VRF In-The-Ceiling Indoor

INSTALLATION MANUAL New Release FAN-1708 201602

INVERTER-DRIVEN
MULTI-SPLIT SYSTEM HEAT PUMP
AIR CONDITIONERS
JTDL022H0NN(B)0AQ JTDM022H0NN(B)0AQ
JTDL028H0NN(B)0AQ JTDM028H0NN(B)0AQ
JTDL036H0NN(B)0AQ JTDM036H0NN(B)0AQ
JTDL043H0NN(B)0AQ JTDM043H0NN(B)0AQ
JTDL050H0NN(B)0AQ JTDM050H0NN(B)0AQ
JTDL056H0NN(B)0AQ JTDM056H0NN(B)0AQ
JTDL063H0NN(B)0AQ JTDM063H0NN(B)0AQ
JTDL071H0NN(B)0AQ JTDM071H0NN(B)0AQ
JTDL084H0NN(B)0AQ JTDH084H0NN(B)0AQ
JTDL090H0NN(B)0AQ JTDH090H0NN(B)0AQ
JTDL112H0NN(B)0AQ JTDH112H0NN(B)0AQ
JTDL142H0NN(B)0AQ JTDH142H0NN(B)0AQ
JTDL160H0NN(B)0AQ JTDH160H0NN(B)0AQ

Issue Date:
5. Feb.2016
15. P00883Q

ORIGINAL INSTRUCTIONS
YORK

YORK

YORK .
IMPORTANT NOTICE

Correct Disposal of this product


This marking indicates that this product should not be disposed with other
household wastes. To prevent possible harm to the environment or human
health from uncontrolled waste disposal, recycle it responsibly to promote the
sustainable reuse of material resources. To return your used device, please use
the return and collection systems or contact the retailer where the product was
purchased. They can take this product for environmental safe recycling.

YORK's
YORK's
3

3
4
4
4
4
4

Section2 Installation & Maintenance Manual

5
5

6
7
7

10

10
10

11
12

12
12
13
13
14
14
14
15
l The appliance is not to be used by children or
person with reduced physical, sensory or mental
capabilities,or lack of experience and knowledge,
unless they have been given supervision or
instruction concerning use of the appliance by a
person responsible for their safety.
l Children should be supervised that they do not
play with the appliance.
l The appliance should not be installed in the
laundry.

(x100W)

IN-THE-CEILING
022 028 036 043 050 056 063 071 084 090

TYPE
112 142 160
Regarding the instructions of Wired Remote
Control Switch or Wireless Remote Control
Switch,read the operation manual attached
to the control switch.

3
4
R410A

5
2.5

6
(unit:mm)

7
(unit:mm)

022~04

050~071

084~112

142~160

8
Model Static Pressure(Pa)
JTDL022~071H0NN(B)0AQ 30
JTDL084~160H0NN(B)0AQ 60
JTDM022~071H0NN(B)0AQ 50(*)/80
JTDH084~160H0NN(B)0AQ 120(*)/90
* Before Shipment

9
10A
unit:mm(in.)

022~043
050~056
063~090
112~160

Flaring Dimension
Perform the flaring work as shown below.
unit:mm(in.)
+0
Diameter A -0.4
R410A R407C
6.35 9.1 9.0
9.53 13.2 13.0
12.7 16.6 16.2
15.88 19.7 19.4
19.05 (*) 23.3

(*)It is impossible to perform the flaring work with


1/2H material. In this case, use an accessory
pipe(with a flare).

An excess or a shortage of refrigerant is the


main cause of trouble to the units.
Charge the correct refrigerant quantity.

(unit:mm)

022~043
050~056
063~071
084~112
142~160

10
2

Drain Pump (Optional) (unit:mm)

Stan ar

11
± 6%

12
022~043 50~160

Cord Clamp

220-240V~/50Hz
220V~/60Hz

JTDM022~071H0NN(B)0AQ

JTDH084~160H0NN(B)0AQ

13
Power Rated
Source EN60 335-1 EN60 335-1
Current 1 1
0.8 ~6.0 22 0-240V
022 ~160 ~/50Hz 5.0A 2.5m m2 0.75mm2
22 0V
~/60Hz

The wire sizes marked with *1 in the above table are selected
at the rated current of the unit according to the European
Standard, EN60335-1.Use the wires which are not lighter than
the ordinary polyvinyl chloride sheathed flexible cord
(code designation H05VV-F).
3

Use an ELB (Electric Leakage Breaker).If not


Rated current Nominal cross-
used ,it will cause an electric shock or a fire. of appliance sectional area
v 88t
Run through the cables using conduit tube,
and Completely seal the end of conduit tube |b a  t#€
with sealing materials. }b  |~ a  t#€
}~  |a a  t#€
}a  |a~ a#€  ƒ
}a~  |t€ t#€  ~
}t€  |bt ƒ  a
}bt  |€ ~  a~
}€  |~b a  t€

14
Ex.) Set at No.5 Cycle
Setting Set by inserting DSW5
Position Slotted screwdriver
into the groove

Set All Pins OFF


Before shipment. DSW5 and RSW2 are set to "0".
RSW2
Max.64 cycles are available to set when all the equipment
to be connected are corresponding to Hi-NET.
Max.16 cycles when the units corresponding/
non-corresponding to Hi-NET are combined. Set at "5"

Ex.) Set at No.16 Unit


Setting Set by inserting DSW6
Position Slotted screwdriver
into the groove

Set No.1 Pin ON


Before shipment. DSW6 and RSW1 are set to "0".
RSW1
Max.64 units are available to set when all the equipment
to be connected are corresponding to H-LINK.
Max.16 units when the units corresponding/
non-corresponding to H-LINK are combined. Set at "6"

Capacity 022 028 036 043 050 056 063

Capacity 071 084 090 112 142 160

15
© 2015 Johnson Controls, Inc. WWW.johonsoncontrols.com FAN-1708 201602
Johnson Controls reserve the right change product features without notice.

P00883Q 2016.02 V00