Contents

1.GENERAL DESCRIPTION ..................................................................................................1


1.1 Basis and Scope of Design .............................................................................................1
1.3 The Parameters of main equipments ...........................................................................1
1.3.1 The Main Parameters of Generator ...........................................................................1
1.3.2 The Main Parameters Of Generator Transformer Are As Below: .......................2
1.3.3 The Main Parameters of Unit Auxiliary(UAT-11&21) & Standby
Transformer(UAT-12&22) Are as Below:.............................................................................2
1.3.4 The Main Parameters of generator circuit breaker................................................3
1.3.5 The Main Parameters of of PIB ...................................................................................3
2. HV ELECTRICAL CONNECTION ......................................................................................8
2.1 Electrical Single Line Diagram.......................................................................................9
2.2 GENERATOR OUTPUT SYSTEM ....................................................................................9
3.SHORT CIRCUIT CURRENT CALCULATION AND EQUIPMENT SELECTION ............ 11
3.1 Short Circuit Current Calculation................................................................................ 11
3.2 Equipment Selection ...................................................................................................... 11
4.MV-LV SINGLE LINE DIAGRAM AND EQUIPMENT SELECTION ................................. 11
4.1 General Description ........................................................................................................ 11
4.2 6.6kV Single Line Diagram ............................................................................................12
4.3 Capacity Calculation Of Unit Auxiliary Transformer And Standby Transformer
....................................................................................................................................................13
4.4 0.4kV PC/MCC And Distribution Panels ....................................................................13
4.6 Calculation Of Auxiliary System Voltage Level .......................................................14
4.7 Selection Of Auxiliary Equipment ...............................................................................15
5.ELECTRIC EQUIPMENT LAYOUT ...................................................................................16
5.1 Layout Of Generator Transformer, Unit Transformer And Standby Service
Transformer .............................................................................................................................16
5.2 6.6kV And 0.4kV Switchgear .........................................................................................16
5.3 Generator Output System And Excitation Equipment ...........................................17
6.LIGHTNING PROTECTION AND EARTHING ..................................................................17
6.1 Lightning Protection System........................................................................................17
6.2 Earthing..............................................................................................................................17
7.CABLING STRUCTURE ....................................................................................................18
8.CABLE FIRE PROOFING: ................................................................................................20
9.CABLE SELECTION .........................................................................................................20
10. VOLUME LIST ................................................................................................................21
1.GENERAL DESCRIPTION

1.1 Basis and Scope of Design

1.1.1Basis of Design

1.1.1.1 The Contract and it’s attachments signed between WUHAN KAIDI
ELECTRIC POWER ENGINEERING CO., LTD. and THANG LONG
THERMAL POWER JOINT STOCK COMPANY.

1.1.1.2 All minutes of meeting for electrical up to now.

1.1.2ScopeWork & Terminal Point

The scope of design includes all the electrical system of the Thanglong
plant.

The terminal point is at the gate-type gantry of the outgoing line.

1.3The Parameters of main equipments

1.3.1 The Main Parameters of Generator

Manufacturer Dongfang Electric Machinery Co., Ltd


Type QFSN-310-2-20
Rated output 310MW
Maximum continuous output 315MW
Rated terminal voltage 20kV
Rated power factor 0.85 (lagging) Rated
0.90 (leading)
Frequency 50Hz
Rated current 10528.2A
Rated field voltage 465.13V
Rated field current 2123.42A
Direct axis transient reactance 26.53%
(unsaturated)
Direct axis transient reactance 23.35%
(saturated)
Short circuit ratio ≥0.5
Efficiency ≥98.80%
Excitation system Static Excitation

1
Cooling system Stator coil:Water inner-cooled
Rotor coil:Hydrogen inner-cooled
Stator core:Hydrogen cooled
Bushing CT for generator 15000/5A
0.2S(60VA)/0.5(60VA)/5P20(60VA)/5P20(60VA)
0.2S(60VA)/0.2S(60VA)/5P20(60VA)/5P20(60VA)
CT for Excitation Tr. 150/1A
0.5(15VA)/0.5(15VA)/5P20(30VA)/5P20(30VA)

1.3.2 The Main ParametersOf Generator Transformer Are As Below:

Manufacturer Siemens Transformer (Guangzhou) Co., Ltd.


Type SFPZ-360000/500
Rated capacity 360MVA
Voltage ratio 500±8×1.25%/20kV
Voltage regulation on-load tap changing
Vector group YNd11
Impedance voltage 14.5%
Cooling system ONAN/ONAF/OFAF
Number of Phases Three (3)

1.3.3 The Main Parameters of Unit Auxiliary(UAT-11&21) & Standby


Transformer(UAT-12&22) Are as Below:

Manufacturer ABB ZHONGSHAN TRANSFORMER CO.LTD


Type SFFZ-63000/20
Rated capacity 63/35-35MVA
Voltage ratio 20±8x1.25%/6.8-6.8kV
Voltage regulation on-load tap changing
Vector group Dyn1yn1
Impedance voltage 21%
Cooling system ONAN/ONAF
Number of Phases Three (3)
CT
2500/1A,0.5 15VA
2500/1A,0.515VA
2500/1A,5P20 30VA
2500/1A,5P20 30VA
15000/1A,5P20 30VA
15000/1A,5P20 30VA

2
1.3.4 The Main Parameters of generator circuit breaker

Manufacturer ALSTOM GRID SAS


Type FKG1F
Nominal operating voltage 27.5kV
Frequency 50Hz
Rated continuous current 12000(50℃)
Rated Fault Level 120kA/2s
Interrupting current 120kA
CT 15000/1A, 5P20(30VA)
15000/1A, 5P20(30VA)
15000/5A, 5P20(60VA)
15000/5A, 5P20(60VA)

1.3.5The Main Parameters of of PIB

Jiangsu Daqo Enclosed Busbar Systems


Manufacturer
Co., Ltd.
Rated voltage 20kV
Maximum voltage 24kV
Rated current
Main conductor 11000A(after derating)
Branch conductor 4000A/2000A(after derating)
Frequency 50Hz
Insulation Levels Lightning Impulse 150 kV
Power Frequency 75 kV
dynamic stable current:
Main conductor 315kA
Branch conductor 630kA
Rated Fault Level
Main conductor 125kA/2s
Branch conductor 250kA/2s

1.3.6The Main Parameters of non-segregated phase bus duct

AC excitation N.P.B DC excitation N.P.B

Manufacturer Jiangsu Daqo Enclosed Busbar Systems Co., Ltd.

Rated voltage ≥1kV ≥1kV

Maximum voltage 3kV 3kV

Rated current 2600A 2200A

3
Frequency 50Hz /

Insulation Levels:

Lightning Impulse 8kV 8kV

Power Frequency 4.2kV 4.2kV

dynamic stable current: 125kA 125kA

Rated Fault Level 50/4s 50/4s

1.3.7The Main Parameters of of 500kV equipment

(a) Circuit breaker

Siemens High Voltage Circuit Breaker


Manufacturer
Co.Ltd.,Hangzhou

Nominal System Voltage 500kV

Highest System Voltage 550kV

Type 3AP2 FI

Current Ratings 5000A

Rated Fault Level 63kA/3s

dynamic stable current 160kA

Lightning Impulse Withstand Voltage


1800kV
(peak)

Power Frequency Withstand Voltage


740kV
(rms)

(b) Disconnector Switch

ABB High Voltage Switchgear


Manufacturer
Co.Ltd.,BeiJing

Nominal System Voltage 500kV

Highest System Voltage 550kV

VKSBIII-AM-550
Type
VKSBIII-2AM-550

4
Current Ratings 4000A

Rated Fault Level 63kA/3s

dynamic stable current 160kA

Lightning Impulse Withstand Voltage


1800kV
(peak)

Power Frequency Withstand Voltage


740kV
(rms)

(c) Current Transformer

Manufacturer Trench China, MWB (Shanghai) Co., Ltd

Nominal System Voltage 500kV

Highest System Voltage 550kV

Type IOSK 550

Type1:

600-1000-1200-2000/1A, 5P20(30VA)

600-1000-1200-2000/1A, 5P20(30VA)

600-1000-1200-2000/1A, 5P20(30VA)

600-1000-1200-2000/1A, 5P20(30VA)

600-1000-1200-2000/1A, 5P20(30VA)

600-1000-1200-2000/1A, 5P20(30VA)

600-1000-1200-2000/1A, 5P20(30VA)
Current Ratings
600-1000-1200-2000/1A, 0.5(15VA)

Type2:

600-1000-1200-2000/1A, 0.5(15VA)

600-1000-1200-2000/1A, 5P20(30VA)

600-1000-1200-2000/1A, 5P20(30VA)

600-1000-1200-2000/1A, 0.5(15VA)

Type3:

600-1000-1200-2000/1A, 0.2(10VA)

5
600-1000-1200-2000/1A, 0.5(15VA)

Details in F416S-D0101-02

Rated Fault Level 40kA/3s

dynamic stable current 100kA

Lightning Impulse Withstand Voltage


1800kV
(peak)

Power Frequency Withstand Voltage


710kV
(rms)

(d) Capacitor Voltage Transformer

Manufacturer Trench China MWB (Shanghai),Co.Ltd.

Nominal System Voltage 500kV

Highest System Voltage 550kV

Type TEMP-500IUHH

500 0.11 0.11


/ / /0.11kV
3 3 3

0.2(15VA)/0.5(15VA)/3P(50VA)

500 0.11 0.11 0.11 0.11


/ / / / kV
3 3 3 3 3

0.5(15VA)/3P(50VA) /3P(50VA) /3P(50VA)

Voltage Ratings

500 0.11 0.11


/ / kV
3 3 3

0.5(15VA)/3P(30VA)

500 0.11 0.11


/ / /0.11kV
3 3 3

0.5(15VA)/ 3P(50VA)/3P(50VA)

6
Lightning Impulse Withstand Voltage
1800kV
(peak)

Power Frequency Withstand Voltage


710kV
(rms)

(e) Surge Arrestor


Manufacturer Siemens Surge Arresters Ltd.

Rated Voltage 420/444kV


3EP6 420-4PF53-2 TZ 1-Z
Type
3EP6 444-4PF53-2 TZ 1-Z

Residual voltage 8/20s 10kA 926/979kV(peak)

Residual voltage 8/20s 20kA 1010/1050kV(peak)

1.3.8The Main Parameters of of dry type transformer

Manufacturer Sunten Electric Equipment Corp.,Ltd.

Type SCB10

Vector Relationship: Dyn11


Type: Cast Resin

Voltages: H V - 6.6 kV
L V – 0.42 V

Tap changer: Off-load


TappingRange: ± 5% in 2½% steps
Cooling: AN (Enclosed type)

Insulation Levels:
HV: Lightning impulse 70kV
Power Frequency 35 kV

LV: Power Frequency 3 kV

1.3.9 Specification of 6.6kV switchboard

Manufacturer ABB Xiamen Switchgear Co., Ltd.

Type UniGear ZS1


Voltage: 6.6 kV

7
Phases: 3
Frequency: 50 Hz
Rated Fault Level: 50kA/3s
Impulse Withstand Voltage: 75 k V peak

1.3.10 Specification of 0.4kV switchboard

Manufacturer Zhongshan Mingyang Electrical


Appliances Co.,Ltd.

Type MNSG
Voltage: 0.4 kV
Phases: 3
Frequency: 50 Hz
Rated Fault Level: 50kA/1s
Impulse Withstand Voltage: 8 kV peak

1.3.11Specification of diesel generator

Manufacturer Guangzhou WANON Electric & Machine


Co.,Ltd.

Type S825CC
Voltage: 0.4/0.23 kV
Capacity 600kW
Phases: 3
Frequency: 50 Hz

1.3.14 Specification of PT&MOA Cubicle


Manufacturer Jiangsu Daqo Enclosed Busbar Systems
Co., Ltd.

PT Type JDZJ-20

Rated Voltage: 20 kV

Voltage Ratings 20/ 3 /0.11/ 3 /0.11/ 3 /0.11/3kV


0.2(50VA) /3P(100VA)/3P (100VA)

20/ 3 /0.11/ 3 /0.11/ 3 /0.11/3kV


0.2(50VA) /3P(100VA)/3P (100VA)

20/ 3 /0.11/ 3 /0.11/ 3 /0.11/3kV


3P(100VA) /0.2(50VA)/3P (100VA)
Fuse RN4-20

8
M.O.A. Y5W1-25/56.2kV

capacitor 24kV 0.125uF

2.HV ELECTRICAL CONNECTION

2.1 Electrical Single Line Diagram

Two sets of 310MW unit are connected to 500kV switchyardthrough


generator-transformer(G-T) group, 500kV switchyard has a quadrangle
configuration.

500kV switchyard transmits power to the national power system, which


includes:

-one feeder to the Quang Ninh 500kV substation

- one feeder to the PHO NOI 500kV substation

HVequipments selectedwith a minimum creepage distance of 31mm/kV.

Surge arrestersare equipped at500kV substation out-going lineand near


the G.Ts in order to protect the HVequipment and the Generator
transformer.

The neutral point of generator transformer is earthed solidly.

One unit auxiliary transformer and one standby transformer are set up for
each 310MW unit, which obtain power source from the generator outlet
terminal.

There is a Generator circuit breaker for each unit.

2.2 GENERATOR OUTPUT SYSTEM

2.2.1 Phase Isolate Busbar (PIB)

The generator is connected to low voltage side of generator transformer


through a self-cooled, totally enclosed fully phase isolated metal clad bus
duct and branching to unit auxiliary(UAT-11,21)and standby
9
transformer(UAT-12,22).

There will be a micro-manometric pressure device.

2.2.2 Accessoriesof PIB

2.2.2.1 Potential transformer

Three (3) sets of PT in which three (3) sets with voltage ratio
20 0.11 0.11 0.11
/ / / kV are equipped for each generator .
3 3 3 3

2.2.2.2 Current transformers

In order to meet the requirements of measurement, protection, energy


metering and voltage regulation, the outlet side / neutral point side of
generator are 4/4 groups CT equipped respectively. The CTs are located
at the terminal bushing of generator.

2.2.2.3 Surge arresters

A lightning arrester and a surge capacitor are equipped at the outlet side
of each generator to prevent the generator stator winding from insulation
damage in the event that induced lightning over voltage impacts theHV
side of the generator transformer.

The surge capacitor: 24kV 0.125uF

2.2.2.4 Generator neutral point grounding equipment

The neutral point of the generator is earthed through a Neutral Earthing


transformer whose secondary winding current is restricted by a resistive
circuit.

(The single line diagram of electrical main connection refer to


Drawing No. 50-F416S-D0101-02)

10
3.SHORT CIRCUIT CURRENT CALCULATION AND EQUIPMENT
SELECTION

3.1 Short Circuit Current Calculation

The conclusions of the calculationsare shown in the below table:

LOCATION OF EARTH SUBTRANSIENT SHORT PEAK VALUE OF SHORT


FAULT CIRCUIT CURRENT(RMS) CIRCUIT CURRENT (kA)
(kA)
500kV BUSBAR 28.6 69.4
20kV(UAT branch) 148.6 404.2
20kV(main conductor 80.4 217.9
generator side)
20kV(main conductor 68.2 187.3
System side))
20kV(ET branch) 148.56 404.2
6.6kV SYSTEM 45.8 121.9
0.4kV SYSTEM(LV 39.9 93.1
tr<2500kVA)
0.4kV SYSTEM(LV tr 49.4 115.5
2500kVA)

The feedback current of 6.6kV motors has been included in the short
circuit current of 6.6kV side.

(For details refer to Drawing No. 50-F416S-D0101-03)

3.2 Equipment Selection

Refer to clause 1.3

(For details refer to Drawing No. 50-F416S-D0101-04)

4.MV-LV SINGLE LINE DIAGRAM AND EQUIPMENT SELECTION

4.1 General Description

The design of MV-LV single line diagram is based upon the Contract and
11
its attachments.

4.2 6.6kV Single Line Diagram

One 63/35-35MVAsplit-winding unitauxiliary transformer(UAT-11&21) is


arranged for each generator unit.

Two buses(A, B) unit sections of 6.6kV busbar are provided for each unit,
which is fed from corresponding generator output terminal through unit
auxiliary transformer. 6.6kV unit motors and LV Auxiliary transformers are
connected to 6.6kV unit section buses A and B separately(eg. Induce fan A
connects to 6.6kV unit section buses A and induce fan B connects to
6.6kV unit section buses B)

Two buses(A,B) Coal & station sections of 6.6kV busbar are provided for
two units, which are fed though 6.6kV unit section 1&2B. 6.6kV Coal &
station motors andstation LV auxiliary transformers are connected to
6.6kV Coal section A and B separately.

Normally, The 6.6kV Coal & station sectionA derives power from 6.6kV
unit section buses 1B, The 6.6kV Coal & station section B derives power
from 6.6kV unit section buses 2B.Onetie connection is provided between
6.6kV Coal & station sections A and B, so they can be fed from the
othersource at abnormal condition.

For the CWP HOUSE and the barge unloaders are far away from the main
plant area,in order to run and supervise the CWP and barge load easily in
local place.Two buses(A,B) CWP section of 6.6kV busbar are provided for
two units, whose work power are fed though the 6.6kV unit section 1A&2A.
6.6kV CWP motor, barge load and LV auxiliary transformers in couples are
connected to CWP 6.6kV section A and B separately.

Normally, The CWP 6.6kV section A derives power from 6.6kV unit section
buses 1A, The CWP6.6kV section B derives power from 6.6kV unit section
buses 2A. Onetie connect CB is provided between CWP 6.6kV sections
A,B so they can be fed from the other source at abnormal condition.

There is also One 63/35-35MVA split-winding standby transformer


12
(UAT-12&22)set for each generator unit. Standby Transformer(UAT-12&22)
is fed from corresponding generator output terminal and can stand by for
the other unit’s MV system.

(The key auxiliary single line diagram refer to Drawing No. 50-
F416S-D0501-02)

4.3 Capacity Calculation Of Unit Auxiliary Transformer And Standby


Transformer

The capacity of each unit auxiliary transformer and standby transformer is


63/35-35MVA to supply the complete auxiliaries of one unit ,6.6kV coal &
station section’s load which are fed by the corresponding bus section and
CWP 6.6kV section’s load which are fed by the corresponding bus section.

The impedance of each auxiliary and standby transformer is: Ud’1-2=21%

The Capacity calculation for unit auxiliary transformer and standby


transformer has considereda over 20% capacity margin.

(The calculation of capacity of these transformers are shown in


drawing of 50-F416S-D0501-03)

4.4 0.4kV PC/MCC And Distribution Panels

(The 0.4kV single diagram refers to Drawing NO.


50-F416S-D0502-02,50-F416S-D0504-02,50-F416S-D050601-02,50-F41
6S-D050701-02,50-F416S-D050801-02,50-F416S-D050901-02,50-F416
S-D051001-02,50-F416S-D0501101-02).

4.4.1 Normal LV Power

The PC (power center) and MCC (motor control center) connection mode
is used for 0.4kV system within power plant.

Unit/coal/JETTY/CWP service transformers are set up in couples(couple


means:Any one of the coupled transformers can takes all loads of the
coupled transformers.), and they are connected to 6.6kV unit/coal section
13
A、Bseparately, as a stand-by for each other.

The PC will distribute power through feeder breakers to large 400V motors
and to MCCs and to some loadsnotat too great a distance to be fed at
400V due to Voltage drop limitations. The MCCs will distribute power to
small 400V motors, to AC distribution boards and to intermediate
400/230V loads. The 400/230V AC distribution boards will distribute power
to smallerdiscrete400/230V loads.

4.4.2 Emergency Power

The function of the Emergency Generation System is to provide power to


facilitate an orderly and safe shutdown of the plantin case the loss of all
power services.There is a set of 600kW diesel generators for each unit.
Each generator feeds two emergency MCC busbars which supplyfor
emergencyloads.

Under normal condition, the Emergency MCCs receive power from


Emergency PCSections which are fed from 1250kVA Emergency
Transformers. Emergency Transformers are supplied via the 1B and 2B
6.6kV busburs respectively. An emergency condition occurs when there is
a power loss from the EmergencyTr. to the Emergency MCCs, the diesel
generator will automatically start and supply power to emergency loads.
For detail calculation for the Emergency Transformer refer to Drawing NO.
50-F416S-D0503-02.

4.5Ground System Of 6.6kV and 0.4kV

The 6.6kV system neutral point is low resistance grounded.

The 0.4kV system neutral point is solidly grounded.

4.6 Calculation Of Auxiliary System Voltage Level

When the biggest motor(feed water pump) start normally, the voltage level
of bus should not fall below 85%of the nominal bus voltage.

14
Items Starting Condition Spec. Power Supply
Voltag
unit
e
transformer63/35-35MVAUd1-2’=
Level
21%(%)(the lowest)
(%)

Normal Starting Motor-driven 85 90.3


starting of feed water pump
max. 6.6kV after the Unit
motor transformer being
normally loaded by
complete auxi. of one
unit

From the tableabove, the voltage level at starting of motors can meet the
Contract.

4.7Selection Of Auxiliary Equipment

The 6.6±2x2.5%/0.42kV transformer is dry type for all plant.

For 6.6kV power system,draw-out vacuum circuit breaker which is sized


based on the highest voltage of 7.2kV and Fuse-contactor elements (for
motor 900kW and below, for transformer 1250kVA and below).6.6kV
switchgear ‘s Interrupting current:50kA(rms) and Dynamic stability current
is125kA(peak)

For 0.4kV power system Both the 0.4kV power center (PC) and motor
control center (MCC) or distribution panel are of draw-out or fixed type
with short circuit withstand current 50kA.

For 0.4kV Draw-out/fixed type air circuit breaker(ACB), electrically and


mechanically operated, stored energy, trip free, will be with provisions for
padlocking in the open (off) position for incomers, bus couplers and tie

15
feeders with ratings above 630A for 0.4kV circuit.Molded case circuit
breakers(MCCB) for smaller rated feeders (rated up to 630A). Fuses
detailed in the Single Line Diagram for 0.4kV is for PT.

Normally,Motors with capacity ≥55kW and ≤ 200 kW are supplied power


from PCs,Motors with capacity <55 kW are supplied power from MCCs.

5.ELECTRIC EQUIPMENT LAYOUT

5.1 Layout Of Generator Transformer, Unit Transformer And Standby


Service Transformer

Generator transformers,unit auxiliary transformers and standby


transformers are located outside column A, andunit auxiliary transformers
and standby transformersare arranged between column A and the
generator transformer under the isolated phase bus duct.

The 500kV side surge arrester of generator transformer are located in


front of generator transformer to protect generator transformer.

The 6.6kV side of the auxiliary and standby transformersare connected to


the 6.6kV switchgear through 6/10kV cables.

Three fire-proof wallsare set up between generator transformer , unit


auxiliary &standby transformer and the column A.

5.2 6.6kV And 0.4kV Switchgear

The 6.6kV unit section is set on 6.3m floor inside turbine house.

The 6.6kV coal &station section is set on 6.3m floor inside the center
control building.

The CWP 6.6kV section is set at the CWP switchroom.

IP42 for 6.6kV Indoor Switchboards.

Most of 0.4kV switchgears are located on 6.3m floor of the central control
building and 0m, 6.3m of turbine room.

16
Other PCs and MCCs are centralized placed at corresponding power load
center(indoor).

IP42 for LV Indoor Switchboards.

5.3 Generator Output System And Excitation Equipment

The isolated phase bus duct(P.I.B) is drawn out from output termination of
the generator and leaded to generator transformer at a central line
elevated ~7.7m. Generator circuit breaker, Neutral point equipment
cubicle and PT cubicle、surge arrester cubicle is located on 6.3m floor,
excitation transformer and excitation equipment cubicle located on the 0m
floor in turbine house.

6.LIGHTNING PROTECTION AND EARTHING

The lightning protection and grounding design is in order to prevent the


equipment and personnel from hurt by over voltage and short circuit
current.

6.1 Lightning Protection System

Lightning protection system will be comprised of lightning rod, lightning


overhead line , lightning conductor, down leading conductors and so on.

The lightning protection use a method of strike sphere and the radius is
30m.

6.2 Earthing

The earthing system provides a low impedance return path for ground to
earth faults. Maintain safe step and touch potentials within the switchyard
and entire power station site during electrical faults.

All underground in soil Earthing conductors shall be copper. Above


ground earthing conductors shall be Galvanised Steel flat bar.

The following metal parts of electric device or facilities, should be

17
grounded

(1) Casing of the generator neutral point cubicle ,outlet cubicle and
busduct.

(2) Foundation and casing of motor , transformer , electric


apparatus,portable or removable electric apparatus .

(3) Transmission device of electric equipment ;

(4) Secondary winding of current transformer,except the one has other


stipulations in relaying .

(5) The metal frames of distribution bord, control pannel, protect pannel
and operations plate;

(6) The gantry of the switchyard, the metal rail and metal door nearby
electrification part.

(7) The cover of electric cable connection box and terminal box , metal
crust of cable, wear steel tube and cable tray ,etc.

(8) The crust of armor controls cable;

(9) Neutral point of high-voltage electrical equipment and transformer. Two


earth connections shall be made to the transformer tank。

7.CABLING STRUCTURE

The cabling structure is mainly overhead cable tray assisted with cable
trench.

All cable trays are of ladder type construction. There is a maximum


spacing of 2000mm between cable tray supports.

For cable routing which space is enough, Not more than one layer of
power cables and two layers of control or instrumentation or
communication cable is installed on a tray.

18
Cables shall be separated to ensure electromagnetic compatibility
between various types of cables. For this purpose all cables are to be
categorised into four types, namely:

Type 1: H.V. power cables i.e. 6.6kV cables

Type 2: L.V. power cables i.e. 400V/230 AC or 220V DC

Type 3: Control cables i.e. 230V AC and DC from 24-48V DC;


analogue/digital signals; redundancies

Type 4: Communications cables i.e. Telephones, data networks, LAN’s

The minimum separation between the various “Types” shall be as follows:

Type 1 to Type 2: 100mm

Type 1 to Type 3 or 4: 300mm

Type 2 to Type 3 or 4: 300mm

Type 3 or Type 4: 100mm

These separation distances may be smaller for short runs where cables
enter cubicles of crossover or encounter an obstruction (e.g. pipe).

The sides of a cable tray shall be capable of withstanding without


permanent deflection a 20kg force acting at a point 60o to the horizontal
midway between support, simultaneously with a distributed cable load
exerting a pressure of 1000N/m2 and concentrated mass of 100 kg
midway between the side. Cable tray shall not deflect more than 2 mm
when loaded with cables.

Cable ladders shall be connected to the site earthing system every 30


meters

Cable tray fittings have a radius equal to or greater than the minimum
bending radius of the cables they contain.

The design vertical clearance for trays is 150 mm or 200mm. A working


19
space of not less than 400mm will be maintained on at least one side of
each tray.

Cable galvanizedconduit will be used to protect unarmored conductors


routed to individual devices in hazardous areas and where the quantity of
cable does not economically justify the use of cable tray.

The cable pass-way between main building and auxiliary plant is overhead
cable tray or cable trench.

Cables above 0m floor are supported by overhead cable trays and Cables
below 0m floor supported by cable racks. The cable conduit is of
water-gas pipe type.

The cable routing from the main plant to the CWP area is thought the coal
conveyor.

8.CABLE FIRE PROOFING:

In the main passage-way, fire proof cable trays, fire proof walls of bags
filled with fireproof material or fireproof barrier-layers are set up
sectionally.

Sealed fireproof material is installed at inlets of switchgear,cable shafts


and two ends of cable conduits.

Fireproof walls with fireproof bags of cable trenches is set up at the


entrance to buildings.

9.CABLE SELECTION

a) MV single core and multicore power copper cables rated as 6/10kV


will have XLPE insulation, PEsheath, galvanized steel or aluminum wire
armour, PE outer sheath.

b) LV single core and multicore power copper cables will be 0.6/1kV


rating having XLPE insulation, PE sheath, galvanized steel or aluminum
wire armour, PEouter sheath.

20
10. SECONDARY DESCRIPTION AND LIGHTING DESCRIPTION

a) Secondary description refer to D0601 volume <ccr general of electrical


secondary wiring>

b) Lighting description refer to D1401 volume <general part for


lighting>

11. VOLUME LIST(PRIMARY PART)

No. Volume No. Volume name

1 D0101 Electric Layout, Explanation And List Of Volume Name

2 D0102 List Of Main Equipment

3 D0103 List Of Main Materials

4 D0201 500kV Switchyard Power Distribution Equipment

5 D0301 Installation Of Main Transformer And Unit Auxiliary Transformer

6 D0302 Installation Of Aerial Line Out The Volume A

7 D0401 Installation Of Generator Outgoing And Isolated Phase Bus Duct


Installation Of Generator Excitaion Bus Duct And the arrangement of Excitation
8 D0402 Equipment

9 D0403 Installation Of UAT transformer LV side cable routing

10 D0501 Single Line Diagram Of 6.6kV Auxiliary Power

11 D0502 Single Line Diagram Of Main House

12 D0503 Single Line Diagram Of Emergency Ac Power

13 D0504 Single Line Diagram Of Lighting And Maintance

14 D050501 Arrangement Of 6.6kV Auxiliary Power

15 D050502 Arrangement Of Lv Power Distribution In Main House

16 D050601 Single Line Diagram Of ESP

17 D050602 Arrangement Of ESP Power Distribution

18 D050701 Single Line Diagram Of Limestone Handing.

19 D050702 Arrangement Of Limestone Handing. Power Distribution

20 D050801 Single Line Diagram Of Water & Waste Water Treatment

21 D050802 Arrangement Of Water & Waste Water Treatment Power Distribution

22 D050901 Single Line Diagram Of Coal Handling

23 D050902 Arrangement Of Coal Handlingpower Distribution

24 D051001 Single Line Diagram Of CIRCULATING WATER PUMP HOUSE

25 D051002 Arrangement Of CIRCULATING WATER PUMP HOUSE

26 D051101 Single Line Diagram Of ADMINISTRATION SYSTEM

27 D051102 Arrangement Of ADMINISTRATION SYSTEM

21
28 D1001 Installation Of Storage Battery In Main House

29 D1002 Installation Of Storage Battery In CONTROL AND RELAY BUILDING

30 D1101 Lightning Protection

31 D1102 Main Earthing Mesh Of The Plant

32 D1103 Earthing In Turbine House

33 D1104 Earthing In Deaerator, Coal Bunker Bay And Boiler House

34 D1105 Earthing In Ccb, ESP And Boiler Rear Area

35 D1106 Earthing In Coal Handlong System

36 D1107 Earthing In Auxiliary Plant

37 D1201 Installation Of Slide-Rail In Turbine House

38 D1202 Installation Of Slide-Rail In Boiler House

39 D1203 Installation Of Slide-Rail Of Coal Handling System

40 D1204 Installation Of Slide-Rail In Other Auxiliary Building

41 D1301 General Description Of Cabling System

42 D130201 Cable Structure In Turbine House

43 D130202 Cable Routing In Turbine House

44 D130301 Cable Structure In Boiler House

45 D130302 Cable Routing In Boiler House

46 D130401 Cable Structure In Central Control Building

47 D130402 Cable Routing In Central Control Building

48 D130501 Cable Structure Of ESP

49 D130502 Cable Routing Of ESP

50 D1306 Cable Routing And Cable Structure Outside Volume A

51 D1307 Cable Routing And Cable Structure In Outdoor Switchyard

52 D130801 Cable Structure Of Coal Handling System

53 D130802 Cable Routing Of Coal Handling System

54 D130901 Cable Structure Of Limestone Handling System

55 D130902 Cable Routing Of Limestone Handling System

56 D131001 Cable Structure Of Water & Waste Water Treatment

57 D131002 Cable Routing Of Water & Waste Water Treatment

58 D131201 Cable Structure In Plant Area And Other Auxilliry House

59 D131202 Cable Routing In Plant Area And Other Auxilliry House

60 D1313 Cable Routing And Cable Structure Of ADMINISTRATION SYSTEM

61 D1314 Cable Routing And Cable Structure Of CIRCULATING WATER PUMP HOUSE

62 D131301 List Of Cable Of The Electrical Primary And Lighting

63 D131302 List Of Cable Of The Electrical Secondary

64 D131401 General Description Of Cable Fire Protection

65 D131402 Cable Fire Protection Of The Main House

66 D131403 Cable Fire Protection Of The Coal Handling System

67 D131404 Cable Fire Protection Of Other Auxilliry House

a) Secondary volume list refer to D0601 volume <ccr general of electrical

22
secondary wiring>

b) Lighting volume list refer to D1401 volume <general part for


lighting>