X80 RANCHI
42 RANCHI-SIPAT-II 405 1X80 RANCHI
43 JEYPORE-GAJUWAKA-I 220 1X80 GAJUWAKA IN SR (SWITCH)
44 JEYPORE-GAJUWAKA-II 220 1X80 GAJUWAKA IN SR (SWITCH)
43 MPL-RANCHI -I 188 1 X50 MPL
1 X50 RANCHI
44 MPL-RANCHI -II 188 1 X50 MPL
1 X50 RANCHI
45 PUSAULI-BIHARSHARIFF-III 198 1 X50 BIHARSARIFF
1 X50 PUSAULI
46 PUSAULI-BALIA 237 1 X50 PUSAULI LINE IS PART 400kV & PART 765 kV
47 BIHARSARIFF-GAYA 189 1 X50 BIHARSARIFF LINE IS PART 400kV & PART 765 kV
48 765 kV GAYA-PUSAULI-FATEHPUR 482 1 X 240 # GAYA 765 kV LINE
(145 & 337) 1 X 330 # PUSAULI MID POINT REACT OR
1 X 330 # FATEHPUR IN NR
49 765 kV PUSAULI-FATHEPUR 356 1 X 330 # PUSAULI 765 kV LINE
50 MAITHON-GAYA-I @ 235 1 X 50 GAYA SWITCHABLE
51 MAITHON-GAYA-II @ 235 1 X 50 GAYA SWITCHABLE
52 MAITHON-KODERMA-I 260 1 X 50 MAITHON SWITCHABLE
53 MAITHON-KODERMA-II 260 1 X 50 MAITHON SWITCHABLE
54 BANKA-BIHARSARIFF I & II 185 2 X 50 BANKA
55 BARIPADA-KEONJHAR 156 1 X 50 BARIPADA
56 BIHARSARIFF-PURNEA I @ 232 1 X 80 BIHARSARIFF SWITCHABLE
TOTAL 4692
# three single phase units, whose combined capacity is indicated
@ Only Reactors are commisioned without line

_________________________________________________________________________
Operating Procedures for Eastern Region Page 147 28-06-2013
ERLDC:POSOCO

REACTIVE COMPENSATION DETAILS


FOR 400 KV AND ABOVE LINES / SUB-STATIONS

57 FARAKKA 2X50
58 BIHARSHARIFF 1X50+1X80
59 KAHALGAON 2X50
60 BARH 1X80
61 MAITHON RIGHT BANK 2 X 50
62 MAITHON 1X50
63 JAMSHEDPUR 2X50
64 ROURKELA 1X50
65 BANKA 1X80
66 KEONJHAR 1X80
67 BOLANGIR 1X80
68 PURNEA 2X125
69 PARULIA 1X50
70 BINAGURI 2X125
71 MUZAFFARPUR 1X63
72 PATNA 1X80+1x125
73 GAYA 2 X125
70 765 kV GAYA 1 x 240 # 765 kV
71 PUSAULI 2 X 125
72 765 kV PUSAULI 1 x 330 # 765 kV
73 RANCHI 1X80+1x125 * TERTIARY
74 RENGALI 31.5* WINDING OF
75 JEYPORE 31.5* +1 x 63 400/220KV ICTs
76 BOLANGIR 1X80
77 ANGUL 1X125
78 JHARSUGUDA 1X125
79 BAKRESWAR 1X50
80 KHARAGPUR 1 X80
81 KODERMA 1X50
82 JEERAT 1X50
83 ARAMBAGH 1X50
84 RAGHUNATHPUR 2X50
TOTAL 3879
# three single phase units, whose combined capacity is indicated
@ Only Reactors are commisioned without line

Filters at Gazuwaka East Number


106 MVAR Doubled Damped Filter 1
106 MVAR 3rd Harmonic/Doubled Damped Filter 2
50 MVAR Bus Reactor 2
Filters at Talcher Number
Doubled Damped filter
120 MVAR (Switchable) 6
97 MVAR 3
66 MVAR Shunt Capacitor 1
72.6 MVAR Shunt Capacitor 2
Filters at Pusauli Number
112 MVAR at North Bus 4
112 MVAR at East Bus 4

_________________________________________________________________________
Operating Procedures for Eastern Region Page 148 28-06-2013
ERLDC:POSOCO

Annexure :XXIV Message for violation of TTC/Flow Gate/System Constraint.

Eastern Regional Load Despatch Centre


POWER SYSTEM OPERATION CORPORATION
14 Golf Club Road, Tollygunje, Kolkata 700033
Tel.: 033-24235435, FAX: 033-24235809 web:www.erldc.org

FAX MESSAGE

Reference: ERLDC/OPRN/SYSCON/_____ Date :_________ TOO :______

FROM: SCE , ERLDC, KOLKATA

TO: SCE : (concerned LDC / ISGS)

Copy To:

Sub: Immediate action for measures detailed below on violation of TTC/Flow Gate/System
constraint.

At present the UI of your control area/ISGS is as follows:


Regional entity / Schedule Actual Overdrawal/Overgeneration(+)/
Region Underdrawal/Undergeneration(-)

The following TTC limits are getting violated at present:

The following flow gate alarms have come:


Name of Flow Gate Name Actual Limit

The following lines are presently critically overloaded:


Name of the line Power Flow (MW)

<Action to be taken>

Remark:

SHIFT CHARGE ENGINEER


ERLDC/KOLKATA

_________________________________________________________________________
Operating Procedures for Eastern Region Page 149 28-06-2013
ERLDC:POSOCO

Annexure :XXV :- Format for Applying and Withdrawing congestion

_________________________________________________________________________
Operating Procedures for Eastern Region Page 150 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 151 28-06-2013
ERLDC:POSOCO

_________________________________________________________________________
Operating Procedures for Eastern Region Page 152 28-06-2013
ERLDC:POSOCO

List of Revisions:
Revision No Date of Revision Remarks
00 31.10.2008
01 08.12.2008 Annexure XXIV ( schedule of Regional
Transmission Assets) added at Page 118-
120
02 31.10.09 1) Chapters 1 to 7 and 9 revised in line with
the draft IEGC (under consideration by
CERC for implementation w.e.f
01.01.2010). All annexures updated &
Annex- XXV (Message format for violation
of TTC) added
2) Chapter 10 for Water Supply system
included
03 29.10.10 1) Chapters 1 ,2,3 and 6 revised in line with
new IEGC (implemented from 03.05.2010)
2) Chapters 7 and 8 are revised.

04 31.12.10 1) All the annexures updated.

05 31.03.2011 1) All the annexures updated.

06 20.05.2011 1) All the annexures updated.

07 29.05.2012 1) Chapter 6 flow gates are reviewed.


2) Chapter 7 scheduling and despatched
procedure revised.
3) All the annexures are updated
08 28.06.2013 1) Chapter 2 Frequency control is reviewed
2) Chapter 3 Voltage control is reviewed
3) Chapter 5 Switching coordination is
introduced
4) Chapter 7 flow gate are reviewed
5) Chapter on Water supply system at
ERLDC is deleted,
6) All annexures are revised

_________________________________________________________________________
Operating Procedures for Eastern Region Page 153 28-06-2013

You might also like