You are on page 1of 5

Doc.

ID: ECS-FL-2022-00
ULTRASONIC LIQUID FLOW
Report No.:31/2022
MEASUREMENT REPORT
Date:20-November-2022
Page: 1 of 5

Ultrasonic liquid flow and


Temperature measurement

Out-Let Line for Chiller

19, Street 32, Second Neighboring, First District, New Damietta, Egypt
Tel. +02-01033316590, Fax. +20-057-2433065
E-Mail: info@ecspdm.com
Doc. ID: ECS-FL-2022-00
ULTRASONIC LIQUID FLOW
Report No.:31/2022
MEASUREMENT REPORT
Date:20-November-2022
Page: 2 of 5

Table of content:

1-Cover Page
2-Flow measurement principle
3-Flow and Temperature measurement result
4-Summary

19, Street 32, Second Neighboring, First District, New Damietta, Egypt
Tel. +02-01033316590, Fax. +20-057-2433065
E-Mail: info@ecspdm.com
Doc. ID: ECS-FL-2022-00
ULTRASONIC LIQUID FLOW
Report No.:31/2022
MEASUREMENT REPORT
Date:20-November-2022
Page: 3 of 5

Transit time difference principle:


In order to measure the flow of a fluid in a pipe, ultrasonic signals are used, employing the transit time
difference. Ultrasonic signals are emitted by a transducer installed on the pipe and received by a second
transducer. These signals are emitted alternately in the flow direction and against it. As the fluid in which
the signals propagate is flowing, the transit time of the ultrasonic signals in the flow direction is shorter
than against the flow direction. The transit time difference, t, is measured and allows the flow meter to
determine the average flow velocity along the propagation path of the ultrasonic signals. A flow profile
correction is then performed in order to obtain the area averaged flow velocity, which is proportional to
the volumetric flow rate. Two integrated microprocessors control the entire measuring process. This allows
the flow meter to remove disturbance signals, and to check each received ultrasonic wave for its validity
which reduces noise.

19, Street 32, Second Neighboring, First District, New Damietta, Egypt
Tel. +02-01033316590, Fax. +20-057-2433065
E-Mail: info@ecspdm.com
Doc. ID: ECS-FL-2022-00
ULTRASONIC LIQUID FLOW
Report No.:31/2022
MEASUREMENT REPORT
Date:20-November-2022
Page: 4 of 5

Flow and Temperature measurement result:

Flow Measurement

No. Equipment tag Pipe specification Vel. Flow Q


Number

Cr =870 mm
Out-Let Line for
1 2.7 m/s 540 m³/h
P-1034E
Thickness =7.5 mm

Temperature measurement

No. Equipment tag Temp


Number

1 In-Let 21.7

2 Out-Let 19.2

19, Street 32, Second Neighboring, First District, New Damietta, Egypt
Tel. +02-01033316590, Fax. +20-057-2433065
E-Mail: info@ecspdm.com
Doc. ID: ECS-FL-2022-00
ULTRASONIC LIQUID FLOW
Report No.:31/2022
MEASUREMENT REPORT
Date:20-November-2022
Page: 5 of 5

Summary:
Many process steps in the manufacturing and power plants require the application of control the flow of
fluids inside the system. Portable ultrasonic flow meter is the ideal measuring instrument for monitoring
the liquids flow required for the necessary output. Their (clamp-on) ultrasonic transducers are simply
mounted on the outside of the respective pipe with nearly no effort.

A plant operator can thus accurately and reliably test if the minimum values for the required flows are met
the requirements or not.

Flow measurement allows operators to know that the right fluid is in the right place, at the right time.

19, Street 32, Second Neighboring, First District, New Damietta, Egypt
Tel. +02-01033316590, Fax. +20-057-2433065
E-Mail: info@ecspdm.com

You might also like