You are on page 1of 38

1 2 3 4 5 6 7 8

A A
ELECTRIFICATION DISTRIBUTION SOLUTION FACTORY, VIET NAM
Lot C3, TS3 Road, Tien Son IZ, Dong Nguyen, Tu Son, Bac Ninh
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B B

Project Title : BYD FACTORY

Project No. : UG23021


C C
Purchaser : BYD

Client :

Sale Order Number : 4202786788

D D

FOR APPROVAL
KINDLY TICK THE FOLLOWING BOX

1 Reviewed & Accepted as Final & Certified.


Manufacture may proceed

2 Reviewed & Accepted as Noted. Revise and Resubmit


Manufacture may proceed
E E
3 Reviewed & Returned. Correct and Resubmit
Manufacture should not proceed

4 Not Reviewed, Information only


Manufacture may proceed

Substation : 12kV SWITCHGEAR FACTORY NO.7 All comments and correction from customer should be mark in red.
This approval drawing should be returned within 2 working weeks.
Drawing Title: GENERAL DRAWINGS No manufacturing work will start before approval.

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


D FOR REVISION 26/09/23 PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 11/08/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1: 1
B FOR REVISION 05/09/23 CUSTOMER: COVER SHEET START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00/A00
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: B01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

TABLE OF CONTENTS
PAGE NAME DRAWING Nr. SHEET Nr. PAGE REVISION
A GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00/A00 A B C D A
COVER SHEET
GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00/B01 A B C D
TABLE CONTENTS
GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00/C00 A B
TECHNICAL DATA
GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00+SLD/A01 A B C D
SINGLE LINE DIAGRAM
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00+SLD/A02 A B C D


SINGLE LINE DIAGRAM
B GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00+SLD/A03 A B B
SINGLE LINE DIAGRAM
GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00+SLD/A04 A B C D
SINGLE LINE DIAGRAM
GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00+GA/D01 A B
GENERAL ARRANGEMENT
GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00+GA/D02 A B
GENERAL ARRANGEMENT
GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00+GA/D03 A B
PLAN VIEW
C C
GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00+GA/D04 A B C
PLAN VIEW
GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00+GA/D05 A B
DETAIL OF SWITCHGEAR INSTALLATION
GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00+GA/D06 A B C
SECTIONAL VIEW
GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00+GA/D07 A B C
SECTIONAL VIEW
GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00+GA/D08 A B C
D SECTIONAL VIEW D
GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00+GA/D09 A B C
SECTIONAL VIEW
GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00+GA/D10 A B C
SECTIONAL VIEW
GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00+GA/D11 A B C
SECTIONAL VIEW
GENERAL DRAWINGS 1YUX200001A0302 ==SWG3=J00+GA/E01 A B C
PANEL RATING

E E

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


D FOR REVISION 26/09/23 PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
BYD FACTORY GENERAL DRAWINGS
C FOR REVISION 11/08/23 SCALE: 1: 1
B FOR REVISION 05/09/23 CUSTOMER: TABLE CONTENTS START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00/B01
EPDS FACTORY, BAC NINH
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 3748 530, TELEFAX: (+84) (222) 3748 531 CONT.: C00
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

NO. CATOGARY DESCRIPTION NO. CATOGARY QTY. DESCRIPTION


1 TECHNICAL System : 10kV 3 PHASE 3 WIRE 50Hz 9 PACKING DETAILS Domestic
CHARACTERISTIC Rated Voltage : 12 kV
Power-frequency withstand voltage: 28 kV
Lighting impulse withstand voltage: 75 kV 10 NOTE
Rate short time withstand current: 25 kA / 3s
Rate peak withstand current: 63 kA
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

2 CONSTRUCTION Type : UniGear ZS1


Material : Metal-clad Switchgear
Access Location : Front Access
B Switching Device Type : Withdrawable Vacuum Circuit Breaker B
Degree of Protection : External - IP 4X, Internal - IP 2X
3 PAINT FINISH Doors and End Covers : RAL7035 "Light Grey"
Remainder : Aluminium-Zinc Steel Sheets 11 REMARKS
4 BUSBAR RATING Main Busbar Rated Current : 1250 A Size : 1 x 80 x 10mm²
Earth Bar Size : 1 x 30 x 8mm²
Insulation : YES Finishing : Bare Copper
5 AUXILIARY CIRCUIT Voltage Supply :
- Protection, Control & Indication 110V DC
- Circuit Breaker Spring Charge Motor 110V DC
- Panel Heater & Cubicle Lighting 220V AC, 50Hz
Wire Size :
C - Control Circuit 1.5mm² Colour : Grey C
- Lighting & Heating Circuit 1.5mm² Colour : Black
- Current Transformer
Phase L1 4.0mm² Colour : Red
Phase L2 4.0mm² Colour : Yellow
Phase L3 4.0mm² Colour : Blue
Phase N 4.0mm² Colour : Black
- Voltage Transformer
Phase L1 2.5mm² Colour : Red
Phase L2 2.5mm² Colour : Yellow
Phase L3 2.5mm² Colour : Blue
Phase N 2.5mm² Colour : Black
D - Earthing Cable 2.5mm² Colour : Green/Yellow D
Wire Specification : 450/750V
Terminal Block : PHOENIX CONTACT
Test Terminal Block : YONGSUNG
Cable Termination : Blade
Cable Marker : Hot Marker
Cable Tray : Self-Extinguishing, Warp Proof PVC
Maximum Service Temperature : 85°C
6 POWER CABLE Entry : Bottom
Maximum Cable Size :
Terminating Facility : Undrilled Aluminium Gland Plate Only
7 CONTROL CABLE Entry : Bottom
E 8 LABEL Black Letter on White Background E
Material : Plastic
Fixing : Internal - Self Adhesive
External - Self Adhesive

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
BYD FACTORY GENERAL DRAWINGS SCALE: 1: 1
B FOR REVISION 11/08/23 CUSTOMER: TECHNICAL DATA START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00/C00
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: +SLD/A01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A 3P3W, 12kV, 1250A, 25kA/3s, 50Hz A


TO NEXT PAGE

-QB
-QB -QB -QB -QB -QB -QB 400A
VCB VCB VCB VCB VCB VCB
M 1250A M 1250A M 1250A M 1250A M 1250A M 1250A

P2 -BC P1 -BC P1 -BC P1 -BC P1 -BC P1 -BC


This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B P2 P2 P2 P2 P2 B
P1

-SA

-BV -QE -QE -QE -QE -QE -R


10KV 7%

EARTHING BUS BAR


TO NEXT PAGE
-PU -PU -PU -PU -PU -PU -PU

C C
10kV-300KVAR

PANEL NUMBER =MV-TR1.1 =MV-TR1.2 =MV-TR1.3 =MV-TR1.4 =MV-TR1.5 =MV-TR1.6 =MV-TR1.7 =MV-TR1.7A
INCOMING PANEL OUTGOING PANEL OUTGOING PANEL OUTGOING PANEL OUTGOING PANEL OUTGOING PANEL CAPACITOR PANEL
MAIN LABEL

MAIN SWITCH VD4/P 12.12.25 P150 VD4/P 12.12.25 P150 VD4/P 12.12.25 P150 VD4/P 12.12.25 P150 VD4/P 12.12.25 P150 VD4/P 12.12.25 P150 ConVac 12/P 400A SCO
D 400/5/1/1A 100/5/5A 100/5/5A 100/5/5A 100/5/5A 100/5/5A
D
CURRENT TRANSFORMER C1: CL0.5, 15VA C1: CL0.5, 15VA C1: CL0.5, 15VA C1: CL0.5, 15VA C1: CL0.5, 15VA C1: CL0.5, 15VA
C2, C3: CL5P15, 20VA C2: CL5P15, 15VA C2: CL5P15, 15VA C2: CL5P15, 15VA C2: CL5P15, 15VA C2: CL5P15, 15VA

CABLE CT
EARTHING SWITCH EK6 EK6 EK6 EK6 EK6
HV FUSE 2A 50A
SURGE ARRESTER SCIHE12(Uc=10.2KV, Ur=12KV)
10 0.11 0.11
V3 V3 V3
VOLTAGE TRANSFORMER CL0.5/3P
30VA/50VA

CAP VOLTAGE DIVIDER 1 1 1 1 1 1 1


DAMPING RESISTOR
E E
PROTECTION REF615-HBFNAEAGNBC1BNA11G REX6101GMBANNNNA REX6101GMBANNNNA REX6101GMBANNNNA REX6101GMBANNNNA REX6101GMBANNNNA
DEVICES 50/50N, 51/51N, 59G, 27/59, 25, 50BF 50/51, 50/51N, 59G, 49, 50BF 50/51, 50/51N, 59G, 49, 50BF 50/51, 50/51N, 59G, 49, 50BF 50/51, 50/51N, 59G, 49, 50BF 50/51, 50/51N, 59G, 49, 50BF

MEASURING MULTI METER MULTI METER MULTI METER MULTI METER MULTI METER MULTI METER
INSTRUMENTS M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5
MULTI TARIFF METER
ELSTER A1700, CL0.5

COMMUNICATION IEC61850 IEC61850 IEC61850 IEC61850 IEC61850 IEC61850


POWER CABLE 1x1C-185mm²/phase - - - - - 1x1C-35mm²/phase

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


D FOR REVISION 26/09/23 PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 11/08/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 1.2
B FOR REVISION 05/09/23 CUSTOMER: SINGLE LINE DIAGRAM START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00+SLD/A01
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: A02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A 3P3W, 12kV, 1250A, 25kA/3s, 50Hz 3P3W, 12kV, 1250A, 25kA/3s, 50Hz A
FROM PREVIOUS PAGE TO NEXT PAGE

-QB -QB
400A 400A -QB -QB
VCB VCB
M 1250A M 1250A

M M

P1 -BC P1 -BC
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B P2 P2 B

-R -R -QE -QE
10KV 7% 10KV 7%

FROM PREVIOUS PAGE EARTHING BUS BAR


TO NEXT PAGE
-PU -PU -PU -PU -PU

C C
10kV-400KVAR 10kV-300KVAR

PANEL NUMBER =MV-TR1.8 =MV-TR1.8A =MV-TR1.9 =MV-TR1.9A =MV-LL =MV-TC =MV-TR2.8


CAPACITOR PANEL CAPACITOR PANEL BUS SECTION PANEL BUS RISER PANEL OUTGOING PANEL
MAIN LABEL

MAIN SWITCH ConVac 12/P 400A SCO ConVac 12/P 400A SCO VD4/P 12.12.25 P150 VD4/P 12.12.25 P150
D 250-500/5/5A 100/5/5A
D
CURRENT TRANSFORMER C1: CL0.5, 15VA C1: CL0.5, 15VA
C2: CL5P15, 15VA C2: CL5P15, 15VA

CABLE CT
EARTHING SWITCH EK6 EK6
HV FUSE 50A 50A
SURGE ARRESTER

VOLTAGE TRANSFORMER

CAP VOLTAGE DIVIDER 1 1 1 1


DAMPING RESISTOR
E E
PROTECTION REF615-HBFNAEAGNBC1BNA11G REX6101GMBANNNNA
DEVICES 50/50N, 51/51N, 25, 49, 86 50/51, 50/51N, 59G, 49, 50BF

MEASURING MULTI METER MULTI METER


INSTRUMENTS M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5

COMMUNICATION IEC61850 IEC61850


POWER CABLE 1x1C-35mm²/phase 1x1C-35mm²/phase 1x1C-35mm²/phase 1x1C-35mm²/phase - -

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


D FOR REVISION 26/09/23 PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 11/08/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 1.2
B FOR REVISION 05/09/23 CUSTOMER: SINGLE LINE DIAGRAM START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00+SLD/A02
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: A03
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A 3P3W, 12kV, 1250A, 25kA/3s, 50Hz A


FROM PREVIOUS PAGE TO NEXT PAGE

-QB -QB
400A 400A -QB -QB -QB
VCB VCB VCB
M 1250A M 1250A M 1250A

M M

P1 -BC P1 -BC P1 -BC


This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B P2 P2 P2 B

-R -R -QE -QE -QE


10KV 7% 10KV 7%

FROM PREVIOUS PAGE EARTHING BUS BAR


TO NEXT PAGE
-PU -PU -PU -PU -PU

C C
10kV-400KVAR 10kV-300KVAR

PANEL NUMBER =MV-TR2.7 =MV-TR2.7A =MV-TR2.6 =MV-TR2.6A =MV-TR2.5 =MV-TR2.4 =MV-TR2.3


CAPACITOR PANEL CAPACITOR PANEL OUTGOING PANEL OUTGOING PANEL OUTGOING PANEL
MAIN LABEL

MAIN SWITCH ConVac 12/P 400A SCO ConVac 12/P 400A SCO VD4/P 12.12.25 P150 VD4/P 12.12.25 P150 VD4/P 12.12.25 P150
D 100/5/5A 100/5/5A 100/5/5A
D
CURRENT TRANSFORMER C1: CL0.5, 15VA C1: CL0.5, 15VA C1: CL0.5, 15VA
C2: CL5P15, 15VA C2: CL5P15, 15VA C2: CL5P15, 15VA

CABLE CT
EARTHING SWITCH EK6 EK6 EK6
HV FUSE 50A 50A
SURGE ARRESTER

VOLTAGE TRANSFORMER

CAP VOLTAGE DIVIDER 1 1 1 1 1


DAMPING RESISTOR
E E
PROTECTION REX6101GMBANNNNA REX6101GMBANNNNA REX6101GMBANNNNA
DEVICES 50/51, 50/51N, 59G, 49, 50BF 50/51, 50/51N, 59G, 49, 50BF 50/51, 50/51N, 59G, 49, 50BF

MEASURING MULTI METER MULTI METER MULTI METER


INSTRUMENTS M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5

COMMUNICATION IEC61850 IEC61850 IEC61850


POWER CABLE 1x1C-35mm²/phase 1x1C-35mm²/phase 1x1C-35mm²/phase 1x1C-35mm²/phase - - -

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 1.2
B FOR REVISION 11/08/23 CUSTOMER: SINGLE LINE DIAGRAM START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00+SLD/A03
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: A04
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A 3P3W, 12kV, 1250A, 25kA/3s, 50Hz A


FROM PREVIOUS PAGE

-QB -QB
VCB VCB
M 1250A M 1250A

P1 -BC P2 -BC
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B P2 B
P1

-SA

-QE -BV

FROM PREVIOUS PAGE EARTHING BUS BAR

-PU -PU

C C

PANEL NUMBER =MV-TR2.2 =MV-TR2.1


OUTGOING PANEL INCOMING PANEL
MAIN LABEL

MAIN SWITCH VD4/P 12.12.25 P150 VD4/P 12.12.25 P150


D 100/5/5A 400/5/1/1A
D
CURRENT TRANSFORMER C1: CL0.5, 15VA C1: CL0.5, 15VA
C2: CL5P15, 15VA C2, C3: CL5P15, 20VA

CABLE CT
EARTHING SWITCH EK6
HV FUSE 2A
SURGE ARRESTER SCIHE12(Uc=10.2KV, Ur=12KV)
10 0.11 0.11
V3 V3 V3
VOLTAGE TRANSFORMER CL0.5/3P
30VA/50VA

CAP VOLTAGE DIVIDER 1 1


DAMPING RESISTOR
E E
PROTECTION REX6101GMBANNNNA REF615-HBFNAEAGNBC1BNA11G
DEVICES 50/51, 50/51N, 59G, 49, 50BF 50/50N, 51/51N, 59G, 27/59, 25, 50BF

MEASURING MULTI METER MULTI METER


INSTRUMENTS M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5
MULTI TARIFF METER
ELSTER A1700, CL0.5

COMMUNICATION IEC61850 IEC61850


POWER CABLE - 1x1C-185mm²/phase

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


D FOR REVISION 26/09/23 PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 11/08/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 1.2
B FOR REVISION 05/09/23 CUSTOMER: SINGLE LINE DIAGRAM START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00+SLD/A04
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: +GA/D01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

15660 mm

A A
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

2200

B B

30 650 650 650 650 650 650 650 650 650 650 650 650
C C

PANEL NO. =MV-TR1.1 =MV-TR1.2 =MV-TR1.3 =MV-TR1.4 =MV-TR1.5 =MV-TR1.6 =MV-TR1.7 =MV-TR1.7A =MV-TR1.8 =MV-TR1.8A =MV-TR1.9 =MV-TR1.9A

PANEL TYPE OUTGOING OUTGOING OUTGOING OUTGOING OUTGOING OUTGOING CAPACITOR CAPACITOR CAPACITOR CAPACITOR CAPACITOR CAPACITOR

D D
CIRCUIT BREAKER VD4/P-1250A VD4/P-1250A VD4/P-1250A VD4/P-1250A VD4/P-1250A VD4/P-1250A ConVac 12/P 300KVAR ConVac 12/P-400A 400KVAR ConVac 12/P-400A 300KVAR

FRONT
PANEL DEPTH : 1340mm

E E

LEGEND:
11 GUIDING HOLE FOR CB/VT TRUCK
12 OPENING FOR EARTH SWITCH AND INDICATOR
13 OPENING FOR RACKING IN & RACKING OUT OF CIRCUIT BREAKER/VOLTAGE TRANSFORMER
14 OPENING FOR MANUAL SPRING CHARGED WHEN CB DOOR IS CLOSING

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 25
B FOR REVISION 11/08/23 CUSTOMER: GENERAL ARRANGEMENT START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00+GA/D01
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

15660 mm
A A
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B B

C 650 650 650 650 650 650 650 650 650 650 650 650 C
30

PANEL NO. =MV-LL =MV-TC =MV-TR2.8 =MV-TR2.7 =MV-TR2.7A =MV-TR2.6 =MV-TR2.6A =MV-TR2.5 =MV-TR2.4 =MV-TR2.3 =MV-TR2.2 =MV-TR2.1

PANEL TYPE BUS SECTION BUS RISER OUTGOING CAPACITOR CAPACITOR CAPACITOR CAPACITOR OUTGOING OUTGOING OUTGOING OUTGOING INCOMING
D D

CIRCUIT BREAKER VD4/P-1250A VD4/P-1250A VD4/P-1250A ConVac 12/P-400A 400KVAR ConVac 12/P-400A 300KVAR VD4/P-1250A VD4/P-1250A VD4/P-1250A VD4/P-1250A VD4/P-1250A

FRONT
PANEL DEPTH : 1340mm

E E

LEGEND:
11 GUIDING HOLE FOR CB/VT TRUCK
12 OPENING FOR EARTH SWITCH AND INDICATOR
13 OPENING FOR RACKING IN & RACKING OUT OF CIRCUIT BREAKER/VOLTAGE TRANSFORMER
14 OPENING FOR MANUAL SPRING CHARGED WHEN CB DOOR IS CLOSING

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 25
B FOR REVISION 11/08/23 CUSTOMER: GENERAL ARRANGEMENT START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00+GA/D02
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D03
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

=MV-TR1.1 =MV-TR1.2 =MV-TR1.3 =MV-TR1.4 =MV-TR1.5 =MV-TR1.6 =MV-TR1.7 =MV-TR1.7A =MV-TR1.8 =MV-TR1.8A =MV-TR1.9 =MV-TR1.9A
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B B

opening for power opening for power opening for power opening for power opening for power opening for power opening for power opening for power opening for power opening for power opening for power opening for power
cables cables cables cables cables cables cables cables cables cables cables cables

6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole
(36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20)

opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control
cables cables cables cables cables cables cables cables cables cables cables cables

C 650 650 650 650 650 650 650 650 650 650 650 650 C

D FRONT D

E E

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 25
B FOR REVISION 11/08/23 CUSTOMER: PLAN VIEW START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00+GA/D03
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D04
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

=MV-LL =MV-TC =MV-TR2.8 =MV-TR2.7 =MV-TR2.7A =MV-TR2.6 =MV-TR2.6A =MV-TR2.5 =MV-TR2.4 =MV-TR2.3 =MV-TR2.2 =MV-TR2.1
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B B

opening for power opening for power opening for power opening for power opening for power opening for power opening for power opening for power opening for power opening for power
cables cables cables cables cables cables cables cables cables cables

6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole
(36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20)

opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control
cables cables cables cables cables cables cables cables cables cables cables cables

C 650 650 650 650 650 650 650 650 650 650 650 650 C

D FRONT D

E E

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 26/09/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 25
B FOR REVISION 11/08/23 CUSTOMER: PLAN VIEW START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00+GA/D04
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D05
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

105 440 105 105 440 105

>0,5
81

81
205
A 100 450 100 A

670
opening for power

843

843
cables

80
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

75 75
6-mounting hole 6-mounting hole
Ø16
(36x20) (36x20)

360

200

200
opening for control opening for control

311

311
B cables cables
BASE IRONS ON CONCRETE FLOOR B

66

66
70 510 70 70 510 70
650 650

FOR PANEL= MV-TR1.1~MV-TR1.9; FOR PANEL= MV-TC & =MV-LL -K1


A1

A2

=MV-TR2.1~MV-TR2.8

80
ANCHORING BOLT FIXING SYSTEM
C Ø16 C

105 440 105 105 440 105


ANCHORING BOLTS ON CONCRETE FLOOR

81

81
205

100 450 100

D D
670

opening for power


843

843
cables

75 75
M12
6-mounting hole 6-mounting hole
(36x20) (36x20)
360

200

200
311

311
opening for control opening for control
cables cables THREADED HOLE ON METAL STRUCTURE
66

66

70 510 70 70 510 70
E E
650 650

FOR PANEL= MV-TR1.1~MV-TR1.9; FOR PANEL= MV-TC & =MV-LL


=MV-TR2.1~MV-TR2.8
M12
BASE IRON FIXING SYSTEM THROUGH HOLE ON METAL STRUCTURE

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 20
B FOR REVISION 11/08/23 CUSTOMER: DETAIL OF SWITCHGEAR INSTALLATION START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00+GA/D05
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D06
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

444 LEGEND :
1 LV COMPARTMENT
2 CB COMPARTMENT
1
3 CABLE COMPARTMENT
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

4 -

705
180

5 VOLTAGE TRANSFORMER
B B
6 WOUND CURRENT TRANSFORMER
7 HEATER
180

8 CAPACITIVE INSULATOR
9 -
304

10 CABLE TERMINATION
A
11 SURGE ARRESTER
7
12 -
205

C 2 C
B
2100

Shutter painted "Signal Red" color 537 in BS381C,


P2
6 Labelled " BUSBAR" with white letters.

1495
P1 8
A BUSBAR
1040

D 10 D
B
B CIRCUIT
3
775

A
7 Shutter painted "Lemon Yellow" color 355 in BS381C,
535

Labelled " CIRCUIT" with white letters.


5
11

CABLE TERMINATION DETAILS CABLE TERMINATION DETAILS (B)


40 40
4 4
35 ∅1 ∅1

100
384 70
E 1340 150 150 150 150 E

25

25
A B
SECTIONAL VIEW FOR INCOMING PANEL =MV-TR1.1 & =MV-TR2.1

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 26/09/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 13
B FOR REVISION 11/08/23 CUSTOMER: SECTIONAL VIEW START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00+GA/D06
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D07
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

LEGEND :
A A
1 LV COMPARTMENT
4
444 2 CB COMPARTMENT
3 CABLE COMPARTMENT
4 -
1
5 VOLTAGE TRANSFORMER
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

6 WOUND CURRENT TRANSFORMER

705
7 HEATER
180

B B
8 CAPACITIVE INSULATOR
9 -
180

10 CABLE TERMINATION
11 -
2
12 -
304

Shutter painted "Signal Red" color 537 in BS381C,


205

C C
B Labelled " BUSBAR" with white letters.
2100

A BUSBAR

6
B CIRCUIT

1495
8
Shutter painted "Lemon Yellow" color 355 in BS381C,
Labelled " CIRCUIT" with white letters.
1040

D 10 D

3
775

7 CABLE TERMINATION DETAILS


535

40
4
∅1

100
9

150 150

25
180 180
35 67
E 1340
E

SECTIONAL VIEW FOR PANEL =MV-TR1.2~MV-TR1.6


AND =MV-TR2.2~MVTR-2.5; =MV-TR2.8

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 26/09/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 13
B FOR REVISION 11/08/23 CUSTOMER: SECTIONAL VIEW START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00+GA/D07
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D08
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

444

LEGEND :
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

1 LV COMPARTMENT
1
2 CB COMPARTMENT
B B
3 CABLE COMPARTMENT

705
4
180

5 EARTHING BAR 30x10


6 -
180

87.5
7 HEATER
8 8 INSULATOR

C C

2
2100

830
1549

1495
D D
8

7
560

220

E E
160

35 227 220 70
1340

SECTIONAL VIEW FOR BUS RISER PANEL =MV-TC

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 26/09/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 13
B FOR REVISION 11/08/23 CUSTOMER: SECTIONAL VIEW START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00+GA/D08
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D09
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

444

1
LEGEND :
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

1 LV COMPARTMENT
2 CB COMPARTMENT

705
B 180 3 CABLE COMPARTMENT B

4
180

8 5 -
6 WOUND CURRENT TRANSFORMER
7 HEATER
2
304

A 8 INSULATOR
7 9 CAPACITIVE INSULATOR
C C
205

B
2100

6 Shutter painted "Signal Red" color 537 in BS381C,


Labelled " BUSBAR" with white letters.

1495
9
A BUSBAR
D D
1040

B
3
BUSBAR
775

7
220

Example for Bus Tie at left hand side of Riser Panel.


160

35 227 220 67
E E
1340

SECTIONAL VIEW FOR BUS SECTION PANEL =MV-LL

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 26/09/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 13
B FOR REVISION 11/08/23 CUSTOMER: SECTIONAL VIEW START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00+GA/D09
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D10
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

445 LEGEND :
1 LV COMPARTMENT
2 CB COMPARTMENT
1
3 CABLE COMPARTMENT
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

4 -

705
5 VOLTAGE TRANSFORMER

180
B B
6 WOUND CURRENT TRANSFORMER
7 HEATER
180
8 CAPACITIVE INSULATOR
9 -
304

10 CABLE TERMINATION
11 -
12 -
205

C 2 C
2100

Shutter painted "Signal Red" color 537 in BS381C,


Labelled " BUSBAR" with white letters.

A BUSBAR

1495
8

A B CIRCUIT
1040

D A 10 D

3
Shutter painted "Lemon Yellow" color 355 in BS381C,
Labelled " CIRCUIT" with white letters.
7

CABLE TERMINATION DETAILS


40
4
∅1

100
35 67 150 150

25
E 1340 E

SECTIONAL VIEW FOR BUS SECTION PANEL =MV-TR2.6; =MV-TR2.7;


=MV-TR1.6; =MV-TR1.7; =MV-TR1.8

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 26/09/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 13
B FOR REVISION 11/08/23 CUSTOMER: SECTIONAL VIEW START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00+GA/D10
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A
444

705
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

180
B B

180
304
2100
C CAPACITOR C
CAPACITOR
SERIES REACTOR
SERIES REACTOR
��

1495

60
1245

A B C

D D
X Y Z

35 67

650 1340 650


E E

SECTIONAL VIEW FOR BUS SECTION PANEL =MV-TR2.6A; =MV-TR2.7A;


=MV-TR1.6A; =MV-TR1.7A; =MV-TR1.8A

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 26/09/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 13
B FOR REVISION 11/08/23 CUSTOMER: SECTIONAL VIEW START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00+GA/D11
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: E01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

Serial number: 1YUX 4202786788 /PANEL/7 Serial number: 1YUX 4202786788 /PANEL/7 Serial number: 1YUX 4202786788 /PANEL/7

IEC62271-200 IEC62271-200 IEC62271-200


This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

Prod. Year: 2023 Prod. Year: 2023 Prod. Year: 2023

Unigear ZS1 Metal-clad Switchgear Unigear ZS1 Metal-clad Switchgear Unigear ZS1 Metal-clad Switchgear

B Rated voltage 12 kV Rated voltage 12 kV Rated voltage 12 kV B


Rated current 630 A Rated current 630 A Rated current 50 A

Rated lightning impulse withstand voltage 75 kV Rated lightning impulse withstand voltage 75 kV Rated lightning impulse withstand voltage 75 kV

Rated power-frequency withstand voltage 28 kV Rated power-frequency withstand voltage 28 kV Rated power-frequency withstand voltage 28 kV
Rated current of main busbar 1250 A Rated current of main busbar 1250 A Rated current of main busbar 1250 A

Rated short time withstand current ( 3s) 25 kA Rated short time withstand current ( 3s) 25 kA Rated short time withstand current ( 3s) 25 kA

Rated peak withstand current 63 kA Rated peak withstand current 63 kA Rated peak withstand current 63 kA

Rated frequency 50 Hz Rated frequency 50 Hz Rated frequency 50 Hz

Protection class IP4X Protection class IP4X Protection class IP4X

Made by ABB Made by ABB Made by ABB


C C

PANEL =MV7-TR1.1~=MV-TR1.6; PANEL =MV-TC & MV-LL PANEL =MV-TR1.7, =MV-TR1.8, =MV-TR1.9
& =MV-TR2.1~=MV-TR2.5, =MV-TR2.8 & =MV-TR2.6, =MV-TR2.7

D D

E E

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 26/09/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1: 1
B FOR REVISION 11/08/23 CUSTOMER: PANEL RATING START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG3=J00+GA/E01
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: +LP/G01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A
ELECTRIFICATION DISTRIBUTION SOLUTION FACTORY, VIET NAM
Lot C3, TS3 Road, Tien Son IZ, Dong Nguyen, Tu Son, Bac Ninh
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B B

Project Title : BYD FACTORY

Project No. : UG23021


C C
Purchaser : BYD

Client :

Sale Order Number : 4202786788

D D

FOR APPROVAL
KINDLY TICK THE FOLLOWING BOX

1 Reviewed & Accepted as Final & Certified.


Manufacture may proceed

2 Reviewed & Accepted as Noted. Revise and Resubmit


Manufacture may proceed
E E
3 Reviewed & Returned. Correct and Resubmit
Manufacture should not proceed

4 Not Reviewed, Information only


Manufacture may proceed

Substation : 12kV SWITCHGEAR FACTORY NO.8 All comments and correction from customer should be mark in red.
This approval drawing should be returned within 2 working weeks.
Drawing Title: GENERAL DRAWINGS No manufacturing work will start before approval.

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


D FOR REVISION 26/09/23 PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 11/08/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1: 1
B FOR REVISION 05/09/23 CUSTOMER: COVER SHEET START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00/A00
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: B01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

TABLE OF CONTENTS
PAGE NAME DRAWING Nr. SHEET Nr. PAGE REVISION
A GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00/A00 A B C D A
COVER SHEET
GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00/B01 A B C D
TABLE CONTENTS
GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00/C00 A B
TECHNICAL DATA
GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00+SLD/A01 A B C D
SINGLE LINE DIAGRAM
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00+SLD/A02 A B C D


SINGLE LINE DIAGRAM
B GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00+SLD/A03 A B B
SINGLE LINE DIAGRAM
GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00+SLD/A04 A B C D
SINGLE LINE DIAGRAM
GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00+GA/D01 A B
GENERAL ARRANGEMENT
GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00+GA/D02 A B
GENERAL ARRANGEMENT
GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00+GA/D03 A B C
PLAN VIEW
C C
GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00+GA/D04 A B
PLAN VIEW
GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00+GA/D05 A B
DETAIL OF SWITCHGEAR INSTALLATION
GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00+GA/D06 A B C
SECTIONAL VIEW
GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00+GA/D07 A B C
SECTIONAL VIEW
GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00+GA/D08 A B C
D SECTIONAL VIEW D
GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00+GA/D09 A B C
SECTIONAL VIEW
GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00+GA/D10 A B C
SECTIONAL VIEW
GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00+GA/D11 A B C
SECTIONAL VIEW
GENERAL DRAWINGS 1YUX200001A0302 ==SWG4=J00+GA/E01 A B C
PANEL RATING

E E

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


D FOR REVISION 26/09/23 PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
BYD FACTORY GENERAL DRAWINGS
C FOR REVISION 11/08/23 SCALE: 1: 1
B FOR REVISION 05/09/23 CUSTOMER: TABLE CONTENTS START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00/B01
EPDS FACTORY, BAC NINH
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 3748 530, TELEFAX: (+84) (222) 3748 531 CONT.: C00
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

NO. CATOGARY DESCRIPTION NO. CATOGARY QTY. DESCRIPTION


1 TECHNICAL System : 10kV 3 PHASE 3 WIRE 50Hz 9 PACKING DETAILS Domestic
CHARACTERISTIC Rated Voltage : 12 kV
Power-frequency withstand voltage: 28 kV
Lighting impulse withstand voltage: 75 kV 10 NOTE
Rate short time withstand current: 25 kA / 3ss
Rate peak withstand current: 63 kA
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

2 CONSTRUCTION Type : UniGear ZS1


Material : Metal-clad Switchgear
Access Location : Front Access
B Switching Device Type : Withdrawable Vacuum Circuit Breaker B
Degree of Protection : External - IP 4X, Internal - IP 2X
3 PAINT FINISH Doors and End Covers : RAL7035 "Light Grey"
Remainder : Aluminium-Zinc Steel Sheets 11 REMARKS
4 BUSBAR RATING Main Busbar Rated Current : 1250 A Size : 1 x 80 x 10mm²
Earth Bar Size : 1 x 30 x 8mm²
Insulation : YES Finishing : Bare Copper
5 AUXILIARY CIRCUIT Voltage Supply :
- Protection, Control & Indication 110V DC
- Circuit Breaker Spring Charge Motor 110V DC
- Panel Heater & Cubicle Lighting 220V AC, 50Hz
Wire Size :
C - Control Circuit 1.5mm² Colour : Grey C
- Lighting & Heating Circuit 1.5mm² Colour : Black
- Current Transformer
Phase L1 4.0mm² Colour : Red
Phase L2 4.0mm² Colour : Yellow
Phase L3 4.0mm² Colour : Blue
Phase N 4.0mm² Colour : Black
- Voltage Transformer
Phase L1 2.5mm² Colour : Red
Phase L2 2.5mm² Colour : Yellow
Phase L3 2.5mm² Colour : Blue
Phase N 2.5mm² Colour : Black
D - Earthing Cable 2.5mm² Colour : Green/Yellow D
Wire Specification : 450/750V
Terminal Block : PHOENIX CONTACT
Test Terminal Block : YONGSUNG
Cable Termination : Blade
Cable Marker : Hot Marker
Cable Tray : Self-Extinguishing, Warp Proof PVC
Maximum Service Temperature : 85°C
6 POWER CABLE Entry : Bottom
Maximum Cable Size :
Terminating Facility : Undrilled Aluminium Gland Plate Only
7 CONTROL CABLE Entry : Bottom
E 8 LABEL Black Letter on White Background E
Material : Plastic
Fixing : Internal - Self Adhesive
External - Self Adhesive

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
BYD FACTORY GENERAL DRAWINGS SCALE: 1: 1
B FOR REVISION 11/08/23 CUSTOMER: TECHNICAL DATA START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00/C00
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: +SLD/A01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A 3P3W, 12kV, 1250A, 25kA/3s, 50Hz A


TO NEXT PAGE

-QB
-QB -QB -QB -QB -QB 400A
VCB VCB VCB VCB VCB
M 1250A M 1250A M 1250A M 1250A M 1250A

P2 -BC P1 -BC P1 -BC P1 -BC P1 -BC


This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B P2 P2 P2 P2 B
P1

-SA

-BV -QE -QE -QE -QE -R


10KV 7%

EARTHING BUS BAR EARTHING BUS BAR


TO NEXT PAGE
-PU -PU -PU -PU -PU -PU

C C
10kV-300KVAR

PANEL NUMBER =MV-TR2.1 =MV-TR2.2 =MV-TR2.3 =MV-TR2.4 =MV-TR2.5 =MV-TR2.6 =MV-TR2.6A


INCOMING PANEL OUTGOING PANEL OUTGOING PANEL OUTGOING PANEL OUTGOING PANEL CAPACITOR PANEL
MAIN LABEL

MAIN SWITCH VD4/P 12.12.25 P150 VD4/P 12.12.25 P150 VD4/P 12.12.25 P150 VD4/P 12.12.25 P150 VD4/P 12.12.25 P150 ConVac 12/P 400A SCO
D 400/5/1/1A 100/5/5A 100/5/5A 100/5/5A 100/5/5A
D
CURRENT TRANSFORMER C1: CL0.5, 15VA C1: CL0.5, 5VA C1: CL0.5, 5VA C1: CL0.5, 5VA C1: CL0.5, 5VA
C2, C3: CL5P15, 20VA C2: CL5P15, 5VA C2: CL5P15, 5VA C2: CL5P15, 5VA C2: CL5P15, 5VA

CABLE CT
EARTHING SWITCH EK6 EK6 EK6 EK6
HV FUSE 2A 50A
SURGE ARRESTER SCIHE12(Uc=10.2KV, Ur=12KV)
10 0.11 0.11
V3 V3 V3
VOLTAGE TRANSFORMER CL0.5/3P
30VA/50VA

CAP VOLTAGE DIVIDER 1 1 1 1 1 1


DAMPING RESISTOR
E E
PROTECTION REF615-HBFNAEAGNBC1BNA11G REX6101GMBANNNNA REX6101GMBANNNNA REX6101GMBANNNNA REX6101GMBANNNNA
DEVICES 50/50N, 51/51N, 59G, 27/59, 25, 50BF 50/51, 50/51N, 59G, 49, 50BF 50/51, 50/51N, 59G, 49, 50BF 50/51, 50/51N, 59G, 49, 50BF 50/51, 50/51N, 59G, 49, 50BF

MEASURING MULTI METER MULTI METER MULTI METER MULTI METER MULTI METER
INSTRUMENTS M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5
MULTI TARIFF METER
ELSTER A1700, CL0.5

COMMUNICATION IEC61850 IEC61850 IEC61850 IEC61850 IEC61850


POWER CABLE 1x1C-185mm²/phase - - - - 1x1C-35mm²/phase

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


D FOR REVISION 26/09/23 PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 11/08/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 1.2
B FOR REVISION 05/09/23 CUSTOMER: SINGLE LINE DIAGRAM START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00+SLD/A01
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: A02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A 3P3W, 12kV, 1250A, 25kA/3s, 50Hz 3P3W, 12kV, 1250A, 25kA/3s, 50Hz A
FROM PREVIOUS PAGE TO NEXT PAGE

-QB -QB
400A -QB -QB 400A
VCB VCB
M 1250A M 1250A

M M

P1 -BC P1 -BC
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B P2 P2 B

-R -QE -QE -R
10KV 7% 10KV 7%

FROM PREVIOUS PAGE EARTHING BUS BAR EARTHING BUS BAR


TO NEXT PAGE
-PU -PU -PU -PU -PU

C C
10kV-400KVAR 10kV-300KVAR

PANEL NUMBER =MV-TR2.7 =MV-TR2.7A =MV-TR2.8 =MV-TC =MV-LL =MV-TR1.9 =MV-TR1.9A


CAPACITOR PANEL OUTGOING PANEL BUS RISER PANEL BUS SECTION PANEL CAPACITOR PANEL
MAIN LABEL

MAIN SWITCH ConVac 12/P 400A SCO VD4/P 12.12.25 P150 VD4/P 12.12.25 P150 ConVac 12/P 400A SCO
D 100/5/5A 250-500/5/5A
D
CURRENT TRANSFORMER C1: CL0.5, 5VA C1: CL0.5, 15VA
C2: CL5P15, 5VA C2: CL5P15, 15VA

CABLE CT
EARTHING SWITCH EK6 EK6
HV FUSE 50A 50A
SURGE ARRESTER

VOLTAGE TRANSFORMER

CAP VOLTAGE DIVIDER 1 1 1 1


DAMPING RESISTOR
E E
PROTECTION REX6101GMBANNNNA REF615-HBFNAEAGNBC1BNA11G
DEVICES 50/51, 50/51N, 59G, 49, 50BF 50/50N, 51/51N, 25, 49, 86

MEASURING MULTI METER MULTI METER


INSTRUMENTS M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5

COMMUNICATION IEC61850 IEC61850


1x1C-35mm²/phase 1x1C-35mm²/phase
POWER CABLE 1x1C-35mm²/phase - - 1x1C-35mm²/phase

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


D FOR REVISION 26/09/23 PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 11/08/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 1.2
B FOR REVISION 05/09/23 CUSTOMER: SINGLE LINE DIAGRAM START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00+SLD/A02
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: A03
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A 3P3W, 12kV, 1250A, 25kA/3s, 50Hz A


FROM PREVIOUS PAGE TO NEXT PAGE

-QB -QB
400A 400A -QB -QB -QB
VCB VCB VCB
M 1250A M 1250A M 1250A

M M

P1 -BC P1 -BC P1 -BC


This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B P2 P2 P2 B

-R -R -QE -QE -QE


10KV 7% 10KV 7%

FROM PREVIOUS PAGE EARTHING BUS BAR


TO NEXT PAGE
-PU -PU -PU -PU -PU

C C
10kV-400KVAR 10kV-300KVAR

PANEL NUMBER =MV-TR1.8 =MV-TR1.8A =MV-TR1.7 =MV-TR1.7A =MV-TR1.6 =MV-TR1.5 =MV-TR1.4


CAPACITOR PANEL CAPACITOR PANEL OUTGOING PANEL OUTGOING PANEL OUTGOING PANEL
MAIN LABEL

MAIN SWITCH ConVac 12/P 400A SCO ConVac 12/P 400A SCO VD4/P 12.12.25 P150 VD4/P 12.12.25 P150 VD4/P 12.12.25 P150
D 100/5/5A 100/5/5A 100/5/5A
D
CURRENT TRANSFORMER C1: CL0.5, 5VA C1: CL0.5, 5VA C1: CL0.5, 5VA
C2: CL5P15, 5VA C2: CL5P15, 5VA C2: CL5P15, 5VA

CABLE CT
EARTHING SWITCH 50A 50A EK6 EK6 EK6
HV FUSE
SURGE ARRESTER

VOLTAGE TRANSFORMER

CAP VOLTAGE DIVIDER 1 1 1 1 1


DAMPING RESISTOR
E E
PROTECTION REX6101GMBANNNNA REX6101GMBANNNNA REX6101GMBANNNNA
DEVICES 50/51, 50/51N, 59G, 49, 50BF 50/51, 50/51N, 59G, 49, 50BF 50/51, 50/51N, 59G, 49, 50BF

MEASURING MULTI METER MULTI METER MULTI METER


INSTRUMENTS M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5

COMMUNICATION IEC61850 IEC61850 IEC61850


POWER CABLE 1x1C-35mm²/phase 1x1C-35mm²/phase 1x1C-35mm²/phase 1x1C-35mm²/phase - - -

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 1.2
B FOR REVISION 11/08/23 CUSTOMER: SINGLE LINE DIAGRAM START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00+SLD/A03
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: A04
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A 3P3W, 12kV, 1250A, 25kA/3s, 50Hz A


FROM PREVIOUS PAGE

-QB -QB -QB


VCB VCB VCB
M 1250A M 1250A M 1250A

P1 -BC P1 -BC P2 -BC


This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B P2 P2 B
P1

-SA

-QE -QE -BV

FROM PREVIOUS PAGE EARTHING BUS BAR

-PU -PU -PU

C C

PANEL NUMBER =MV-TR1.3 =MV-TR1.2 =MV-TR1.1


OUTGOING PANEL OUTGOING PANEL INCOMING PANEL
MAIN LABEL

MAIN SWITCH VD4/P 12.12.25 P150 VD4/P 12.12.25 P150 VD4/P 12.12.25 P150
D 100/5/5A 100/5/5A 400/5/1/1A
D
CURRENT TRANSFORMER C1: CL0.5, 5VA C1: CL0.5, 5VA C1: CL0.5, 15VA
C2: CL5P15, 5VA C2: CL5P15, 5VA C2, C3: CL5P15, 20VA

CABLE CT
EARTHING SWITCH EK6 EK6
HV FUSE 2A
SURGE ARRESTER SCIHE12(Uc=10.2KV, Ur=12KV)
10 0.11 0.11
V3 V3 V3
VOLTAGE TRANSFORMER CL0.5/3P
30VA/50VA

CAP VOLTAGE DIVIDER 1 1 1


DAMPING RESISTOR
E E
PROTECTION REX6101GMBANNNNA REX6101GMBANNNNA REF615-HBFNAEAGNBC1BNA11G
DEVICES 50/51, 50/51N, 59G, 49, 50BF 50/51, 50/51N, 59G, 49, 50BF 50/50N, 51/51N, 59G, 27/59, 25, 50BF

MEASURING MULTI METER MULTI METER MULTI METER


INSTRUMENTS M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5 M4M 30, Modbus TCP/IP, CL0.5
MULTI TARIFF METER
ELSTER A1700, CL0.5

COMMUNICATION IEC61850 IEC61850 IEC61850


POWER CABLE - - 1x1C-185mm²/phase

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


D FOR REVISION 26/09/23 PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 11/08/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 1.2
B FOR REVISION 05/09/23 CUSTOMER: SINGLE LINE DIAGRAM START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00+SLD/A04
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: +GA/D01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

15660 mm

A A
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

2200

B B

30 650 650 650 650 650 650 650 650 650 650 650 650
C C

PANEL NO. =MV-TR2.1 =MV-TR2.2 =MV-TR2.3 =MV-TR2.4 =MV-TR2.5 =MV-TR2.6 =MV-TR2.6A =MV-TR2.7 =MV-TR2.7A =MV-TR2.8 =MV-TC =MV-LL

PANEL TYPE OUTGOING OUTGOING OUTGOING OUTGOING OUTGOING CAPACITOR CAPACITOR CAPACITOR CAPACITOR OUTGOING BUS RISER BUS SECTION

D D
CIRCUIT BREAKER VD4/P-1250A VD4/P-1250A VD4/P-1250A VD4/P-1250A VD4/P-1250A ConVac 12/P 300KVAR ConVac 12/P-400A 400KVAR VD4/P-1250A VD4/P-1250A VD4/P-1250A

FRONT
PANEL DEPTH : 1340mm

E E

LEGEND:
11 GUIDING HOLE FOR CB/VT TRUCK
12 OPENING FOR EARTH SWITCH AND INDICATOR
13 OPENING FOR RACKING IN & RACKING OUT OF CIRCUIT BREAKER/VOLTAGE TRANSFORMER
14 OPENING FOR MANUAL SPRING CHARGED WHEN CB DOOR IS CLOSING

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 25
B FOR REVISION 11/08/23 CUSTOMER: GENERAL ARRANGEMENT START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00+GA/D01
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

15660 mm
A A
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B B

C 650 650 650 650 650 650 650 650 650 650 650 650 C
30

PANEL NO. =MV-TR1.9 =MV-TR1.9A =MV-TR1.8 =MV-TR1.8A =MV-TR1.7 =MV-TR1.7A =MV-TR1.6 =MV-TR1.5 =MV-TR1.4 =MV-TR1.3 =MV-TR1.2 =MV-TR1.1

PANEL TYPE CAPACITOR CAPACITOR CAPACITOR CAPACITOR CAPACITOR CAPACITOR OUTGOING OUTGOING OUTGOING OUTGOING OUTGOING INCOMING
D D

CIRCUIT BREAKER ConVac 12/P-400A 300KVAR ConVac 12/P-400A 400KVAR ConVac 12/P-400A 300KVAR VD4/P-1250A VD4/P-1250A VD4/P-1250A VD4/P-1250A VD4/P-1250A VD4/P-1250A

FRONT
PANEL DEPTH : 1340mm

E E

LEGEND:
11 GUIDING HOLE FOR CB/VT TRUCK
12 OPENING FOR EARTH SWITCH AND INDICATOR
13 OPENING FOR RACKING IN & RACKING OUT OF CIRCUIT BREAKER/VOLTAGE TRANSFORMER
14 OPENING FOR MANUAL SPRING CHARGED WHEN CB DOOR IS CLOSING

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 25
B FOR REVISION 11/08/23 CUSTOMER: GENERAL ARRANGEMENT START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00+GA/D02
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D03
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

=MV-TR2.1 =MV-TR2.2 =MV-TR2.3 =MV-TR2.4 =MV-TR2.5 =MV-TR2.6 =MV-TR2.6A =MV-TR2.7 =MV-TR2.7A =MV-TR2.8 =MV-TC =MV-LL
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B B

opening for power opening for power opening for power opening for power opening for power opening for power opening for power opening for power opening for power opening for power
cables cables cables cables cables cables cables cables cables cables

6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole
(36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20)

opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control
cables cables cables cables cables cables cables cables cables cables cables cables

C 650 650 650 650 650 650 650 650 650 650 650 650 C

D FRONT D

E E

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 26/09/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 25
B FOR REVISION 11/08/23 CUSTOMER: PLAN VIEW START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00+GA/D03
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D04
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

=MV-TR1.9 =MV-TR1.9A =MV-TR1.8 =MV-TR1.8A =MV-TR1.7 =MV-TR1.7A =MV-TR1.6 =MV-TR1.5 =MV-TR1.4 =MV-TR1.3 =MV-TR1.2 =MV-TR1.1
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B B

opening for power opening for power opening for power opening for power opening for power opening for power opening for power opening for power opening for power opening for power opening for power opening for power
cables cables cables cables cables cables cables cables cables cables cables cables

6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole 6-mounting hole
(36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20) (36x20)

opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control opening for control
cables cables cables cables cables cables cables cables cables cables cables cables

C 650 650 650 650 650 650 650 650 650 650 650 650 C

D FRONT D

E E

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 25
B FOR REVISION 11/08/23 CUSTOMER: PLAN VIEW START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00+GA/D04
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D05
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

105 440 105 105 440 105

>0,5
81

81
205
A 100 450 100 A

670
opening for power

843

843
cables

80
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

75 75
6-mounting hole 6-mounting hole
Ø16
(36x20) (36x20)

360

200

200
opening for control opening for control

311

311
B cables cables
BASE IRONS ON CONCRETE FLOOR B

66

66
70 510 70 70 510 70
650 650

FOR PANEL= MV-TR1.1~MV-TR1.9; FOR PANEL= MV-TC & =MV-LL -K1


A1

A2

=MV-TR2.1~MV-TR2.8

80
ANCHORING BOLT FIXING SYSTEM
C Ø16 C

105 440 105 105 440 105


ANCHORING BOLTS ON CONCRETE FLOOR

81

81
205

100 450 100

D D
670

opening for power


843

843
cables

75 75
M12
6-mounting hole 6-mounting hole
(36x20) (36x20)
360

200

200
311

311
opening for control opening for control
cables cables THREADED HOLE ON METAL STRUCTURE
66

66

70 510 70 70 510 70
E E
650 650

FOR PANEL= MV-TR1.1~MV-TR1.9; FOR PANEL= MV-TC & =MV-LL


=MV-TR2.1~MV-TR2.8
M12
BASE IRON FIXING SYSTEM THROUGH HOLE ON METAL STRUCTURE

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 20
B FOR REVISION 11/08/23 CUSTOMER: DETAIL OF SWITCHGEAR INSTALLATION START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00+GA/D05
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D06
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

444 LEGEND :
1 LV COMPARTMENT
2 CB COMPARTMENT
1
3 CABLE COMPARTMENT
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

4 -

705
180

5 VOLTAGE TRANSFORMER
B B
6 WOUND CURRENT TRANSFORMER
7 HEATER
180

8 CAPACITIVE INSULATOR
9 -
304

10 CABLE TERMINATION
A
11 SURGE ARRESTER
7
12 -
205

C 2 C
B
2100

Shutter painted "Signal Red" color 537 in BS381C,


P2
6 Labelled " BUSBAR" with white letters.

1495
P1 8
A BUSBAR
1040

D 10 D
B
B CIRCUIT
3
A
775

7 Shutter painted "Lemon Yellow" color 355 in BS381C,


535

Labelled " CIRCUIT" with white letters.


5
11
CABLE TERMINATION DETAILS (A) CABLE TERMINATION DETAILS (B)

60 80
4 4
∅1 ∅1
35
384 70
E 1340 150 150 150 150 E

25
25
A B
SECTIONAL VIEW FOR INCOMING PANEL =MV-TR1.1 & =MV-TR2.1

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 26/09/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 13
B FOR REVISION 11/08/23 CUSTOMER: SECTIONAL VIEW START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00+GA/D06
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D07
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

LEGEND :
A A
1 LV COMPARTMENT
4
444 2 CB COMPARTMENT
3 CABLE COMPARTMENT
4 -
1
5 VOLTAGE TRANSFORMER
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

6 WOUND CURRENT TRANSFORMER

705
7 HEATER
180

B B
8 CAPACITIVE INSULATOR
9 -
180

10 CABLE TERMINATION
11 -
2
12 -
304

Shutter painted "Signal Red" color 537 in BS381C,


205

C C
B Labelled " BUSBAR" with white letters.
2100

A BUSBAR

6
B CIRCUIT

1495
8
Shutter painted "Lemon Yellow" color 355 in BS381C,
Labelled " CIRCUIT" with white letters.
1040

D D
B
3
A
775

CABLE TERMINATION DETAILS (A) CABLE TERMINATION DETAILS (B)


7
60 80
535

4 4
∅1 ∅1
9
150 150 150 150

25
25
A B
180 180
35 67
E 1340
E

SECTIONAL VIEW FOR PANEL =MV-TR1.2~MV-TR1.6


AND =MV-TR2.2~MVTR-2.5; =MV-TR2.8

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 26/09/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 13
B FOR REVISION 11/08/23 CUSTOMER: SECTIONAL VIEW START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00+GA/D07
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D08
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

444

LEGEND :
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

1 LV COMPARTMENT
1
2 CB COMPARTMENT
B B
3 CABLE COMPARTMENT

705
4
180

5 EARTHING BAR 30x10


6 -
180

87.5
7 HEATER
8 8 INSULATOR

C C

2
2100

830
1549

1495
D D
8

7
560

220

E E
160

35 227 220 70
1340

SECTIONAL VIEW FOR BUS RISER PANEL =MV-TC

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 26/09/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 13
B FOR REVISION 11/08/23 CUSTOMER: SECTIONAL VIEW START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00+GA/D08
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D09
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

444

1
LEGEND :
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

1 LV COMPARTMENT
2 CB COMPARTMENT

705
B 180 3 CABLE COMPARTMENT B

4
180

8 5 -
6 WOUND CURRENT TRANSFORMER
7 HEATER
2
304

A 8 INSULATOR
7 9 CAPACITIVE INSULATOR
C C
205

B
2100

6 Shutter painted "Signal Red" color 537 in BS381C,


Labelled " BUSBAR" with white letters.

1495
9
A BUSBAR
D D
1040

B
3
BUSBAR
775

7
220

Example for Bus Tie at left hand side of Riser Panel.


160

35 227 220 67
E E
1340

SECTIONAL VIEW FOR BUS SECTION PANEL =MV-LL

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 26/09/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 13
B FOR REVISION 11/08/23 CUSTOMER: SECTIONAL VIEW START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00+GA/D09
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D10
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

445 LEGEND :
1 LV COMPARTMENT
2 CB COMPARTMENT
1
3 CABLE COMPARTMENT
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

4 -

705
5 VOLTAGE TRANSFORMER

180
B B
6 WOUND CURRENT TRANSFORMER
7 HEATER
180
8 CAPACITIVE INSULATOR
9 -
304

10 CABLE TERMINATION
11 -
12 -
205

C 2 C
2100

Shutter painted "Signal Red" color 537 in BS381C,


Labelled " BUSBAR" with white letters.

A BUSBAR

1495
8

A B CIRCUIT
1040

D A 7 D

3
Shutter painted "Lemon Yellow" color 355 in BS381C,
Labelled " CIRCUIT" with white letters.
7

CABLE TERMINATION DETAILS


40
4
∅1

100
35 67 150 150

25
E 1340 E

SECTIONAL VIEW FOR BUS SECTION PANEL =MV-TR2.6; =MV-TR2.7;


=MV-TR1.6; =MV-TR1.7; =MV-TR1.8

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 26/09/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 13
B FOR REVISION 11/08/23 CUSTOMER: SECTIONAL VIEW START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00+GA/D10
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: D11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A
444

705
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

180
B B

180
304
2100
C CAPACITOR C
CAPACITOR
SERIES REACTOR
SERIES REACTOR
��

1495

60
1245

A B C

D D
X Y Z

35 67

650 1340 650


E E

SECTIONAL VIEW FOR BUS SECTION PANEL =MV-TR2.6A; =MV-TR2.7A;


=MV-TR1.6A; =MV-TR1.7A; =MV-TR1.8A

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 26/09/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1 : 13
B FOR REVISION 11/08/23 CUSTOMER: SECTIONAL VIEW START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00+GA/D11
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: E01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A A

Serial number: 1YUX 4202786788 /PANEL/8 Serial number: 1YUX 4202786788 /PANEL/8 Serial number: 1YUX 4202786788 /PANEL/8

Prod. Year: 2023 IEC62271-200 Prod. Year: 2023 IEC62271-200 Prod. Year: 2023 IEC62271-200
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

Unigear ZS1 Metal-clad Switchgear Unigear ZS1 Metal-clad Switchgear Unigear ZS1 Metal-clad Switchgear

Rated voltage 12 kV Rated voltage 12 kV Rated voltage 12 kV


B B
Rated current 630 A Rated current 630 A Rated current 50 A

Rated lightning impulse withstand voltage 75 kV Rated lightning impulse withstand voltage 75 kV Rated lightning impulse withstand voltage 75 kV

Rated power-frequency withstand voltage 28 kV Rated power-frequency withstand voltage 28 kV Rated power-frequency withstand voltage 28 kV
Rated current of main busbar 1250 A Rated current of main busbar 1250 A Rated current of main busbar 1250 A

Rated short time withstand current ( 3s) 25 kA Rated short time withstand current ( 3s) 25 kA Rated short time withstand current ( 3s) 25 kA

Rated peak withstand current 63 kA Rated peak withstand current 63 kA Rated peak withstand current 63 kA

Rated frequency 50 Hz Rated frequency 50 Hz Rated frequency 50 Hz

Protection class IP4X Protection class IP4X Protection class IP4X

Made by ABB Made by ABB Made by ABB


C C

PANEL =MV7-TR1.1~=MV-TR1.6; PANEL =MV-TC & MV-LL PANEL =MV-TR1.7, =MV-TR1.8, =MV-TR1.9
& =MV-TR2.1~=MV-TR2.5, =MV-TR2.8 & =MV-TR2.6, =MV-TR2.7

D D

E E

F PROJECT NO.: UG23021 DRAWING NO.: 1YUX200001A0302 F


PROJECT TITLE: DRAWING TITLE: LANGUAGE: ENG
C FOR REVISION 26/09/23 BYD FACTORY GENERAL DRAWINGS SCALE: 1: 1
B FOR REVISION 11/08/23 CUSTOMER: PANEL RATING START: 24/08/2023
BYD
A FOR APPROVAL 31/08/23 SHEET: ==SWG4=J00+GA/E01
ELDS FACTORY
REV. DESCRIPTION DATE DESIGNED: HANG PTD CHECKED: KIM NH APPROVED: TUAT MB TEL: (+84) (222) 374 8535, TELEFAX: (+84) (222) 3748 531 CONT.: +LP/G01
1 2 3 4 5 6 7 8