Project: Tropical City Mall + Office

Comparison Between Water Cooled Chiller A/C System & Air Cooled Chiller system
Office Air Cooled Chiller System Water Cooled Chiller System
Office Air Cooled Chiller - 2 unit 300Tr running at 100% - 348kw x2 Mall Water Cooled Chiller - 2 unit 900Tr running at 100% - 504kw x2
CHWP 1 & 2 - 22kw x 2 Mall Water Cooled Chiller - 1 unit 500Tr running at 100% - 280kw x1
Total Chiller system kw - 740kw CHWP 1 & 2 - 90kw x 2 CHWP 3 - 55kw x 1
Total Chiller Tr - 600 TR CWP 1 & 2 - 55kw x 2 CWP 3 - 37kw x 1
Total system kw/Tr = 1.23 kw/tr Cooling tower - 11 kw x 10
Total Chiller system kw - 1780kw
Total Chiller Tr - 2300 TR
Total system kw/Tr = 0.77 kw/tr

Saving of the System kw/Tr per Hr = 1.23kw/tr - 0.77 kw/tr


= 0.46 kw/tr saving

Base on Total Office Cooling Cap. about 90% diversity factor = 0.9 X 600
540 Tr
Air Cooled Chiller System
system kw/tr x TR duty = 540TR x 1.23 kw/Tr
=664.2 kw
Water Cooled Chiller System
system kw/tr x TR duty = 540TR x 0.77 kw/Tr
=415.8 kw

saving of Duty kw = 248.4 kw

Base on 10 hr Operating/Day = 2484 kwh


assume offce working 52 week x 5 day = 260 day
Total annual kwh saving 645840 kwh
base on TNB tariff Rm. 0.365 per kwh = 645840 x 0.365
$ 235,731.60