Professional Documents
Culture Documents
SENTRY III
®
OFF
COOL WASH
SAMPLE
AGITAT E
0308 8824349
DFE0230
Attachments
Figure 18a—Control Box Wiring Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 18b—Rear Junction Box Field Wiring (Full Cabinet Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 19—Rear Junction Box Field Wiring (Half-Cabinet - 400C, 500, and 600 Gallon Models) . . . . . . . . . . . . .
SECTION 1.O - INTRODUCTION
1.1 General
The Mueller® Model “OHF” Milk Cooler and Sentry® III refrigeration and cleaning control system are
custom designed and manufactured for cooling and storing milk.
Durable construction and enhanced control circuitry ensures maximum cooling and energy efficiencies,
superior automation, and long-term reliability.
Local, state, and/or country regulations pertaining to the installation, operation, and service of the
Mueller milk cooler may vary and must be followed accordingly.
The installation and service of the Mueller milk cooler must be performed by authorized service
technicians who have the proper training and certification to install and service refrigeration and
electrical equipment.
United States EPA regulations require that any technician performing refrigerant installation or service
on a high-pressure refrigeration appliance be certified as a Type II Technician in accordance with
Section 608 of the Clean Air Act. The Clean Air Act regulations may change or differ for your locality.
It is the responsibility of the technician performing the refrigerant service and/or installation to abide
by all regulatory requirements and procedures for their locality, state, and country.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 1 Revised April 28, 2008
1.4 Sentry III Control Box Assembly
A. Sentry III Control Box Assembly J. Temperature Display
B. Wash/Cool/Cycle Time Display K. Bottom Unit Cooling Switch/Indicator
C. Detergent Switch/Indicator L. All Units Cooling Switch/Indicator
D. Advance Switch M. Pre-Start Cooling Switch/Indicator
E. Acid Switch/Indicator N. Pre-Start Agitation Switch/Indicator
F. Sanitize Switch/Indicator O. Temperature Alarm Indicator
G. Circulation Pump Indicator P. Full Tank Alarm (Optional)
H. Drain Valve Indicator Q. Sample Agitation Switch/Indicator
I. Cool/Off/Wash Switch
I A
SENTRY III
®
J B
OFF
COOL WASH
K C
TEMPERATURE CYCLE TIME
SAMPLE
AGITAT E
L D
BOTTOM UNIT PRE-RINSE CYCLE
® G
0308 8824349 H
O DFE0230
P Q
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 2 Revised April 28, 2008
1.5 Sentry III and "OHF" Milk Cooler Components
A. Agitator Motor J. Spray Dish
B. Agitator K. Measuring Stick (Internal)
C. Air Vent and Front Milk Inlet L. Rear Milk Inlet (Optional)
D. Manway M. Chemical Dosing Box
E. Sentry III Control N. Electrical Junction Box
F. Milk Outlet Valve O. External Trough Raceway
G. Wash-Pump Assembly P. Water Solenoid Valves
H. Electric Drain Valve Q. Wash Cap
I. Ladder
E I M
SENTRY III
®
OFF
COOL WASH
SAMPLE
AGITAT E
BOTTOM UNIT
DELAYED START
ALL UNITS
DELAYED START
AGITAT E
PRE-RINSE CYCLE
RINSE CYCLE
DETERGENT CYCLE
0308 8824349
DFE0230
G
Q
F
H F H
P
N A
D
L C
B K
E
O
H
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 3 Revised April 28, 2008
1.6 Sentry III Control Cabinet Components
A. Sentry III Control Box1
B. Peristaltic Pump (Sanitize)
C. Peristaltic Pump (Acid)
D. Peristaltic Pump (Detergent)
E. Chemical Line Priming Disconnect
F. Wash/Fill Tube
G. Fill/Float Valve
H. Pressure Switch (No Water Alarm/Optional)
I. Outlet Valve Assembly
J. Water Solenoid Valves (Hot/Cold)
K. Electric Drain Valve Assembly
L. Wash Cap
M. Wash Pump Motor
1The Sentry III Control Box is wall mounted on 400C, 500, and 600-gallon models.
A
Half cabinet shown for 400C-, 500-,
and 600-gallon models.
SENTRY III
®
OFF
COOL WASH
SAMPLE
AGITAT E
®
DRAIN VA LVE
0308 8824349
DFE0230
G
M D
E
L
K
I
J
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 4 Revised April 28, 2008
SECTION 2.0 - INSTALLATION
1. Remove any open-type crating and the packaged parts. Do not remove the skids attached to the
milk cooler legs at this time.
2. Inspect the milk cooler and report any damage to the transportation carrier. File a claim
immediately if the milk cooler is damaged.
3. Move the milk cooler into the milk house and position it to meet all regulatory requirements for
the locality.
2. Lower the milk cooler and repeat the procedure on the opposite end.
3. Remove cross-bracing members, leaving the two skids under the milk cooler’s legs.
4. Raise one end of the milk cooler with a floor jack and wooden-cradle block. Pivot the skids away
from the milk cooler. Lower the milk cooler and repeat the procedure for the other end.
SENTRY III
®
SENTRY III
®
OFF OFF
SAMPLE SAMPLE
AGITAT E AGITAT E
AGITAT E AGITAT E
DELAYED START POST RINSE CYCLE DELAYED START POST RINSE CYCLE
FULL TANK ALARM DRAIN VALVE FULL TANK ALARM DRAIN VALVE
® ®
Cross
Brace
DFE0161
Skid
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 5 Revised April 28, 2008
2.3 Site Requirements
It is the responsibility of the installer and/or purchaser to provide adequate electrical service, water
supply, floor drains, and footer foundations for the installation. Failure to do so can cause non-
warranted structural damage to the milk cooler and/or costly service problems for the user.
Electrical installation requirements for the refrigeration units should be obtained from the Installation
and Operation Manual specific to the refrigeration unit(s) being installed.
NOTE: All wiring to be performed in accordance with the National Electrical Code and/or regulatory
agency for the installation locality. All wiring that enters the Sentry III control box must be sealed with
cord grips or liquid-tight conduit connectors.
1. A drawing showing the layout location of the milk cooler’s legs. See Section 8.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 6 Revised April 28, 2008
Formula 1 - Gross Weight of Milk Cooler
IMPORTANT NOTE: Mueller warrants to the original purchaser/user that the Mueller factory calibration
! of a Mueller milk cooler will not be affected (i.e. exceed the tolerances prescribed by the National
Institute of Standards and Technology) by distortion or structural change for a period of five (5) years
from the date of installation or sixty-six (66) months from the date of shipment from the Company
factory, whichever occurs first. The Company’s obligation shall be limited to the correction of the
calibration only, and does not cover reimbursement of product loss. This warranty will not apply if
distortion is caused by changes in the floor or foundation on which the milk cooler is installed. Refer
to the Mueller Milk Cooler Warranty Card for complete warranty information.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 7 Revised April 28, 2008
2.8 Leveling the Milk Cooler
With the assistance of a floor jack and protective wooden-cradle block, level the milk cooler as
described in the following steps:
1. Adjust the inner legs off the floor until the proper pitch is obtained with the four corner legs.
2. Place a carpenter’s level across the brim of the manway opening and level the milk cooler by
adjusting the corner legs with a nylon strap wrench. Legs may be extended by turning the legs
counterclockwise, and retracted by turning the legs clockwise.
3. Using the levels located on the side of the cooler, adjust each end of the milk cooler until the
proper height and pitch is obtained. (The milk cooler should pitch 1/4" per foot towards the outlet
valve.)
4. Using a certified seraphin, add the exact volume of water indicated for the “Set-Up Reading” on
the calibration chart.
5. Adjust the final pitch of the milk cooler, matching the calibration gauge reading with the “Set-Up
Reading” on the calibration chart.
6. When the front and back corner legs are positioned properly, the inner legs should be extended
firmly against the floor.
7. Ensure that the final location and position complies with all regulations for the installation locality,
including the proper height of the milk outlet and the proper dimensions beneath and around the
milk cooler.
SENTRY III
®
OFF
COOL WASH
SAMPLE
AGITAT E
DFE0161
Floor Jack
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 8 Revised April 28, 2008
2.9 Bulk Head Installations
If the milk cooler is bulkheaded through a wall, the wall must be free-standing and not load bearing
against the milk cooler. Mueller offers an optional steel-formed structural support channel that may be
installed in masonry walls to prevent the wall from bearing load on the milk cooler. Contact Mueller’s
Sales Department for availability and pricing.
A weather shield kit, Part No. 93750, is required for agitator(s) that are located exterior of the milk
house wall. See Figures 7, 8, and 10, and Section 2.11 for additional installation instructions.
Model KO
31393 BB
Neoprene Gasket —
Do not use on Model KO.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 9 Revised April 28, 2008
2.10 Milk Room Installations
Ensure proper clearances between the milk cooler and other obstacles or equipment as required by the
regulations in your locality. Special attention should be placed on floor drain locations, high-traffic and
working areas, and ease of access for the operators.
The milk cooler parts box includes two stainless steel brackets to secure the incoming water supply
lines to the rear head of the milk cooler, Part Nos. 8823254 (top) and 8823253 (bottom). These brackets
are supplied with 1.125-inch ID rubber grommets to facilitate the installation of .75-inch PVC pipe. The
milk cooler is pre-drilled and supplied with stainless steel hardware for the attachment of the water
line brackets. See Figure 9.
2. Position the spacer sleeves (Item 3) on the studs located on the top of the cooler. Apply Never-
Seez® to the shaft end (Item 7) and threads of the cap screws (Item 1). Slip the agitator shaft
through the agitator drive and secure in place with cap screws (Item 1), lock washers (Item 2),
and spacer sleeves (Item 3).
3. Align the hole in the agitator shaft with the hole in the output shaft of the agitator drive and insert
the roll-pin (Item 5).
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 10 Revised April 28, 2008
4. Place the blue plastic cap [silver metal cap for stainless steel agitator] (Item 6) over the top of the
output shaft after assembly.
5a. Model KO — Thread the 90° liquid-tight conduit fitting (Item 10) through the plastic nut (Item 11)
with the flat-washer flange facing the motor. Slip the cut gasket (Item 12) over the threads and
thread the assembly into the agitator motor. Insert the 3-wire cable through the straight conduit
fitting, conduit, and 90° fitting installed in the motor. Thread the straight liquid-tight conduit fitting
into the full coupling attached to the milk cooler. Connect L1 and L2 as shown on the wiring
schematic in motor, secure the ground wire under the grounding screw in the motor housing.
Ensure clockwise rotation as viewed from the top of the drive.
5b. Stainless Steel Agitator — Insert the 90° liquid-tight conduit fitting (Item 10) into the electrical
junction box on the motor. Slip the gasket (item 12) over the threads and secure the fitting into the
junction box using the plastic nut (item 11). Insert the 3-wire cable through the straight conduit
fitting, conduit, and 90° fitting installed in the motor. Thread the straight liquid-tight conduit fitting
into the full coupling attached to the milk cooler. Connect L1 and L2 and instructed on wires in the
electrical junction box on the motor. Secure the ground wire under the ground screw in junction
box. Ensure clockwise rotation as viewed from the top of the drive.
6. The optional agitator weather shield (Item 13) must be installed on all agitators that are located
exterior of the milk room.
11 12
10
13
11
11 12
10 12
3
8
4
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 11 Revised April 28, 2008
2.12 Water Line Connections
1. Hot and cold water must be supplied to the water solenoid valves located in the lower right rear
corner of the stainless steel cabinet that encloses the Sentry III control box and pump assembly.
Refer to Figure 11.
2. Insert and clamp one of the four barbed hose fittings in each end of the nylon reinforced supply
hoses provided in the parts box. The hoses may be cut to length to facilitate different installation
methods. Prior to installation, mark one of the water hoses on each end to ensure that the hoses
are not crossed and proper hot and cold connections are made at the opposite end.
3. Connect the hot and cold water hoses to the water solenoid valve protruding from the back of the
stainless steel housing. Connect the hot water supply hose to the top solenoid valve and the cold
water supply to the bottom solenoid valve.
4. The solenoid valve assembly may be slipped upward and away from the cabinet to facilitate front
access and service of the solenoid valve. Refer to Figure 12.
5. Route the hot and cold water supply hoses through the milk cooler's external trough raceway to
the hot and cold water supply valves. See the examples shown in Figures 8 and 9.
6. Connect the supply hoses to the hot and cold water supply valves with the check valves included
in the parts box. Refer to Figures 8 and 9.
7. Ensure that these hose connections are leak-free and provide the proper water temperature during
the start-up inspection.
SENTRY III
®
OFF
COOL WASH
SAMPLE
AGITAT E
0308 8824349
DFE0230
Cold
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 12 Revised April 28, 2008
Figure 12 - Water Solenoid Valve Connections
Hot Hot
Cold Cold
Slide the solenoid valve assembly Slide the solenoid valve assembly
upward and away from cabinet to back into bracket after servicing or
faciliate easy access for water connecting the water supply hoses.
connections and valve service.
2. Connect the chemical supply hoses between the chemical drums and the inlet of each peristaltic
pump as follows:
a. Insert the clear-colored chemical supply hose to the bottom of the detergent drum.
b. Route the other end of the hose through the milk cooler’s external raceway and connect it to
the suction inlet fitting (left side) of the peristaltic pump labeled “Detergent.” Refer to Figures
8, 9, and 13.
c. Repeat the procedure for the acid and sanitize connections, connecting the red hose to acid
and the blue hose to sanitize.
NOTE: The maximum distance allowed between the chemical drums and peristaltic pumps is 28 feet
or 8 meters.
SAFETY/ALERT: Wear protective clothing and eye protection when handling caustic
chemicals! Always observe the chemical manufacturer’s precautions, warnings, and usage
recommendations! Store all chemicals in a location protected from freezing, unauthorized
access, and direct sunlight.
CAUTION
WEAR EYE PROTECTION, CORROSIVE POISON
RUBBER GLOVES, AND
APRONS WHEN HANDLING
CHEMICALS
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 13 Revised April 28, 2008
Figure 13 - Chemical Line Connections (Peristaltic Pumps)
SENTRY III
OFF
COOL W ASH
TEMPERA
TURE CYCLETIME
SAMPLE
AGITATE
DELA
YED START RINSE CYCLE
PRE-ST
ART COOLING ACID CYCLE
PRE-ST
ART AGITATE SANITIZECYCLE
TEMPERA
TUREALARM CIRCULA
TION PUMP
0308 8824349
DFE0230
Priming Disconnect
DETERGENT ACID SANITIZE
Fittings (Right Side)
WARNI G
Exploded View
Priming
Disconnect
PERISTALTIC PUMP OPERATION - PART NO. 8825611, 108 RPM, COUNTERCLOCKWISE ROTATION
Priming
Disconnect
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 14 Revised April 28, 2008
2.14 Manway Wash Tube Installation
The manway wash tube provides positive wash of the manway opening and cover. The tube is
inserted in the stainless steel nipple in the top of the milk cooler and held in place with a stainless
steel pin. Refer to the drawing in Figure 14 for detailed installation procedures.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 15 Revised April 28, 2008
2.15 Spray Dish Installation
The spray dishes connect to the internal or external CIP wash line with a stainless steel keeper pin.
Check for proper spray dish installation and orientation during the installation and start-up inspection.
The rectangular notch cut across the bottom of the spray dish tube must face the front and rear heads
of the milk cooler and the slot cut in the bottom of the dish must point towards the center of the
agitator shaft. See Figure 15.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 16 Revised April 28, 2008
2.16 Milk Cooler Vent Assembly Installation
Install the milk cooler vent assembly by rotating the vent assembly clockwise and allow the retaining
straps to engage in the retaining lugs. See Figure 16.
IMPORTANT: The vent for the milk cooler must be in place at all times. The vent prevents
! contaminates from entering the milk cooler and provides proper air flow to prevent internal damage
resulting from vacuum or pressurization when the milk cooler is washed or emptied. Mueller Model
“OHF” milk coolers are designed for operation at normal atmospheric pressure only.
CAUTION
VENT ASSEMBLY
MUST BE OVER
MILK INLET AT
ALL TIMES.
MISE EN GARDE
LE MONTAGE DE
VENTILATION DOIT
ÊTRE AU DESSUS DE
L’ENTRÉE DU LAIT
EN TOUT TEMPS.
¡PRECAUCIÓN!
EL ENSAMBLE DE
RESPIRACIÓN DEBE
ESTAR SOBRE LA
ENTRADA DE LECHE
EN TODO MOMENTO.
0408 30166
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 17 Revised April 28, 2008
SECTION 3.0 - ELECTRICAL WIRING
3. Open the quick-connect terminal connection by inserting a 3-mm screwdriver into the bottom of
socket “A”.
4. Press the correct 16-gauge conductor into the terminal connection “B” and remove the screwdriver,
allowing the quick-connect terminal to close on the conductor.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 18 Revised April 28, 2008
WARNING! RISK OF ELECTRICAL SHOCK. CAN CAUSE INJURY OR DEATH.
19
RELAY BOARD
LOGIC BOARD
HIGH VOLTAGE
8002256 (8824864)
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 20 Revised April 28, 2008
Figure 19 - Rear Junction Box Field Wiring (Half-Cabinet - 400C, 500, and 600
Gallon Models) - Full-Size Drawing Attached in Back
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 21 Revised April 28, 2008
Figure 20 - Electrical Schematic - Wash-Pump Motor
P2 Insulate
Grd.
Rotation must be clockwise Grd.
Red 5
looking down on agitator drive
Line 1
To change rotation, interchange Black 240 VAC
Line 2
Black and Red leads. A
NOTE:
Use white and red for bright
illumination. Use white and
black for low illumination.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 22 Revised April 28, 2008
SECTION 4.0 - SENTRY III TEMPERATURE CONTROL
1. Fabricate an insertion rod from a 5-foot piece of 10-gauge solid wire by forming a 3/8" open loop
on one end. See Figure 24.
2. Slip the loop of the insertion rod over the sensor wire and push the sensor down the raceway until
it seats into the spring-clip at the end of the sensor raceway.
3. Being careful not to pull the sensor from the spring clip, withdraw the insertion rod from the
sensor raceway. See Figures 23 and 24.
SENTRY III
®
OFF
COOL WASH
SAMPLE
AGITAT E
0308 8824349
DFE0230
Raceway
for sensor
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 23 Revised April 28, 2008
Figure 24 - Sentry III Digital Sensor Installation
IMPORTANT: Cut the white wire, drain wire (bare wire), and aluminum foil wrap back to the
! cable jacket and insulate with electrical tape at the right front access opening. The foil and drain
wire must be insulated so that it does not make contact with the stainless steel shell of the milk
cooler! See Figure 26.
2. Route the shielded extension cable (Part No. 8824887) through the internal conduit to the left
access opening.
NOTE: The shielded wire provided by Paul Mueller Company MUST be used to ensure the proper
conductor capacitance.
3. Drop the extension cable down through the grommet in the left-hand access opening, routing it
through the external raceway and up through the stainless steel enclosure. Route the extension
wire to the right side of the pump compartment, up over the auto-dosing box, and into the Sentry
III control box.
4. Connect the red, black and green wires to the proper terminal connections at the bottom left
corner of the Sentry III relay board.
IMPORTANT: Trim the white wire back to the insulation and connect the bare drain wire in the
! shielded cable to earth ground in the Sentry III cabinet. See Figure 26.
NOTE: If the temperature display shows “?°” (question mark and degree symbol) you have a poor
connection at the splice or a miss-wire of the sensor circuit.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 24 Revised April 28, 2008
4.4 Half-Cabinet, Wall Mounted Sentry III Digital Sensor Wiring
1. Splice the sensor cable to the shielded extension cable at the right front access opening. Use
sealing splice crimp connectors (Part No. 8825009). Do not strip the insulation from the single
conductors. Fully insert two like-colors into the splice and pinch closed with pliers. Splice green to
green, red to red, and black to black.
IMPORTANT: Cut the white wire, drain wire (bare wire), and aluminum foil wrap back to the
! cable jacket and insulate with electrical tape at the right front access opening. The foil and drain
wire must be insulated so that it does not make contact with the stainless steel shell of the milk
cooler! See Figure 26.
2. Route the shielded extension cable (Part No. 8824887) through the internal conduit to the left
access opening.
NOTE: The shielded wire provided by Paul Mueller Company MUST be used to ensure the proper
conductor capacitance.
3. Exit the rear top junction box in a separate conduit and route to the Sentry III enclosure. Do not
route with other high-voltage cables or route sensor conduit parallel in close proximity with other
high-voltage conduits.
4. Route the shielded cable into the bottom of the Sentry III enclosure and cut the white wire and
aluminum foil wrap back to the cable jacket.
IMPORTANT: Do not cut off the drain wire. The drain wire must connect to the earth
! ground inside the Sentry III cabinet.
4. Connect the red, black and green wires to the proper terminal connections at the bottom left
corner of the Sentry III relay board.
NOTE: If the temperature display shows “?°” (question mark and degree symbol) you have a poor
connection at the splice or a miss-wire of the sensor circuit.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 25 Revised April 28, 2008
Figure 25 - Sentry III Digital Sensor Wiring
SENTRY III
®
OFF
COOL WASH
SAMPLE
AGITAT E
0308 8824349
DFE0230
Left-hand
access opening Right-hand
access opening
Splicing is required.
External Follow instructions accurately.
Internal conduit raceways to raceway
top-rear junction box.
Grommet
A conduit raceway located between the
inner and outer milk cooler shell connects
the right and left access openings.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 26 Revised April 28, 2008
SECTION 5.0 - SENTRY III PROGRAM PARAMETERS
Press the “All Units Switch” to cycle through the program parameters. The parameter will be displayed
in the “Temperature” display and the value will be displayed in the “Cycle Time” display. After viewing
parameters the control will revert back to normal operating mode after being left idle for 30-60
seconds. See Section 5.2, “Cooling Parameters.”
13 ADB/WWB N/A Remote Cool Lamp N/A Output for “Remote Cool Lamp” will duplicate the “Bottom Unit Delayed Start LED” and the “Bottom Unit LED”
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 27 Revised April 28, 2008
5.3 View Wash Parameters
In viewing mode, the parameters cannot be changed, they may only be viewed. To view the washing
parameters, place the “COOL/OFF/WASH” switch in the “OFF” position. Press and hold the “Full Wash
Switch” until “WSH” is displayed in the cycle time display. The “Cycle Time” display will show which
configuration the control is programmed for, “WWB” for wall mount water box, “ADB” for auto-dosing
box or “MMB” for Mueller Matic® box. See washing parameter chart for program acronyms and range.
Press the “Advance Key” to cycle through the program parameters. The parameter will be displayed in
the “Temperature” display and the value will be displayed in the “Cycle Time” display. After viewing
parameters the control will revert back to normal operating mode after being left idle for 30-60
seconds. See Section 5.4, “Wash Parameters for ADB and WWB.”
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 28 Revised April 28, 2008
5.4 Washing Parameters for ADB or WWB
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 29 Revised April 28, 2008
5.5 Washing Parameters for MMB
Press the “Bottom Unit Switch” to enter into the cooling parameter programming. The temperature
display will show the program parameter and the cycle time will show the parameter setting. See
Cooling Parameters for program options.
To view different parameters use the “All Units Switch” to advance to the next parameter and use the
“Bottom Unit Switch” to move back to the previous parameter. Once a parameter has been selected to
change use the “Pre-Start Cooling Switch” to increase the displayed value in the cycle time display or
the “Pre-Start Agitation Switch” to decrease the value.
If no key is pressed for 30-60 seconds the control will revert back to normal operation mode.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 30 Revised April 28, 2008
Example: With the rotary switch in the “OFF” mode, press and hold the roman numeral III until “COL”
and “WSH” are displayed. Press the “Bottom Unit Switch”, the display windows will show “BUD” and
the delay time that is programmed. Press and release the “All Unit Switch” until “SPT” is displayed in
the temperature display. This is the setpoint for refrigeration to shut off, use the “Pre-Start Cooling
Switch” to increase the displayed value in the cycle time display or the “Pre-Start Agitate Switch” to
decrease the value.
After programming is complete on the cooling parameters, press the roman numeral “III” to return to
automatic operation, or if no key is pressed for 30-60 seconds the control will revert back to normal
operation mode.
Press the “Detergent Wash Switch” to enter into the wash parameter programming. The temperature
display will show the program parameter and the cycle time will show the parameter setting. See Wash
Parameters for program options.
To view different parameters use the “Advance Switch” to advance to the next parameter and use the
“Detergent Wash Switch” to move back to the previous parameter. Once a parameter has been selected
to change use the “Acid Cycle Switch” to increase the displayed value in the cycle time display or the
“Sanitize Cycle Switch” to decrease the value.
Example: The first parameter that needs checked or changed is the “CON” parameter. This parameter
selects how the control box will be utilized as either an auto-dosing box (ADB OHF only), a wall
mount water works box (WWB), or as a retrofit replacement of an older Mueller Matic style wash
control utilizing a water operated drain valve (MMB).
With the rotary switch in the “OFF” mode, press and hold the roman numeral III until “COL” and
“WSH” are displayed. Press the “Detergent Wash Switch”, the display windows will show “CON” and
either WWB, ADB, or MMB. Press the “Acid Cycle Switch” or the “Sanitize Cycle Switch” to cycle
between MMB, WWB, and ADB.
After selecting the control type continue through the wash parameters. After programming is complete
on the wash parameters press the roman numeral III to return to the normal operation or if no key is
pressed for 30-60 seconds the control will revert back to normal operating mode.
1. To enter the test program place the rotary switch in the “OFF” position, press and HOLD the “Pre-
Start Agitate” switch. After 15 seconds the temperature display will show “TST” and the cycle time
display will show the software version number.
2. Release the “Pre-Start Agitate” and all segments of the alpha numeric displays will illuminate. This
will validate that all segments are working on the 16 segment displays.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 31 Revised April 28, 2008
3. Press and release the advance key once, all of the LED lights will be illuminated.
4. Press and release the advance key again and the level alarm input can be checked. The
temperature display will show “LVL” and the cycle time will show “OPN” for open or “CLS” for
closed. If no level switch is installed, use a jumper wire from “GND” to “LVL” on TB1 terminal
block to simulate a closed level alarm.
5. Press and release the advance key again and the water pressure switch can be checked. The
temperature display will show “PSW” and the cycle time will show “OPN” or “CLS”.
NOTE: The water pressure switch is optional on “OHF” front-mount controls, and must be
jumpered if no switch is used.
6. Press and release the advance key again, “K1” will be displayed in the temperature window and
condensing unit number one will be energized.
7. Continue pressing and releasing the advance key to cycle through relays K1-K17. After K17 the
control will revert back to normal operation mode.
Sentry
Sentry III
III “OHF”
“OHF” Installation
Installation and
and Operation
Operation Manual
Manual Effective
Effective May
May 26,
26, 2004
2004
Part 32
Part No.
No. 8824990
8824990 Revised
Revised April
April 28,
28, 2008
2008
SECTION 6.0 - AUTOMATIC CHEMICAL DOSING
6.1 Initial Start-Up Procedures for Automatic Dosing and Chemical Usage
The chemical usage will vary depending on the make and manufacturer, the amount of water required
for each cycle, and the water quality. It is very important to have your Chemical Supplier test the water
supply and determine the proper usage and concentrations of each specific chemical. This information
should be posted on a cleaning chart near the milk cooler.
IMPORTANT NOTE: Improper chemical usage can cause non-warranted and non-repairable damage to
! your stainless steel milk cooler. Chemicals should be purchased from a reputable source that
specializes in the proper application and usage of dairy cleansers for clean-in-place (CIP) applications.
• Read and abide by all Material Safety Data Sheets (MSDS), labels, instructions, warnings,
and health hazard information provided by the Chemical Manufacturer.
• Prime peristaltic pumps in a glass jar only. Do not prime the pumps into the milk cooler.
• Without proper dilution, chemicals can damage the stainless steel milk cooler.
• Ensure that all drains are properly trapped to prevent mixed chemical gasses from re-
entering the workplace.
• Store chemicals in an area protected from freezing and out of direct sunlight.
CAUTION
WEAR EYE PROTECTION, CORROSIVE POISON
RUBBER GLOVES, AND
APRONS WHEN HANDLING
CHEMICALS
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 33 Revised April 28, 2008
6.4 Peristaltic Pump Priming
The peristaltic chemical pumps will require priming upon the initial installation and each time the
chemical supply drums are emptied and replaced thereafter. The following procedure provides the
proper method of priming each pump:
1. While holding the female barbed fitting stationary, separate the in-line disconnect by pulling the
quick-connect down and turning it a 1/2 turn counterclockwise.
2. Place the COOL/OFF/WASH rotary switch in the “OFF” position. While holding a glass jar beneath
the pump’s discharge, press and hold the appropriate cycle switch of the pump to be primed.
Holding the switch for 15 seconds will begin priming. Once primed, release the switch.
3. Reconnect the quick-connect fitting by inserting the male end into the female socket and turning
1/2 turn clockwise to lock it into position.
5. Thoroughly wash all chemical traces from the glass jar and repeat the procedure for the remaining
peristaltic chemical pumps.
SENTRY III
®
COOL WASH
SAMPLE
AGITAT E
0308 8824349
DFE0230
Press and hold for 15 seconds and priming will start.
Priming
Disconnect Hold stationary.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 34 Revised April 28, 2008
Table 1A - Peristaltic Pump Timing for Specific Chemical Concentrations
(2 to 160 seconds) (See Section 5.4, Item Nos. 29-32)
8822976 Motor 8825611 Motor 8822976 Motor 8825611 Motor
Model No. 105-4058 Model No. 105-60108 Model No. 105-4058 Model No. 105-60108
Sec. ml. oz. Sec. ml. oz. Sec. ml. oz. Sec. ml. oz.
2 5.2 0.18 2 11.67 0.39 82 213.2 7.21 82 478.33 16.17
4 10.4 0.35 4 23.33 0.79 84 218.4 7.38 84 490.00 16.57
6 15.6 0.53 6 35.00 1.18 86 223.6 7.56 86 501.67 16.96
8 20.8 0.70 8 46.67 1.58 88 228.8 7.74 88 513.33 17.36
10 26 0.88 10 58.33 1.97 90 234 7.91 90 525.00 17.75
12 31.2 1.05 12 70.00 2.37 92 239.2 8.09 92 536.67 18.15
14 36.4 1.23 14 81.67 2.76 94 244.4 8.26 94 548.33 18.54
16 41.6 1.41 16 93.33 3.16 96 249.6 8.44 96 560.00 18.94
18 46.8 1.58 18 105.00 3.55 98 254.8 8.61 98 571.67 19.33
20 52 1.76 20 116.67 3.94 100 260 8.79 100 583.33 19.72
22 57.2 1.93 22 128.33 4.34 102 265.2 8.97 102 595.00 20.12
24 62.4 2.11 24 140.00 4.73 104 270.4 9.14 104 606.67 20.51
26 67.6 2.29 26 151.67 5.13 106 275.6 9.32 106 618.33 20.91
28 72.8 2.46 28 163.33 5.52 108 280.8 9.49 108 630.00 21.30
30 78 2.64 30 175.00 5.92 110 286 9.67 110 641.67 21.70
32 83.2 2.81 32 186.67 6.31 112 291.2 9.84 112 653.33 22.09
34 88.4 2.99 34 198.33 6.71 114 296.4 10.02 114 665.00 22.49
36 93.6 3.16 36 210.00 7.10 116 301.6 10.20 116 676.67 22.88
38 98.8 3.34 38 221.67 7.50 118 306.8 10.37 118 688.33 23.28
40 104 3.52 40 233.33 7.89 120 312 10.55 120 700.00 23.67
42 109.2 3.69 42 245.00 8.28 122 317.2 10.72 122 711.67 24.06
44 114.4 3.87 44 256.67 8.68 124 322.4 10.90 124 723.33 24.46
46 119.6 4.04 46 268.33 9.07 126 327.6 11.08 126 735.00 24.85
48 124.8 4.22 48 280.00 9.47 128 332.8 11.25 128 746.67 25.25
50 130 4.40 50 291.67 9.86 130 338 11.43 130 758.33 25.64
52 135.2 4.57 52 303.33 10.26 132 343.2 11.60 132 770.00 26.04
54 140.4 4.75 54 315.00 10.65 134 348.4 11.78 134 781.67 26.43
56 145.6 4.92 56 326.67 11.05 136 353.6 11.95 136 793.33 26.83
58 150.8 5.10 58 338.33 11.44 138 358.8 12.13 138 805.00 27.22
60 156 5.27 60 350.00 11.83 140 364 12.31 140 816.67 27.61
62 161.2 5.45 62 361.67 12.23 142 369.2 12.48 142 828.33 28.01
64 166.4 5.63 64 373.33 12.62 144 374.4 12.66 144 840.00 28.40
66 171.6 5.80 66 385.00 13.02 146 379.6 12.83 146 851.67 28.80
68 176.8 5.98 68 396.67 13.41 148 384.8 13.01 148 863.33 29.19
70 182 6.15 70 408.33 13.81 150 390 13.19 150 875.00 29.59
72 187.2 6.33 72 420.00 14.20 152 395.2 13.36 152 886.67 29.98
74 192.4 6.50 74 431.67 14.60 154 400.4 13.54 154 898.33 30.38
76 197.6 6.68 76 443.33 14.99 156 405.6 13.71 156 910.00 30.77
78 202.8 6.86 78 455.00 15.39 158 410.8 13.89 158 921.67 31.17
80 208 7.03 80 466.67 15.78 160 416 14.06 160 933.33 31.56
NOTE: Validate pump motor model number to determine chemical dispensing rate.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 35 Revised April 28, 2008
Table 1B - Peristaltic Pump Timing for Specific Chemical Concentrations
(162 to 318 seconds) (See Section 5.4, Item Nos. 29-32)
8822976 Motor 8825611 Motor 8822976 Motor 8825611 Motor
Model No. 105-4058 Model No. 105-60108 Model No. 105-4058 Model No. 105-60108
Sec. ml. oz. Sec. ml. oz. Sec. ml. oz. Sec. ml. oz.
162 421.2 14.24 162 945.00 31.95 240 624 21.10 240 1400.00 47.34
164 426.4 14.42 164 956.67 32.35 242 629.2 21.27 242 1411.67 47.73
166 431.6 14.59 166 968.33 32.74 244 634.4 21.45 244 1423.33 48.13
168 436.8 14.77 168 980.00 33.14 246 639.6 21.62 246 1435.00 48.52
170 442 14.94 170 991.67 33.53 248 644.8 21.80 248 1446.67 48.92
172 447.2 15.12 172 1003.33 33.93 250 650 21.98 250 1458.33 49.31
174 452.4 15.29 174 1015.00 34.32 252 655.2 22.15 252 1470.00 49.71
176 457.6 15.47 176 1026.67 34.72 254 660.4 22.33 254 1481.67 50.10
178 462.8 15.65 178 1038.33 35.11 256 665.6 22.50 256 1493.33 50.50
180 468 15.82 180 1050.00 35.50 258 670.8 22.68 258 1505.00 50.89
182 473.2 16.00 182 1061.67 35.90 260 676 22.85 260 1516.67 51.28
184 478.4 16.17 184 1073.33 36.29 262 681.2 23.03 262 1528.33 51.68
186 483.6 16.35 186 1085.00 36.69 264 686.4 23.21 264 1540.00 52.07
188 488.8 16.53 188 1096.67 37.08 266 691.6 23.38 266 1551.67 52.47
190 494 16.70 190 1108.33 37.48 268 696.8 23.56 268 1563.33 52.86
192 499.2 16.88 192 1120.00 37.87 270 702 23.73 270 1575.00 53.26
194 504.4 17.05 194 1131.67 38.27 272 707.2 23.91 272 1586.67 53.65
196 509.6 17.23 196 1143.33 38.66 274 712.4 24.08 274 1598.33 54.05
198 514.8 17.40 198 1155.00 39.06 276 717.6 24.26 276 1610.00 54.44
200 520 17.58 200 1166.67 39.45 278 722.8 24.44 278 1621.67 54.84
202 525.2 17.76 202 1178.33 39.84 280 728 24.61 280 1633.33 55.23
204 530.4 17.93 204 1190.00 40.24 282 733.2 24.79 282 1645.00 55.62
206 535.6 18.11 206 1201.67 40.63 284 738.4 24.96 284 1656.67 56.02
208 540.8 18.28 208 1213.33 41.03 286 743.6 25.14 286 1668.33 56.41
210 546 18.46 210 1225.00 41.42 288 748.8 25.32 288 1680.00 56.81
212 551.2 18.63 212 1236.67 41.2 290 754 25.49 290 1691.67 57.20
214 556.4 18.81 214 148.33 42.21 292 759.2 25.67 292 1703.33 57.60
216 561.6 18.99 216 1260.00 42.61 294 764.4 25.84 294 1715.00 57.99
218 566.8 19.16 218 1271.67 43.00 296 769.6 26.02 296 1726.67 58.39
220 572 19.34 220 1283.33 43.39 298 774.8 26.19 298 1738.33 58.78
222 577.2 19.51 222 1295.00 43.79 300 780 26.37 300 1750.00 59.17
224 582.4 19.69 224 1306.67 44.18 302 785.2 26.55 302 1761.67 59.57
226 587.6 19.87 226 1318.33 44.58 304 790.4 26.72 304 1773.33 59.96
228 592.8 20.04 228 1330.00 44.97 306 795.6 26.90 306 1785.00 60.36
230 598 20.22 230 1341.67 45.37 308 800.8 27.07 308 1796.67 60.75
232 603.2 20.39 232 1353.33 45.76 310 806 27.25 310 1808.33 61.15
234 608.4 20.57 234 1365.00 46.16 312 811.2 27.42 312 1820.00 61.54
236 613.6 20.74 236 1376.67 46.55 314 816.4 27.60 314 1831.67 61.94
238 618.8 20.92 238 1388.33 46.95 316 821.6 27.78 316 1843.33 62.33
240 624 21.10 240 1400.00 47.34 318 826.8 27.95 318 1855.00 62.73
NOTE: Validate pump motor model number to determine chemical dispensing rate.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 36 Revised April 28, 2008
Table 1C - Peristaltic Pump Timing for Specific Chemical Concentrations
(320 to 478 seconds) (See Section 5.4, Item Nos. 29-32)
8822976 Motor 8825611 Motor 8822976 Motor 8825611 Motor
Model No. 105-4058 Model No. 105-60108 Model No. 105-4058 Model No. 105-60108
Sec. ml. oz. Sec. ml. oz. Sec. ml. oz. Sec. ml. oz.
320 832 28.13 320 1866.67 63.12 400 1040 35.16 400 2333.33 78.90
322 837.2 28.30 322 1878.33 63.51 402 1045.2 35.34 402 2345.00 79.29
324 842.4 28.48 324 1890.00 63.91 404 1050.4 35.51 404 2356.67 79.69
326 847.6 28.66 326 1901.67 64.30 406 1055.6 35.69 406 2368.33 80.08
328 852.8 28.83 328 1913.33 64.70 408 1060.8 35.86 408 2380.00 80.48
330 858 29.01 330 1925.00 65.09 410 1066 36.04 410 2391.67 80.87
332 863.2 29.18 332 1936.67 65.49 412 1071.2 36.21 412 2403.33 81.27
334 868.4 29.36 334 1948.33 65.88 414 1076.4 36.39 414 2415.00 81.66
336 873.6 29.53 336 1960.00 66.28 416 1081.6 36.57 416 2426.67 82.06
338 878.8 29.71 338 1971.67 66.67 418 1086.8 36.74 418 2438.33 82.45
340 884 29.89 340 1983.33 67.06 420 1092 36.92 420 2450.00 82.84
342 889.2 30.06 342 1995.00 67.46 422 1097.2 37.09 422 2461.67 83.24
344 894.4 30.24 344 2006.67 67.85 424 1102.4 37.27 424 2473.33 83.63
346 899.6 30.41 346 2018.33 68.25 426 1107.6 37.45 426 2485.00 84.03
348 904.8 30.59 348 2030.00 68.64 428 1112.8 37.62 428 2496.67 84.42
350 910 30.77 350 2041.67 69.04 430 1118 37.80 430 2508.33 84.82
352 915.2 30.94 352 2053.33 69.43 432 1123.2 37.97 432 2520.00 85.21
354 920.4 31.12 354 2065.00 69.83 434 1128.4 38.15 434 2531.67 85.61
356 925.6 31.29 356 2076.67 70.22 436 1133.6 38.32 436 2543.33 86.00
358 930.8 31.47 358 2088.33 70.61 438 1138.8 38.50 438 2555.00 86.39
360 936 31.64 360 2100.00 71.01 440 1144 38.68 440 2566.67 86.79
362 941.2 31.82 362 2111.67 71.40 442 1149.2 38.85 442 2578.33 87.18
364 946.4 32.00 364 2123.33 71.80 444 1154.4 39.03 444 2590.00 87.58
366 951.6 32.17 366 2135.00 72.19 446 1159.6 39.20 446 2601.67 87.97
368 956.8 32.35 368 2146.67 72.59 448 1164.8 39.38 448 2613.33 88.37
370 962 32.52 370 2158.33 72.98 450 1170 39.56 450 2625.00 88.76
372 967.2 32.70 372 2170.00 73.38 452 1175.2 39.73 452 2636.67 89.16
374 972.4 32.87 374 2181.67 73.77 454 1180.4 39.91 454 2648.33 89.55
376 977.6 33.05 376 2193.33 74.17 456 1185.6 40.08 456 2660.00 89.95
378 982.8 33.23 378 2205.00 74.56 458 1190.8 40.26 458 2671.67 90.34
380 988 33.40 380 2216.67 74.95 460 1196 40.43 460 2683.33 90.73
382 993.2 33.58 382 2228.33 75.35 462 1201.2 40.61 462 2695.00 91.13
384 998.4 33.75 384 2240.00 75.74 464 1206.4 40.79 464 2706.67 91.52
386 1003.6 33.93 386 2251.67 76.14 466 1211.6 40.96 466 2718.33 91.92
388 1008.8 34.11 388 2263.33 76.53 468 1216.8 41.14 468 2730.00 92.31
390 1014 34.28 390 2275.00 76.93 470 1222 41.31 470 2741.67 92.71
392 1019.2 34.46 392 2286.67 77.32 472 1227.2 41.49 472 2753.33 93.10
394 1024.4 34.63 394 2298.33 77.72 474 1232.4 41.66 474 2765.00 93.50
396 1029.6 34.81 396 2310.00 78.11 476 1237.6 41.84 476 2776.67 93.89
398 1034.8 34.98 398 2321.67 78.50 478 1242.8 42.02 478 2788.33 94.28
NOTE: Validate pump motor model number to determine chemical dispensing rate.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 37 Revised April 28, 2008
Table 1D - Peristaltic Pump Timing for Specific Chemical Concentrations
(478 to 600 seconds) (See Section 5.4, Item Nos. 29-32)
8822976 Motor 8825611 Motor 8822976 Motor 8825611 Motor
Model No. 105-4058 Model No. 105-60108 Model No. 105-4058 Model No. 105-60108
Sec. ml. oz. Sec. ml. oz. Sec. ml. oz. Sec. ml. oz.
478 1242.8 42.02 478 2788.33 94.28 568 1476.8 49.93 568 3313.33 112.04
480 1248 42.19 480 2800.00 94.68 570 1482 50.10 570 3325.00 112.43
482 1253.2 42.37 482 2811.67 95.07 572 1487.2 50.28 572 3336.67 112.83
484 1258.4 42.54 484 2823.33 95.47 574 1492.4 50.45 574 3348.33 113.22
486 1263.6 42.72 486 2835.00 95.86 576 1497.6 50.63 576 3360.00 113.62
488 1268.8 42.90 488 2846.67 96.26 578 1502.8 50.81 578 3371.67 114.01
490 1274 43.07 490 2858.33 96.65 580 1508 50.98 580 3383.33 114.40
492 1279.2 43.25 492 2870.00 97.05 582 1513.2 51.16 582 3395.00 114.80
494 1284.4 43.42 494 2881.67 97.44 584 1518.4 51.33 584 3406.67 115.19
496 1289.6 43.60 496 2893.33 97.84 586 1523.6 51.51 586 3418.33 115.59
498 1294.8 43.77 498 2905.00 98.23 588 1528.8 51.69 588 3430.00 115.98
500 1300 43.95 500 2916.67 98.62 590 1534 51.86 590 3441.67 116.38
502 1305.2 44.13 502 2928.33 99.02 592 1539.2 52.04 592 3453.33 116.77
504 1310.4 44.30 504 2940.00 99.41 594 1544.4 52.21 594 3465.00 117.17
506 1315.6 44.48 506 2951.67 99.81 596 1549.6 52.39 596 3476.67 117.56
508 1320.8 44.65 508 2963.33 100.20 598 1554.8 52.56 598 3488.33 117.95
510 1326 44.83 510 2975.00 100.60 600 1560 52.74 600 3500.00 118.35
512 1331.2 45.00 512 2986.67 100.99
514 1336.4 45.18 514 2998.33 101.39
516 1341.6 45.36 516 3010.00 101.78
518 1346.8 45.53 518 3021.67 102.17
520 1352 45.71 520 3033.33 102.57
522 1357 45.88 522 3045.00 102.96
524 1362.4 46.06 524 3056.67 103.36
526 1367.6 46.24 526 3068.33 103.75
528 1372.8 46.41 528 3080.00 104.15
530 1378 46.59 530 3091.67 104.54
532 1383.2 46.76 532 3103.33 104.94
534 1388.4 46.94 534 3115.00 105.33
536 1393.6 47.11 536 3126.67 105.73
538 1398.8 47.29 538 3138.33 106.12
540 1404 47.47 540 3150.00 106.51
542 1409.2 47.64 542 3161.67 106.91
544 1414.4 47.82 544 3173.33 107.30
546 1419.6 47.99 546 3185.00 107.70
548 1424.8 48.17 548 3196.67 108.09
550 1430 48.35 550 3208.33 108.49
552 1435.2 48.52 552 3220.00 108.88
554 1440.4 48.70 554 3231.67 109.28
556 1445.6 48.87 556 3243.33 109.67
NOTE: Validate pump motor model number to determine chemical dispensing rate.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 38 Revised April 28, 2008
6.5 Determining Water Usage Requirements
The Sentry III is fully programmable for wash water fill and drain time through the wash program
setup. See Section 5 for programming.
There are three factors that must be considered when determining the amount of water required
during the wash cycle:
1. The first requirement is to ensure there is sufficient water to prevent cavitation of the wash pump.
See Table 2 for minimum water requirements.
2. The second requirement is to ensure that there is sufficient water to maintain a minimum drain
temperature of 115°F (46°C) at the end of the hot-detergent wash cycle. The volume of water
required to satisfy the minimum drain temperature will vary depending on the surface area and
temperature of the milk cooler and the inlet supply water temperature. The installation technician
will need to adjust the fill water volume until the minimum drain temperature is achieved for the
hot-detergent cycle.
3. The third requirement is to ensure that there is sufficient drain time between cycles. This is to
prevent chemical mixing and redeposit of materials on the milk cooler surface.
2. Determine the programmed wash fill time “WFT” from Section 5.4, Item No. 6.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 39 Revised April 28, 2008
Table 3 - Calculated Water Usage (Fill-Time/Supply Pressure)
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 40 Revised April 28, 2008
Figure 28 - Wash Cycle Timing Sequence
The Sentry III provides several programming options for the wash cycles.
START "R1?"
"R4" Optional
"R4?" Optional Pre-Rinse
Post-Rinse "R1T" C/W/H
"R4T" C/W/H "R1C" 1/2-5 min.
"R4C" 1/2-5 min. "R1D" DR1 or 2
"AR"
"AR?" Optional "WD"
Acid-Rinse Optional
"ART" C/W ALL CYCLES: Wash-Delay
"ARC" 1/2-5 min. 0-120 min.
"WFT" Water Fill Time: 3-20 min.
ACID CYCLE, "WWB" MODELS ACID CYCLE, "ADB" MODELS SANITIZE CYCLE
"AR" "AW"
Acid-Rinse Acid-Wash
"ART" C/W "AWT" C/W/H
"ARC" 1/2-5 min. "AWC" 2-10 min.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 41 Revised April 28, 2008
SECTION 7.0 - OPERATING INSTRUCTIONS
7.1 General
! MANDATORY ACTION
The Sentry III control system is designed for —MILK COOLING AND STORAGE— —WASH—
“CAP MUST BE REMOVED” “CAP MUST BE ATTACHED”
easy, touch-of-a-button operation with simple
visual notification of each operational mode SCREEN MUST BE
INSPECTED AND
with bright, LED indicators. CLEANED
REGULARLY.
CAP SCREEN
SENTRY III
®
OFF
COOL WASH
SAMPLE
AGITAT E
0308 8824349
DFE0230
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 42 Revised April 28, 2008
7.2 “Cool-Off-Wash” Rotary-Selector Switch
Select “COOL” for cooling modes, “OFF” for sample agitation and programming or when the milk
cooler is not in use, and “WASH” for cleaning modes.
2. Pressing the “Cooling Bottom Unit” switch a second time will bypass the programmable time delay
and immediately start the bottom refrigeration unit(s).
3. To cancel the bottom or all refrigeration unit(s), turn the “COOL — OFF — WASH” rotary switch to
the “OFF” position.
4. During the cooling cycle, the “Cycle Time” display will show the accumulated run time of the
bottom refrigeration unit(s) in 1/10 hours. The run time will continue to accumulate until the rotary
selector switch is turned to the “OFF” position.
NOTE: The time delay for the “Cooling All Units” will not start timing until the “Cooling Bottom
Unit” time delay expires.
2. After the “Cooling All Units” time delay has expired the “All Units” LED will illuminate and the side
refrigeration unit(s) will energize if the temperature control is calling for cooling.
3. Pressing the “Cooling All Units” switch a second time will bypass the programmable time delay
and immediately start the bottom and side refrigeration units.
4. To cancel the bottom or all refrigeration unit(s), turn the “COOL — OFF — WASH” rotary switch to
the “OFF” position.
2. After the programmed time period expires, the refrigeration unit(s) will return to the normal
cooling mode.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 43 Revised April 28, 2008
3. This feature will pre-cool and blend the milk to 34°F (1.1°C) at the onset of the second, third, or
fourth milkings.
2. This feature blends the warm incoming milk at the onset of the second, third, or fourth milkings.
2. A remote alarm is also incorporated into the relay board inside of the control box. This is a 24-vac
output that can be connected to a remote lamp or buzzer. See wiring schematic for remote alarm
wiring.
2. A remote “Full Tank Alarm” is also incorporated into the relay board inside of the control box. This
is a 24vac output that can be connected to a remote lamp or buzzer. See wiring schematic for
remote alarm wiring.
1. With the rotary switch in the “WASH” position, press the “Detergent Cycle” switch.
2. The “Detergent Cycle” utilizes program parameter “DWP” for detergent dispensing and “ARP” for
acid dispensing.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 44 Revised April 28, 2008
3. A programmable 0 to 120-minute delayed start is available to allow sufficient recovery time for the
water-heating device. If a time delay is programmed, the program will perform the pre-rinse cycle
then delay for the programmed time. After the delay expires the wash cycle will continue with the
rinse, detergent, post rinse, acid/sanitize cycles. See programmable options for “WD.”
4. At the end of the cycle the display will flash “0”, this indicates the wash is complete and another
function may be started.
5. Also incorporated into the detergent wash cycle is a low water temperature alarm “LWT”. The
“LWT” takes a temperature reading during the detergent drain cycle, if this reading is below the
programmed “LWT” at the end of the wash cycle “LWT” will be displayed in the cycle time display.
This is only an indicator of low detergent wash temperatures and all wash cycles function
normally, when the rotary switch is turned to the “OFF” position the alarm is cleared. See
programmable options for “LWT.”
6. To cancel and reset the “WASH” cycle, turn the “COOL — OFF — WASH” rotary switch to the
“OFF” position.
2. Press once to advance to drain of current cycle. This allows water and chemicals to be drained
before the next cycle can be started to prevent mixing of chemicals in the milk cooler.
2. The acid cycle switch utilizes program parameter “AWP” for acid dispensing.
3. To cancel and reset the “ACID WASH,” turn the “COOL — OFF — WASH” rotary switch to the
“OFF” position.
2. The sanitize cycle switch utilizes program parameter “SRP” for sanitizer dispensing.
3. To cancel and reset the “SANITIZE” cycle, turn the “COOL — OFF — WASH” rotary switch to the
“OFF” position.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 45 Revised April 28, 2008
7.15 Agitate Sample Switch
1. With the rotary selector switch in the “OFF” position, press the “Agitate Sample” switch once to
start the agitator(s) for milk sampling. The agitator(s) will operate for the programmed period of 5
or 10 minutes, and shut off automatically. See Sections 5.2, Item No. 10.
2. During the cooling cycle, the “Cycle Time” display will show the accumulated run time of the
bottom refrigeration unit(s) in 1/10 hours. The run time will continue to accumulate until the rotary
selector switch is turned to the “OFF” position.
3. During the wash cycles, the “Cycle Time” display will count down the time remaining in the wash
cycle and display a flashing “0” when complete. Turning the rotary switch to the “OFF” position
will clear the display.
4. The “Cycle Time” display is also utilized to display the parameter settings while programming the
Sentry III.
7.18 Cooling Override Switch (FOR AUTHORIZED SERVICE TECHNICIAN USE ONLY)
WARNING! RISK OF ELECTRICAL SHOCK. Failure to disconnect power from Sentry III control
before servicing may result in death or serious injury. Service should be performed by an
authorized service technician only.
1. The Sentry III has an emergency override switch located inside the enclosure. This will override
the temperature control and several other components and engage the bottom refrigeration unit(s)
and agitator(s) in an emergency situation.
2. To access and activate this switch, turn the power off to the Sentry III control box, open the door
and move this switch to the “Manual” position. Close the door, secure the door screws, and
reapply power.
IMPORTANT NOTE: There will be no automatic temperature control in the “Manual Over-Ride
! Position.” When the product temperature is at a safe holding temperature, turn the power supply off to
the Sentry III control. (This switch is for authorized Mueller Technician use only.)
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 46 Revised April 28, 2008
SECTION 8.0 - WEIGHTS AND DIMENSIONS
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 47 Revised April 28, 2008
8.2 Metric Weights and Dimensions
Dimensions not to be used for construction unless certified.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 48 Revised April 28, 2008
SECTION 9.0 - SENTRY III EQUIPMENT MARKINGS
9.2 Label No. 8820482, Caution - Disconnect Power and Retain Latch
HOT
3791
COLD
3792
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 49 Revised April 28, 2008
9.9 Label No. 8823014, Warning - Chemical Pump Priming
WARNING
▲ WEAR EYE PROTECTION, RUBBER GLOVES, AND APRONS WHEN
HANDLING CHEMICALS.
▲ FOLLOW ALL INSTRUCTIONS, WARNINGS, AND HEALTH HAZARD
INFORMATION PROVIDED BY THE CHEMICAL MANUFACTURER.
▲ SEE MANUAL FOR PRIMING INSTRUCTIONS.
▲ DO NOT PRIME CHEMICAL PUMPS INTO THE FLO AT VALV E
ASSEMBLY. PRIME INTO A CLEAN CONTAINER ONLY.
▲ DO NOT MIX CHEMICALS—A HAZARDOUS VAPOR COULD RESULT.
▲ WITHOUT PROPER DILUTION, CHEMICALS CAN DAMAGE THE
STAINLESS STEEL MILK COOLER.
AVERTISSEMENT
▲ PORTER UN PROTECTEUR OCULAIRE, GANTS DE CAOUTCHOUC ET
TABLIER LORS DE LA MANUTENTION DES PR ODUITS CHIMIQUES.
▲ SUIVRE TOUTES LES INSTRUCTIONS, ALERTES ET INFORMATION
SUR LE DANGER POUR LA SANTÉ FOURNIS PAR LE FABRICANT DU
PRODUIT CHIMIQUE.
▲ VOIR LE MANUEL POUR L’ APPRÊTAGE.
▲ NE PAS AMORCER LES POMPES POUR PRODUITS CHIMIQUES DANS
L’ ASSEMBLAGE DU RÉGLEUR À FLOTTEUR. AMORCER SEULEMENT
DANS UN CONTENANT PROPRE.
▲ NE PAS MÉLANGER LES PRODUITS CHIMIQUES. UNE VAPEUR
DANGEREUSE POURRAIT ÊTRE PROVOQUÉE.
▲ SI LES PRODUITS CHIMIQUES NE SONT PAS PROPREMENT DILUÉS.
ILS PEUVENT ENDOMMAGER LES BASSINS À LAIT EN ACIER
INOXYDABLE.
¡ADVERTENCIA!
▲ USE GUANTES Y DELANTAL DE HULE ASÍ COMO GAFAS DE SEGURIDAD
DURANTE EL MANEJO DE QUÍMICOS.
▲ SIGA TODAS LAS INSTRUCCIONES, ADVERTENCIAS Y LEA
CUIDADOSAMENTE TODA LA INFORMACIÓN SOBRE LOS RIESGOS A LA
SALUD PROPORCIONADOS POR EL PROVEEDOR DE QUÍMICOS.
▲ LEA EL MANUAL DE INSTRUCCIONES SOBRE PURGADO.
▲ NO PURGUE LAS BOMBAS DE QUÍMICOS EN EL ENSAMBLE DE LA
VÁLVULA DE FLOTACIÓN. PURGUE LAS BOMBAS A UN RECIPIENTE
LIMPIO ÚNICAMENTE.
▲ NO MEZCLE LOS QUÍMICOS — UN VAPOR PELIGROSO PUEDE
FORMARSE.
▲ SIN LA APROPIADA DISOLUCIÓN, LOS QUÍMICOS, PUEDEN DAÑAR EL
ACERO INOXIDABLE DE SU TANQUE ENFRIADOR.
0408 8823014
WARNING
DISCONNECT CONTROL
CABINET FROM MAIN POWER
SUPPLY BEFORE SERVICING.
AVERTISSEMENT
DÉBRANCHER L’ARMOIRE DE
COMMANDE DE LA SOURCE
ÉLECTRIQUE PRINCIPALE
AVANT D’EFFECTUER LA
MAINTENANCE.
¡ADVERTENCIA!
CORTE EL SUMINISTRO
PRINCIPAL DE CORRIENTE
ELÉCTRICA ANTES DE DAR
SERVICIO AL GABINETE DE
CONTROL.
0408 8823013
Year of Construction
Année de fabrication
Año de fabricación
Model Number
Numéro de modèle
Número de modelo
Serial Number
Numéro de série
Número de serie
Noise Level
Niveau de bruit
Nivel de ruido
Weight
Poids
Peso
0408 8822225
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 50 Revised April 28, 2008
9.12 Label No. 8801150, Warning - Disconnect Power Before Servicing
WARNING
DISCONNECT BOTH CONDENSING
UNIT AND CONTROL CABINET
FROM MAIN POWER SUPPLY
BEFORE SERVICING.
AVERTISSEMENT
DÉBRANCHEZ L’ UNITÉ
RÉFRIGÉRANTE ET LA BOÎTE DE
CONTRÔLE DU SYSTÈME
D’ALIMENTATION ÉLECTRIQUE
AVANT DE RÉPARER.
¡ADVERTENCIA!
DESCONECTE LAS UNIDADES DE
CONDENSACIÓN Y EL GABINETE
DE CONTROL DEL SUMINISTRO
ELÉCTRICO PRINCIPAL ANTES DE
DAR SERVICIO.
0408 8801150
PA U L M U EL L E R C OM PA N Y
M I L K C OOL ER
MODEL PA RT NO. SERIAL NO.
8820410
Notice
The accuracy of these charts depends upon the proper
installation of the cooler.
IMPORTANT
THIS EQUIPMENT CONTAINS A HOLDING CHARGE OF DRY
NITROGEN GAS. SLOWLY RELEASE PRESSURE THROUGH SERVICE
PORTS OR SCHRADER VALVES BEFORE REMOVING FITTINGS.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 51 Revised April 28, 2008
9.16 Label No. 8822705, Canadian and U.S. Certification
LR67608
NPI 8822705
9.17 Label No. 8805299, Warning - HCFC Class II Refrigerant (To Be Applied After Installation)
WA R N I N G
THIS EQUIPMENT CONTAINS R-22 HYDROCHLOROFLUOROCARBON (HCFC CLASS II)
A SUBSTANCE THAT, IF RELEASED INTO THE ENVIRONMENT, WILL CONTRIBUTE TO A SERIOUS PUBLIC HEALTH AND ENVIRONMENTAL
PROBLEM BY DEPLETING THE OZONE LAYER. OZONE LAYER DEPLETION INCREASES THE RISK OF SKIN CANCER AND OTHER DISEASES
IN HUMANS AND IS HARMFUL TO PLANT AND ANIMAL LIFE.
THIS EQUIPMENT SHALL BE SERVICED AND DISPOSED OF ONLY IN ACCORDANCE WITH THE OZONE DEPLETING SUBSTANCES
REGULATION - CLEAN ENVIRONMENT ACT.
N.B. This regulation is consolidated to September 30, 1992.
PRODUCT
Stainless
Steel
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 52 Revised April 28, 2008
9.21 Label No. 8822558, Mueller Milk Cooler Data Tag
®
MUELLER MILK COOLER
Model & Nominal Capacity U.S. Gallons Calibrated Capacity Serial Number Refrigerant
Evaporator Design Note: For electrical characteristics of the condensing unit, refer to the data plate on the condensing unit.
Working Pressure PSI This cooler is designed for use with a Mueller cooling control and wash system.
This cooler is designed for every-day or every-other-day pickup. The maximum rate at which milk can
enter the cooler and meet the cooling requirements of the 3-A Sanitary Standards for Farm Milk Cooling and Holding Tanks, Serial Number
13-09, is U.S. gallons per hour for every-day pickup and U.S. gallons per hour for every-other-day
pickup. When milk enters the cooler at the maximum rate, the minimum condensing unit capacity is Btu/hr at
°F saturated suction temperature. The agitator of this cooler is designed that it must be in continuous operation
minutes before removing a product sample. The agitator of this tank is designed so that the portion of the
agitator shaft outside of the farm tank does not have to be in the milk room when used with an external weather shield. NUMBER 13-09
Note: The cooling performance specified above is based upon use of the largest condensing unit recommended for this cooler.
Smaller condensing units may be used, but at reduced fill rates. Contact your Mueller dealer for assistance in condensing unit sizing.
9.22 Label No. 30166, Caution - Vent Must Be Over Milk Inlet
CAUTION
VENT ASSEMBLY
MUST BE OVER
MILK INLET AT
ALL TIMES.
MISE EN GARDE
LE MONTAGE DE
VENTILATION DOIT
ÊTRE AU DESSUS DE
L’ENTRÉE DU LAIT
EN TOUT TEMPS.
¡PRECAUCIÓN!
EL ENSAMBLE DE
RESPIRACIÓN DEBE
ESTAR SOBRE LA
ENTRADA DE LECHE
EN TODO MOMENTO.
0408 30166
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 53 Revised April 28, 2008
9.24 Label No. 8824401, Mandatory Action
! MANDATORY ACTION
—MILK COOLING AND STORAGE— —WASH—
“CAP MUST BE REMOVED” “CAP MUST BE ATTACHED”
SCREEN MUST BE
INSPECTED AND
CLEANED
REGULARLY.
CAP SCREEN
! ACTION OBLIGATOIRE
—REFROIDISSEMENT ET —LAVAGE—
ENTREPOSAGE DU LAIT— “LE BOUCHON DOIT ÊTRE ATTACHÉ”
“LE BOUCHON DOIT ÊTRE ENLEVÉ”
LE GRILLAGE
DOIT ÊTRE
RÉGULIÈREMENT
INSPECTÉ ET
NETTOYÉ
BOUCHON GRILLAGE
! ACCION OBLIGATORIA
—DURANTE EL ALMACENAJE Y —DURANTE EL LAVADO—
ENFRIAMIENTO DE LECHE— “EL TAPÓN DEBE ESTAR PUESTO”
“EL TAPÓN DEBE SER REMOVIDO”
LA MALLA
DEBE SER
INSPECCIONADA Y
LIMPIADA
REGULARMENTE
TAPÓN MALLA
0408 8824401
Wire Terminal
1 #1 L1 Main Power
(240v)
2 #2 L2 Main Power
3 #3 Agitator (Wire 1)
4 #4 Agitator (Wire 2)
5 #5 Condenser #1
6 #6 Condenser #2
7 #7 Remote Alarm
8 #8 Remote Wash
0403
9 #9 Remote Cool
(24v)
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 54 Revised April 28, 2008
SECTION 10.0 - SAFETY
Safety/Alert: See all safety, warning, and caution labels displayed in Section 9.
10.1 General
1. The Mueller milk cooler and Sentry III control system should be operated by qualified personnel
who are familiar with the equipment and instructions.
2. Improper handling, operation, or service of the equipment, cleaning chemicals, and/or electricity
can create a health hazard and possible non-warranted damage to the equipment.
3. An authorized Mueller Service Representative who is trained and certified in electrical and
refrigeration work must perform all service.
4. The equipment can start automatically! Use extreme caution when servicing. All guards and covers
must be in place during operation to prevent mechanical and electrical hazards.
In the need to enter the milk cooler for inspection or maintenance follow the “Confined Entry” laws
and perform the following steps:
WARNING: Failure to perform the following steps can present personal injury due to live
moving parts and possible electrical shock.
1. Disconnect and lock-out the main power supply to the milk cooler prior to entry.
2. Remove the milk cooler manway lock and locking strap and retain during entry.
3. Detach the milk cooler manway cover and place in secure location.
Proper use of the fixed ladder system will contribute significantly to safety. Haste, sudden movements,
lack of attention during use, ladder condition (worn or damaged), and physical condition contribute to
falls. The footwear employed by the user may also contribute to falls. Improper climbing posture
which creates user clumsiness on the ladder may also cause falls. Ladders shall be routinely inspected
to ensure they meet the criteria set forth by the American National Standards Institute (ANSI) and
Occupational Safety and Health Act (OSHA).
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 55 Revised April 28, 2008
A. Inspection — ANSI and OSHA recommend performing the following checklist before each use:
4. Inspect all ladder welds to ensure they are secure and free of cracks.
5. Inspect all mounting hardware to ensure that it is tight, secure, and free of wear.
B. Proper Use
1. When ascending/descending a ladder, the user shall face the ladder and maintain a three-point
contact at all times. Three-point contact consists of two feet and one hand or two hands and
one foot, which is safely supporting user’s weight when ascending/descending ladders.
2. The user shall not carry tools or equipment while ascending/descending a ladder. Both hands
and arms shall remain free for climbing. Hand tools shall be carried in a pouch holster or
otherwise secured, to help avoid creating a hazard. Alternative methods, other than being
carried by the ladder user, shall be implemented to handle materials and supplies.
3. The user shall never jump or slide down from a ladder or climb more than one step/rung at a
time.
6. Do not use a ladder when impaired with a medical condition or influenced by any drug.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 56 Revised April 28, 2008
SECTION 11.0 - DISPOSAL
11.1 General
If the milk cooler and controls are removed from the installation site, ensure the materials, refrigerants,
and chemicals are handled and/or disposed of according to applicable codes and regulations.
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 57 Revised April 28, 2008
®
Sentry® III Service Reference Form
Programmable Features
Please complete for future service reference:
Name: Name:
Address: Address:
Phone: Phone:
Contact: Contact:
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 58 Revised April 28, 2008
Sentry® III Service Reference Form - Programmable Features - Page 2
Please record the selected program options:
Comments:
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 59 Revised April 28, 2008
Figure 18a - Control Box Wiring Schematic
WARNING! RISK OF ELECTRICAL SHOCK. CAN CAUSE INJURY OR DEATH.
DISCONNECT ALL REMOTE ELECTRIC POWER SUPPLIES TO THE SENTRY III
CONTROL CABINET BEFORE SERVICING.
POWER BOARD
RELAY BOARD
LOGIC BOARD
HIGH VOLTAGE
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 Revised April 28, 2008
Figure 18b - Rear Junction Box Field Wiring (Full Cabinet Models)
8002256 (8824864)
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 Revised April 28, 2008
Figure 19 - Rear Junction Box Field
Wiring (Half-Cabinet - 400C, 500,
and 600 Gallon Models)
Sentry III “OHF” Installation and Operation Manual Effective May 26, 2004
Part No. 8824990 Revised April 28, 2008
®