Type Model

RPI-0.8FSNQL(H)
RPI-1.0FSNQL(H)
RPI-1.3FSNQL(H)
RPI-1.5FSNQL(H)
IN-THE-CEILING RPI-1.8FSNQL(H)
RPI-2.0FSNQL(H)
TYPE
RPI-2.3FSNQL(H)
RPI-2.5FSNQL(H)
RPI-3.0FSNQL(H)
RPI-3.3FSNQL(H)
RPI-4.0FSNQL(H)
RPI-5.0FSNQL(H)
RPI-6.0FSNQL(H)

P01068Q

ORIGINAL INSTRUCTIONS
HITACHI

HITACHI

HITACHI .
IMPORTANT NOTICE

Correct Disposal of this product


This marking indicates that this product should not be disposed with other
household wastes. To prevent possible harm to the environment or human
health from uncontrolled waste disposal, recycle it responsibly to promote the
sustainable reuse of material resources. To return your used device, please use
the return and collection systems or contact the retailer where the product was
purchased. They can take this product for environmental safe recycling.

HITACHI's
HITACHI's
3

3
4
4
4
4
4

Section2 Installation & Maintenance Manual

5
5

6
7
7

10

10
10

11
12

12
12
13
13
14
14
14
15
It is recommended that the room be ventilated
every 3 to 4 hours.

l The appliance is not to be used by children or


person with reduced physical, sensory or mental
capabilities,or lack of experience and knowledge,
unless they have been given supervision or
instruction concerning use of the appliance by a
person responsible for their safety.
l Children should be supervised that they do not
play with the appliance.
l The appliance should not be installed in the
laundry.

(HP)
0.8 1.0 1.3 1.5 1.8 2.0 2.3 2.5 3.0 3.3
IN-THE-CEILING
TYPE
4.0 5.0 6.0
Regarding the instructions of Wired Remote
Control Switch or Wireless Remote Control
Switch,read the operation manual attached
to the control switch.

3
4
R410A

5
2.5

6
(unit:mm)

7
(unit:mm)

0.8 ~1.5

1.8 ~2.5

3.0 ~4.0

5.0 ~6.0

8
Model Static Pressure(Pa)
RPI-0.8 ~1.5FSNQL , RPI-1.8 ~2.5FSNQL 30
RPI-3.0 ~4.0FSNQL , RPI-5.0 ~6.0FSNQL 60
RPI-0.8 ~1.5FSNQH , RPI-1.8 ~2.5FSNQH 50(*)/80
RPI-3.0 ~4.0FSNQH , RPI-5.0 ~6.0FSNQH 120(*)/90
* Before Shipment

9
10A
unit:mm(in.)

0.8 ~1.5
1.8 ~2.0
2.3 ~3.3
4.0 ~6.0

Flaring Dimension
Perform the flaring work as shown below.
unit:mm(in.)
+0
Diameter A -0.4
R410A R407C
6.35 9.1 9.0
9.53 13.2 13.0
12.7 16.6 16.2
15.88 19.7 19.4
19.05 (*) 23.3

(*)It is impossible to perform the flaring work with


1/2H material. In this case, use an accessory
pipe(with a flare).

An excess or a shortage of refrigerant is the


main cause of trouble to the units.
Charge the correct refrigerant quantity.

(unit:mm)

0.8 ~ 1.5
1.8 ~ 2.0
2.3 ~ 2.5
3.0 ~ 4.0
5.0 ~ 6.0

10
2

Drain Pump (Optional) (unit:mm)

Stan ar

11
± 6%

12
RPI-1.8 ~2.5FSNQL(H)
RPI-3.0 ~4.0FSNQL(H)
RPI-0.8 ~1.5FSNQL(H) RPI-5.0 ~6.0FSNQL(H)

Cord Clamp

220-240V~/50Hz
220V~/60Hz

RPI-0.8 ~1.5FSNQH
RPI-1.8 ~2.5FSNQH

RPI-3.0 ~4.0FSNQH
RPI-5.0 ~6.0FSNQH

13
Power Rated
Source EN 60335-1 EN 60335-1
Current 1 1
0.8 ~6.0 22 0-240V
0.8 ~6.0 ~/50Hz 5.0A 2.5mm2 0.75mm2
22 0V
~/60Hz

The wire sizes marked with *1 in the above table are selected
at the rated current of the unit according to the European
Standard, EN 60335-1.Use the wires which are not lighter than
the ordinary polyvinyl chloride sheathed flexible cord
(code designation H05VV-F).
3

Use an ELB (Electric Leakage Breaker).If not $FFRUGLQJWREN 60335-1


used ,it will cause an electric shock or a fire. &XUUHQW $ :LUH6L]H PP

Run through the cables using conduit tube,  


and Completely seal the end of conduit tube   
with sealing materials. 
 
  
  
  
  1
  
,QWKHFDVHWKDWFXUUHQWH[FHHGV$
GRQRWFRQQHFWFDEOHVLQVHULHV

14
Ex.) Set at No.5 Cycle
Setting Set by inserting DSW5
Position Slotted screwdriver
into the groove

Set All Pins OFF


Before shipment. DSW5 and RSW2 are set to "0".
RSW2
Max.64 cycles are available to set when all the equipment
to be connected are corresponding to Hi-NET.
Max.16 cycles when the units corresponding/
non-corresponding to Hi-NET are combined. Set at "5"

Ex.) Set at No.16 Unit


Setting Set by inserting DSW6
Position Slotted screwdriver
into the groove

Set No.1 Pin ON


Before shipment. DSW6 and RSW1 are set to "0".
RSW1
Max.64 units are available to set when all the equipment
to be connected are corresponding to H-LINK.
Max.16 units when the units corresponding/
non-corresponding to H-LINK are combined. Set at "6"

Capacity 0.8 1.0 1.3 1.5 1.8 2.0 2.3

Capacity 2.5 3.0 3.3 4.0 5.0 6.0

15
Qingdao Hisense Hitachi Air-conditioning Systems Co., Ltd.
Add. : 17,Donghai Xi Road,Qingdao 266071,P.R. China

P01068Q 2016.10 V00