1. Equivalent circuit

𝑍𝑀 = 𝑅0  𝑗𝑋0 = 𝑅𝑐  𝑗𝑋𝑀

Facebook page : EEE Career Academy | Facebook


2
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

2. 𝐸𝑥 = 4.44 𝑓 𝑁𝑥

𝐸1 = 4.44 𝑓 𝑁1
𝐸2 = 4.44 𝑓 𝑁2

Transformation ratio
1 𝑁2 𝐸2 𝐼1
=k= 𝑎
= 𝑁1
= 𝐸1
 𝐼2

3.
𝑅02 = 𝑅2 + 𝑅1′ = 𝑅2 + 𝐾 2 𝑅1

𝑅2 𝑅2 + 𝑘 2 𝑅1 𝑅02
𝑅01 = 𝑅1 + 𝑅2′ = 𝑅1 + = =
𝐾2 𝐾2 𝐾2

4.
𝐼1 = 𝐼0 + 𝑘𝐼2

𝑉1 = 𝐸1 + 𝐼1 𝑍1
𝐸2 = 𝑉2 + 𝐼2 𝑍2

5. I0 −0 = 𝐼𝑤 − 𝑗𝐼

Facebook page : EEE Career Academy | Facebook


3
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

6.
O.C. Test:
Normally H.V. side is kept open, done for rated voltage

( 𝑰𝟐 = 𝟎, 𝑰𝟏 = 𝑰𝟎 (𝒗𝒆𝒓𝒚 𝒗𝒆𝒓𝒚 𝒔𝒎𝒂𝒍𝒍)


𝑽𝟏 = 𝑬𝟏 + 𝑰𝟎 𝒁𝟏  𝑬𝟏 𝑓𝑜𝑟 𝑂. 𝐶. 𝑡𝑒𝑠𝑡 )
(when 𝑽𝟏𝜭 = 𝑬𝟏𝜭 = 𝟎 𝒐𝒓 𝑽𝟏  𝑬𝟏 𝒂𝒔 𝒓𝒆𝒇𝒆𝒓𝒆𝒏𝒄𝒆 )

𝑉1 𝑉1
𝑅0 = =
𝐼0 𝐶𝑜𝑠 0 𝐼𝑤

𝑉1 𝑉1
𝑋0 = =
𝐼0 𝑆𝑖𝑛 0 𝐼

Actually
(Core Power) 𝑺0 = 𝐸1 𝐼0∗ = 𝑊0 + 𝑗𝑄0
I0 −0 = 𝐼𝑤 − 𝑗𝐼

2
|𝐸1 |
𝑊0 = Re ( 𝐸1 𝐼0∗ ) = = |𝑰𝟎 |𝟐 𝑹𝒆(𝒁𝑴 )
𝑅0
= 𝐸1 𝐼0 cos(𝐸1𝛳 − 0 )
(𝑣𝑒𝑟𝑖𝑓𝑖𝑒𝑑 𝑓𝑟𝑜𝑚 𝐸𝑥 32.25)

⃗⃗⃗⃗1
𝐸
ZM = R 0  jX0 =
𝐼⃗⃗⃗0

|𝑬𝟏 |𝟐 𝐸1
𝑅0 = =
𝑷𝒄 𝐼0 𝐶𝑜𝑠 (𝐸1𝛳 − 0 )

|𝑬𝟏 |𝟐 𝐸1
𝑋0 = =
𝑸𝒄 𝐼0 𝑆𝑖𝑛 (𝐸1𝛳 − 0 )

Facebook page : EEE Career Academy | Facebook


4
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

7.
E  𝑓𝐵𝑚

Hysteresis Loss, 𝑊ℎ  𝑓𝐵𝑚


1.6

Eddy current Loss, 𝑊𝑒  𝑓 2 𝐵𝑚


2

8.
S.C. Test:
Normally L.V. side is short-circuited, done for rated current

𝑉𝑠𝑐 = 𝐼𝑠𝑐 𝑍𝑜𝑥

𝐼𝑠𝑐 = ?

𝑊𝑠𝑐 = 𝐼𝑠𝑐2 𝑅𝑜𝑥

9.
%R = % Cu Loss
𝐹𝑢𝑙𝑙 𝐿𝑜𝑎𝑑 𝐶𝑢 𝐿𝑜𝑠𝑠 𝑦
= × 100 % = × 100 %
𝐹𝑢𝑙𝑙 𝐿𝑜𝑎𝑑 𝐾𝑉𝐴 𝐹𝑢𝑙𝑙 𝐿𝑜𝑎𝑑 𝐾𝑉𝐴

10.
efficiency,
𝑙𝑜𝑎𝑑 = 𝐿𝑜𝑎𝑑 𝐾𝑉𝐴 × 𝑝𝑓
𝐿𝑜𝑎𝑑 𝐾𝑉𝐴 2 × 100%
𝐿𝑜𝑎𝑑 𝐾𝑉𝐴 × 𝑝𝑓 + 𝐶𝑜𝑟𝑒 𝐿𝑜𝑠𝑠 + ( ) × 𝐹𝑢𝑙𝑙 𝐿𝑜𝑎𝑑 𝐶𝑢 𝐿𝑜𝑠𝑠
𝐹𝑢𝑙𝑙 𝐿𝑜𝑎𝑑 𝐾𝑉𝐴

𝐿𝑜𝑎𝑑 𝐾𝑉𝐴 × 𝑝𝑓
= 𝐿𝑜𝑎𝑑 𝐾𝑉𝐴 2 × 100%
𝐿𝑜𝑎𝑑 𝐾𝑉𝐴 × 𝑝𝑓 + 𝑥 + (𝐹𝑢𝑙𝑙 𝐿𝑜𝑎𝑑 𝐾𝑉𝐴) ×𝑦

Facebook page : EEE Career Academy | Facebook


5
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

11.
For Max efficiency: 𝑚𝑎𝑥
Cu Loss equals to Core Loss

𝐶𝑜𝑟𝑒 𝐿𝑜𝑠𝑠
KVA for 𝑚𝑎𝑥 = Full Load KVA √
𝐹𝑢𝑙𝑙 𝐿𝑜𝑎𝑑 𝐶𝑢 𝐿𝑜𝑠𝑠
𝑥
= Full Load KVA √
𝑦

KVA for 𝑚𝑎𝑥 × 𝑝𝑓


 𝑚𝑎𝑥 = × 100%
KVA for 𝑚𝑎𝑥 × 𝑝𝑓 + 𝐶𝑜𝑟𝑒 𝐿𝑜𝑠𝑠 + 𝐶𝑜𝑟𝑒 𝐿𝑜𝑠𝑠

KVA for 𝑚𝑎𝑥 × 𝑝𝑓


= × 100%
KVA for 𝑚𝑎𝑥 × 𝑝𝑓 + 𝑥 + 𝑥

12.

Regulation
(According to B.L. Threza)

Page: 1156-1157

Facebook page : EEE Career Academy | Facebook


6
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

(According to Hubert) P-69 (exact equation without cosidering the Core)

%𝒓𝒆𝒈𝑳𝒐𝒂𝒅 = √(𝑹𝒑𝒖 (𝑳𝒐𝒂𝒅) + 𝑪𝒐𝒔)𝟐 + (𝑿𝒑𝒖 (𝑳𝒐𝒂𝒅)  𝑺𝒊𝒏)𝟐 − 𝟏

𝐕𝟏 − 𝐕𝟐′  𝐕𝟏′ −𝐕𝟐 


%𝐫𝐞𝐠 =  𝟏𝟎𝟎% =  𝟏𝟎𝟎%
𝐕𝟐′  𝐕𝟐 
𝑉2
where 𝑉2′ = , 𝑉1′ = 𝐾𝑉1
𝐾

(According to Chapman, P-100)

𝐕𝟏 − 𝐕𝟐′  𝐕𝟏′ −𝐕𝟐 


%𝐫𝐞𝐠 =  𝟏𝟎𝟎% =  𝟏𝟎𝟎%
𝐕𝟐′  𝐕𝟐 
𝑉2
where 𝑉2′ = , 𝑉1′ = 𝐾𝑉1
𝐾

(According to Hadi Saadat, P-71)

𝐕𝟏 − 𝐕𝟐′  𝐕𝟏′ −𝐕𝟐 


%𝐫𝐞𝐠 =  𝟏𝟎𝟎% =  𝟏𝟎𝟎%
𝐕𝟐′  𝐕𝟐 

Facebook page : EEE Career Academy | Facebook


7
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

𝑉2
where 𝑉2′ = , 𝑉1′ = 𝐾𝑉1
𝐾

13. Load Sharing

Facebook page : EEE Career Academy | Facebook


8
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

1.
(a)

Ans: 1300 W, 1400 W

(b) * PGCB-2021

When a transformer is connected to a 240-v, 25-Hz supply; Hysteresis Loss is 846 w;


what will be this loss at 240-v, 60-Hz
Ans: 500.315 w

2.

Ans: 3495 W, 1210 W; 3196 W, 1000 W; 3299 W, 1210 W

3. (Hubert Exc 2-7/8)

A single phase transformer has the following data

75-kVA, 480/120-v,

Hysteresis loss 215 w & Eddy current loss 115 w.

Magnetizing current is 2.5% rated current. Transformer is operating in step-up mode.


Determine
(i) Exciting current
(ii) No-Load power factor
(iii) Reactive power input at no-Load
Ans: 15.87 A; 0.173; 1875 W

Facebook page : EEE Career Academy | Facebook


9
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

4.

Ans: 0.572 A, 0.182 A; 0.476 A, 0.15 A

5.

Ans: 5.93 A, 73.3 degree

6.

7.

Ans: 275 A, 152.42 KW


Facebook page : EEE Career Academy | Facebook
10
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

8.

Ans: 0.4472 (lagging), 5.59

9.
(a)

Ans: 4.019228992% (Hubert), 4.02% (Threza)

(b) (Hubert Ex-2.11, P-71)

25-kVA, 7620/480-V distribution transformer is supplying a 10-KVA load at 0.65


power factor lagging. The percent IR drop and the percent IX drop are 1.2 and 1.4,
respectively. Determine the transformer regulation for the specific load.
Ans: 0.7375631592%

(c)

Ans: 3.718314512%

Facebook page : EEE Career Academy | Facebook


11
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

10.
(a)

Ans: 40 kW, 7.814655776%

(b)

Ans: 114.2+800i ; 5.118980208%


(c)

Ans: 3.718314512%

11.

Find
(a) Iron loss
(b) Working component of no-Load current
(c) Magnetizing component of no-Load current

Facebook page : EEE Career Academy | Facebook


12
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

(d) 𝑅0 =? & 𝑋0 =?
Ans: 29.85 W, 0.136363̈ A, 0.4810456929 A; 1620.237521 , 456.9976947 

Solve:

Facebook page : EEE Career Academy | Facebook


13
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

12. (Hubert Ex 2.5)


A 75-KVA, 4800-240 v, 60-Hz, 1-phase Transformer has the following data:

𝑅1 =2.488  𝑋1=4.8384 
𝑅2 =0.006  𝑋2=0.0121 
𝑅0 =44202 
𝑋0=7798.6 

The transformer is delivering ½ rated load at rated voltage at 0.96 p.f. lagging.
Determine

(i) input impedance


(ii) actual input voltage at the H.V.side
(iii) voltage regulation
(iv) Transformer efficiency
(v) Exciting current
(vi) input impedance if the Load is dis-connected
(vii) Exciting current if the Load is dis-connected

Ans: 599.159243720.94988481 , 4861.4870620.717818798 v, 1.280980463%, 97.72577692%,


0.6287365429-79.62579112, 7685.18244279.98222441 ; 0.6325792652-79.264460561 A

Solve: here V2 is taken as as reference V2= 240 v  V2= 2400

Facebook page : EEE Career Academy | Facebook


14
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

′ ′
𝐕𝟏 − 𝐕𝟐  𝐕𝟏 −𝐕𝟐 
%𝐫𝐞𝐠 =  𝟏𝟎𝟎% =  𝟏𝟎𝟎%
𝐕𝟐′  𝐕𝟐 
𝑉2
= 1.280980463% where 𝑉2′ = , 𝑉1′ = 𝐾𝑉1
𝐾

Verification

Approximate solution for regulation


( ignoring the core when 𝒁𝑴 >> 𝒁𝟎𝟏 )

Facebook page : EEE Career Academy | Facebook


15
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

13.

& voltage regulation=?

Ans: 46.00877926(Lagging), 87.39120185%, 18.40841389%


Solve:
Here V2 is taken as as reference V2= 500 v  V2= 5000

Facebook page : EEE Career Academy | Facebook


16
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

Approximate solution for regulation


( ignoring the core when 𝒁𝑴 >> 𝒁𝟎𝟏 )
Same as previous math

Facebook page : EEE Career Academy | Facebook


17
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

14. (Chapman Exc 2-2)

=?
Ans: 8197.5357090.3311607135 v, 2.469196361%, 96.51068961%

Solve:
Method 1: V2 is taken as as reference  V2= 480 v  V2= 4800

Facebook page : EEE Career Academy | Facebook


18
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

𝐕𝟏 − 𝐕𝟐′  𝐕𝟏′ −𝐕𝟐 


%𝐫𝐞𝐠 =  𝟏𝟎𝟎% =  𝟏𝟎𝟎%
𝐕𝟐′  𝐕𝟐 
𝑉2
= 2.469196361% where 𝑉2′ = , 𝑉1′ = 𝐾𝑉1
𝐾

Approximate solution for regulation


( ignoring the core when 𝒁𝑴 >> 𝒁𝟎𝟏 )
Same as previous math

Facebook page : EEE Career Academy | Facebook


19
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

15.

Find Primary power factor, efficiency, voltage regulation, secondary output terminal voltage=?

Ans: Cos 33.67421931, 78.90752365%, 3.002916282%, 223.2946486-1.079275579


(Exactly same as B.L. Threza)
Solve:
Method1: Here V1 is taken as as reference  V1= 2300 v  V1= 23000

𝐕𝟏 − 𝐕𝟐′  𝐕𝟏′ −𝐕𝟐 


%𝐫𝐞𝐠 =  𝟏𝟎𝟎% =  𝟏𝟎𝟎%
𝐕𝟐′  𝐕𝟐 
2300−2232.946486 230−223.2946486
%𝑟𝑒𝑔 =  100% =  100% = 3.002916282% Ans
2232.946486 223.2946486

Facebook page : EEE Career Academy | Facebook


20
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

Method2: Here V1 is taken as as reference  V1= 2300 v  V1= 23000

Facebook page : EEE Career Academy | Facebook


21
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

𝐕𝟏 − 𝐕𝟐′  𝐕𝟏′ −𝐕𝟐 


%𝐫𝐞𝐠 =  𝟏𝟎𝟎% =  𝟏𝟎𝟎%
𝐕𝟐′  𝐕𝟐 
𝑉2
where 𝑉2′ = , 𝑉1′ = 𝐾𝑉1
𝐾

2300−2232.946486 230−223.2946486
%𝑟𝑒𝑔 =  100% =  100% = 3.002916282% Ans
2232.946486 223.2946486

Facebook page : EEE Career Academy | Facebook


22
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

Approximate solution for regulation ( ignoring the core when 𝒁𝑴 >> 𝒁𝟎𝟏 )

Facebook page : EEE Career Academy | Facebook


23
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

16. (Chapman Exc 2-6)

If primary applied voltage is 7967 v, Find secondary voltage, voltage regulation=?


When

(a) Load impedance is 3.2 + j1.5 

(b) Load impedance is -j3.5 


Ans: 218.55193357-3.040018123 v, 4.819671551%;
246.4655589-1.164860088 v, -7.06561557%
Solve:
Here exact analysis can’t be done.  approximate analysis (ignoring core)
Result may be slightly different for other 2 model of approximation with the Core

Facebook page : EEE Career Academy | Facebook


24
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

17. (Chapman Exc 2-4)


A single-phase power system is shown in the Figure below. The Power source feeds a
100-kVA, 12/2.4-kV transformer through a feeder impedance of 40 + j150 . The
transformer’s equivalent series impedance referred to low-voltage side is
0.12 + j0.15 . The load on the transformer is 90-kW at 0.85 pf lagging at 2300 V

Find
(i) Voltage at the power source=?
(ii) system voltage regulation=? & Transformer voltage regulation=?
(iii) overall efficiency=? & Transformer efficiency=?

Ans: 14437.149843.72152241 v; 7.606085763%, 0.7339543074%; 97.03967655%, 99.7182235%


Solve:
Here V2 is taken as as reference  V2= 2300 v  V2= 23000

Facebook page : EEE Career Academy | Facebook


25
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

Facebook page : EEE Career Academy | Facebook


26
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

solution for regulation

Facebook page : EEE Career Academy | Facebook


27
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

18.
(a) (Chapman Exc 2.14 )

Ans: 0.9988492093

(b) (Chapman Ex 2.3, P-97 )

Find voltage across the Load=?


Voltage regulation=?

Ans: 237.1812183-0.5940058609 v, 1.188450627%, 4871.819875 W, 28.12746516 W

480−𝑉2′′
𝑉2′′ = 474.3624366-0.5940058609 v, %reg =
𝑉2′′ 

Facebook page : EEE Career Academy | Facebook


28
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

19.
(a) (V.K. Mehta) (Power System-161)

Ans: 35625.22218∠1.658234898 v, Cos 38.52813254, 94.72654%

Hints: Find Zin ; Vs= I1 Zin Here regulation indicate system regulation

(b) (Gupta Ex-3.6) P-58

A 3-phase load of 1-MW at a power factor of 0.8 lagging is supplied by a 30-kV


line of resistance 25 ohm and inductive reactance 12 ohm per phase. The voltage
across the load is 10 kV. A 30/10 kV transformer step downs the voltage at the
receiving end. The equivalent resistance and reactance of the transformer as referred
to 10-kV side are 0.8 ohm and 2.5 ohm respectively. Find sending end voltage and
regulation.
Ans: 31.937696780.62 kV, 6.46%
Hints: 𝑉2=10 kV = voltage across the Load, 𝑉2′ =30 kV= voltage across the Load referred to primary
here regulation indicate system regulation

Facebook page : EEE Career Academy | Facebook


29
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

20.
(a)

Ans: 247.69335881.573155856 KV, 249.72184531.789910608 KV


Hints: ZL= 4.3236.87, Vs =Vin= I1Zin , Vs= V1 + I1ZFeeder

(b)

Ans: 13.3461167793.621171583 kV

21.

Ans: 0.4387209057
4800
6600𝑘 −
Hints: %reg = 4800
√3
100%
√3

Facebook page : EEE Career Academy | Facebook


30
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

22. (Hubert Ex 2.9)

A Single-phase transformer, rated 50-KVA, 7200/600 v is supplying rated KVA


at 600-v at 0.75 p.f. lagging.
The percent resistance and reactance are 1.3 and 3.8, respectively. Determine

(i) secondary voltage when the load is disconnected (No-Load secondary voltage)
(ii) input voltage that must be applied to the primary in order to obtain rated secondary
voltage when carrying rated load at 0.75 p.f. lagging

Ans: 621.0455853 v, 7452.547023 v


𝑉1 − 𝑉2′
Hints: Part(b) %reg =  100%
𝑉2′

23. (Hubert Ex 2.6)

A 37.5-KVA, 2400-600 v, 60-Hz, 1-phase Transformer has the following data:

R01= 2.8 , X01=6

If 2400 v is applied to the primary &

a load impedance of 1020  is connected to the low side. Determine

(i) Zin=?
(ii) voltage across the load=?
Ans: 164.749759521.62797776 , 582.7019127-1.627977761 v

Facebook page : EEE Career Academy | Facebook


31
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

24.

Find
(e) Iron loss
(f) Working component of no-Load current
(g) Magnetizing component of no-Load current
(h) 𝑅0 =? & 𝑋0 =?
Ans: 29.85 W, 0.136363̈ A, 0.4810456929 A; 1620.237521 , 456.9976947 

Solve:

Facebook page : EEE Career Academy | Facebook


32
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

25.

Ans: 500 v, 0.7448594196-63.43494882 A, 166.5556296 W, Core Loss=166.4446665 W;


23.40939982 V, 40 A, 880 W

Solve:

Facebook page : EEE Career Academy | Facebook


33
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

26.

𝑅02 = 0.55  , 𝑋02 = 0.225 

Ans: 500 v, 0.7453559925-63.4353559925 A, 166.666666666 W;


23.76972865 V, 40 A, 880 W

Solve:

27. (Chapman Exc 2-6)

Load impedance is 3.2 + j1.5 

If primary applied voltage is 7967 v, Find secondary voltage ,voltage regulation & =?

Ans: 218.55193357-3.040018123 v, 4.819671551%; 96.57285314%

Solve:

Facebook page : EEE Career Academy | Facebook


34
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

Here exact analysis can’t be done.  approximate analysis (ignoring core)


Result may be slightly different for other 2 model of approximation with the Core

Facebook page : EEE Career Academy | Facebook


35
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

28.

Calculate

Also Find voltage regulation=?


Ans: 257.35380640.8854656465 v, 96.39844691%, 2.941522577%

Hints: Here exact analysis can’t be done.  approximate analysis (ignoring core)
.005  V1 −V′2
𝑅𝑝𝑢 = 𝑅02 × %reg = × 100%
.52 V′2

Solve:
K=2

Facebook page : EEE Career Academy | Facebook


36
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

reference 𝑉2 = 500 𝑣 V2 = 5000 v

when 𝑽𝟏 is used as reference

Facebook page : EEE Career Academy | Facebook


37
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

29.

Ans: %reg = 3.872958742%; 6.855615277 kV


Solve:

Load

Facebook page : EEE Career Academy | Facebook


38
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

𝑉𝐴 (𝐿𝑜𝑎𝑑)
𝑅𝑝𝑢 (𝐿𝑜𝑎𝑑) = 𝑅02 ×
𝑉22

𝑉𝐴 (𝐹. 𝐿. )
𝑅𝑝𝑢 (𝐹. 𝐿. ) = 𝑅02 ×
𝑉22

we can’t find 𝑅𝑝𝑢 without 𝑽𝟐

30.

Ans: 1.185987636 kW

31.

Ans: 6261.795253-2805415387 v, 5.0401082812%

Facebook page : EEE Career Academy | Facebook


39
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

Facebook page : EEE Career Academy | Facebook


40
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

32.

Ans: -1.590216047%, 447.1100152-2.225656524 v

Solve:

Facebook page : EEE Career Academy | Facebook


41
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

33.

Ans: 40405.2894079-3.472116618 v, 92.55776892%

Solve:

Facebook page : EEE Career Academy | Facebook


42
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

34.
(a)

Ans: 160k, 38.44732241k; 38.4 , 191.7936391 

(b)

Calculate

Also Find voltage regulation=?


Ans: 257.35380640.8854656465 v, 96.39844691%, 2.941522577%
Solve:

Facebook page : EEE Career Academy | Facebook


43
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

(c)

Ans: 966.7452354-1.0099525 v, 3.439868473%

Solve:

Facebook page : EEE Career Academy | Facebook


44
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

(d)

Ans: 91.60305344%, 8.496346845%


Solve:

(e)

Ans: 2531.25 , 406.9449615 ; 0.24348673 , 0.360090249 ; 97.56097561%,


97.32360097%; 2.068258235%

Solve:

Facebook page : EEE Career Academy | Facebook


45
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

Facebook page : EEE Career Academy | Facebook


46
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

35. (Chapman Exc 2-10)

Ans: 14215.245241.520574108 v, 3.01463118%


Solve:

Facebook page : EEE Career Academy | Facebook


47
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

36. (Chapman Exc 2-18)

Ans: 3.702556261% ; 97.28906206%


Hints: F.L. Cu Loss = 935.8723958 W
Solve:

Facebook page : EEE Career Academy | Facebook


48
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

37. (DESCO-2019)

Input Power, 𝑃𝑆 =?
With respect to Power dissipated by 18 

Ans: 1.75
Solve:

Facebook page : EEE Career Academy | Facebook


49
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

38. (Dhaka Wasa-2018)

𝑉𝑆 =? 𝐼𝑛𝑝𝑢𝑡 𝑝. 𝑓. =?
For ideal Transformer when
𝑉2 = 120 𝑣, 𝑃𝑆 = 5600 𝑤

Ans: 240.28339752.783020754 v, 0.9988205698 (Lagging)


Solve:

Facebook page : EEE Career Academy | Facebook


50
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

39.
Phasor Diagram

Facebook page : EEE Career Academy | Facebook


51
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

40.
(a)

Ans: 160.3567451 kVA, 98.04349249%; 96.85230024%


(b)

Ans: 4.0733244414 kW, 8.072504576 kW; 98.86614828%


(c)

Ans: 92.57283545%
(d)

Ans: 3.805768773%
(e)

Ans: 97.56101051%
(f)

Ans: 95.62514941%, 96.52509653%

(g) (Hubert Ex 2.13)

100-KVA, 4800/240-v, 60-Hz transformer has core loss, resistance loss and leakage
reactance loss expressed in percent are 0.45, 1.46 and 3.38 respectively. Determine
the efficiency at 70% load with 0.8 power factor lagging.
Ans: 97.96135425%
Facebook page : EEE Career Academy | Facebook
52
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

41. (Hubert Ex 2.8)

The percent resistance and reactance of a 75-kVA, 2400-240 v, 60-Hz transformer are
0.9% and 1.3%, respectively.
Determine high-side fault current if an accidental short-circuit of 0.016 ohm occur at
the secondary when 2300 v is impressed across the primary.
Ans: 920.2650745-23.54536638 A
Solve:

42.

Ans: 3.9204 , 7.780064771 , 8.7 ohm; 378.7878-63.25631605 A


Solve:

Facebook page : EEE Career Academy | Facebook


53
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

43. (Hubert Exc 2-25/12)

A 500-KVA, 7200/240-v, 60-Hz transformer with 2.2% impedance was severely


damaged as a result of a dead short-circuit across the secondary terminals. Determine
(i) Short-circuit current
(ii) Required percent impedance of a replacement transformer that will limit the Low-
side short-circuit current to 60,000 A

Hints: Isc/ I2FL= 100 / %Z


Ans: 94696.9697 A; 3.472̇%
Solve:

44. (Hubert Exc 2-9/5)

7200/240-v, 60-Hz transformer is connected for step-up operation and 14446  load
is connected to the secondary. Assume the transformer is ideal and the input voltage is
220v at 60-Hz, Determine
(i) Secondary voltage
(ii) Secondary current
(iii) Primary current
(iv) Zin Ans: 6600 v; 45.83̇ -46 A; 1375 A; 0.1646 

Solve:

Facebook page : EEE Career Academy | Facebook


54
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

45. (Gupta Ex-3.3) P-55 (Stevenson Junior Ex-2.12) P-75

A 3-pahse 3-winding Y-Y-∆ transformer is rated as under

Primary 132 kV 30 MVA

Secondary 11 kV 20 MVA

Tertiary 6.6 kV 10 MVA

The result of short circuit tests are under:

Secondary short circuited, tertiary open circuited, primary excited


X = 7% on 132-kV, 30-MVA base

Secondary open circuited, tertiary short circuited, primary excited


X = 9% on 132-kV, 30-MVA base

Tertiary short circuited, primary open circuited, secondary excited


X = 4% on 11-kV, 20-MVA base

Find 𝑋1 , 𝑋2 , 𝑋3= ??

Ans: 0.05, 0.02, 0.04 pu

Solve:

Facebook page : EEE Career Academy | Facebook


55
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

46.

Facebook page : EEE Career Academy | Facebook


56
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

47.

Ans: 97.62789465%

48.

Ans: 89.5592741%

49.

Ans: 95.31142359%

50.

Ans: 97.97886955%

Facebook page : EEE Career Academy | Facebook


57
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

51.

Ans: 63.07808485; 62.1031511 kVA

52.

Ans: 471.1257364 ; 281.1655279 kVA

53.

Ans: 609.0319214, 392.8137862 kVA

54.

Ans: 1.5460295155 times normal current of 200 kVA unit

Facebook page : EEE Career Academy | Facebook


58
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

55.

Ans: 25.09486359-70.92166306 A

Ans: 315.6565̈ A

Facebook page : EEE Career Academy | Facebook


59
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

56.

Ans: 80%

57. (Ex-32.89)

Determine the core area, number of turns and position of tapping point for a 500-kVA,
50-Hz, single-phase, 6600/5000-V auto transformer, assuming the following
approximate values: emf per turn 8 V. Maximum flus density q.3 Wb/𝑚2

Ans: 277 cm2,

Facebook page : EEE Career Academy | Facebook


60
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

58.
(a)

A 2-winding transformer is connected according to following figure

If this transformer is re-connected as a auto-transformer in additive polarity. Find rating


of both Transformer=? Also find 𝐼𝑐 =?
Ans: 48 VA, 1008 VA, 0.2 A

(b) A 2-winding transformer rated 48-VA, 240/12-v. If this transformer is re-


connected as a auto-transformer in additive polarity.
Find rating of Transformer=? Also find 𝐼𝑐 =?
Ans: 1008 VA, 0.2 A
(c)

A 2-winding transformer rated 60-VA, 120/10-v. If this transformer is re-connected


as a auto-transformer in additive polarity.
Find rating of Transformer=? Also find 𝐼𝑐 =?
Ans: 780 VA, 0.5 A
(d) (Ex-32.90)

A 20-KVA, 2400/240-V, two-winding transformer is connected as an auto


transformer with additive polarity.
Calculate
(i) KVA rating of auto transformer
(ii) 𝐼𝑐
(iii) overload of primary winding when used as auto transformer
𝐼 (𝑎𝑢𝑡𝑜)−𝐼1 (2−𝑤𝑖𝑛𝑑𝑖𝑛𝑔)
Ans: 220 kVA, 8.33̇ A, 1 𝐼1 (2−𝑤𝑖𝑛𝑑𝑖𝑛𝑔)

Facebook page : EEE Career Academy | Facebook


61
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

59. (Ex-32.90)

A 20-KVA, 2400/240-V, two-winding transformer is connected as an auto transformer


with subtractive polarity.
Calculate
(i) KVA rating of auto transformer
(ii) 𝐼𝑐
(iii) overload of primary winding when used as auto transformer
𝐼 (𝑎𝑢𝑡𝑜)−𝐼1 (2−𝑤𝑖𝑛𝑑𝑖𝑛𝑔)
Ans: kVA, 8.33̇ A, 1 = 900%
𝐼1 (2−𝑤𝑖𝑛𝑑𝑖𝑛𝑔)

60.

Ans: 360-kVA; 99.31034483%

61.

Ans: 21 KVA, 96%

Facebook page : EEE Career Academy | Facebook


62
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

62.

Ans: 3.985 w
63.

Ans: 1500 w, 1500 w


Hints: Inductively transferred power = Power handled by the common winding = Re 𝑉𝑐 𝐼𝑐∗ 
Conductively transferred power = Total Power - Inductively transferred power

64.

Ans: 550 kVA; 50 kW, 500 kW

Facebook page : EEE Career Academy | Facebook


63
Iftikhar Reza (iftikhar.reza08@gmail.com)
Contact : 01715 591 542

65. (Hubert Ex 3.1)

A 400 turn auto-transformer operating in step-down mode with 25% tap,


Supplies a 4.8-KVA, 0.85 p.f. lagging load. The Input to the transformer is 2400-v, 60-
Hz.
Determine
(i) Transformed current (𝐼𝑐 )
(ii) Conductively transformed power
(iii) Inductively transformed power
Ans: 6-31.78833062 A; 1020 W; 3060 W