You are on page 1of 2

GP 12-45s (12V45Ah)

GP12-45 is a general purpose battery with 10 years floating design


life, meet with IEC, JIS .BS and Eurobat standard. With heavy duty
grid, thickness plates, special additives, GP series battery have
long and reliable standby service life. Our GP Series batteries keep
high consistent for better performance in series usage.
S pe c ific a tio n
C e lls P e r U n it 6
Vo lta g e P e r U n i t 12
C a pa c i ty 45Ah@10hr-rate to 1.75V per cell @25 oC
W eight Approx. 14.0 Kg
Ma x . D i s c h a r g e C u r r e n t 450A (5 sec)
In te r n a l R e s i s ta n c e Approx. 15 mΩ
o o
O pe r a ti n g Te m pe r a tu r e R a n g e Discharge: -20 C ~60 C
Charge: 0 oC~50 oC
o o
Storage: -20 C~60 C

N o r m a l O pe r a tin g T e m pe r a tu r e R a n g e 25 oC±5 oC
F lo a t c h a r g in g V o lta g e 13.6 to 13.8 VDC/unit Average at 25 oC
R e c o m m e n d e d M a x im u m C h a r g in g 13.5 A
C u r r e n t L im it
E q u a liz a tio n a n d C y c le S e r v ic e 14.6 to 14.8 VDC/unit Average at 25 oC
S e lf D i s c h a r g e GETPOWER batteries can be stored for more than 6
months at 25 oC. Self-discharge ratio less than 3% per
month at 25 oC. Please charge batteries before using.
Te r m in a l Terminal F4/F11
C o n ta in e r M a te r ia l A.B.S. (UL94-HB), Flammability resistance of UL94-V1
can be available upon request.

D im e n s io n s
U n it: m m Dimension: 198(L)×166(W)×171(H)

C o n s ta n t C u r r e n t D is c h a r g e C h a r a c te r is tic s : A ( 25 o C )

F. V /T i m e 5 MI N 1 0 MI N 1 5 MI N 3 0 MI N 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR


9.60V 1 5 7 .2 5 1 1 5 .7 8 8 4 .2 4 0 5 1 .7 50 2 9 .2 50 16. 339 11. 745 9. 7200 7. 9560 5. 5898 4 .7 2 6 3 2 .4 9 9 5
10.0V 1 5 2 .7 0 1 1 0 .1 6 8 2 .5 1 2 5 0 .8 95 2 9 .1 15 16. 216 11. 700 9. 6750 7. 9092 5. 5444 4 .6 8 0 9 2 .4 5 4 1
10.2V 1 4 8 .1 8 1 0 6 .2 7 8 1 .2 1 6 5 0 .4 45 2 8 .8 45 16. 093 11. 610 9. 6300 7. 8624 5. 4989 4 .6 3 5 4 2 .4 0 8 6
10.5V 1 3 3 .0 6 9 8 .0 6 4 7 7 .3 2 8 4 9 .1 85 2 8 .5 75 15. 971 11. 565 9. 5400 7. 7688 5. 4535 4 .5 9 0 0 2 .3 6 3 2
10.8V 1 2 0 .1 0 8 9 .4 2 4 7 1 .2 8 0 4 7 .0 25 2 7 .9 00 15. 684 11. 250 9. 3150 7. 6284 5. 3626 4 .5 4 4 6 2 .3 1 7 7
11 . 1 V 1 0 4 .5 4 7 9 .9 2 0 6 3 .9 3 6 4 4 .0 55 2 6 .5 05 14. 988 10. 755 8. 8650 7. 3008 5. 1353 4 .4 0 8 2 2 .1 8 1 4

C o n s ta n t P o we r D is c h a r g e C h a r a c te r is tic s : W ( 25 o C )
F. V /T i m e 5 MI N 1 0 MI N 1 5 MI N 3 0 MI N 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
9.60V 164 9.2 1 231.1 9 06.47 554. 81 334. 53 187. 96 135. 54 112. 32 92. 102 64. 864 5 3.145 28.071
10.0V 160 5.1 1 175.9 8 87.64 547. 88 332. 91 187. 22 135. 27 112. 05 91. 541 64. 592 5 2.600 27.799
10.2V 155 6.8 1 136.7 8 75.59 541. 47 330. 48 185. 50 134. 46 111. 51 91. 260 64. 046 5 2.327 27.526
10.5V 140 1.9 1 050.4 8 34.91 529. 16 327. 24 183. 78 133. 65 110. 70 90. 418 63. 501 5 1.782 27.254
10.8V 126 1.0 9 53.68 7 67.11 505. 05 319. 14 181. 08 130. 41 107. 73 89. 014 62. 139 5 1.237 26.981
11 . 1 V 108 8.5 8 46.96 6 85.00 473. 24 302. 40 172. 73 123. 93 102. 60 84. 521 59. 958 4 9.602 25.891

2018 GetPower inc.


GP 12-45s 12V45Ah

S to r a g e c h a r a c te r is tic

15 100 Supplementary charge required


(Carry out supplementary charge
0℃
before use if 100% capacity is
12 80 requires)

Capacity (%)
10℃ Supplementary charge
Life E xpectancy (years)

60 requiredbefore use.This
9 supplementary charge will help to
20℃ recover the capacity and should
be made as early as possible.
40 40℃ 30℃
6
Supplementary charge may
oftenfail to recover the capacity.The
20 battery should never be left
3 standing till this state is reached

0 Supplementary charge and storage


0 2 4 6 8 10 12 14 16 18 20 22 24 guidelines
0 10 20 30 40 50 Storage Time (months)
Battery Temperature (℃)

15 7.5 5.0 120 0.24


Chcrge Volume 13 6.5 4.3

14 7.0 4.7 100 0.20


Chcrge Voltage
Terminal Voltage (V)

12 6.0 4.0
Charge Voltage(V)

Charge Volume (%)

Charge Current (CA)

13 6.5 4.3 80 0.16


① Discharge
100%(0.05CA×20h) 11 5.5 3.7
12 6.0 4.0 50%(0.05CA×10h) 60 0.12 0.05C
② Charge
0.16C 0.093C
Chcrge Voltage2.275V/C 0.35C
Charge Current0.1CA 10 5.0 3.3 0.62C
11 5.5 3.7 40 0.08
③ Temperature 25℃
3C 1C
10 5.0 3.3 20 0.04 9 4.5 3.0
Charge Current

0.6 1.2 3 6 12 30 1 2 5 10 20 24
9 4.5 3.0 0 0
0 2 4 6 8 10 12 14 16 18 20 24 28 min Hr

Charge Time(h) Discharge Time

C apac ity F ac tors Wi th Different T emperature


B atter y Type -20℃ -10℃ 0℃ 5℃ 10℃ 20℃ 25℃ 30℃ 40℃ 45℃
GEL 6V&12V 50% 70% 83% 85% 90% 98% 100% 102% 104% 105%
Battery 2V 60% 75% 85% 88% 92% 99% 100% 103% 105% 106%
AGM 6V&12V 46% 66% 76% 83% 90% 98% 100% 103% 107% 109%
Battery 2V 55% 70% 80% 85% 92% 99% 100% 104% 108% 110%

D is c h a r g e C u r r e n t V S . D is c h a r g e V o lta g e Ma in te n a n c e & C a u tio n s

Final Discharge Fl oa t S e rv ice :


1.75V 1.70V 1.60V
Voltage V/cell
※ Every month, recommend inspection every battery voltage.
Discharge (A)≥1.0C
(A)≤0.2C 0.2C<(A)<1.0C
Current (A)
※ Every three months, recommend equalization charge for one time.

Equalization charge method:


C h a r g e t h e b a tte r ie s a t l e a s t o n c e e v e r y s ix m o n th s ,
i f t h e y a r e s to r e d a t 2 5 o C . Discharge: 100% rate capacity discharge.

Charging Method: Charge: Max. current 0.3CA, constant voltage 2.4-2.45V/Cell charge 24h.

※ Effect of temperature on float charge voltage: -3mV/℃/Cell.


Constant Voltage -0.2Cx2h+2.4-2.45V/cellx24h,Max. Current 0.3CA
※ Length of service life will be directly affected by the number of discharge
Constant Current -0.2Cx2h+0.1CAx 12h
.
cycles, depth of discharge, ambient temperature and charging voltage.
Fast -0.2Cx2h+0.3CAx4.0h