You are on page 1of 50
CATHELCO: C-SHIELD ICCP MARINE IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM INSTALLATION & INSTRUCTION MANUAL CLIENT: SCANEL INTERNATIONAL A/S VESSEL: OLYMPIC PRINCE: CATHELCO REFERENCE: Ca 4932 Jesu By: AW Date: 19-Oct-10 MARINE HOUSE, DUNSTON ROAD, CHESTERFIELD, DERBYS. S41 8NY, UK TEL: +44 (0)1246 457900. FAX: +44 (0) 1246 457901. E-MAIL: technieal@eatheleo.com ‘Section 0 Rev 0 Page 1 of 3 C-SHIELD MANUAL INDEX: 0.0 10 2.0 30 40 5.0 6.0 70 8.0 9.0 List of drawings, Introduction, General Descriptions. Installation of Equipment. Power Supply Operating Instructions. Routine Operating Procedure, Service & Fault Finding C-Shield Commissioning Check Li World Wide Agencies. Diver Change Instructions Section 0 Rev 0 Page 3 0f3 1.0 INTRODUCTION: 1.0.1 PRINCIPLES OF CORROSION AND CATHODIC PROTECTION: e i termed activity or potential. These potentials can be tabulated and form the electrochemical ‘A more practical approach is the determination of the tendency of certain metals to corrode in a particular electrolyte, such as sea water. Thie i termed the Balvanic series of which the following table is an abridged fon Active or Anodic Magnesium Zine Mild Stee! Wrought Iron Cast Iron Ni-Resist 18.8.3 % Molybdenum SS, Type 316 (Active) Lead Tin Manganese Bronze Naval Brass Aluminium Bronze Copper 70 Copper 30 Nickel Nickel (Passive) Monel, 70% Nickel - 30 % Copper 18.8.3 % Molybdenum 8S, Type 316 (Passive) Noble or Cathodic Note Some metals and alloys have two positions in the series, marked Active and Passive; the active position is equivalent to the position if corrosion is occurring and approaches the electro-chemical series position for the material. The passive position relates to a non-corroding situation where the material is, protected by a self forming surface film. For example, type 316 stainless stee! in sea water is more likely to be passive than type 304 and is therefore generally preferred for immersed marine applications. Section 1 Rev 0 Page | of 3 crt will pass through the clay fom tte ti 1, The least active met entree sal onto the least active metal THe X sore ete is tered the cade. The more metal, the anodes into solution and the flow of electrical current increases. This isa aretvon transfer process i.e it rTodes ‘This simple cell may be represented as: Figure 1.1 - Simple Corrosion Cell ‘The Anodic and cathodic areas in a corrosion cell may be due to the electrical Teetaet of two dissimilar metals, termed galvanic corrosion. ‘Anodic. and Cathodic areas may be formed on a single metal surface as micro-cells for instance by rain drops on uncoated steel. Alternatively, they may be close but aes cells found when accelerated corrosion occurs at uncoated Anodic areas Gna generally coated cathodic structure. In addition there are long line type ors that oecur on pipelines that pass through aggressive low resistivity soils ‘These sections form Anodic areas and corrode in preference to cathodic areas in less aggressive higher resistivity soils. Large currents can occur at small Anodic areas and lead to rapid corrosion of marine structures such as ship's internal tanks, external hull plates, sheet steel piling in harbours and tubular structures common in jetties and petrochemical drilling and production platforms. Cathodie Protection is a system of i i ‘ preventing corrosion by forcing all ofa structure to be cathodes by providing external ee aaa Section 1 Rev 0 Page 2 of 3 Snsure a galvanic cell is not created, Typical examples of galvanic cells are: 4) Steel or cast iron Jeter boxes in contact with non ferrous (often copper based) tube plates in condenser water boxes in ships or generating Plant. Rapid corrosion ofthe ferrous water bog Occurs close to the tube Plate, >) Brass or bronze valves fitted to immersed steel buoyancy tanks or Rooding chambers on marine petrochemical structures. Accelerated corrosion of the steel occurs near the valve © The connection oF ‘steel pipes into an otherwise cast iron system. Accelerated corrosion ofthe steel occurs near the cast iron sections, Sacrificial anode cathodic protection achieves corrosion prevention on a Particular structure or component by forming a galvanic cell where an Guthodie. For steel under normal non anaerobic conditions it cay te shown theoretically, and is accepted practically, that a steel/electrolyte potential more negative than -0.85 volts measured against a standard copper/copper sulphate electrode indicates that cathodic protection is achieved. This is eguivalers to 0.80 volts measured against silver / silver chloride electrode and + 0.24 volts against a zinc electrode as indicated in figure 1.3 SACRIFICIAL ANODE CATHODIC PROTECTION: As indicated previously, a metal can be made cathodic by electrically connecting it to a more Anodic metal within the electrolyte. The most i nium, zine and magnesium, commonly used Anodic metals are alloys of aluminium, zi Anodes of these metals corrode preferentially; the corrosion current of the anode achieving cathodic protection of the structure to which they are connected. The anodes deteriorate as an essential part of their function and they are therefore termed sacrificial, Section | Rev 0 Page 3 of 3 2.0 GENERAL DESCRIPTIONS: 211 IMPRESSED CURRENT CATHODIC PROTECTION: A metal also can be made cathodic by clectrcally connecting it to another ietallic component in the same electrolyte through a source of direct seers urrent and directing the current flow to occur off the surface of added menllic component (anode), into the electrolyte and onto the metal (cathode) This cay easily be visualised by reference to the simple cell and assuming yet another electrode with a power source is introduced and that the current flew om thas electrode is sufficient to overcome the natural corrosion current, Because an external current source is employ i ion i e ed, this type of protect termed UMPRESSED CURRENT CATHODIC PROTECTION, erent Figure 1.2. - Cathodic Protection Applied to a Simple Corrosion Cell A source of direct current is required, this is generally obtained from mains power units that contain a transformer and rectifier, The magnitude of this current may be automatically controlled in response to a continuous monitor of the cathode / electrolyte potential or may be manually controlled after intermittent measurement, The impressed current anode material is ideally non-consumed by the passage of current from it into the electrolyte, in practice the materials used are a ‘compromise between this ideal and the cost and physical properties of available materials. Impressed current anodes are made from graphite, silicon iron, lead alloys some with platinum bi-clectrodes, platinised titanium or more exotic ‘combinations such as platinum clad niobium. The selection of the correct anode material is critical in the formulation of an effective and economic cathodic protection scheme, Section 2 Rev 0 Page | of 6 sacrificial’ anodes feasible, sophisticated j Figure 1.3 - Comparison of Reference Electrodes & Interpretation 2.2.0 MARINE IMPRESSED CURRENT SYSTEM: The C-Shield Marine Impressed Current System comprises the following components, as illustrated in figure 1.4. 2.2.1 Impressed Current Anodes The function of the anode is to conduct the d.c. protective current into the sea water. C-Shield anodes have been designed to perform this function whilst maintaining a low electrical resistance contact with the sea water. Standard surface mounted anodes are available with from 50 to 300 Ampere ratings. For forward mounted systems and for special applications 50 and 75 Ampere recessed anodes are available, Materials now used by C-Shield for Anodes have now gone beyond lead alloy with specialist coated titanium based Anodes now available. All C-Shield anode designs utilise a tough, chlorine resistant, but slightly flexible plastic carrer. Section 2 Rev 0 Page 2 of 6 222 The use of a 24 volt system reduces the number and length of the anodes from that required with @ 12 volt system. The increased anode/sea water resistance ne potential of the hull steel to the sea water is unaffected by this increase in driving voltage, as the resistive effects are local to the anode and the hliace Potential is @ function of the current flow, the sea water and the coating condition, not the driving voltage. ‘The electrical connections to the active surface are made at the back of the Anode and are fully encapsulated and protected by the hull penetration, Recessed anodes of essentially similar construction are provided for bons section applications. All Tull penetrations are provided with substantial doubler plates and cofferdams. The penetrations themselves are made watertight with heavy duty packing glands, the cofferdams are fully sealed and provided with watertight cable glands, all conforming to the requirements of Classification Societies. Impressed Current Reference Electrodes, The high purity, high stability, zinc reference electrodes are designed to give a stable reference against which the hull/sea Potentials can be measured and a small current flow that is used in the closed loop circuit to maintain the pre-set levels of protection. The construction and the quantity of zinc employed within the electrodes are such that a minimum life of fifteen years is available without maintenance or replacement, The minimum number of reference electrodes per power supply is one although normally two will be fitted. Ideally, these should be located a minimum of 7.5 metres distant from the anodes. In the case of a stern only installation with the anodes more than 150 metres from the bows, one reference electrode may be located in the bows. A novel feature of the C-Shield closed circuit is that additional reference cells may be placed at areas that may be susceptible to over-protection such as adjacent to the anode dielectric shields. These additional reference cells provide a permanent check, thus preventing any coating damage due to over-protection if conditions of operation change from those anticipated. This feature is offered as an optional extra to the standard schemes. Al hull penetrations are provided with substantial cofferdams. The penetrations themselves are made watertight with heavy duty packing glands. The cofferdams are fully sealed and provided with watertight cable glands all conforming to the requirements of the Classification Societies. Section 2 Rev 0 Page 3 of 6 Power Supply Unit: The C - Shield impressed current Cathodic protection power supply unit is a thyristor system housed in a range of different sized cabinets. ‘The specific Power supply unit supplied is illustrated on the drawing included with this snanual. The system comprises of a control PCB, a Thyristor PCB and. Thyristor unit (consisting of a transformer, a choke and a thyristor bridge) ranging in size from 100 Amperes upto 800 Amperes. The supply requirements are 415 Vac +/-10%, three phase, 50/60 He. The control PCB is a micro-processor based system having a 2 line 16 character backlit LCD display which is located in the top centre of the cabinet door. The display is used to monitor and allow control of the system, Below the LCD are four push buttons, which are the controls for changing the system parameters. To the right of the LCD is a power on indicator, which also acts as an alarm indicator. On the reverse side arc a Totary switch and a potentiometer. The switch toggles between manual override and normal operation. This allows the operator, in the event of a fault, to disable the micro-processor control system, and to control the ‘output current with the potentiometer. DISPLAY: This allows the operator to control and monitor the running and set parameters of the system. It comprises of a 2 line 16 character backlit LCD display, 4 push button switches and an Alarm LED. This is mounted on the door of the cabinet. MAIN CONTROL PCB This board controls the operation of the system. It provides control signals i a ic the output current and to the thyristor driver PCB, which allow control over the outpy voltage of the system. This is mounted on the back of the cabinet door. THYRISTOR PCB This board monitors and conditions the signals supplied to the thyristor unit, Section 2 Rev 0 Page 5 of 6 2.2.4 Bonding To enable the rudder to receive protection it is Provided with a dedicated electrical bond in the form of a flexible cable from the top of the rudder stock to the main ship structure. In the same way any stabilisers are bonded to allow protective current to these surfaces, Section 2 Rev 0 Page 6 of 6 30 3.0.01 3.0.02 3.0.03 3.0.04 INSTALLATION OF EQUIPMENT: Description: It is very important that the installation instructions biggest cause of future problems found with the ru Section 3 Rev 0 Page | of | 35 POWER SUPPLY UNIT: 3.5.1 The units are designed for bulkhead and plinth mounting, typically using the mounting holes provided. 3.5.2 To ensure adequate ventilation it is recommended that an air gap be maintained all around the equipment for all units, 3.5.3 Provide and install appropriate input power supply cables, terminating them at the terminals provided. Check that the supply source conforms to the voltage, phase and frequency specification given on the rating plate of the equipment. 3.5.4 Provide and terminate single core cables with a voltage rating in excess of 24V d.c, from the anode junction box or cable splice to the appropriately labelled connection studs on the terminal board. Equivalent area multi-core cables may be used with all cores connected. The cables should be sized according to the following table to ensure that the maximum voltage drop in each cable is equal and does not exceed 3 volts. TABLE OF CABLE LENGTHS FOR DIFFERENT ANODE SIZE TO MAINTAIN MINIMUM 3-VOLT DROP S50A | 75 | 100A | 150A | 175A | 200A | 300A | CONDUCTOR SIZE SINGLE CORE CABLE 45M 16MM* 70M | 47M 25MM 100M | 67M | SOM 35MM? 125M | 83M | 62M | 41M 50MM? 180M | 120M | 90M | 60M | SIM | 45M 70MM? 250M | 167M | 125M | 83M | 71M | 62M | 41M 95MM? 315M | 210M | 158M | 105M | 90M | 79M | 53M 120MM? Section 3.5 Rev 0 Page | of 2 3.5.6 3.8.7 3.5.8 3.5.9 and terminate single core screened cables with a area of minimum 1.0mm from the reference electrode Junction boxes to the Appropriately labelled terminals on the distribution board within the equipment, The metallic braid Screens of these cables should be continuous and be connected to the ‘Ground’ terminal only ine ferminal plate within the power unit De ‘not connect the screen at the junction box end. Provide sectional The reference electrode connec internally inthe Power Supply Unit. ion block is earthed Provide and install « connection to the ship's earthing Coe riom the cubicle earth stud, typically 1 X 16mm Core Cable, PLEASE ENSURE THAT WHEN WELDING WORK IS BEING CARRIED OUT ON THE VESSEL THAT THE PANEL _IS_ SWITCHED OFF ANDTHE SYSTEM \GATIVE CABLE I DISCONNECTED, Section 3.5 Rev O Page 2 of 2 40 POWER SUPPLY UNIT OPERATING INSTRUCTIONS: 4.0.1 The system is controlled by the four push buttons on the front panel, with the information displayed on the 2 line 16 character display above them. The four buttons are marked from left to right CTRL, ENT, ft, U. At power up, achieved by operating the MCB switch mounted on the side or front of the cabinet, the system displays " CATHELCO C - SHIELD X X X A SYSTEM" for approximately 3 seconds and then displays " CATHELCO C-- SHIELD ZINC ELECTRODE" or " CATHELCO C - SHIELD SILVER ELECTRODE” for approximately 2 seconds. The system then reverts to the last operational mode prior to power down, 4.0.2 OPERATING MODE SELECTION There are 4 Operating modes :~ 1) STAND-BY MODE, 2) MANUAL MODE, 3) AUTOMATIC MODE 4) CONFIGURATION MODE Section 4 Rev 0 Page 1 of 11 In addition there is 1 functional modet :. ACCESS CODE NOTES: 4.0.3 Pressing the CTRL button to enter the SELECT MODE menu does not exit the mode until a new mode has been selected, Configuration mode is only accessible when a valid pass number has been entered. See PASS NUMBER mode MODE DESCRIPTIONS : STANDBY MODE: In this mode all output current from the equipment is shut down to zero. The display indicates the output voltage and automatically steps through indicating electrode values and alarms (if any) thus:- STAND-BY V? ELI 22??mV nv stepping to:~ STAND-BY V?272V EL2 222?mV stepping to:- STAND-BY V?222V EL3 277?mV stepping to:- Section 4 Rev 0 Page 2 of 11 4.0.4 STAND-BY v2?77y EL42222mV stepping to:- STAND-BY V??72V ALARMS (see 4.0.6) stepping back to the start Where 222? is the measured value. Note that in the case of the Anode voltage the display will be the back emf of the anode system MANUAL MODE In this mode the output current from the equipment is set and maintained at a constant level. The display indicates the set value of current as a percentage of the total system capacity and automatically steps through indicating electrode values, anode voltage and system current in Amperes and alarms (if any). Thus :- MANUAL 168% ELI 227?mv stepping to:- MANUAL 1 £££% EL2 2272_mV stepping to:- MANUAL I £££% EL3 7772mV stepping to:- MANUAL I£££% EL4 2222mV stepping to:- Section 4 Rev 0 Page 3 of 11 4.0.5 MANUAL rese% Vv stepping to:- MANUAL Teee% 1227 stepping to:- MANUAL I£28% “ALARMS” (see 4.0.6) stepping back to the start, AUTOMATIC MODE: In this mode the output current from the equipment is varied to maintain a constant electrode potential. The display indicates the value of current as a percentage of the total system capacity and automatically steps through indicating electrode values, anode voltage, system current in Amperes and alarms (if any). ‘Thus:- AUTOMATIC ££££% ELI mV stepping to:- AUTOMATIC ££8£% EL2 stepping to:~ Section 4 Rev 0 Page 4 of 11 4.0.6 AUTOMATIC sese, EL3 2272mVy stepping to:- AUTOMATIC seeey EL4 2222my stepping to:- AUTOMATIC se¢¢% Vv 220V stepping to:- AUTOMATIC £¢¢2% 122724 stepping AUTOMATIC ss¢8% “ALARMS” (see 4.0.6) stepping back to the start. Where 22? is the measured value and the £££ is the set value ALARM STATUS: This mode is embedded in the above 3 operational modes and displays the status of any alarm, thus:~ SYSTEM FAILURE MODULE FAILURE ELECTRODE FAILURE UNDER-PRO FAIL OVER-PRO FAIL Section 4 Rev 0 Page 5 of 11 4.0.7 ACCESS CODE pais mode a valid pass number needs 16 f° entered, Initially the display shows the following ACCESS CODE 0000 Correct numbers have been entered, pressing the ENT button will allow Access to the service functions. If the number entered was incorrect then the message ACCESS. CODE INVALD will be displayed, Section 4 Rev 0 Page 6 of 11 41 CHANGING CONTROLLER SET POINTS: ALL ‘hich will allow access to the setting of t 1 ti the sys Parameters. The display will read :- oe CONFIGURATION ZLLLLLLLIILIL where 2222222277722 is one ofthe following:- SYSTEM SIZE ELECTRODE TYPE ELECTRODE NUMBER ELECTRODE SET mv OVER PROTECT UNDER PROTECT CURRENT LIMIT QUIT CONFIG ‘The 10 buttons allow scrolling through the menu items, and pressing the ENT button will enter the displayed configuration mode, as follow:- SYSTEM SIZE This parameter will allow the user to define the size in steps of 50Amps. The display will be as follows, during which time using the 1!) buttons will vary the setting. SYSTEM SIZE wx A where xxx is the set value in the range SOA to 800A. To store the set value, the ENT button is pressed. Pressing the CTRL button will return to the configuration ‘menu. Section 4 Rev 0 Page 7 of 11 413 4d ELECTRODE TYPE one "The dty wa © ne a tin ‘sing the TU buttons will vary the setting, ets ELECTRODE Typp ZINC ELECTRODE or ELECTRODE Type SILVER ELECTRODE To store the set type, the ENT button is pressed. Pressing the CTRL bution will return to the configuration menu, ELECTRODE NUMBER This parameter is used to define the number of electrodes. The display will be ad follows, during which time using the 1M. buttons will vary the setting ELECTRODE NUMBER a where x is the set value in the range of 1 to 4. To store the set value, the ENT button is pressed. Pressing the CTRL button will return to the configuration menu. Section 4 Rev 0 Page 8 of 11 41s 4.16 417 ELECTRODE SET mv This parameter will allow the user to define the set point about which the AUTOMATIC MODE will maintain a Constant potential at the electrodes. The display will be as follows, during which time using the MU buttons will vary the setting ELECTRODE SET my xxx mV Where xx is the set potential range of -100 to +400 mV in the case of Zine Electrode and -1,170 to 670 mV in the Case of Silver Electrode. To store the set value, the ENT button is pressed, Pressing the CTRL bution will return to the configuration menu, OVER PROTECT This parameter will allow the user to define the set point at Which the OVER PROTECTION alarm trigger. The display will be as follows, during which time using the fil buttons will vary the setting, OVER PROTECT, xxx mV Where xox is the set value in the range OFF, -995 to 0 mV in the case of Zine Electrode and OFF, -2,065 to -1,070 in the case of Silver Electrode. To store the set value, the ENT button is pressed, Pressing the CTRL button will return to the configuration menu. UNDER PROTECT This parameter will allow the user to define the set point at which the UNDER PROTECTION alarm triggers. The display will be as follows, during which time using the ft buttons will vary the setting. Section 4 Rev 0 Page 9 of 11 418 419 UNDER PROTECT, xxx mV ‘Where xxx is the set value in the range OFF, 0 to 995 mV in the case of Zinc Electrode and OFF, -75 to -1070 in the case of Silver Electrode. To store the set value, the ENT button is pressed. peel menu. the CTRL button will return to the configuration SYSTEM CURRENT This parameter will allow the user to define the current limit that will restrict the maximum output current in either MANUAL or AUTOMATIC modes. The display will be as follow. during which time using the f1U. buttons will vary the setting. SYSTEM CURRENT, xxx % Where xxx js the set value in the range 0 to 100%. To store the set value, the ENT button is pressed, Pressing the CTRL button will return to the configuration menu, QUIT CONFIG This mode will allow the user to exit from the configuration menu. The display will read :- QUIT CONFIG, ENT TO CONFIRM Pressing the ENT button will then exit from the configuration mode, resetting the whole system, If the CTRL button is pressed, then it will cancel the quit request and return to the configuration menu, Section 4 Rev 0 Page 10 of 11 42 SELF CHECKING: 42.1 422 Every § hours & upon entry to manual & automatic modes, timed from the last power up, the system automatically enters @ self test mode, This mode checks the correct finetion of anodes and electrodes and lasts approximately 10 seconds. During this time the display reads:- SELFTEST PLEASEWAIT Zhe Power output is shut down to zero and the potential From each of the system electrodes is measured. Output second period. At the start (0A) and at every 1 second interval the potential from each of the system electrodes is Measured. During this test the output voltage required to deliver the current is also monitored. If the output voltage at 30% current output exceeds 20V, then the system is deemed to be operating in non-standard sea water and the results of the test are ignored, with the test repeated after a further 8 hour period. Any electrode that retums a Potential of less than 100mV at zero current output and does alter its potential by at least 30mV when 50 % output is achieved is deemed to have failed. Signals from electrodes that have not passed the test are Suspended from the control function for the next 8 hour period and an alarm generated to indicate an electrode fault. The test is repeated automatically on all electrodes (including those that have previously been suspended) after an 8 hour interval, ERROR CHECKING is provided wi f built in self The equipment is provided with a number 0 checking funetions. These functions ensure the conn running of the equipment, Section 4 Rev 0 Page 11 of 11 The Cathelco Marine impressed Current System is completely automatic with litle maintenance required ang Will normally require no adjustments during routine operation of the vessel However, careful attention on a roming basis should be given to the following Points, by the ships staff to ensure thee the System is kept operating at maximum efficiency at all times, 5.0.1 EVERY Day: Check that the LCD of the Power Supply unit display is illuminated, and that the ON/AL, ‘ARM LED is lit. If either of these are incorrect then refer to the faut finding section. the C-Shield log sheets provided. Refer te figure 5.1 for an example of how to complete the log sheet, NOTES; |. Ifthe O/P Current is set to display % then ress the 'ENT" button to toggle to Amperes, 2. Pressing either the up or down buttons will toggle the display to read cither electrodes | & 2 of electrodes 3 & 4, 5.0.2 EVERY WEEK: pri for cleanliness, for wear Once weekly the slipring should be checked 2 on the brushes and "0 coafien that the brushes both move Seely in their holders and are held firmly onto the sliprng by the brush older spring. Check the rudder stock bonding cable for any fraying of the conductor at the connection points. 5.0.3 EVERY MONTH: hich the copies has space for a complete month after which the should ‘be eum to Cathelco, Chesterfield for scrutiny and comment. Section 5 Revo Page | of 3 5.0.4 5.0.5 5.0.6 5.0.7 EVERY 3 MONTHS: Fvety 3 months switch off the equi ent i povver em? 2" signs of toose wires or other ian defects. The depends Ply unit is, under normal operation cooled, and depends on free circulation of cooling air through the vents ts ventana working temperature of componene’ Check that the Creation grilles in the sides and top are nee obstructed in anyway, Clean any dust and dirt from the Unit paying particular attention ty Replace all covers provide power and operate the mains switch to t (On position and shut the front door sae 30 DAYS PRIOR To. DRY-DOCKING: ne month before the dry docking ensure that daily log sheets have been maintained and forwarded to: Catheln for assessment with information that dry docking is expected. ‘This Crk ensure that any the spate putes can be despatched in good time. Continue ss log System, FRESH WATER OPERATION; At times when the vessel enters a river estuary where the water may be ftesh or brackish the effect will be to limit the spread of cane ftom the anodes because of the much higher electrical resistivity of Water. Normally this will cause the automatic control to increase the transformer rectifier Output voltage to the maximum but this will be accompanied by a very low level curent and the reference electrode Potentials may indicate under protection. However, this has been taken care of by our computer and is explained in a separate paragraph in 6.1 The system will return the hull to the optimum protective level as soon as the vessel returns to the sea water, PREVENTATIVE MAINTENANCE, It is recommended practice that routine service by Catheleo should be carried out as recommended by the classification body for the vessel which in some instances is 2 yearly. Section 5 RevO Page 2 of 3 6.0 61 SERVICE AND FAULT FINDING: 6.0.1 6.0.2 6.0.3 6.0.4 6.0.7 6.0.8 RECOGNITION OF 4 PROBLEM: The a. ; a 2 re 1 Tabu Voltage is the driving potential that Produces the protective gaze ng andar Cathelo Shield Marine Impressed Current Ssere s ding #8e Output OF 24VDC but this is i regulated sccording to the current requirement and with fey ae vessel at low current output the DC Voltage will normally be around) 13 {est equipment is used. To check insulation of ‘any cables outside the Power Supply Unit disconnect them at both ends. Ifthe LCD display is not illuminated then first check the mains supply to the cabinet and that the system is switched on, If ne fault can be found then 1port conditions to Cathelco (Chesterfield), If the Power Supply Unit On/Alarm LED is not lit, then note any of the alarm conditions that are found to be displayed and contact Cathelos (Chesterfield) giving full details of the alarm, VESSEL IN FRESH WATER, ICCP systems have experienced problems in the past when the vessel has to enter a harbour or estuary where the water is either fresh or brackish. The C-Shield computer controler has been programmed to identify. this situation by analysing the voltage reading, the amperage reading and the reference electrode inputs. The ICCP system remains in automatic mode and endeavours to provide the maximum available protection level around the hull in this water condition. In fresh water conditions it is normal for the output voltage from the system to increase and for current outputs to decrease. This is caused by the increase in resistivity of the sea water solution. When the vessel returns to normal sea water the output voltage should begin to decrease and current outputs should begin to increase. Section 6 Rev 0 Page 1 of | 7.0 C-SHIELD COMMISSIONING CHECK LIST 7.0.1 Upon completion of the system installation, after allowing a minimum of 48 hours for the di-electric shield areas to harden, commissioning may now be 7-02 Follow the attached check list entering readings as requested, 7.03 Itis recommended that completed check lists be copied and submitted to Cathelco for analysis. Keep the original copy with the ships manus, Section 7Rev0 Page C- Shield Commissioning Cheek List Vessel Shipyard : Newbuilding No. : System Size Owner : 1. Check shipyard cable connections to panel fuse terminals. 2. Check shipyard cables to reference electrode inputs. 3. Check ground connection at terminal in panel. 4. Check shipyard mains input cables are connected. 5. Check any auxiliary circuit input cables if applicable. 6. Check panel holding bolts and frame. Make sure panel is rigid. 7. Locate shipyard mains input voltage supply point. 8. Make a physical check of the unit for any possible transit damage. Section 7 Rev Page? of C- Shield Commissioning Check Li it Con Before switching unit "ON", Check mains input voltage. A-B A-C B-C A- Ground B- Ground C- Ground Disconnect Shipyard anode input cables from fuse terminals in panel. Measure anode open circuit potential. ( Anode - ground) For a new installation where the anodes have never had Power applied to them readings should be in the range of 0.400 V - 0, Re-connect anode cables to panel terminals / fuses, Disconnect shipyard reference electrode wires from panel input terminal Measure reference cell potentials, L 2. 3. 4. ‘These reading will vary in accordance with the state of the hull paint coating adjacent to the reference cell location. For a newly painted installation the readings will be in the range of 200 mV - 300 mY. For a hull in bad painted condition the readings will be higher ie. 300 mV +. Re- connect reference electrode cable inputs to terminal block. Measure -v terminal to ground. ohms (Should be zero) Sexton 7 Rev Page 30f7 C- Shield Commissioning Check List Cont'd On completion of all the tests as detailed in the above check list You can switch the system on. Watch display and note unit will indicate the following: CATHELCO CSHIELD * * * A SYSTEM The unit will then automatically go into the standby mode indicating as follows: STANDBY VOLTS 1 ***mv 2 *** mv (To obtain reference cells 3 & 4 if applicable press "up" arrow. Press "up" arrow to return to1 & 2), Manual Mode. Press "CTRL" button once and unit will go into Select mode. Press "Up arrow" to choose Manual Mode. When this appears Press "ENT". The unit will show the following statement. SELF TEST PLEASE WAIT. The unit then does a self analysis of all its circuits and modules checking reference electrodes and all relevant electrical data. On completion of the self test the unit goes into Manual Mode. The following will appear on the display panel: MANUAL 1 % ELI ** mv The bottom half of the display is a continuous read out of Ref 1 &2&3& 4 followed by the voltage followed by the current. At start up the I % should be "zero". The unit is now ready for testing, Seaton 7 Revo Page 4of7 C- Shield Commissioning Check List Cont' Manual Mode Cont' By pressing the "UP arrow" you will be able to increase the I %. This will result in the reference cell readings reducing and the voltage and current increasing. To avoid applying too much current to the hull at this stage we recommendthat this test is carried out toa maximumof "I 25%". Log the data as follows: I = 5% ELI mV EL2 mV EL3 mV EL4 mV Voltage _V Current___A I = 10% I = 15% ELI mV ELI mV EL2 mV EL2 mV EL3, mV EL3 mV EL4 mV EL4__ mv Voltage Vv Voltage. v Current A Current___A I = 20% I = 25% ELI mV EL1___smV EL2. mV EL2____mV EL3 nV EL3__mvV EL4 mV EL4, mV Voltage Vv Voltage___V Current___A Current__A This establishes the correct operation of the manual mode. Reduce I % back to zero by continuously pressing the "down arrow". When the I % is zero press "CNTL" this takes it back to STANDBY then press "ENT" Section 7 Rev Page oT C- Shield Commissioning Check List Cont' Automatic Mod The unit is now ready for automatic operation. Press the "CNTL" button once and the unit will go into the Select mode, Press the "Up arrow" until Automatic Mode appears. Press "ENT", The unit will show the following statement, SELF TEST PLEASE WAIT The following will appear on the display panel: ELI“ my ~ #4 EL2 ***my y *¥ BY pressing the "Up arrow" you can read EL3 & EL 4 if applicable. Record readings immediately, EL1 mv EL27 amv Amps A Volts After 30 minutes record readings again. EL1 mV EL2 mV Amps ___ A Volts v After One (1) Hour record readings. _After Two (2) Hours record readings. ELI mv ee a — Amps Amps ___ + Volts v Volts Sect 7 eyo Page Gof7 After six (6) Hours record readings, After (wenty four (24) Hours record readings, ELI mV EL1 mv EL2 mV EL2 mv Amps ___ A Amps___ A Volts v Volts Soy The system can now be left Permanently in "AUTOMATIC MODE" and the readings should be taken daily. These should be filled in on the C - Shield log sheet which has been provided and then returned to Catheleo head office monthly for analysis, Please review the instruction manual for “Alarm Conditions" Ifthere are any problems relating to these instructions or else the computer control unit does not funetion as it should then please immediately contact Cathelco head office for further instructions. C- Shield Systems Cathelco Limited Marine House Dunston Road Chesterfield S41 8NY U.K. Telephone: (01246) 457900 Fast (01246) 457901 E-mail: technical@cathelco.com Section 7Rev 0 ‘Page 7087 8.0 WORLD WIDE AGENCIES 8.0.1 8.0.2 8.0.3 Cathelco Ltd are world leaders in the supply of corrosion suppression and Control systems to the marine industry. Backed with over 33 years of experience the C-Shield marine impressed current cathodic protection In order to meet customers requirements world-wide, Cathelco have an extensive agency network of Catheleo trained Engineers. These Engineer are available to assist with installation and commissioning as well ws providing on site instruction for operating staff, Please contact Cathelco UK in the first instance for details of ‘your nearest agent world-wide, CATHELCO LTD MARINE HOUSE DUNSTON ROAD CHESTERFIELD DERBYS ‘S41 8NY UK Tel: 00 44 (0)1246 457900 Fax: 0044 (0)1246 457901 E-Mail: technical@cathelco.com Section 8 Rev 0 Page 1 of | ICCP Full System Check Cathelco= Half Cell Plot Connect the cable tail of the Half Cell into the Common Socket of the multimeter and allow the Half Cell to dangle in Telatively still water. This test should not be carried out whilst the vessel is in motion. Plug the red probe into the ‘Positive Socket of the multimeter and hold the probe against a suitable section of the vessel (paint removal to bare metal is required to ensure a good connection). Set the multimeter to the 2000mV DC setting and record the vaules at various points around the hull on the following sheet It should be noted that if the plot is done whilst the vessel is in dock the results received can be affected by other vessels as well as the dock itself Half call plot layout diagram Sectional plots ‘round the vessel Tm Pm PMWM MMPI mv] ate Fed > 2am rm Tem | PPM Ideal Value for protection Halfcell atleast 1m CS bslow sea level : | O+- Half cell vy -—to! ICCP Full System Check Cathelco= Automatic Mode Checks Change the panel to Automatic Mode as described in the operators manual. Depending on the system type the unit may now run a self test before going into Automatic Mode. Does the panel show a fault? If so which one? wo Record the panel readings immediately Voltage = 2(V Vv (Forcanicopant wee Up Arow oad EL BELA wh aplestle) Current OA A Blt = -65 mv EL2 Oe mV Eig = mv El4 = mv Record the panel readings after 30 minutes Voltage = LOY vy Current = Of A Ell = “6 mv El2 = =20 mv E30 = mV El4 = mv Record the panel readings after 1 hour Voltage = U2 v Current 04 A Eu ~16 mv EL2 -25 mv EL3 mv EL4 mv Record the panel readings after 2 hours Voltage = 1, z Vv Current = ¢ A EL AS mV EL2 ~20 mv EL3 mV EL4 mv ICCP Full System Check Cathelco= = Additional Comments Please include any information that may help us with your query. EL-CHETER: FLOKE ZZ Iv MOLTV4STER WE ARE CETlME "OUEK FRO” cUcY Kkiten Stides 1O0-1¢ KV0B, WE ANE Sarclaé Filci~ APPERDEE an Fo Mutes woRrrhe Fe A PCat oRex, ‘ 5 MACS AcE cece wftor wer Powe 4 YE Pow? Ca THe recs REAop RUBLE ele Contact Information Once this form has been completed it should be emailed back to the person who Tequested it, or to technical@cathelco.com with details of why the test was carried out. Ifyou require any spare parts or would like to request a service engineer's visit, please Contact us at sales@cathielco.com or alternatively contact your local agent (see \www.catheloo.com for further information) ICCP Full System Check Cathelco= Half Cell Plot (continued) Take readings at various Points around the vessel and record the readings below Type of half cell Port/Forward mv Starboard/Forward mv Port/Fore-Mid mv Starboard/Fore-Mid mv Port/Midship mv Starboard/Midship mV Port/Mid-Aft mv Starboard/Mid-Aft mv PortlAft mv Starboard/Aft mv Record the panel Teadings when the Half Cell measurements are taken Forward System Aft System Error Message Error Message Voltage Vv Voltage = Vv Current A Current == A ELI = mV El1 = mv El2 = mv El2 = mv EL3 = mV EL30 = mV El4 = mV El4 = mV ICCP Full System Check Catheico= Manual Mode Checks The system should now be turned on. Put the panel fo Manual Mode as described in the operators manual. Depending on the system type the unit may now run a self test and before going into Meriual Mode Does the panel show a fault? If so which one? NO The current output from the system should now be increased in steps (starting at 0) whilst recording the voltage and reference cell Potentials. To avoid applying too much Current to the hull, this test should be carried out up to 25% of the maximur output of the system. Depending on the type of system the steps maybe as a percentage of the maximum output (0%, 8%, 10% ete.) or as defined levels (1, 2, 3 etc), Please note that the values EL1, EL2 etc. represent the reference cells and that these may be labelled differently on different systems, Stepws.o%tec) = 120% Step = 226% Voltage av Vv Voltage = wee Vv Current on A Curent = ? A Et = -/9 mv Et = “M65 ny El2 = 25 mv Bi2 = -166 oy EL3 = mv EL3 = mV EL4 = mv El4 = mv Step = 32-16% Step = Y=/S% Voltage = Og ay Vv Volage = 32 Vv Curent = [24 A Curent = 228 4 Eli = 728" mv El1 = ~f00 ny E2 = -2% mV EL2 “355 my EL3. = mv EL3 mv El4 = mV El4 = mv Step = 20% Step 25% Vottage = 10,fu Vv Voltage "GV oy Current A Current 384 A Eu mv Eu pA mv EL2 mv EL2 620 mv EL3 mv EL3 mv EL4 mv EL4 mv Once complete, reduce 1% back to zero as described in the operator's manual. ICCP Full System Check Cathelco= Voltage Checks Please take care to note the units when entering these readings Tur the unit off and check the following mains A-B WE / input voltages ao unt ony uses single phase supp, pease : Sr gy NH Pec oeeaee B-C 43, 2. A- Ground 2606 B-Ground

You might also like