LUX READING TEST QCDD FORM

Pin No. 00040017 Date 05-11-2023


Location QATAR UNIVERSITY Application No.
Project Name CLINICAL SKILLS TRAINING LABORATORY
Owner QATAR UNIVERSITY

QCD Approved Drawing Ref. No. N/2022/0008781


Date 28-05-2023 Test Status ✔ Passed
System Information
FIRE DETECTION AND ALARM SYSTEM

Initial Illumination (lux) Reading Illumination Reading (lux) within 90 minutes duration
Area
Corridor Lobby Stair 1 Stair 2 Stair 3 Stair 4 Corridor Lobby Stair 1 Stair 2 Stair 3 Stair 4

Floor Level GF 62.4 41.9 112 117.6 N/A N/A 56.2 38.5 109.3 114.4 N/A N/A

Floor Level 1F 46.4 N/A 129.4 122.6 N/A N/A 46.2 N/A 119.8 118.6 N/A N/A

Floor Level RF N/A N/A 120.0 N/A N/A N/A N/A N/A 109.0 N/A N/A N/A

Other Essential Rooms


Fire Command
Center N/A
Fire Pump room N/A
Generator Room N/A
Test status : 
✔ Passed

Provide additional information if necessary

Instrument Used Calibrated by Calibration Certificate No. Certificate Expiration Date


DIGITAL LIGHTMETER Dime Marine Services CR/DM/QTR/2023/QN-19864.001
CR/DM/QTR/2023/QN-11401.002 24-10-2024

CERTIFICATION
The system as specified above has been installed and tested, in accordance with latest edition of NFPA, QCDD FSS and QCDD
approved drawings

Mohammed Sabah ul Islam


________________________________
22284 / 28935624275 / 31228576
_______________________________________________
Contractor (QCDD Certificate No. / ID No. / Mobile No.)
(Signature over Printed Name with Stamp)

Page 1 of 2
LUX READING TEST QCDD FORM
CERTIFICATION
The undersigned accepted the testing report for the system as specified herein.

________________________________ _______________________________________________
Consultant (UPDA No. / ID No. / Mobile No.)
(Signature over Printed Name with Stamp)

Page 2 of 2