Model ESFR-17
16.8 K-factor Pendent Sprinkler
Early Suppression, Fast Response
General compared to ESFR Sprinklers having
a nominal K-factor of 14.0. This feature
Description offers flexibility when sizing system
piping, as well as possibly reducing or
TYCO Model ESFR-17 Pendent Sprin- eliminating the need for a system fire
klers are Early Suppression, Fast pump.
Response (ESFR) sprinklers having a Applications for the ESFR-17 Pendent
nominal K-factor of 16.8 (Ref. Figures Sprinklers are expanding beyond cur-
1 and 2). They are suppression mode rently recognized installation stan-
sprinklers that are especially advanta- dards. For information on research fire
geous as a means of eliminating in-rack tests, such as flammable liquids and
sprinklers when protecting high-piled aerosols, that may be acceptable to
storage. an authority having jurisdiction, contact
Model ESFR-17 Pendent Sprinklers are Technical Services.
primarily used for ceiling-only sprinkler
protection of, but not limited to, the fol- WARNING
lowing storage applications: Orange protector must not be removed
• most encapsulated or non-encap- until sprinkler is to be placed in service.
sulated common materials including
cartoned, unexpanded plastics
The W-Type 35 sprinkler wrench must
be used for proper installation of the Sprinkler
• cartoned, expanded plastics
sprinkler. Failure to do so may result in
equipment damage or failure. Identification
• uncartoned, unexpanded plastics
NOTICE
Number (SIN)
• uncartoned, expanded plastics
The Model ESFR-17 Pendent Sprinklers Refer to Table A for sprinkler identifica-
• some storage arrangements of described herein must be installed and tion number.
rubber tires, roll paper, and aerosols maintained in compliance with this
For more specific criteria, refer to Table
B in this technical data sheet as well as
document, as well as with the appli-
cable standards of the National Fire
Technical
the applicable design standard. Protection Association (NFPA), in addi-
tion to the standards of any authorities
Data
The Model ESFR-17 Pendent Sprin- having jurisdiction, such as FM Global. Approvals
klers provide the system designer Failure to do so may impair the perfor- UL and C-UL Listed
with hydraulic and sprinkler place- mance of these devices. FM Approved
ment options not presently available
to traditional ESFR Sprinklers having The owner is responsible for main- Finish
taining their fire protection system Natural Brass
a nominal K-factor of 14.0. In particu-
lar, Model ESFR-17 Pendent Sprinklers and devices in proper operating con- Physical Characteristics
are designed to operate at substan- dition. Contact the installing contrac- Frame ���������������������������������������������������������Brass
tor or product manufacturer with any Deflector ���������������������������������������������������Bronze
tially lower-end head pressures, as Compression Screw �������������������� Stainless Steel
questions. Hook ��������������������������������������������������������MONEL
IMPORTANT In all cases, the appropriate NFPA or Strut ���������������������������������������������������������MONEL
Refer to Technical Data Sheet FM Global installation standard, or Link Assembly ��������������������������������Solder, Nickel
TFP2300 for warnings pertaining to Button. . . . . . . . . . . . . . . . . . . . Phosphor Bronze
other applicable standard, must be ref- Sealing Assembly. . Beryllium Nickel w/TEFLON
regulatory and health information. erenced to ensure applicability and to
Always refer to Technical Data obtain complete installation guidelines. Additional Technical Data
Sheet TFP700 for the “INSTALLER The general guidelines in this technical Refer to Table A for additional techni-
WARNING” that provides cautions data sheet are not intended to provide cal data.
with respect to handling and instal- complete installation criteria.
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 4 AUGUST 2018 TFP317


TFP317
Page 2 of 4

Components: 1
1 - Frame
2 - Deflector * 7 3/4" **
3 - Compression Screw NPT
4 - Hook 8 1-1/2"
5 - Strut (38,1 mm)
6 1/2"
6 - Link Assembly 2-3/8"
(12,7 mm)
7 - Button (60,3 mm)
4 NOMINAL
8 - Sealing Assembly MAKE-IN
* Temperature rating is indicated 5
on Deflector. THERMAL WRENCH
3 SENSING FLATS
** ISO 7-R 3/4 pipe thread can be
ELEMENT
provided on special request.
2*
FIGURE 1
MODEL ESFR-17 PENDENT SPRINKLER, 16.8K, 165°F (74°C)
EARLY SUPPRESSION, FAST RESPONSE

Components: 1
1 - Frame
2 - Deflector * 7 3/4" **
3 - Compression Screw NPT
4 - Hook 8 1-1/2"
5 - Strut (38,1 mm)
6 1/2"
6 - Link Assembly 2-3/8"
(12,7 mm)
7 - Button (60,3 mm)
4 NOMINAL
8 - Sealing Assembly MAKE-IN
* Temperature rating is indicated 5
on Deflector. THERMAL WRENCH
3 SENSING FLATS
** ISO 7-R 3/4 pipe thread can be
ELEMENT
provided on special request.
2*
FIGURE 2
MODEL ESFR-17 PENDENT SPRINKLER, 16.8K, 212°F (100°C)
EARLY SUPPRESSION, FAST RESPONSE

Operation Item Description

Sprinkler Identification Number (SIN) TY7223


The fusible link assembly is com-
prised of two link halves that are joined K Factor, (gpm/psi½) (lpm/bar ½) 16.8 gpm/psi½ (241,9 lpm/bar½)
together by a thin layer of solder. When
the rated temperature is reached, the 165ºF (74ºC)
solder melts and the two link halves Temperature Rating ºF (ºC) 212ºF (100ºC)
separate, activating the sprinkler and
flowing water. Thread Size 3/4 in. NPT or ISO 7-R 3/4

Design Sprinkler Orientation Pendent

Criteria
Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)

TABLE A
The following general guidelines pro- MODEL ESFR-17 PENDENT SPRINKLER
vided for the TYCO Model ESFR-17 TECHNICAL DATA
Pendent Sprinklers can be used for a
quick reference. In all cases, the appropriate NFPA or • TFP312
The National Fire Protection Associa- FM Global installation standard must Model ESFR-25 (TY9226)
tion (NFPA) and FM Global (FM Approv- be referenced to ensure applicabil- K=25.2 Pendent Sprinkler
als) provide installation standards that ity and to obtain complete installa- • TFP313
must be used to properly design an tion guidelines. The following general Model ESFR-22 (TY8226)
automatic sprinkler system utilizing guidelines are not intended to provide K=22.4 Pendnet Sprinkler
Early Suppression, Fast Response complete installation criteria.
(ESFR) Sprinklers. The guidelines pro- • TFP315
In addition to this technical data sheet, Model ESFR-17 (TY7226)
vided by NFPA and FM Global may the following data sheets describe
differ. Consequently, the appropri- K=16.8 Pendent Sprinkler
other TYCO ESFR Sprinklers:
ate standard must be used for a given • TFP316
installation. Refer to Table B for addi- Model ESFR-17 (TY7126)
tional information. K=16.8 Upright Sprinkler
TFP317
Page 3 of 4

Storage Type NFPA FM Global

Sprinkler Type ESFR Storage

Response Type QR QR

System Type Wet Wet

165ºF (74ºC) 165ºF (74ºC)


Temperature Rating ºF (ºC) 212ºF (100ºC) 212ºF (100ºC)

Open Frame (i.e., no solid shelves) Single, Double, Multiple-


Row, or Portable Rack Storage of Class I-IV and Group A or Refer to NFPA 13 Refer to FM 2-0 and 8-9
B Plastics

Solid Pile or Palletized Storage of Class I-IV and Group A or Refer to NFPA 13 Refer to FM 2-0 and 8-9
B Plastics

Idle Pallet Storage Refer to NFPA 13 Refer to FM 2-0, 8-9, and 8-24

Rubber Tire Storage Refer to NFPA 13 Refer to FM 2-0 and 8-3

Roll Paper Storage Refer to NFPA 13 Refer to FM 8-21


(Refer to the Standard)

Flammable/Ignitable Liquid Storage Refer to NFPA 30 Refer to FM 7-29


(Refer to the Standard)

Aerosol Storage Refer to NFPA 30B Refer to FM 7-31


(Refer to the Standard)

Automotive Components in Portable Racks N/A N/A


(Control mode only; refer to the Standard)

N/A – Not Applicable


TABLE B
MODEL ESFR-17 PENDENT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW

• TFP318 Maximum Coverage Area FM Global 2-0


Model ESFR-1 (TY6226) 100 ft² (9,3 m²) Consult FM Global and/or FM Global
K=14.0 Pendent Sprinkler guidelines for allowable deflector-to-
In some cases, the installation stan-
ceiling distances as well as thermal
• TFP319 dards permit a greater coverage area.
sensing element-to-ceiling criteria.
Model ESFR-14 (TY6236)
Minimum Coverage Area
K=14.0 Pendent Sprinkler
64 ft² (5,8 m²) per NFPA 13
• TFP320
Model ESFR-17 (TY7229) Maximum Spacing
K=16.8 Pendent Sprinkler 12 ft (3,7 m) for building heights up to
30 ft (9,1 m)
Roof Construction
10 ft (3,1 m) for building heights greater
Unobstructed or obstructed construc-
than 30 ft (9,1 m)
tion, such as smooth ceiling, bar joists,
beam and girder. Minimum Spacing
Where the depths of the solid structural 8 ft (2,4 m)
members, such as beams and stem, Minimum Clearance to Commodity
exceed 12 in. (302 mm), install ESFR 36 in. (914 mm)
Sprinklers in each channel formed by
the structural members. NFPA 13
Deflector-to-Ceiling Distance
Ceiling Slope 6 in. to 14 in. (152 mm to 356 mm)
Maximum 2 in. rise for 12 in. run (16.7%)
TFP317
Page 4 of 4

"FITTING SIDE"
TOWARD
Step 3. After installation, inspect the
Link Assembly of each Model ESFR-17 Limited
LINK
SPRINKLER
FITTING
Sprinkler for damage. In particular,
verify that the Link Assembly and Hook Warranty
PROTECTOR are positioned as illustrated in Figures
For warranty terms and conditions, visit
1 and 2, and that the Link Assembly
www.tyco-fire.com.
is not bent, creased, or forced out of

Ordering
normal position in any way. Replace
damaged sprinklers.

WRENCH Care and Procedure


RECESS
Maintenance Contact your local distributor for avail-
ability. When placing an order, indicate
FIGURE 3 the full product name and part number
W-TYPE 35 TYCO Model ESFR-17 Early Suppres-
(P/N).
SPRINKLER WRENCH sion, Fast Response 16.8K Pendent
Sprinklers must be maintained and ser- Sprinkler Assemblies with
viced in accordance with this section. 3/4 NPT Thread Connection
Installation Before closing a fire protection system
main control valve for maintenance
Specify: Model ESFR-17 Early Sup-
pression, Fast Response 16.8K
TYCO Model ESFR-17 Early Suppres- work on the fire protection system Pendent Sprinklers (TY7223) with 3/4
sion, Fast Response 16.8K Pendent that it controls, obtain permission to NPT thread connection, (specify tem-
Sprinklers must be installed in accor- shut down the affected fire protection perature rating), with Natural Brass
dance with this section. system from the proper authorities finish, P/N (specify):
General Instructions and notify all personnel who may be 165°F (74°C) . . . . . . . . . . . . . . . . . . 58-457-1-165
affected by this action. 212°F (100°C) . . . . . . . . . . . . . . . . . 58-457-1-214
Avoid damage to the fusible Link
Assembly during installation by using Sprinklers which are found to be Special Order
only the Frame arms to handle the leaking or exhibiting visible signs of Sprinkler Assemblies with
sprinkler and by using the appropri- corrosion must be replaced. ISO 7-R 3/4 Thread Connection
ate sprinkler wrench. Do not apply Specify: Model ESFR-17 Early Suppres-
pressure to the fusible Link Assembly. Automatic sprinklers must never be sion, Fast Response 16.8K Pendent
Failure to do so can lead to an unstable painted, plated, coated, or other- Sprinklers (TY7223) with ISO 7-R 3/4
link assembly and premature activation wise altered after leaving the factory. thread connection, (specify tempera-
of the sprinkler. Damaged sprinklers Modified sprinklers must be replaced. ture rating), with Natural Brass finish,
must be replaced. Sprinklers that have been exposed to P/N (specify):
corrosive products of combustion, but
A leak-tight 3/4 in. NPT sprinkler joint have not operated, should be replaced 165°F (74°C) . . . . . . . . . . . . . . . . . 58-458-1-165
should be obtained by applying a min- if they cannot be completely cleaned 212°F (100°C) . . . . . . . . . . . . . . . . 58-458-1-214
imum-to-maximum torque of 10 to 20 by wiping the sprinkler with a cloth or Sprinkler Wrench
lb-ft (13,4 to 26,8 N∙m), or by hand- by brushing it with a soft bristle brush. Specify: W-Type 35 Sprinkler Wrench
tightening and applying an additional P/N 56-463-1-001
1-1/4 to 1-1/2 revolutions of the wrench. Care must be exercised to avoid
Higher levels of torque can distort the damage to the sprinklers before,
sprinkler inlet with consequent leakage during, and after installation. Sprin-
or impairment of the sprinkler. klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
WARNING be replaced. Also, replace any sprinkler
Orange protector must not be removed that has a cracked bulb or that has lost
until sprinkler is to be placed in service. liquid from its bulb. Refer to Installation
The W-Type 35 sprinkler wrench must section for additional information.
be used for proper installation of the The owner is responsible for the
sprinkler. Failure to do so may result in inspection, testing, and maintenance of
equipment damage or failure. their fire protection system and devices
Note: Install the Model ESFR-17 in compliance with this document, as
Pendent Sprinkler only in the pendent well as with the applicable standards
position (Ref. Figure 3). of the National Fire Protection Associ-
ation, such as NFPA 25, in addition to
Step 1. With pipe-thread sealant the standards of any authorities having
applied, hand-tighten the sprinkler into jurisdiction. Contact the installing con-
the sprinkler fitting. Do not apply pres- tractor or product manufacturer with
sure to the Link Assembly, and handle any questions.
the Model ESFR-17 Sprinkler only by
the Frame arms. Automatic sprinkler systems are rec-
ommended to be inspected, tested,
Step 2. Wrench-tighten the Model and maintained by a qualified Inspec-
ESFR-17 Sprinkler using only the tion Service in accordance with local
W-Type 35 Sprinkler Wrench (Ref. requirements and/or national codes.
Figure 3), and by fully engaging
(seating) the wrench on the sprinkler
wrench flats (Ref. Figures 1 and 2).
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
MONEL is a registered trademark of Special Metals Corporation;
TEFLON is a registered trademark of DuPont