Professional Documents
Culture Documents
Air Charging System Service Manual
Air Charging System Service Manual
KAESER KOMPRESSOREN
96410 Coburg - PO Box 2143 - GERMANY
Material No.: .........................................
Tel. +49---(0)9561---6400
Serial no.: .......................................
Fax +49---(0)9561--640130
http://www.kaeser.com
DHS
DESIGN VERSIONS OF AIR MAIN CHARGING SYSTEM
Important
Operating personnel must be given instruction before
putting the air main charging system into operation.
DHS 2 / 52 9_5855_12E
Function
SAFE COMPRESSED AIR QUALITY SAFE COMPRESSED AIR SUPPLY
(AS-SUPPLIED SETTING) (SET ON SITE)
Air main Air main
Power supply Pressure charging Power supply Pressure charging
system system
0 0 Closed 0 0 Closed
0 1 Closed 0 1* Open
1 0 Closed 1 0 Closed
1 1 Open 1 1 Open
9_5855_12E 3 / 52
DHS
Contents 10.1 Safe compressed air quality
(as-supplied setting) 23
1 Safety regulations 5
10.2 Safe compressed air supply
1.1 Explanation of symbols and signs 5
(set on site) 23
1.2 General safety information 5
11 Manual override 23
1.3 Spare parts 5
12 Commissioning 24
1.4 Environmental protection 5
13 Visual position indicator 24
2 General information 5
13.1 LED indicator 24
2.1 Correct use 5
13.2 Mechanical indicator 24
2.2 Use for purposes other than intended 6
14 Operation 25
2.3 Copyright 6
14.1 Operating and display elements 25
2.4 Electrical connection 6
14.2 General notes on operation 25
3 Description 6
15 Menu structure 27
3.1 Problem 6
16 Parameters table 29
3.2 Consequences 6
17 EC Declaration of conformity 32
3.3 How the air main charging system operates 6
18 Explanation of parameters 33
3.3.1 Automatic pressure maintenance 6
18.1 Menu 1 SetCalibration 33
3.3.2 Start-up principle 6
18.1.1 Basic settings 33
3.3.3 Remote operation option 6
18.1.2 Logging onto and off the system 34
3.4 Specifications supplied 7
18.2 Menu 2 SetFunction 34
4 Versions 7
18.2.1 Setting outputs 34
5 Air main charging system for 0.5 - 16 bar 7
18.3 Menu 3 Service 35
5.1 Overview of order numbers 7
18.3.1 Viewing inputs and outputs 35
5.2 Control unit technical data 7
18.3.2 Diagnostic functions 35
5.3 Design of 16 bar ball valve and butterfly valve
18.3.3 Reading device-specific data 36
version 8
18.4 Menu 4 SetBasics 36
5.4 Dimensions of 16 bar air main charging system
18.4.1 Resetting the system 36
with ball valve 9
18.4.2 Automatic log-off 36
5.5 Dimensions of 10 bar / 16 bar air main charging
18.4.3 Operating mode of the air main charging
system with butterfly valve 10
system/pressure relief valve 36
5.6 Ball valve technical data 11
19 Error messages 36
5.7 Butterfly valve technical data 11
20 Installation and setting 37
6 Air main charging system for 16 - 63 bar 12
21 Changing the control unit position 37
6.1 Overview of order numbers 12
22 Inspection and servicing 38
6.2 Control unit technical data 12
23 Options 39
6.3 Design of 63 bar ball valve version 13
24 Function selection of the air main
6.3.1 Dimensions of 63 bar air main charging system
charging system/pressure relief valve 39
with ball valve 14
25 Spare parts 39
6.4 Ball valve technical data 14
26 Air main charging system – piping and
6.5 Pressure reducer 15
instrument circuit diagrams 40
6.5.1 Setting the pressure reducer 15
26.1 Installation examples for 4 - 16 bar and
6.5.2 Pressure reducer technical data 15
16 - 63 bar air main charging systems 40
6.5.3 Pressure reducer dimensions 15
26.2 P&I circuit diagram for air main charging
7 Installation 16
system for system pressure of 4 - 16 bar 41
7.1 Installation of air main charging system 16
26.3 P&I circuit diagram for air main charging
7.2 Installation of ball valve 17
system for system pressure of 16 - 63 bar 42
7.3 Installation of butterfly valve 18
26.4 Installation example for external feed air main
8 Control air connection 20
charging system with system pressure of
8.1 Control air connection with system
0.5 - 4 bar 43
pressure of 4 to 16 bar 20
26.5 P&I circuit diagram for external feed air main
8.2 Control air connection with system
charging system for system pressure of
pressure of 16 to 63 bar 20
0.5 - 4 bar 44
8.3 Control air connection with system
27 Wiring diagrams 45
pressure of 0.5 to 4 bar 20
27.1 16 bar air main charging system,
8.3.1 Method of operation 20
24 V DC power supply 45
8.3.2 Conversion 20
27.2 63 bar air main charging system,
8.4 Control pressure indication (pressure gauge) 21
24 V DC power supply 46
9 Electrical connection 21
27.3 16 bar air main charging system,
9.1 Terminals 21
90 - 264 V AC power supply 47
9.1.1 Terminal block X1 21
27.4 63 bar air main charging system,
9.1.2 Terminal block X2 22
90 - 264 V AC power supply 48
9.2 Internal fuses 22
28 Updating the software 49
9.3 External cut-out 23
10 Changing operating mode 23 Goods return declaration 51
DHS 4 / 52 9_5855_12E
1 Safety regulations 1.2 General safety information
Before commissioning or carrying out adjustment Work on power-operated equipment must
or servicing work, it is essential that these operating only be carried out by properly trained or
instructions are read and the directions in them followed. instructed staff or specialist technicians.
1.1 Explanation of symbols and signs Important Conversion work not described in these
operating instructions and carried out
This symbol appears alongside all health without prior consultation with and approval
and safety instructions in this instruction of KAESER KOMPRESSOREN will void
manual where persons are potentially at any guarantee entitlement. This symbol
risk of life and limb. In such cases, following appears at those points in the operating
these instructions and exercising care instructions that require particular attention
are particularly important. All health and in order that the directives, regulations,
safety instructions must also be passed on instructions and correct sequence of
to other users. As well as the instructions operations are followed and damage or
in this instruction manual, the generally destruction of equipment is avoided.
applicable safety and accident prevention
regulations must be followed. Installation, operation, servicing and repairs must be
carried out in accordance with the European Directives.
Important This symbol appears at those points in the
Where the European Standards have not yet been
operating instructions that require particular
incorporated in national law, the applicable existing
attention in order that the directives,
regulations of the country concerned are to be applied.
regulations, instructions and correct
Operators of compressor systems outside the area in
sequence of operations are followed and
which European Standards are applicable are obliged to
damage or destruction of equipment is
observe the applicable safety and accident prevention
avoided.
regulations of the country in which the system is
This symbol identifies important operated. If necessary, appropriate measures must be
environmental protection information or taken prior to commissioning to ensure compliance with
measures. the regulations of the country concerned.
There must be no naked flames or airborne sparks at the
This symbol identifies information of installation site.
particular importance to the operators.
1.3 Spare parts
This symbol marks items in a list.
Genuine KAESER spare parts are individually designed
®®
PP This symbol identifies instructions on what for the technical requirements and compatibility with one
to do. another.
9_5855_12E 5 / 52
DHS
2.2 Use for purposes other than intended When installing a compressed-air accumulator
downstream of the shut-off valve without sufficient
Compressed air must never be directed at storage capacity upstream of the shut-off valve,
persons. As it is a form of stored energy, problems with the upstream compressor unit(s) can
there is a risk of fatal injury. occur (switching frequency too high).
2.3 Copyright 3.3 How the air main charging system operates
The copyright to these operating instructions is
owned by KAESER KOMPRESSOREN. These 3.3.1 Automatic pressure maintenance
operating instructions are intended for the installation,
operative, service and monitoring personnel. They KAESER offers air main charging systems
contain specifications and drawings of a technical for system pressures of 4 - 16 bar as
nature that may not be reproduced, disseminated, butterfly valve and ball valve versions and for
commercially exploited for the purposes of competition system pressures of 16 - 63 bar as ball valve
or communicated to others either as a whole or in part. versions.
The 4 - 16 bar air main charging systems
2.4 Electrical connection can also be used for system pressures of
0.5 - 4 bar by means of an on-site conversion.
Connection to the mains power supply It is important in this connection to
and the safety measures it requires are to distinguish between the system pressure
be carried out by an authorised electrician (= the pressure to be monitored in the
in accordance with the requirements of compressed air system) and the control
European Standard EN 1012 Part 1 and pressure (= control pressure required for the
EN 60204-1, Annex B and the specifications control unit of the air main charging system).
of the electricity supplier concerned. The control pressure is always taken from
the system pressure via a pressure reducer
in air main charging systems for system
3 Description
pressures of 4 - 16 and 16 - 63 bar. That
means that, with those pressures, only one
3.1 Problem connection is required for detecting the
Where supply systems are depressurised and the system pressure and the control pressure
compressed air supply has to be started up again, the (see chapters 8.1, 8.2, 26.2 and 26.3). With
entire compressed air system must be brought up from monitored system pressures of 0.5 to 4 bar,
0 bar to the maximum system pressure. In the process, an external control pressure feed (4 - 16 bar)
compressed air conditioning systems are subjected to must be connected to the control unit (see
several times the normal volumetric flow of compressed chapters 8.3 and 26.5).
air.
An isolating device (ball valve or butterfly valve) with a
3.2 Consequences pneumatic rotary actuator cuts off the compressed air
system from the air compressor or the conditioning units
No condensate discharge at the conditioning units but
when there is no pressure or the operating pressure is
®®
DHS 6 / 52 9_5855_12E
3.4 Specifications supplied 5.2 Control unit technical data
®® Butterfly valve or ball valve isolator with pneumatic, Installation position Any
single-action quarter turn actuator and control unit Ambient temperature 0…60°C
assembled as a complete unit Storage temperature 0…60°C
®® Option: remote control with buttons for remotely Temperature of control max. 60°C
operating the air main charging system medium
®® The quarter turn actuators are supplied with a Enclosure rating IP 65
spring for a minimum control pressure of 4 bar and a Control medium Dust and oil-free compressed air
maximum control pressure of 10 bar. Quality classes to DIN ISO 8573-1
Particle size must not exceed 30 µm
ISO 8573 Part 1 Class 3
4 Versions ISO 8573 Part 1 Class 4
The air main charging system is supplied in a choice of Dust content Class 3
(max. particle size 5 µm)
two versions:
(max. particle density 5 mg/m³)
®® 0.5 - 16 bar
Pressure dew point Class 5
®® 16 - 63 bar (max. pressure dew point 7 °C)
Oil content Class 3
5 Air main charging system for 0.5 - 16 bar (max. oil concentration 1 mg/m³)
Power consumption Approx. 15W
5.1 Overview of order numbers Recommended connecting 1 x PG 12 – 3…6.5 mm
cable diameter 2 x PG 16 – 4…10 mm
Ball valve air main charging system for 0.5 - 16 bar Terminals Phoenix contact,
MKDSN 1,5 / 2 HTBK
Order number Connection size to Operating
DIN EN ISO 228-1 pressure Core cross-sectional area 1.5 mm²
920021.0 G 1/2 PS 16 Accuracy of the pressure 16 bar: +/- 0.2 bar
sensors 63 bar: +/- 1.0 bar
920022.0 G 3/4 PS 16
Analogue output 4 ... 20 mA passive
920023.0 G1 PS 16
load resistor 150 ... 600 Ω
920024.0 G 1 1/4 PS 16
External cut-out I = 2.8 mA
920025.0 G 1 1/2 PS 16
920026.0 G2 PS 16
920027.0 G 2 1/2 PS 16
920028.0 G3 PS 16
Butterfly valve air main charging system
for 0.5 - 16 bar
Order number Connection size Operating pressure
920001.0 DN 40 PN 16 PS 16
920002.0 DN 50 PN 16 PS 16
920003.0 DN 65 PN 16 PS 16
920004.0 DN 80 PN 16 PS 16
920005.0 DN 100 PN 16 PS 16
920006.0 DN 125 PN 16 PS 16
920007.0 DN 150 PN 16 PS 16
920008.0 DN 200 PN 16 PS 16
Butterfly valve air main charging system
for 0.5 - 10 bar
Order number Connection size Operating pressure
920009.0 DN 250 PN 10 PS 10
920010.0 DN 300 PN 10 PS 10
920011.0 DN 350 PN 10 PS 10
920012.0 DN 400 PN 10 PS 10
9_5855_12E 7 / 52
DHS
5.3 Design of 16 bar ball valve and butterfly valve version
Cable glands
Manual override
Display cover
Sealed keypad
The compressed air supply to the air main charging system must be tapped off the compressed air line upstream of
air main charging system using the control line and screw-in elbow union supplied (see chapter 8).
Important The electrical power supply must be connected on site by a qualified electrician.
DHS 8 / 52 9_5855_12E
5.4 Dimensions of 16 bar air main charging system with ball valve
226 173
26 170 33 107
A
B
C
D
SW
G
E H I
F J
Dimensions [mm]
Connection Weight
thread DN A B C D E F G H I J SW [kg]
G 1/2 15 263.6 85 38.6 18.5 65 195 16 56 87 143 26 4.5
G 3/4 20 271.1 85 46.1 21.5 74.6 195 17 56 87 143 32 4.6
G1 25 303.6 107 56.6 26 88 217 21 66 87 153 40 5.9
G 1 1/4 32 308 107 61 31.5 102 217 22 66 87 153 49 7.7
G 1 1/2 40 334.5 117 77.5 36.5 110 258 22 71 87 158 56 8.8
G2 50 342.2 117 85.2 45.4 125 258 26 71 87 158 70 10.9
G 2 1/2 65 383.7 135 108.7 59.3 160.6 299 31 78 87 165 87 17.3
G3 80 409.4 182 117.4 69.8 178 348.5 34 86 87 173 104 23.7
9_5855_12E 9 / 52
DHS
5.5 Dimensions of 10 bar / 16 bar air main charging system with butterfly valve
G H
226 173
26 170 33 107
B
A
C
I
D
E øJ
F øK
øL
Dimensions [mm]
Weight
PN DN A B C D E F G H I J K L [kg]
40 357 107 110 54 33 217 66 87 4 x M16 76 110 140 8.2
50 367 107 120 59.5 43 217 66 87 4 x M16 100 125 156 9.1
65 392 117 135 66.5 46 258 71 87 8 x M16 108 145 175 10.6
max. 80 398 117 141 91 46 258 71 87 8 x M16 124 160 194 12.1
16 bar 100 440 135 165 105 52 299 78 87 8 x M16 147 180 224 16.2
125 472 152 180 125 56 348 86 87 8 x M16 180 210 267 23.2
150 508 169 193 136.5 56 397 96 87 8 x M20 206 240 292 28.4
200 562 191 225 171 60 473 106 87 12 x M20 257 295 352 38.6
250 641.5 219 282.5 210 68 560 116 87 12 x M20 324 350 409 63.4
max. 300 788 250 308 240 78 601 131 87 12 x M20 376 400 480 88
10 bar 350 881.5 283 338.5 263 78 702 128.5 87 16 x M20 430 460 522 158.5
400 993 353 380 308 102 738 177.5 87 16 x M24 485 515 595 259.5
DHS 10 / 52 9_5855_12E
5.6 Ball valve technical data 5.7 Butterfly valve technical data
Pneumatically operated shut-off valve consisting of ball Pneumatically operated shut-off valve consisting of
valve and actuator. butterfly valve and actuator.
Design Two-part ball valve with floating-bearing Design Wafer pattern butterfly valve
high-precision ball Actuation type Pneumatic single-action, normally closed
Actuation type Pneumatic single-action, normally Connection type Lug body type
closed Nominal size DN 40 - 400
Connection type Female thread G1/2 ... G3 Installation position Any
to DIN EN ISO 228-1 Operating pressure DN 40 - 200 = PS 16
Nominal size DN 15 - 80 DN 250 - 400 = PS 10
Installation position Any Control medium Compressed air, conditioned
Operating pressure See pressure/temperature graph Nominal pressure DN 40 - 200 = PN 16
Control medium Compressed air, conditioned DN 250 - 400 = PN 10
Nominal pressure PN 63 Temperature range Medium: -20 – +80 °C
Temperature range Medium: -20 – +100 °C Environment: -10 – +70 °C
Environment: -10 – + 70 °C Length To DIN 3202, Part 3, Series K1
Flow direction Any Flow direction Any
Working media All inert gases Working media All inert gases
Material: Material:
Body CF8M (1.4408) Body EN-GJS-400-15 (GGG40),
Ball SUS 316 (1.4401) epoxy coated 120 µm
Switching shaft SUS 316 (1.4401) Disc EN-GJS-400-15 (GGG40),
Seals PTFE epoxy coated
Actuator shaft seal PTFE Shaft AISI 420 / 1.4021
Seat FPM
Lubricants Silicone-free grease 3M 5-way Penetrant Corrosion protection Powder-coated with artificial resin coating
(similar to RAL 5021)
Important Pneumatic actuator is under spring force Lubricants Silicone-free grease Klüberplex BE31-502
Pressure/temperature graph
Important Pneumatic actuator is under spring force
76 1100
69 1000
63 900
55 800
48 700
41 600
Pressure in bar
34 500
Pressure in psi
28 400
21 300
14 200
7 100
0 0
- 20 38 93 149 204 260
(- 4) (100) (200) (300) (400) (500)
Temperature in °C (°F)
9_5855_12E 11 / 52
DHS
6 Air main charging system for 16 - 63 bar
DHS 12 / 52 9_5855_12E
6.3 Design of 63 bar ball valve version
Cable glands
Manual override
Pressure reducer
Compressed air connection
Visual position indicator
The compressed air supply to the air main charging system must be tapped off the compressed air line upstream of
air main charging system using the control line and screw-in elbow union supplied (see chapter 8).
Important The electrical power supply must be connected on site by a qualified electrician.
9_5855_12E 13 / 52
DHS
6.3.1 Dimensions of 63 bar air main charging system with ball valve
316 173
26 170 33 107
A
B
C
SW
D
G
E H I
F J
Dimensions [mm]
Connection Weight
thread DN A B C D E F G H I J SW [kg]
G 1/2 15 263.6 85 38.6 18.5 65 195 16 56 87 143 26 5.5
G 3/4 20 271.1 85 46.1 21.5 74.6 195 17 56 87 143 32 5.6
G1 25 303.6 107 56.6 26 88 217 21 66 87 153 40 6.9
G 1 1/4 32 308 107 61 31.5 102 217 22 66 87 153 49 8.7
G 1 1/2 40 334.5 117 77.5 36.5 110 258 22.5 71 87 158 56 9.8
G2 50 342.2 117 85.2 45.4 125 258 26 71 87 158 70 11.9
G 2 1/2 65 383.7 135 108.7 59.3 160.6 299 31 78 87 165 87 18.3
G3 80 409.4 182 117.4 69.8 178 348.5 34 86 87 173 104 24.7
DHS 14 / 52 9_5855_12E
6.5 Pressure reducer 6.5.3 Pressure reducer dimensions
The 63 bar air main charging system has an upstream
pressure reducer that reduces the compressed air for the Ø 57,7
control unit.
136,5 / 123,8
on the pressure gauge on the control side
(see chapter 8.4).
The purpose of a pressure reducer is to keep the line Diaphragm
pressure constant regardless of the air consumption and Seat
supply pressure fluctuations. Main valve
The pressure reducer is fitted with a pressure relief
valve that allows air to escape into the atmosphere as Output Input
soon as the pressure on the secondary side rises above
19,1
the set level. The pressure relief valve also enables the
secondary pressure to be reduced even when the air is
not flowing. 50,3
The pressure reducer is factory-set to 5.5 bar and does
not have to be adjusted.
9_5855_12E 15 / 52
DHS
7 Installation 7.1 Installation of air main charging system
CAUTION The air main charging system can be fitted any way in the
pipeline. If required, the control unit can be rotated, for
Important information for silicone-free application. details see chapter 21.
PP Check the marking on the components:
Caution!
Silicone-free components
Incorrect handling of the components can cause the com-
pressed air to become contaminated.
PP Follow the operating instructions
PP Have any maintenance carried out by authorised, trained
DHS 16 / 52 9_5855_12E
7.2 Installation of ball valve Assembly:
PP Shut off plant or plant component.
WARNING PP Secure against re-commissioning.
Danger - maiming! PP Depressurise the plant or plant component.
Risk of limb amputation! PP Completely empty the plant or plant component and
PP When working on the valve always allow it to cool down until any risk of scalding can be
depressurise the system beforehand and ruled out.
unscrew control medium line(s) from the PP Correctly decontaminate, rinse and ventilate the plant
valve. or plant component.
9_5855_12E 17 / 52
DHS
7.3 Installation of butterfly valve Installation location:
WARNING CAUTION
Danger - maiming!
PP Do not apply external force to the butterfly valve.
Risk of limb amputation!
PP Choose the installation location so that the butterfly
PP When working on the valve always valve cannot be used as a foothold.
depressurise the system beforehand and
PP Lay the pipeline so that the valve body is protected
unscrew control medium line(s) from the against transverse and bending forces, and also
valve. vibrations and tension.
PP Inside diameter of the piping must correspond to
WARNING the nominal diameter of the butterfly valve.
DN 40 50 65 80 100 125
The equipment is subject to pressure!
D max 50 61 75 90 115 140
Risk of severe injury or death!
D min 30 40 55 70 95 120
PP Only work on depressurised plant.
DN 150 200 250 300 350 400
CAUTION D max 170 220 270 325 370 420
D min 145 200 245 295 345 395
Hot plant components!
PP Risk of burns!
PP Only work on plant that has cooled down. Butterfly valve
PP Installation work must only be performed by trained
personnel. Shut-off seal
PP Wear personal protective gear as specified in the
system operator's regulations.
ø D max ø D min
DHS 18 / 52 9_5855_12E
Installation position: PP Clamp the butterfly valve with slightly opened disc
The installation position is optional. KAESER recommends centred between pipes with flanges. The disc must
that with contaminated media and DN ≥ 300, the butterfly not project from the body.
valve should be fitted horizontally so that the actuator is to
the right or left of the pipeline and the bottom edge of the
disc opens in the flow direction. This is to prevent deposits.
Installation:
PP Shut off plant or plant component.
PP Secure against re-commissioning.
PP Depressurise the plant or plant component.
PP Completely drain the plant (or plant component) and
let it cool down until the temperature is below the
media vaporization temperature and scalding can be The butterfly valve must be in a slightly
ruled out. open position. Tightening the bolts in closed
PP Correctly decontaminate, rinse and ventilate the plant position will result in leakage and increased
or plant component. torques.
Remove any rough areas (rust, dirt, etc.) from the
Fully open the disc and check the alignment of the
PP
PP
pipe flanges.
piping.
Sufficiently spread the piping flanges. If this is not
Fully tighten the bolts in a diagonal sequence (for
PP
PP
done, the seat/butterfly valve may be damaged.
tightening torques see table) until the flange is
Do not use any flange seals!
completely flush against the body.
PP
Tightening torques
DN 40 50 65 80 100 125 150
PN 16 40 Nm 52 Nm 52 Nm 31 Nm 45 Nm 55 Nm 90 Nm
9_5855_12E 19 / 52
DHS
8 Control air connection 8.2 Control air connection with system
pressure of 16 to 63 bar
PP The air main charging system must be connected to
the feeder pipe using the hose supplied. PP Connect control unit pressure reducer connection P1
PP The air main charging system for system pressures to compressed air line upstream of the valve.
> 16 - 63 bar must be connected to the feeder pipe
(Pos. P1) by suitable means (e. g. copper or stainless
steel pipe) provided on site. No hose is supplied with
P1
this version (see chapter 8.2).
PP If the system pressure is between 0.5 and 4 bar, the
air main charging system must also be connected
to an external compressed air supply. This requires
converting the compressed air system (see
chapter 8.3).
P1
DHS 20 / 52 9_5855_12E
PP Connect control unit connection P1 to compressed air 9 Electrical connection
line upstream of the valve.
PP Connect the additional (external) 9.1 Terminals
compressed air supply (4 - 16 bar) to PP Undo the housing screws and open the housing cover.
connection P2.
PP Make sure that the pressure difference
between P1 and P2 is greater than 1 bar. 3
1 2
P1
P2
To compressed
air system PP Feed the connecting lead 1 through the cable gland 2.
PP Feed the connecting lead in the housing through the
From compressed air ferrite core 3 (only for power supply 90 - 264 V AC).
conditioning system PP Tight the cable gland 2.
PP Connect the cores required to the terminal block.
PP Connect up the 24 V DC or 90 - 264 V AC power
8.4 Control pressure indication (pressure gauge) supply.
The control pressure present can be read off from the 9.1.1 Terminal block X1
pressure gauge (1).
PE N U 4 5 6 7 8 9 10 11
X1
1
Power supply -N
90 - 264 V AC - U
Relay K1
Pressure monitoring
Relay K2
Valve CLOSED
Relay K3
Valve OPEN
Relay K4
Collective fault
PE
9_5855_12E 21 / 52
DHS
9.1.2 Terminal block X2 9.2 Internal fuses
Proceed as follows when replacing fuses:
1 2 3 4 5 6 7 8 PP Switch off the power supply
X2 PP Undo the housing screws and open the housing cover
PP Replace fuses
10
11
9
8
7
6
5
4
3
2
1
8
X1
7
6
IN OUT IN OUT
5
Ext. pressure
sensor
100 bar
External
cut-out
4
3
2
1
Sicherung T 1 A
X2
A
Sicherung T 1,25 A
= Connection
active output
DHS 22 / 52 9_5855_12E
9.3 External cut-out 10.2 Safe compressed air supply
The air main charging system has an "External cut- (set on site)
out" input on terminal block X2, terminals 3 and 4. The Switch position = to the left
external cut-out is intended to be used for monitoring the (blue mark on securing plate)
conditioning system. A fault signal from the dryer causes
the air main charging system to shut off. The external cut-
out can also be tripped by an external switch (e.g. time
switch) during non-working hours.
3
PP Once inserted, turn the key 90° clockwise.
2 1
PP To change the operating mode, remove the hexagon
socket screw (1), the knurled head screw (2) and the
securing plate (3).
PP For "Safe compressed air quality" mode, set the
switch to the right (yellow mark).
9_5855_12E 23 / 52
DHS
13 Visual position indicator
Two-colour LED
DHS 24 / 52 9_5855_12E
14 Operation Example:
The open pressure is to be changed from 5.5 bar to 6.5
CAUTION bar.
Important information for silicone-free application.
PP Operate the air main charging system in a silicone- 1.1
Open pressure
5.5 bar
2-line display,
16 characters,
illuminated
Forwards key
Back key
Upward key
Downward key
9_5855_12E 25 / 52
DHS
DHS 26 / 52 9_5855_12E
15
1 2 3 4 5
SetCalibration SetFunction Service SetBasics Back
9_5855_12E
3.1 3.2 3.3 3.4 3.5
In / Output Diagnosis DHS specific Calibration Back
27 / 52
3.2.1 3.2.2 3.2.3 3.2.4 3.2.5 3.2.6
Error list Hours counter Errors Error function ErrList delete Back
DHS
DHS 28 / 52 9_5855_12E
16 Parameters table
System setting: Safe compressed-air quality Safe compressed-air supply
Name/Date Name/Date
9_5855_12E 29 / 52
DHS
DHS 30 / 52 9_5855_12E
Please detach and keep safe.
9_5855_12E
System in which fitted: Material number:
31 / 52
Installed on: Serial number:
DHS
17 EC Declaration of conformity
EC Declaration of conformity
according to the EC Machinery Directive 2006/42/EC, Annex II, 1.A
The air main charging system is intended exclusively for controlling compressed air systems.
We also declare that the specific technical documentation has been compiled in accordance with part A of
Annex VII.
We expressly declare that the machinery complies with the relevant provisions of the following EC
directives:
2006/42/EC:2006-05-17: (Machinery Directive) Directive 2006/42/EC of the European Parliament
and of the Council of 17 May 2006 on machinery, and amending
Directive 95/16/EC (recast) (1)
2006/95/EG:2006-12-12: (Low voltage directive) DIRECTIVE 2006/95/EC OF THE EUROPEAN PARLIAMENT
AND OF THE COUNCIL of 12 December 2006 on the harmonisation of the laws of
Member States relating to electrical equipment designed for use within certain voltage
limits (codified version)
2004/108/EG:2004-12-15: (electromagnetic compatibility) DIRECTIVE 2004/108/EC OF THE EUROPEAN
PARLIAMENT AND OF THE COUNCIL of 15 December 2004 on the approximation of
the laws of the Member States relating to electromagnetic compatibility and repealing
Directive 89/336/EEC
97/23/EG:1997-05-29 (Pressure Equipment Directive) DIRECTIVE 97/23/EC OF THE EUROPEAN
PARLIAMENT AND OF THE COUNCIL of 29 May 1997 on the approximation of the
laws of the Member States concerning pressure equipment
Joachim Brien
Head of Technical Department
Ingelfingen-Criesbach, February 16
DHS 32 / 52 9_5855_12E
18 Explanation of parameters Menu 1.7 - Unit
Factory setting: bar
18.1 Menu 1 SetCalibration
18.1.1 Basic settings
PP For setting the units in which pressure is displayed,
Menu 1.1 - Open Pressure i.e. bar or psi.
PP For setting the pressure at which the valve opens. Menu 1.8 - Pressure range
PP Open pressure is set according to the selected unit PP For setting the system pressure range.
(bar/psi) and pressure range. PP The pressure range is set according to the selected
0…16 bar / 0…63 bar unit (bar/psi).
0… 230 psi / 0…910 psi The pressure range must match the pressure range of
Menu 1.2 - Hysteresis the pressure sensor used.
Factory setting: 1.0 bar
PP Pressure range 0…16 bar / 0...230 psi
PP Pressure sensor 0…25 bar / 0...363 psi
PP Pressure range 0…63 bar / 0...910 psi
PP For setting hysteresis with which valve closes. PP Pressure sensor 0…100 bar / 0...1450 psi
PP Hysteresis is set according to the selected unit Menu 1.9 - Language
(bar/psi) and pressure range.
Factory setting: German
0…16 bar / 0…63 bar
0… 230 psi / 0…910 psi
Menu 1.3 - Open Time The display language for the parameter names can be
Factory setting: 20 selected. The name of the language is listed on the menu
in the language concerned, see words in brackets.
®® German (Deutsch)
Opening time can be set within the range of 0.1 - 100 % ®® Russian (Russkiy)
(in 0.1% increments). The setting 100 % equates to the ®® English (English)
maximum valve speed. ®® French (Français)
When the operating function is changed (see ®® Italian (Italiano)
chapter 18.4.3), the opening time setting remains ®® Brasilian Portuguese (Português 2)
unchanged. ®® Finnish (Suomalainen)
®® Dutch (Nederlands)
Menu 1.4 - Close Time ®® Turkish (Türk)
Factory setting: 20 ®® Norwegian (Norsk)
®® Spanish (Español)
®® Portuguese (Português)
Closing time can be set within the range of 0.1 - 100 % ®® Swedish (Svensk)
(in 0.1 % increments). ®® Danish (Dansk)
The setting 100% equates to the maximum valve speed. . ®® Polish (Polski)
When the operating mode is changed (see ®® Czech (Český)
chapter 18.4.3), the closing time setting remains ®® Estonian (Eesti)
unchanged. ®® French (Français 2)
®® Greek (Ellinikos)
Hungarian (Magyar)
[bar]
Pressure p
®®
14
®® Croatian (Hrvatski)
12 System
pressure
®® Romanian (Românesc)
10 ®® Slovenian (Slovenščina)
8 Open
Pressure
®® American English (English 2)
6 ®® American Spanish (Español 2)
4 Hysteresis
2 Menu 1.10 - Mounting angle
0
Time t Factory setting: 0°
Valve position
Open
9_5855_12E 33 / 52
DHS
18.1.2 Logging onto and off the system Menu 1.6 - Log Out
Pressing the button disables user access. No more
Menu 1.5 - Login Code changes can be made. The system is locked.
Entry of the password allows user access. The device If there is no user input for the length of time specified
password is: (see chapter 18.4.2), the user is automatically logged off.
1 = logged in
®® Display 0 = logged out
®® Display 1 = logged in
DHS 34 / 52 9_5855_12E
Menu 2.4 Output 4 (Cumulative error) 18.3 Menu 3 Service
Factory setting: Error all
18.3.1 Viewing inputs and outputs
9_5855_12E 35 / 52
DHS
Menu 3.2.4 - Error function 18.4.3 Operating mode of the air main charging
system/pressure relief valve
Important Factory setting: goClose
Factory setting: Normal
The type of error function for errors 02 and 03 (see
chapter "19 Error messages“ on page 36) can be set:
goOpen: If an error occurs, the valve is opened.
goClose: If an error occurs, the valve is closed.. After the operating function is switched to
the reverse setting, the air main charging
Menu 3.2.5 - ErrList delete system works as a pressure relief valve (see
All stored faults are deleted from the error list. chapter 24). In this function, it cannot be
18.3.3 Reading device-specific data used to ensure the compressed-air quality or
as a system start-up aid.
Menu 3.3 - DHS specific The air main charging system can be operated with two
Submenu for reading specific data operating functions:
Menu 3.3.1 - SW Version Normal: operation as a air main charging system
The current software version of the system is displayed. Reverse: operation as a pressure relief valve
Menu 3.3.2 - Serial Number
[bar]
Pressure p
The current serial number of the system is displayed.
14
Menu 3.4 - Calibration 12
System pressure
This menu is intended for the calibration of the pressure 10
Open
DHS 36 / 52 9_5855_12E
Function in the event of an error 21 Changing the control unit position
The control unit position on the pneumatic actuator can
Setting error func- be altered in 90° increments.
tion parameter
Error message Valve position PP Completely shut down the air main charging system.
goClose goOpen PP Disconnect the air hose between the actuator and the
X Closed control unit.
01: DHS closed Undo the four fixing screws (1) on the connection
X Closed
PP
adapter (2).
02: Actual value > X Closed
20.5 mA X Open
03: Actual value < X Closed
3.5 mA X Open
X Not defined
04: Drive Error
X Not defined
9_5855_12E 37 / 52
DHS
Variant 3:
®® Control unit position = 270°
®® Setting for parameter 1.9 - Mounting angle = 90°
WARNING
Hot plant components!
Risk of burns!
Variant 1:
PP
Variant 2:
®® Control unit position = 180°
®® Setting for parameter 1.9 - Mounting angle = 0°
DHS 38 / 52 9_5855_12E
CAUTION P1
Important information for silicone-free application. 8 bar 4 bar
PP Carry out maintenance, repair and cleaning work
with silicone-free gloves.
PP Use only silicone-free cleaning agents when
carrying out cleaning work on the air main charging
system or any of its components.
PP Mounting aids and tools must be silicone-free.
PP Maintenance and repair work on components that
come into direct contact with compressed air or
oil must only be carried out by authorised, trained
KAESER personnel.
Only use genuine KAESER spare parts.
When ordering spare parts, please quote
the full material and serial number for the air
The system pressure P1 must be recorded on the
main charging system (see product label).
low-pressure side. We recommend that you install a
The operator must carry out regular visual examination pressure switch on the high-pressure side that must be
of the butterfly/ball valve dependent on the operating switched to the external release terminal X2: 3 and 4 of
conditions and the potential danger in order to prevent the air main charging system. This should protect the
leakage and damage. high-pressure system from drops in pressure by the low-
pressure system.
With the reverse function, only the valve activation is
23 Options reversed (command: Open => CLOSED and CLOSED
An external remote control unit for wall-mounting is => Open). All other basic functions remain the same
obtainable as an option. (print parameters, opening and closing times).
For details see separate operating instructions The operating mode switch should be set to "safe
compressed-air quality".
CAUTION CAUTION
The equipment is subject to pressure! Important information for silicone-free application.
PP When filling a different compressed-air system,
PP For parts that are to be serviced or replaced and
make sure that the operating pressure of the which come into contact with compressed air or oil,
compressed-air system and its built-in components note the following:
is not exceeded.
®® Use only silicone-free, genuine KAESER parts
®® For every order item, specify "silicone-free" in the
CAUTION item text
Manual override Only use genuine KAESER spare parts.
PP Operating the manual override immediately and When ordering spare parts, please quote
permanently opens the air main charging system. the full material and serial number for the air
PP It is possible to damage the compressed-air system main charging system (see product label).
and the built-in components.
9_5855_12E 39 / 52
DHS
1 2 3 4 5 6 7 8
26
26.1
DHS
2
P1
Compressed air A1
Kompressor
Compressor Druckluftbehälter Kältetrockner
Chiller/dryer Filter
Filter
accumulator
40 / 52
Legende:
Key:
P1 Systemdruck
System pressure
A1 Steuerluftversorgung
Control zum Antrieb
air supply to actuator
1 Steuereinheit
Control ESI
unit ESI (4...16
(4...16 bar
bar oroder 16...63
16...63 bar) bar)
2 Externe Abschaltung
External cut-out
9_5855_12E
c
b
RI-Fließbild Gemeinsame
Common feedEinspeisung
a Installationsbeispiel für Blatt 1
Änderung Datum Name Ersatz durch: Ersatz für: Ursprung: Druckhaltesystem 4...63 bar D
1 2 3 4 5 6 7 8
26.2
Handnotbetätigung
Manual override
Armatur
Valve
9_5855_12E
Umschaltung
Operating mode
Betriebsart
switch
Manometer
41 / 52
Pressure gauge
Legende:
Key:
Druckregler
Pressure 16 bar
regulator, 16 bar
P1 Systemdruck
System pressure
P2 External Steuerlufteingang
Externercontrol (verschlossen)
air inlet (sealed)
Rückschlagventil
Non-return valve
Rückschlagventil
Non-return valve
Drucksensor
Pressure sensor
Systemdruck
System pressure
P2 P1
P&I circuit diagram for air main charging system for system pressure of 4 - 16 bar
c
b
RI-Fließbild
a Druckhaltesystem Blatt 3
Änderung Datum Name Ersatz durch: Ersatz für: Ursprung: max. Netzdruck 16 bar D
DHS
1 2 3 4 5 6 7 8
26.3
DHS
Handnotbetätigung
Manual override
Armatur
Valve
Umschaltung
Operating mode
Betriebsart
switch
Manometer
Pressure gauge
42 / 52
Legende:
Key:
P1 Systemdruck
System pressure
Pressure regulator,
Druckregler 63 bar63 bar
Drucksensor
Pressure sensor
Systemdruck
System pressure
P1
P&I circuit diagram for air main charging system for system pressure of 16 - 63 bar
9_5855_12E
c
b
RI-Fließbild
a Druckhaltesystem Blatt 4
Änderung Datum Name Ersatz durch: Ersatz für: Ursprung: max. Netzdruck 63 bar D
1 2 3 4 5 6 7 8
26.4
1
External Steuerluft
Externecontrol air
P2
(4...16 bar)
(4...16 bar)
9_5855_12E
P1
A1
Kompressor Druckluftbehälter
Compressed air Kältetrockner Filter
Filter
Compressor Chiller/dryer
accumulator
Druckhaltesystem
Air main charging system Druckluftnetz
Compressed
air system
43 / 52
Legende:
Key:
P1 Systemdruck
System pressure
P2 External Steuerlufteingang
Externercontrol air inlet (sealed)
A1 Steuerluftversorgung
Control zum Antrieb
air supply to actuator
1 Steuereinheit
Control unit ESIESI (4...16
(4...16 bar)
bar)
Kondensatablass 2 External Abschaltung
Externecut-out
Condensate drain
3 Absperrarmatur,
Shut-off einfachwirkend
valve, single action
c
b
RI-Fließbild Externe Einspeisung
a Installationsbeispiel für Blatt 2
Änderung Datum Name Ersatz durch: Ersatz für: Ursprung: Druckhaltesystem 0,5...4 bar D
Installation example for external feed air main charging system with system pressure of 0.5 - 4 bar
DHS
1 2 3 4 5 6 7 8
26.5
DHS
Manual override
Handnotbetätigung
Armatur
Valve
Umschaltung
Operating mode
Betriebsart
switch
Manometer
44 / 52
Pressure gauge
Legende:
Key:
Druckregler
Pressure 16 bar
regulator, 16 bar
P1 Systemdruck
System pressure
P2 External Steuerlufteingang
Externercontrol (verwendet)
air inlet (in use)
Rückschlagventil
Non-return valve
Non-return valve
Rückschlagventil
Drucksensor
Pressure sensor
Steuerdruck
Control pressure Systemdruck
System pressure
4...16 bar
4...16 bar
P2 P1
9_5855_12E
c
b
RI-Fließbild
a Druckhaltesystem Blatt 5
Änderung Datum Name Ersatz durch: Ersatz für: Ursprung: externe Einspeisung D
P&I circuit diagram for external feed air main charging system for system pressure of 0.5 - 4 bar
27
1 2 3 4 5 6 7 8
27.1
1) Remove jumper if external
cut-out is to be used.
Wiring diagrams
9_5855_12E
Druckhaltesystem
Air main charging system
GND 24V
DC
7 8 4 5 6 7 8 9 10 11 1 2 3 4 5 6
X2 X1 X2
1)
Provided
45 / 52
on site
16 bar air main charging system, 24 V DC power supply
GND
monitor CLOSED OPEN fault 4...20 mA cut-out
24V DC
(passive)
c
Stromlaufplan
b Druckhaltesystem 16bar Blatt 6
a K1 und K4 25.10.2011 MR Versorgung 24V DC D
getauscht
Änderung Datum Name Ersatz durch: Ersatz für: Ursprung:
DHS
1 2 3 4 5 6 7 8
27.2
1) Remove jumper if external
cut-out is to be used.
DHS
Air main charging
Druckhaltesystem
system
GND 24V
DC
7 8 4 5 6 7 8 9 10 11 1 2 3 4 5 6
X2 X1 X2
Pressure
1) sensor 100 bar
Provided on
46 / 52
site
63 bar air main charging system, 24 V DC power supply
GND
monitor CLOSED OPEN fault 4...20 mA cut-out
24V DC
(passive)
Max. Stromaufnahme
max.power consumption<<1A
1A
9_5855_12E
c
Stromlaufplan
b Druckhaltesystem 63bar Blatt 7
a K1 und K4 25.10.2011 MR Versorgung 24V DC D
getauscht
Änderung Datum Name Ersatz durch: Ersatz für: Ursprung:
1 2 3 4 5 6 7 8
27.3
9_5855_12E
Druckhaltesystem
Air main charging
system
PE N U 4 5 6 7 8 9 10 11 1 2 3 4 5 6
X1 X1 X2
1)
Provided on
47 / 52
site
max. 16A
16 bar air main charging system, 90 - 264 V AC power supply
c
Stromlaufplan
b Druckhaltesystem 16bar Blatt 8
a K1 und K4 25.10.2011 MR Versorgung 90 - 264V 50/60Hz D
getauscht
Änderung Datum Name Ersatz durch: Ersatz für: Ursprung:
DHS
1 2 3 4 5 6 7 8
27.4
1) Remove jumper if external
DHS
cut-out is to be used.
Druckhaltesystem
Air main charging
system
PE N U 4 5 6 7 8 9 10 11 1 2 3 4 5 6
X1 X1 X2
Drucksensor
Pressure
1)
sensor
100100
barbar
Installation
Provided on
48 / 52
Bauseits
site
max. 16A
63 bar air main charging system, 90 - 264 V AC power supply
9_5855_12E
c
Stromlaufplan
b Druckhaltesystem 63bar Blatt 9
a K1 und K4 25.10.2011 MR Versorgung 90 - 264V 50/60Hz D
getauscht
Änderung Datum Name Ersatz durch: Ersatz für: Ursprung:
28 Updating the software PP Different display messages may be shown depending
on the result of the check:
CAUTION
High intensity LED lighting. Update x % Error
PP Risk of eye injury. ReadFile
PP Do not look into the activated LEDs.. OK
The software can be updated while the
system is in operation. While the update is Update x % Error
in progress, the butterfly valve/ball valve is DecryptData
completely closed and then opened again. OK
To prevent that happening, the manual
override must be operated. Update x % Error
CheckFile
PP Operate manual override (see chapter 11). OK
PP Undo the housing screws and open the housing cover
PP Insert appropriate memory card (type microSD card)
Update x% Error
in card slot. Program
OK
Update 100 %
Error
2 GB Remove SD Card
> 2 GB
Error N x%
Remove SD Card
9_5855_12E 49 / 52
DHS
Error messages in the update function
In the event of an error, the message "Error" will be
issued followed by an error number.
Error
message Cause
0 No error
1 Unknown error
Software cannot work with present processor
2
module
Software cannot work with present device
3
hardware
4 Software does not belong to the device
5 Software version already present on the device
6 Error reading the update file
7 Update file contains errors
8 Time-out when reading the update file
9 User exit
10 Error initializing the update
11 Error booting the new software
The update cannot be applied to the existing
12
software version
13 Update not permitted for this device
DHS 50 / 52 9_5855_12E
Goods return declaration (copy specimen)
Legal regulations for the protection of the environment and personnel require that you include the
completed and signed goods return declaration with your dispatch documents.
If this declaration is not completed or not included with the dispatch documents, your return
will not be processed!
If the valve / device was operated with poisonous, corrosive, flammable, aggressive or water-
endangering media, all medium wetted parts must be emptied carefully, decontaminated and rinsed.
Select an appropriate transport container, label it with the name of media which the valve / device has
been in contact. This serves to avoid personal injury or damage to property from the media remains.
Company: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
......................................... ..........................................
......................................... ..........................................
9_5855_12E 51 / 52
DHS
Subject to alteration · 02/2016 · 88363101 *88363101*