Professional Documents
Culture Documents
Regard - Classic - English
Regard - Classic - English
com
REGARD
REGARD 4 20 and Ex CHANNEL CARDS INSTALLATION
AND OPERATION MANUAL
Dräger Limited
Kitty Brewster Industrial Estate
Blyth
Northumberland
NE24-4RG
CONTENT
• New team60-9 to set the analog output behavior during alarm blocking.
• The lower limit value of the fault alarm threshold for abnormal concentration drop
(command 10-7, FLTU) is reduced to -15% of the measuring range.
• The upper limit value of the fault alarm threshold for abnormal concentration
increase (command 10-8, FLTO) is reduced to 115% of the measuring range.
• New team60-9 to set the analog output behavior during alarm blocking.
• An external watchman that guarantees fault-tolerant operation under any conditions viah.
Version 6 software must be used with 4-20 cards version 1.5 or higher. To check the
tightness of the Polytron Cl heads2and HF/HCL, an additional relay must be installed on
the card.
4 Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
Regard Ex Version 4
• New team60-9 to set the analog output behavior during alarm blocking.
• Gaps between PCB tracks leading to the relay are increased up to 3 mm.
• An external watchman that guarantees fault-tolerant operation under any conditions viah.
• Reset button. Ex cards now have a blue reset button. Cards 4-20 and Master cards still
use the black and red reset buttons, respectively.
Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996 5
1. INTRODUCTION
The Regard controller cards and rack are designed for use in a control room
environment. The atmosphere must be free of contaminants and pollutants harmful to
electronic equipment.
Regard controller cards are not designed or certified for use in areas where
flammable or explosive gas mixtures may be present.
1.2 Description
Channel cards are installed in a rack that has screw terminals for all connections to the
card. DC power is supplied to the cards either from a rack-mounted AC power module or
from an external DC power source through the appropriate terminals on the back of the
rack.
Each channel card has connections for the transmitter, alarm relays, analog output and
remote reset. The 4-character display shows the gas concentration at the measuring
head. The buttons on the front panel allow you to display the name of the gas, units of
measurement and measuring range.
Each channel card includes three alarm relays, which are typically configured to trigger
two gas concentration and fault alarms. If required, the fault relay can be configured to
activate a third gas alarm. The analog output provides a 4-20mA, 0-20mA, 1-5V or 0-5V
signal proportional to the reading on the display.
All adjustment, calibration and card testing operations are carried out only using the
front panel controls - no trimming potentiometers are provided. In addition to adjusting
zero, sensitivity, and alarm thresholds, the following settings can be made:
Warning! Do not install 4-20 channel cards in rack positions connected to SE-Ex
heads: higher voltage at the head power terminals will permanently damage the
pellistors.
6 Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
2 COMMAND MODE
2.1 Introduction
All map parameters, including measuring range, zero point, sensitivity, alarm thresholds,
gas name and alarm processing mode, are configured using the corresponding
commands in command mode.
There are three levels of access in command mode, two of which are password protected:
• Reading level, where the configuration settings can be read but not changed, and basic
testing operations can be carried out (access to the level does not require a password).
• Level of service, which allows you to access commands that are used for regular
calibration and maintenance (you must enter a maintenance password).
• Configuration level, which allows you to access all the commands that are used to
configure the map (you must enter the configuration password).
All commands are called as follows: buttonsc and d select but- measures the desired
command (for example, 10-0), then press Reset. The display will show the name of the
command (ZERO in our example) for about one second, and then its current settings.
After that, for most commands, use the buttonsc and d you can change the settings.
Press againReset returns to command number. “Fix” the settings by pressing Reset again,
and the command number will be displayed again.
Save the configuration settings with command 00-2. Exit command mode by selecting
command 00-0. The configuration settings are retained when the card's power is turned
off.
In commands of type 04-6, where the command name (in this example "FR") refers to a
fault alarm relay, the character "F" will change to "A3" if relay 3 is configured as a gas
alarm relay. In this example, "FR" will become "A3 R".
The service level password is set at the factory to "MMMM"; configuration level password
"CCCC".
In command mode, you can manually change the state of the alarm relays using
commands 14-4 (relay A1), 14-5 (relay A2) and 14-6 (fault alarm/A3 relay).
8 Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
2.4 Example
• Press and hold the buttonReset(R) five seconds. The map will
show the software version
software (v1.6) and will switch to V1.6 00-0
command mode.
• Click the buttonReset: The card shows the team P.WD ????
name and is ready for the password to be entered.
• Clickreset. SAVE NO
• Clickreset. QUIT NO
Display
In standard mode, the display shows the gas concentration
• Flashing message "FSD" indicates that the gas concentration has gone beyond the
upper limit of the measuring range.
• A flashing LED indicates that an alarm has been activated and the corresponding
signal The external relay is in the alarm state (assuming the relay is not blocked). The
alarm is acknowledged by pressing the Reset button.
• A solid LED indicates that the alarm has been acknowledged, but The readings on the
display are still above the alarm threshold. The status of the alarm relay depends on
its self-latching/handshaking settings (see section 3.2.2).
• An unlit LED indicates that the alarm has been cleared or is not present.
In command mode, these LEDs indicate whether the gas alarm condition would be in
normal mode: activated (LED on) or not activated (LED off). Recall that in command mode
all relays are blocked.
SD Fault
The Fault LED indicates a fault in the measuring circuit or head.
• Flashing LEDFault indicates that a fault alarm is active and the fault relay is in alarm
(assuming the relay is not disabled). The alarm is acknowledged by pressing Reset.
• Constantly lit LEDFault indicates that a fault alarm has been acknowledged, but the
condition that triggered the alarm still exists. The status of the fault alarm relay
depends on its self-latching/acknowledgement settings.
10 Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
• An unlit LED indicates that the alarm has been cleared or is not present.
In command mode, the fault indication LEDs indicate whether the fault alarm condition
would be in normal mode: activated (LED on) or not activated (LED off).
SD Power
The Power LED is lit when the card has DC power and is operating normally.
The Power LED flashes in the event of an operational failure (see Appendix A).
SD Inhibit
The Inhibit LED lights up to indicate that the alarm relays are disabled. The alarm relays
are disabled when: the card is in command mode, a fault alarm is activated, the card has
detected a 1 Hz calibration signal from the Polytron measuring head, and within 30
seconds after power-on.
The Inhibit LED flashesturning onevery two seconds to indicate that one or more alarm
relays have been disabled. In command mode, when the Inhibit LED is normally lit, it will
flash,turning offevery two seconds.
R (Reset)
The Reset button is used to:
• Acknowledge alarms;
• Enter command mode and select commands and configuration options, such as
walking in command mode.
Alarms can also be acknowledged and reset by short-circuiting the remote reset outputs.
ButtonscAndd
Buttonsc and d are used in command mode to select commands and set wok
configuration.
Use commands 11-7 (relay A1), 11-8 (relay A2) and 11-9 (fault relay / A3) to configure relay
operation.
Use command 11-1 to set the A1 alarm threshold and 11-2 to set the A2 alarm threshold.
Command 11-3 can be used to set the A3 alarm threshold if relay 3 is configured as a gas
alarm relay.
Alarm A3 can be configured as high or low gas alarm, or as FLT (fault alarm). If you set A3
as FLT, the A3 alarm will be disabled and relay 3 will go into fault alarm mode.
Use commands 11-4 and 11-5 to set A1 and A2 as high or low gas alarms and 11-6 to set
A3 as high or low gas alarm or FLT.
1 Gap between activation threshold and alarm reset. It is sometimes called the "dead zone".
12 Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
Use commands 60-4, 60-5 and 60-6 to disable the alarm relays.
Warning! A latched relay will not operate when a gas alarm occurs.
Fault alarms can be set for each channel when the measurement range is exceeded. This
allows a fault alarm to be activated if the signal from the transmitter falls below zero or
exceeds the upper range limit by a pre-set value. The value by which the signal must fall
below zero or exceed the upper limit of the measuring range can be set independently
for the abnormal rise and fall alarms. Both alarms can be set at the same time.
If a fault alarm is set for an abnormal increase in concentration, then the growth rate of
the signal from the measuring head is monitored. If the signal goes out of range faster
than can be expected based on the response time of the transmitter, then an abnormal
rise alarm will be triggered without activating the gas concentration alarm. Similarly, if an
abnormal drop in concentration alarm is set, decreasing the signal too quickly will trigger
an abnormal drop in concentration alarm without activating the low gas alarm.
Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996 13
Command 10-7 allows you to set or disable the abnormal concentration drop alarm.
Command 10-8 allows you to set or disable the abnormal concentration increase alarm.
A short circuit in the cable leading to the pellistor head usually triggers a gas alarm or a
fault alarm. However, if there is a short circuit between two current-carrying cores of the
cable leading to the head, or between all three cores, the signal change may not be
sufficient to activate a gas alarm or a fault alarm.
The power supply voltage applied to the head cable is measured at the power supply
terminals of the Ex card head. Typically, when the resistance of the measuring head
changes, this voltage does not change by more than a few hundred millivolts (recall that
the head is supplied with a fixed current), but an open connection will change this
voltage by 1 V or more. For example, if the supply voltage applied to the head cable is 5 V
on the card and 2 V on the measuring head, then shorting two current-carrying strands
somewhere between the system and the head will reduce the supply voltage by at least 2
V. Similarly, an open circuit will increase the supply voltage to the transmitter cable.
The head power failure alarm will be triggered if the head power supply voltage change
exceeds the alarm threshold. The change in supply voltage is measured relative to the
reference value - the power supply voltage of the head, fixed at the last zeroing of the
display by command 10-0 (ZERO). In the event of a power failure, the message “HFLT” will
flash on the display and a fault alarm will be activated.
Use command 10-9 to set the alarm threshold or disable the transmitter power failure
alarm. The head power failure alarm threshold can be set in the range of 0.5 – 2.0 V.
Warning! If the power supply voltage of the measuring head on the card is close to
the maximum value (9 V), then it is impossible to detect an open circuit in the
power supply of the head.
14 Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
The analog output can drive a maximum load of 500Ω in current mode, or a minimum
load of 1kΩ in voltage mode. The maximum output signal at the analog output is 20mA
(or 5V in voltage mode).
Command 14-2 allows you to control the output signal in display resolution increments,
and command 14-3 sets the output signal in milliamps.
• teams14-2 and 14-3 you can manually change the output signal.
• During the initial alarm blocking period at power-up, the output signal is held at the
level corresponding to the absence of gas.
Command 60-9 allows you to set the behavior of the analog output during alarm
blocking.
Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996 15
CH4,H2S, CO, O2, Cl2, SO2, NO, NO2, NH3, O3, CO2, ClO2, HCN, HCl, HBr, HF, H2, Br2, H2O2,
EO, Ash3.PH3, B2H6, SiH4.
Ex cards The gas type is set to 'Ex'. This setting can be changed by specifying a user-defined type
of gas using command 52-0 and selecting the USER option in command 04-1.
3.6 Units
The following predefined units can be selected:
Use command 04-1 to set the units. Command 52-0 allows you to enter an additional,
user-defined unit of measure.
0-1, 0-2, 0-3, 0-5, 0-10, 0-20, 0-25, 0-30, 0-50, 0-100, 0-200, 0-250, 0- 300, 0-500, 0-1000,
0-3000, 0-9999.
The display resolution changes depending on the selected range (see Appendix C). If
required, other ranges can be programmed by Dräger.
Use command 10-0 to set zero and command 10-1 to set upper range limit.
3.9.2 Ex cards
The Ex card will show zero with a zero signal at the output of the measuring bridge, and
the upper limit of the measuring range with a preset signal at the output of the
measuring bridge between 50 and 350 mV.
16 Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
Command 10-0 can be set to zero on the display, balancing the bridge sensor.
Command 10-1 allows you to set the calibration gas concentration on the display.
Command 10-2 allows you to set the zero drift deadband between 0% and 5% of the
upper limit of the measurement range.
The Zero Drift Deadband setting does not affect travel. analog you-
Use:
• team10-9 to set the test mode on or off and set the level that the 4-20mA transmitter
signal must reach for the transmitter to pass the test. This threshold applies to both
automatic and manual testing.
If the test is successful, the display will show the message “PASS” for 30 seconds, after
which the card will return to normal mode.
If the head fails the test, the message "FAIL" will be displayed. After 30 seconds, a fault
alarm will be triggered and the card will continue to operate normally. The message
“FAIL” will remain on the display until the fault alarm is acknowledged. Gas alarms and all
other map functions will remain operational.
2 To use the head test for Cl2, this additional relay must be installed by Dräger.
18 Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
4 INSTALLATION
4.1 Grounding
The ground terminal of the mains connector (E) on the rear panel is not electrically
connected to the metal of the rack. A ground strip must be installed from the rack to the
ground. The L, N and E pins on the rear panel connector must only be connected to a DIN
type mains connector.
DC power can be connected to either DC connector or both, but these connectors should
not be used to “daisy-chain” power from one rack to the next.
An internal rack-mounted power supply module can be located on the left side of the
rack, occupying one or more channel card slots. Specifications for internal power supply
modules are given in Appendix B. Use the power consumption figures given in Appendix
C to determine power supply requirements.
If a 3-wire transmitter is used with the 4-20 card, the current drawn by the transmitter
must be added to the current drawn for that channel. The maximum current supplied by
the 4-20 card to the measuring head is 700 mA.
4.3 Cooling
Each channel card typically dissipates 3-4 watts of heat. Therefore, if a large number of
cards and racks are installed in an enclosed space, forced air cooling must be used to
prevent the cards from overheating. Use the power dissipation values below to
determine the required cooling.
The power dissipation is given for a supply voltage of 24 V. If the supply voltage is
increased or decreased, these values increase or decrease proportionally. The “typical”
value is for the card in normal mode with one relay energized and no alarms. The
“maximum” value refers to the card in the alarm state, when all LEDs are lit and all relays
are on.
The DC input terminals do not have blocking diodes to prevent current from flowing from
the rack-mounted power supply module to the battery or external DC power. Therefore,
the emergency power supply must have adequate backfeed protection. For more
information on emergency power supplies, see Dräger's manual."Working with an
emergency power source".
Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996 19
If the emergency battery is to be charged from the internal power supply module, the
battery must always be connected to the DC terminals on the back of the power supply
module. This prevents excess current from flowing through the back panel PCB traces
when charging a fully discharged battery.
A single-core armored PVC cable without a shield or braid does not provide adequate
protection against RF interference. Such cables may only be used for connection to
transmitters if it is known that RF interference is unlikely to occur during operation of the
installation, or if the cabling method provides sufficient protection against RF
interference.
To determine the maximum cable length for the 4-20mA heads, see the heads manual.
Put each card into command mode using the configuration level password. It is advisable
to lock each card in command mode with command 60-0 to prevent automatic return to
normal mode during system setup.
Use commands 11-4 and 11-5 to set up high or low concentration alarm.
2. In the absence of gas in the measuring head, the buttonsc and d zero for now- display.
3. If the display is still above zero, and when you pressd output "END-", then the signal
from the measuring head is too high and does not allow zeroing; if the display shows
a negative value, and when pressedd “END+” is displayed, the head output is too low.
If necessary, check the measuring head and recalibrate it.
2. Apply a known concentration of gas to the transmitter and wait for the display to
stabilize.
22 Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
3. Buttonsc and d adjust the display until it matches with calibration gas concentration.
The card is now calibrated and configured for normal operation. If necessary, other
configuration settings can be changed, such as normally energized alarm relays,
abnormal concentration alarm, or zero drift deadband, without affecting the main
settings or calibration.
Once the settings have been saved, removing the card or turning off the power will not
cause the settings to be lost.
5.2 Ex cards
The following sections describe the basic setup and calibration procedure for Ex cards
that must be completed for each Ex card installed in the system.
1. Select command 04-8. The display will show the transmitter current.
2. Press the buttonc to increase the current or d to decrease it. Sign A '+' after the value
indicates that the current is slightly above the value; the '-' sign means that the current is
slightly lower.
"MAX" on the display means that the maximum output voltage of the card is set;
"MIN" means that the minimum output voltage is set.
"END+" on the display indicates that the maximum value of the current regulation
range is set (about 350 mA); "END-" indicates the minimum current.
3. Click Reset.
Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996 23
Allow the head to stabilize for at least one hour. Before carrying out the following
operations, check the current of the measuring head again: it may change slightly due to
heating3cards.
Use commands 11-4 and 11-5 to set up high or low concentration alarm.
Always adjust the alarm thresholds after changing the range, because when the range is
changed, the alarm thresholds are automatically reset to the factory default settings.
2. In the absence of explosive gas on the measuring head, push buttonsc ord set the
display to "YES" and press Reset.
A flashing "LOW" or "HIGH" message indicates that the transmitter zero error is too
high. Check head and/or connections.
A flashing "FAIL" message indicates that the signal from the head has changed during
the zero adjustment. Wait for the head to fully stabilize and repeat the zeroing
procedure again.
2. Apply a gas of known concentration to the transmitter and wait for the display to
stabilize.
3. Buttonsc and d adjust the display until it matches the calibration gas concentration.
Occasionally, the message “WAIT” may appear on the display while the card gain is
adjusted to maintain the optimal resolution.
The display message "END+" or "END-" indicates that the card has reached the
maximum or minimum gain: the output from the probe is either too low or too high.
The display will show the calculated head output in volts, corresponding to the upper
limit of the measuring range. You can use this value to control how the head
sensitivity changes during subsequent calibrations.
3 Like changes in operating temperature, changes in ambient temperature within the specified operating
limits do not change the transmitter current.
24 Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
Each card is now calibrated and set up for normal operation. If necessary, other
configuration settings can be changed, such as normally energized alarm relays,
abnormal concentration alarm, or zero drift deadband, without affecting the main
settings or calibration.
Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996 25
6 COMMANDS SUMMARY
Note: When changing the range, both alarms are automatically set to increase in
concentration with thresholds of 20% and 40% of the upper limit of the measuring
range.
04-3 FSDL Enabling or disabling the self-locking mode for exceeding the measuring
range
1. Select command 04-3 and press Reset.
2. The display will show "YES" if the overrange self-lock mode is enabled, or "NO" if it is
disabled.
3. Buttonsc or d change the setting.
4. Click Reset.
Note: If the overrange self-latching mode is set, the alarms will be self-latching even if
they have been configured as non-self-latching by commands 11-7, 11-8 or 11-9.
04–7 ACl2 Setting the automatic head leak test interval to Cl (only for cards 4-20)
2
Sets the interval between automatic tests or disables automatic testing. This command
is only available in software version 1.5 or higher.
5. When the bridge is balanced, the display will show “OK” and the display will return
to command 10-0.
• If the measuring bridge cannot be balanced, the display will show flashing message
"LOW" or "HIGH" is displayed. Press Reset to return to command 10-0. Check head
and connections.
• If the flashing message "FAIL”, the head signal has changed during the zero
adjustment. Press Reset to return to the 10-0 command and wait for the head to fully
stabilize.
28 Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
5. Click Reset.
Note: The point in the measuring range can only be adjusted within ±1 mA. If you cannot
get the correct reading on the display, the transmitter may need to be recalibrated.
5. Click Reset.
Occasionally, the message “WAIT” may appear on the display while the card's gain is
adjusted to maintain optimal resolution. Before pressing the buttons againc or d, wait
until the display shows gas concentration is shown.
If by pressing the buttonc, you get the message "END+", the head output is too low for
proper calibration. If by pressing the button
d, you get the message "END-", then the output signal of the head exceeds the
maximum range of the card.
5. Click Reset.
The signal can be set to 4mA even if the analog output is configured as 0-20. If the
analog output is set to voltage mode, then set the output voltage to 1.0 V. The
adjustment range is approximately ±0.1 V in 5 mV steps.
Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996 29
10-7 FLTU Setting the alarm threshold for abnormal concentration drop
Cards 4-20 From 0.5 mA to 3.5 mA inclusive in 0.1 mA steps; or OFF (disabled).
Ex cards From -15% to -5% of the upper limit of the measuring range in steps of 1%; or OFF
(disabled).
1. Select command 10-7 and press Reset.
2. The display will show the current abnormal concentration alarm threshold.
3. Clickc or d to change the setting. Choice "OFF” disables the abnormal concentration
drop alarm.
4. Click Reset.
10-8 FLTO Setting the alarm threshold for abnormal concentration increase
Cards 4-20 From 20.5 mA to 23.5 mA inclusive in 0.1 mA steps; or OFF (disabled).
Ex cards From 105% to 115% of the upper limit of the measuring range in steps of 1%; or OFF
(disabled).
1. Select command 10-8 and press Reset.
2. The display will show the current abnormal alarm threshold.
3. Clickc or d to change the setting. Choice "OFF” turns off the abnormal concentration
alarm.
4. Click Reset.
10-9 LCI2 Threshold setting for Cl2 head leak test (cards 4-20)
Sets the threshold for the test or blocks the test. The threshold is entered as a
percentage of the upper limit of the measuring range. The minimum threshold for
verification is 20%, the maximum is 100%. Selecting "OFF" disables the check. This
command is only available in software version 1.5 or higher.
1. Select command 10-9 and press Reset.
2. The display will show the current threshold for leak testing or "OFF" if testing is
disabled.
3. Pressingc or d, change the setting. "OFF” is selected by pressingc, when the display
shows 100%, ord when the display shows20%.
4. Click Reset.
10-9 FLTS Threshold voltage setting for head power failure alarm (Ex
cards)
Sets a change in head supply voltage that triggers a fault alarm. The threshold voltage
can be set from 0.5V to 2.0V in 0.1V steps, or disabled by selecting "OFF". The “OFF”
setting disables the triggering of a fault alarm when the head supply voltage changes.
4. Click Reset.
11-0 HYST Alarm hysteresis setting
The alarm hysteresis can be set within 0-5% of the upper limit of the measuring range in
0.5% steps.
1. Select command 11-0 and press Reset.
2. The display will show the current hysteresis setting.
3. Clickc or d to change the setting.
4. Click Reset.
thirty Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
11-6 A3M Alarm setting A3,as a fault alarm or as anxiety about rising or
falling concentration
1. Select command 11-6 and press Reset.
2. The display will show the current setting: "FLT" for a fault alarm, "RISE" for a rise
alarm, or "FALL" for a fall alarm.
5. The display will show "WAIT" for a second and then "TEST".
6. If the head output exceeds the test threshold (set by command 10-9), the display will
briefly show the message "PASS" and then return to command 14-7.
7. If the head output does not exceed the test threshold within 1 second, the display will
show a flashing 'FALT' message. Click Reset.
60–9 AINH Setting the behavior of the analog output when blocking alarms
This command is only available in software version 1.5 or higher.
1. Select command 60-9 and press Reset.
2. The display will show the current setting.
3. Buttonsc or d choose: OFF
The output continues to indicate the current gas
concentration.
HOLD The output is latched to the value that occurred before the
alarm was disabled.
3/5 The output signal switches at a frequency of 1 Hz between 3 mA and 5
mA (Polytron calibration signal).
4. Click Reset.
Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996 35
7.1 Maintenance
Regard controller systems are maintenance free, but should be checked regularly for
proper operation.
The measuring heads should be checked and re-calibrated at the intervals specified in
the respective measuring head operating instructions.
An operational failure is a malfunction in the operation of the cards that is not related to
problems in the transmitter circuit. Operational faults are divided intocritical, which can
stop the system, andnot criticalwhen the system is still running but its functionality may
be limited.
The Power LED will flash once per second and the standard display will alternate with one
of the fault codes shown in the following table. Critical faults are also reported by turning
the fault relay on and off at a rate of 1 per second.
If relay 3 is configured as a gas alarm, it will not turn on and off to indicate a critical fault.
However, failure of the microcontroller (FLTM) will cause this relay to switch, regardless
of its configuration.
Operational faults are self-latching and cannot be acknowledged. After removing the
cause of the fault, press Reset to reset the fault indication. If the display does not reset
after pressing Reset, the fault has not yet been rectified.
FLTC Communication error.Critical. The functions Check the card number (command
controlled by the master card will not 52-1), master card configuration and
work, but the channel card will continue to work RS-485 connections.
FLTD Data error.critical. Try to save the new settings with
The configuration settings have been corrupted. command 00-2. If this does not reset
Alarms may turn out to be unreliable. The default the fault, then replace the card.
configuration settings will be used.
FLTH Supply voltage too high. Critical. Check the power supply.
FLTI Data mismatch in RAM.Not critical. Data mismatch If repeated, replace the card.
detected in EEPROM and RAM. Data in RAM corrected
using data from EEPROM.
FLTL Supply voltage too low. critical Check the power supply.
FLTM Microcontroller failure.critical. If the card does not reset, replace it.
The screen alternates between "FLTM" and an
additional fault code. The card should reset
automatically after 2 seconds.
FLTP (Ex cards only.) EEPOT malfunction. Not Press Reset to reset the fault. Re-zero
critical.Mistaken change state of the the map if necessary.
potentiometer balancing the electronic circuit.
FLTR Remote reset failure.Do not criticize chesky.There is Check the operation of the remote
information that contacts dis- tantal reset permanently reset and connection.
closed. The remote reset input will be ignored.
FLTW Reset watchman.Not critical. An unknown If the problem persists, replace the
software error caused the card to reset card.
automatically.
The card will continue to operate
normally, but all alarms can be reset.
Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996 37
zd
4 24 V
6 24 V
8 24 V
10 0V
12 0V
14 0V
16 NC
18 NC
20 NC
22 NC
24 NC
26 NC
28 NEUTRAL (NEUTRAL)
thirty LIVE (LINE)
32 EARTH
NC = NOT CONNECTED
Note that pins 4, 6 and 8 are connected to each other on the rear panel. Therefore, it is
not necessary to supply power to all these terminals. For example, you can use a power
supply that has a 24V output on pin 4 + a control wire on pin 6, and pin 8 is not
connected. Similarly, it is not necessary to apply 0 V to each of pins 10, 12, and 14.
38 Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
APPENDIX C: SPECIFICATIONS
Environmental conditions
Temperature 0 - 50 °C
Relates humidity 0 - 90% non-condensing
Vibration Resp. BS 2011 Part 2.1 Fc
Current consumption at 24 V
Map 4-20 typical 125 mA
(without head) maximum 300 mA
Ex card typical 200 mA
(with head) maximum 500 mA
analog output
Max. load (current mode) 500 ohm
Min. load (voltage mode) 1 kOhm
Weight
Rack 2.1 kg
Channel cards 220 g
SIDE VIEW
195
NOT TO SCALE
133
132.5 38 57 38
PANEL IN SECTION
FRONT VIEW
483 (19")
465
465
450
57 57
Ø6.5
40 Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
SIDE VIEW
NOT TO SCALE
195
133
132.5 38 57 38
FRONT VIEW
268
252
252
236
57
Ø6.5
57
E.1 Rear Panel Terminals
Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
supply + + supply
permanent permanent
current - - current
1 Breaker-
-
2 Collection - FAULT RELAY/A3
-
3 contactor-
4 Breaker-
-
5 Collection - RELAY A2 RELAYS SHOWN IN DISCONNECTED STATE
-
6 contactor-
7 Breaker-
-
8 Collection - RELAY A1
-
9 contactor-
10 Nutrition - CONNECTIONS SHOWN FOR ONE
- CHANNEL: OTHER CHANNELS ARE
eleven Signal - MEASURING HEAD
- IDENTICAL
12 0V -
13 -
- REMOTE RESET
14 -
15 Exit -
- ANALOGUE OUTPUT
16 0V - L
supply
N
network
E food
B A
RS485
41
42 Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
PERMANENT
CHANNELS
TERMINALS
TERMINALS
SUPPLY
REGARD REAR BOARD
TOKA
24 V
0V
eleven
10
12
MEASURING HEAD
+
-
Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996 43
FAST. TOKA
CHANNELS
TERMINALS
TERMINALS
SUPPLY
REGARD REAR BOARD
24 V
0V
eleven
10
12
MEASURING HEAD
-
Nutrition
0V
Signal
44 Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
FAST. TOKA
CHANNELS
TERMINALS
TERMINALS
SUPPLY
REGARD REAR BOARD
24V
eleven
10
12
0V
E
K1
K2
K3
K4
MEASURING HEAD
E.5
Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
Wiring diagram for 2-wire 4-20 mA transmitter through a safety barrier
REGARD REAR BOARD
2-WIRE EX-PROOF MEASURING HEAD
SECURITY BARRIER
MTL 787S+
+ 3 1 10
TERMINALS
- 4 2 eleven
CHANNELS
12
24 V TERMINALS
0V SUPPLY
FAST. TOKA
45
46 Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996
E.6 Connection diagram of a two-wire measuring head through the safety
barrier MTL3041
FAST. TOKA
REGARD REAR BOARD
CHANNELS
TERMINALS
TERMINALS
SUPPLY
24 V
0V
eleven
10
12
1
2
3
4
EX-PROOF ZONE
MTL3041
5
6
2-WIRE EX-PROOF MEASURING HEAD
EXPLOSIVE AREA
+
-
Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996 47
FAST. TOKA
CHANNELS
TERMINALS
TERMINALS
REGARD REAR BOARD
SUPPLY
24 V
0V
eleven
10
12
LOVKA
POLYTRON SE-Ex
ISMHERITAL GO
Yellow
Black
Brown
48 Channel cards REGARD4-20 and Ex. Installation and operation manual. Vol. 4. January 1996