www.tyco-fire.com
Contacts
Model ESFR-17
16.8 K-factor Pendent Sprinkler
Early Suppression, Fast Response
General compared to ESFR Sprinklers having
a nominal K-factor of 14.0. This feature
Description offers flexibility when sizing system
piping, as well as possibly reducing or
TYCO Model ESFR-17 Pendent Sprin- eliminating the need for a system fire
klers are Early Suppression, Fast pump.
Response (ESFR) sprinklers having a Applications for the ESFR-17 Pendent
nominal K-factor of 16.8 (Ref. Figures Sprinklers are expanding beyond cur-
1 and 2). They are suppression mode rently recognized installation stan-
sprinklers that are especially advanta- dards. For information on research fire
geous as a means of eliminating in-rack tests, such as flammable liquids and
sprinklers when protecting high-piled aerosols, that may be acceptable to
storage. an authority having jurisdiction, contact
Model ESFR-17 Pendent Sprinklers are Technical Services.
primarily used for ceiling-only sprinkler
protection of, but not limited to, the fol- WARNING
lowing storage applications: Orange protector must not be removed
• most encapsulated or non-encap- until sprinkler is to be placed in service.
sulated common materials including
cartoned, unexpanded plastics
The W-Type 35 sprinkler wrench must
be used for proper installation of the Sprinkler
• cartoned, expanded plastics
sprinkler. Failure to do so may result in
equipment damage or failure. Identification
• uncartoned, unexpanded plastics
NOTICE
Number (SIN)
• uncartoned, expanded plastics
The Model ESFR-17 Pendent Sprinklers Refer to Table A for sprinkler identifica-
• some storage arrangements of described herein must be installed and tion number.
rubber tires, roll paper, and aerosols maintained in compliance with this
For more specific criteria, refer to Table
B in this technical data sheet as well as
document, as well as with the appli-
cable standards of the National Fire
Technical
the applicable design standard. Protection Association (NFPA), in addi-
tion to the standards of any authorities
Data
The Model ESFR-17 Pendent Sprin- having jurisdiction, such as FM Global. Approvals
klers provide the system designer Failure to do so may impair the perfor- UL and C-UL Listed
with hydraulic and sprinkler place- mance of these devices. FM Approved
ment options not presently available
to traditional ESFR Sprinklers having The owner is responsible for main- Finish
taining their fire protection system Natural Brass
a nominal K-factor of 14.0. In particu-
lar, Model ESFR-17 Pendent Sprinklers and devices in proper operating con- Physical Characteristics
are designed to operate at substan- dition. Contact the installing contrac- Frame ���������������������������������������������������������Brass
tor or product manufacturer with any Deflector ���������������������������������������������������Bronze
tially lower-end head pressures, as Compression Screw �������������������� Stainless Steel
questions. Hook ��������������������������������������������������������MONEL
IMPORTANT In all cases, the appropriate NFPA or Strut ���������������������������������������������������������MONEL
Refer to Technical Data Sheet FM Global installation standard, or Link Assembly ��������������������������������Solder, Nickel
TFP2300 for warnings pertaining to Button. . . . . . . . . . . . . . . . . . . . Phosphor Bronze
other applicable standard, must be ref- Sealing Assembly. . Beryllium Nickel w/TEFLON
regulatory and health information. erenced to ensure applicability and to
Always refer to Technical Data obtain complete installation guidelines. Additional Technical Data
Sheet TFP700 for the “INSTALLER The general guidelines in this technical Refer to Table A for additional techni-
WARNING” that provides cautions data sheet are not intended to provide cal data.
with respect to handling and instal- complete installation criteria.
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Components: 1
1 - Frame
2 - Deflector * 7 3/4" **
3 - Compression Screw NPT
4 - Hook 8 1-1/2"
5 - Strut (38,1 mm)
6 1/2"
6 - Link Assembly 2-3/8"
(12,7 mm)
7 - Button (60,3 mm)
4 NOMINAL
8 - Sealing Assembly MAKE-IN
* Temperature rating is indicated 5
on Deflector. THERMAL WRENCH
3 SENSING FLATS
** ISO 7-R 3/4 pipe thread can be
ELEMENT
provided on special request.
2*
FIGURE 1
MODEL ESFR-17 PENDENT SPRINKLER, 16.8K, 165°F (74°C)
EARLY SUPPRESSION, FAST RESPONSE
Components: 1
1 - Frame
2 - Deflector * 7 3/4" **
3 - Compression Screw NPT
4 - Hook 8 1-1/2"
5 - Strut (38,1 mm)
6 1/2"
6 - Link Assembly 2-3/8"
(12,7 mm)
7 - Button (60,3 mm)
4 NOMINAL
8 - Sealing Assembly MAKE-IN
* Temperature rating is indicated 5
on Deflector. THERMAL WRENCH
3 SENSING FLATS
** ISO 7-R 3/4 pipe thread can be
ELEMENT
provided on special request.
2*
FIGURE 2
MODEL ESFR-17 PENDENT SPRINKLER, 16.8K, 212°F (100°C)
EARLY SUPPRESSION, FAST RESPONSE
Criteria
Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
TABLE A
The following general guidelines pro- MODEL ESFR-17 PENDENT SPRINKLER
vided for the TYCO Model ESFR-17 TECHNICAL DATA
Pendent Sprinklers can be used for a
quick reference. In all cases, the appropriate NFPA or • TFP312
The National Fire Protection Associa- FM Global installation standard must Model ESFR-25 (TY9226)
tion (NFPA) and FM Global (FM Approv- be referenced to ensure applicabil- K=25.2 Pendent Sprinkler
als) provide installation standards that ity and to obtain complete installa- • TFP313
must be used to properly design an tion guidelines. The following general Model ESFR-22 (TY8226)
automatic sprinkler system utilizing guidelines are not intended to provide K=22.4 Pendnet Sprinkler
Early Suppression, Fast Response complete installation criteria.
(ESFR) Sprinklers. The guidelines pro- • TFP315
In addition to this technical data sheet, Model ESFR-17 (TY7226)
vided by NFPA and FM Global may the following data sheets describe
differ. Consequently, the appropri- K=16.8 Pendent Sprinkler
other TYCO ESFR Sprinklers:
ate standard must be used for a given • TFP316
installation. Refer to Table B for addi- Model ESFR-17 (TY7126)
tional information. K=16.8 Upright Sprinkler
TFP317
Page 3 of 4
Response Type QR QR
Solid Pile or Palletized Storage of Class I-IV and Group A or Refer to NFPA 13 Refer to FM 2-0 and 8-9
B Plastics
Idle Pallet Storage Refer to NFPA 13 Refer to FM 2-0, 8-9, and 8-24
"FITTING SIDE"
TOWARD
Step 3. After installation, inspect the
Link Assembly of each Model ESFR-17 Limited
LINK
SPRINKLER
FITTING
Sprinkler for damage. In particular,
verify that the Link Assembly and Hook Warranty
PROTECTOR are positioned as illustrated in Figures
For warranty terms and conditions, visit
1 and 2, and that the Link Assembly
www.tyco-fire.com.
is not bent, creased, or forced out of
Ordering
normal position in any way. Replace
damaged sprinklers.