Series Pressure Sensor

Instruction Sheet
Thank you very much for choosing Delta DPB series pressure sensor. Please read this instruction sheet carefully before using your DPB.
Keep this instruction sheet handy for quick reference.

 Warning
DANGER! CAUTION! ELECTRIC SHOCK!
DPB is a pressure measurement device. DO NOT use it out of its specification. Improper pressure or incorrect wiring may
cause series injuries on staff or damages on other devices.
1. Keep away from high-voltage and high-frequency environment during the installation in case of interference. Prevent using the device in
premises which contain:
(a) dust or corrosive gas; (b) high humidity and high radiation; (c) shock and vibration.
2. DPB can only be used for air pressure measurement and should avoid corrosive, inflammable or toxic gas measurement.
3. Make sure the power supply is switched off when installing or dismounting DPB and the pressure source stops its action in case harms
occur on human body and properties.
4. DO use parts compatible to the specification of the pressure pore for connection to avoid mistaken measurement or safety problems.
5. Before switching on the power supply, check the signal connection, e.g. the input voltage and polarity. Voltage that is too high may cause
damages on DPB.
6. DO use dry cloth and DO NOT use acid or alkaline liquid to clean the device.

 Product Profile & Outline

1
3 2
8
4 6
5 7 9

1. Pressure/parameter display 6. SET key


2. SV/setup item display 7. DOWN key
3. Pressure unit display 8. Power supply and output terminals
4. Digital output 1/2 indicator 9. Pressure input pore
5. UP key

 Contents in the pack: Pressure sensor, signal wire, instruction sheet


 Optional accessories: Panel mounting parts DPA-PFKit, metal mounting parts DPA-FMKit

-1-
 Ordering Information

Series name DPB: Delta DPB series pressure sensor

1 2 01: -100kPa ~ 100kPa


Measurable pressure range 10: -100kPa ~ 1,000kPa

N: NPN output
3 Output types
P: PNP output
P: Outer pore PT 1/8, inner pore M5
4 Pressure pore types N: Outer pore NPT 1/8, inner pore M5
G: Outer pore G 1/8, inner pore M5

 Electrical Specifications
Voltage range 12 ~ 24V DC +/- 10% no isolation
Power supply
Power consumption 40mA Max.
Pressure type Non-corrosive gas, gauge type
DPB01: -100kPa ~ 100kPa
Measurable range
DPB10: -100kPa ~ 1,000kPa
Pressure
DPB01: 200kPa
measurement Max. durable pressure
DPB10: 1,500kPa
Accuracy +/- 3% entire process
Temperature inaccuracy +/- 2% entire process
Setup display 2-line LCD display, 4 digits for measured value and 3.5 digits for setup display
Status display LCD output status display
Display
Display mode 3 colors for different modes
Cycle 100ms, 250ms, 500ms, 1,000ms
Number of outputs Built-in 2 NPN or PNP transistor digital outputs
NPN: Max. durable pressure 30V/100mA, residual voltage 1.5V
Transistor output
Output PNP: Max. durable pressure 30V/100mA, residual voltage 1.5V
Response time 2ms, 4ms, 10ms, 30ms, 50ms, 100ms, 250ms, 500ms, 1,000ms, 5,000ms
Output inaccuracy Linear inaccuracy: < +/- 2% entire process
P Outer pore PT 1/8, inner pore M5
Pore size N Outer pore NPT 1/8, inner pore M5
G Outer pore G 1/8, inner pore M5
Shock immunity 10 ~ 500Hz, 10mm 3 axes for 2 hours
2
Vibration immunity Max. 100m/ s 3 axes 6 directions, 3 times each
Ambient temperature 0°C ~ +50°C
Storage temperature -20°C ~ +65°C
Altitude < 2,000m
Ambient humidity 35% ~ 80% RH (non-condensing)

-2-
 How to Set up Parameters
 Switching modes: DPB will be in the “Measuring Mode” when it is switched on, displaying PV and SV. Press for more than 2 seconds
in this mode to switch to the “Quick Setup Mode”. Press for more than 4 seconds in the “measuring mode” to switch to “Advanced
Setup Mode”. Press in the “Quick Setup Mode” or “Advanced Setup Mode” to return to the “Measuring Mode”.

 Setting up parameters: In the three modes, press once to select the parameter to set up. When you find the parameter to be set up
or modify, use to modify the setting.

Switching on DPB

Press > 4 secs. Press > 4 secs.


Advance Setup Measuring Mode Quick Setup
Mode Mode
Press > 2 secs. Press > 4 secs.

 Quick Setup Mode:

 Advanced Setup Mode:

-3-
 Measuring Mode:

Quick Setup Mode Advanced Setup Mode Measuring Mode

Set up OUT1 mode Set up auxiliary display Set up upper limit of OUT1
(Change SV display method) (Set OUT1 to hysteresis mode / window
mode)

Press  Press  Press 

Set up OUT2 mode Set up displayed speed Set up lower limit of OUT1
(Set OUT1 to hysteresis mode / window
mode)

Press  Press  Press 

Set up N.O./N.C. of OUT1 and Set up hysteresis SV of OUT1


OUT2 (Set OUT1 to easy mode)

Press  Press  Press 

Set up output response time Set up switching color referencing Set up upper limit of OUT2
output items (Set OUT2 to hysteresis mode / window
mode)

Press  Press  Press 

Set up PV display color Set up code Set up lower limit of OUT2


(Set OUT2 to hysteresis mode / window
mode)

Press  Press  Press 

-4-
Quick Setup Mode Advanced Setup Mode Measuring Mode

Set up unit Return to default settings SV of OUT2


(Set OUT2 to easy mode)
Press  Return to “set up OUT1 mode” Press  Return to “set up auxiliary Press  Returning to output setting
display”

 Initial Setting
2
1. Units: DPB provides many units for users, including kPa, kgf/cm , bar, psi, mmHg and inchHg. In the easy mode, you can press and
find to set the unit to the desired one.
2. Output status: You can set up 2 output status in DPB, N.O. (normally open) and N.C. (normally closed). In the easy mode, you can press
and fine to set up the output status for OUT1 and OUT2.
3. Response time: Referring to the time required for the pressure to reach output status. For example, “50” refers to once the pressure has
reached the output status, it has to last for 50ms before the output starts to operate. In the easy mode, press and find .
Use to set up the response time.

 Output Mode Setting


There are 3 output modes in DPB: Easy, Hysteresis and Window

1. Easy Mode: Set up pressure P. When the pressure measured is bigger than (P + dP), the output will be ON. When the pressure measured
is smaller than P, the output will be OFF. (See Figure 1: Output in Easy Mode)

 In the “Measuring Mode”, press and find (OUT1) and (OUT2). Use to set up P value.

 In the “Advanced Setup Mode”, press and find . Use to set up “dP” value.

[Figure 1: Output in Easy Mode]

2. Hysteresis Mode: Set up pressure Hi/Lo. When the pressure measured is bigger than the Hi value, the output will be ON. When the
pressure measured is smaller than the Lo value, the output will be OFF. (See Figure 2: Output in Hysteresis Mode)

 In the “Measuring Mode”, press and find (OUT1 Hi), (OUT1 Lo), (OUT2 Hi) and (OUT2
Lo). Use to set up Hi/Lo values.

[Figure 2: Output in Hysteresis Mode]

3. Window Mode: Set up pressure Hi/Lo. When the pressure measured is bigger than Hi or smaller than Lo, the output will be OFF. When the
pressure measured is bigger than Lo and smaller than Hi, the output will be ON. (See Figure 3: Output in Window Mode)

-5-
 In the “Measuring Mode”, press and find (OUT1 Hi), (OUT1 Lo), (OUT2 Hi) and (OUT2
Lo). Use to set up Hi/Lo values.

 In the “Advanced Setup Mode”, press and find . Use to set up “dP” value.

[Figure 3: Output in Window Mode]

Note: Supposed the output is ON and the output status is set to N.O. (normally open), the output will then be off. If the output status is set
to N.C (normally closed), the output will then be on. Supposed the output is OFF and the output status is set to N.O., the output will then be on.
If the output status is set to N.C., the output will then be off.

 Zero Returning
In the "Measuring Mode”, press together, and you will see . The zero returning will start. Release the keys to end the zero
returning.

 Key Locking Function

 Lock On: Press and together for 2 seconds until is displayed. You will then see the display of pressure value (PV) and
set value (SV).

 Lock Off: Press and together for 2 seconds until is displayed. You will then see the display of pressure value (PV) and
set value (SV).

 Lock Display: Press any key in the key locking mode, and you will see the display of pressure value (PV) and (SV). Release the
key, and the PV and SV will return to original values.

 Switching Colors
In DPB, different output statuses can have different display colors. The output statuses for DPB are “OUT1”, “OUT2”, ”OUT1 and OUT2”,
“OUT1 or OUT2”. See below explanations for how to set:

1. Setting up output status: In the “Measuring Mode”, press for more than 4 seconds and release the key after you see . You
are now in the “Advanced Setup Mode”. Press for 4 times and find the switching color referencing items (see Advanced Setup Mode
chart). Use to select the referencing item you'd like.

2. Switching colors: In the “Measuring Mode”, press for more than 2 seconds to enter the “Quick Setup Mode”. Press for 4 times
and find the parameter for setting up colors (see Quick Setup Mode chart). Use to select the color you’d like.
Note: “OUT1 and OUT2” will be ON only when both OUT1 and OUT2 are ON; otherwise, it will be OFF. “OUT1 or OUT2” will be OFF only
when both OUT1 and OUT2 are OFF; otherwise, it will be ON.

 Code
DPB offers codes for the user to set up. In the “Measuring Mode”, press for more than 4 seconds and release the key after you see

. You are now in the “Advanced Setup Mode”. Press for 5 times to find the parameter to set up codes (see Advanced Setup Mode

chart). displays in turn.

-6-
See the meanings of codes in the table below:
st nd rd th
1 digit 2 digit 3 digit 4 digit
Code

OUT1 mode N.O./N.C. OUT2 mode N.O./N.C. Response time Color Referencing item for color
N.O. N.O. 2ms OUT1
Easy Easy
N.C. N.C. 4ms Red when OUT2
N.O. N.O. 10ms ON OUT1 and OUT2
Hysteresis Hysteresis
N.C. N.C. 30ms OUT1 or OUT2
N.O. N.O. 50ms OUT1
Window Window
N.C. N.C. 100ms Green OUT2
- - - - 250ms when ON OUT1 and OUT2
- - - - 500ms OUT1 or OUT2
- - - - 1,000ms OUT1
- - - - 5,000ms Red OUT2
- - - - - OUT1 and OUT2
- - - - - Red OUT1 or OUT2
- - - - - OUT1
- - - - - OUT2
Green
- - - - - OUT1 and OUT2
- - - - - OUT1 or OUT2

6th digit 7th digit 8th digit


Code

Pressure unit Speed Auxiliary display Hysteresis setting

kPa Standard 0
2
kgf/cm 100ms Off 1
bar Unit. 2
psi Standard. 3
mmHg 250ms Off 4
inchHg Unit 5
- Standard 6
- 500ms Off 7
- Unit 8
- Standard 9
- 1,000ms Off A
- Unit B

-7-
 How to Install  Dimension
 Panel: Use optional accessory DPA-PFKit.

 To install the fixing frame, you have to purchase the optional


accessory: DPA-FMKit.

 Internal Circuit
(NPN output) (PNP output)

 Terminals
1. Positive power supply input (brown)
2. Digital output 1 signal (black)
3. Digital output 2 signal (white)
4. None (orange)
5. Negative power supply input (blue)

 Error Message
/ : If the 1/2 output load current is large than 150 mA, please check the reason why the load current is too large.