Low voltage product<1.2kV Medium voltage product 1.2kV~10kV High voltage product >10kV
Electrical CB Product classification
Disconnector/Earthing Switch
Total 6 gas-chamber. 2
The pressure in gas-chamber for
CB will be higher than other gas-
chambers
1
3
Red insulator means gas 5 4 6 Green (or Yellow) insulator means gas
isolated connected
GIS introduction
Rated pressure (filling pressure): the pressure with enough insulation and arc-quenching capability.
Alarm pressure: inform the user that the device was in low pressure status, which need to do the
maintenance and gas re-filling.
Locking pressure: the lowest working pressure, to lock the CB in the current ON/OFF position or to
automatically switch-off.
SF6 gas properties
Atomic weight 146, about five times the air Greenhouse effect, equivalent to 22,000 times the
CO2
11
Failure Statistics
Global Statistics of SF6 Equipment Failures
12
Source: TSO EU 2014
SF6 Gas Density Monitor
Basic knowledge
Formula:
p = F/A
Density vs. Pressure
Density is constant, but relative pressure can change due to temperature and ambient pressure
effects
Gas Tank
à A pressure indicator will show the correct pressure, but will fluctuate although there is no
leakage
à For plant safety the amount of SF6 gas inside the compartment is important, not the actual
pressure
17 [ 19.02.21 ]
Basic knowledge
0,6-60 bar 60-5000 bar 10 mbar-40 bar 2,5 mbar-0,6 bar 2,5 mbar-0,6 bar
Mechanical pressure measurement
Pointer
Bourdon tube gauge
The movement of a bourdon tube gauge Bourdon tube
contains a single edge fixed, elastic
End of tube
bourdon tube. This deforms in proportion
to the upcoming pressure. The force
Pull rod
F=p*A results from the definition of
pressure p=F/A.
Dial Toothed segment
Pressure
Mechanical pressure measurement
Typ 516.41
SF6 Density Monitor Principle
> 20 °C
T
< 20 °C 20°C 60°C
displacement
of bourdon tube Bimetal
< 20 °C indication
pCAL = pTANK
Displacement
equivalent to
> 20 °C
-1,042 bar
T
20°C 60°C
Bimetal
p
Indication
WIKA - WEgrid Solutions
T
20°C 60°C
Principle of the bimetal
26 [ 19.02.21 ]
Summary
1. SF6 Merupakan satu satunya pemadam busur api dan isolasi
di peralatan switching
27 [ 19.02.21 ]
Contoh permasalahan Gas Density Meter
Problem:
Dial GDM tidak dapat terbaca
Solusi WIKA:
Permasalahan:
Tidak terdapat port pengisian di breaker,
Resiko:
- Sealing pada filling port akan cepat usang karena sering dicopot
dan terekspos pada humidity
Contoh permasalahan Gas Density Meter
Valve on / off
Filling port
Contoh permasalahan Gas Density Meter
Permasalahan:
Gas Density Meter terpasang
terlalu tinggi, lebih dari 2
meter. Sehingga menyulitkan
monitoring.
Resiko:
Proses monitoring menjadi
terhambat, sehingga salah satu
parameter penting di PMT tidak
dapat termonitor dengan baik.
Contoh permasalahan Gas Density Meter
Customized
Capilary
Contoh permasalahan Gas Density Meter
Contoh permasalahan Gas Density Meter
Permasalahan:
Ditemukan kebocoran pada Gas
Density Meter
Resiko:
Permasalahan:
1x10^-5mbar·l/s
hermetically sealed case.
Contoh permasalahan Gas Density Meter
Permasalahan:
Resiko:
Salah pembacaan level pressure dan dapat
berakibat salah filling pressure yg dapat
merusak rupture disk (relieve valve)
Contoh permasalahan Gas Density Meter
Permasalahan:
Resiko:
Permasalahan:
Resiko:
Permasalahan:
Resiko: