Professional Documents
Culture Documents
Electric-Motor-Driven Systems
By Fernando J.T.E. Ferreira and Aníbal T. de Almeida
©ISTOCKPHOTO.COM/SIRAANAMWONG
ElEctric-motor systEms convErt nEarly half of the integral optimization of electric-motor-driven systems
worldwide electric energy into the mechanical ener- (EmoDss), including the use of high-efficiency, well-sized
gy ultimately used in the final application or process. components, is the key strategy to effectively maximize
their overall efficiency. however, the largest energy savings
potential in motor-driven systems is associated with the
Digital Object Identifier 10.1109/MIAS.2016.2600685
Date of publication: 31 August 2017 reduction of the power required by the driven equipment
(CDM or Starter)
mission (iEc) 60034-30-1 [7], iEc Feeding Section Motor
60034-30-2 [8], European standard Auxiliaries Starter
CDM
Contactor,
Motor System
and so on
Extended Product
J 2
v T ,ω 30° slope and K 1 = K 2 /2,the power
Pump
decreases 18.6% with a 10% speed
m
h h
F P decrease. therefore, increasing the
M1
α pumping time 10% will lead to the
T ,ω
m
α
r H same amount of pumped water but
to 10.5% energy savings.
the possibility of deviating and
extending the pumping period to
FIGURE 3. The material- and fluid-elevating systems. the reservoirs to match, as much as
FIGURE 8. The input power in a plastic injection machine driven by an IE2-class 37-kW SCIM: (a) without VSD and (b) with VSD [19].
10,000
15,000
20,000
25,000
30,000
35,000
40,000
45,000
50,000
10,000
15,000
20,000
25,000
30,000
35,000
40,000
5,000
5,000
0
0
10:53:40 8:25:27
With VSD
Without VSD
10:53:41 8:25:29
10:53:43 8:25:31
10:53:45 8:25:33
10:53:47 8:25:35
10:53:49 8:25:37
10:53:51 8:25:39
10:53:53 8:25:41
10:53:55 8:25:43
10:53:57 8:25:45
10:53:59 8:25:47
10:54:01 8:25:49
10:54:03 8:25:51
10:54:05 8:25:53
10:54:07 8:25:55
10:54:09 8:25:57
10:54:11 8:25:59
10:54:13 8:26:01
10:54:15 8:26:03
10:54:17 8:26:05
10:54:19 8:26:07
10:54:21 8:26:09
Operating Cycle
10:54:23 8:26:11
10:54:25 8:26:13
10:54:27 8:26:15
10:54:29 8:26:17
10:54:31 8:26:19
10:54:33 8:26:21
Operating Cycle
10:54:35 8:26:23
Time
Time
10:54:37 8:26:25
(b)
(a)
10:54:39 8:26:27
10:54:41 8:26:29
10:54:43 8:26:31
10:54:45 8:26:33
10:54:47 8:26:35
10:54:49 8:26:37
10:54:51 8:26:39
10:54:53 8:26:41
10:54:55 8:26:43
10:54:57 8:26:45
10:54:59 8:26:47
10:55:01 8:26:49
10:55:03 8:26:51
10:55:05 8:26:53
10:55:07 8:26:55
10:55:09 8:26:57
10:55:11 8:26:59
10:55:13 8:27:01
10:55:15 8:27:03
10:55:17 8:27:05
10:55:19 8:27:07
10:55:21 8:27:09
10:55:23 8:27:11
10:55:25 8:27:13
10:55:27 8:27:15
10:55:29 8:27:17
10:55:31 8:27:19
10:55:33 8:27:21
10:55:35 8:27:23
10:55:37 8:27:25
the hydraulic oil and the mechanical
and hydraulic components as well as
100% Output lower acoustic noise. moreover, the
Flow Flow
speed control is extremely important
Input 225 r/min to ensure that an adequate quantity
Power Fan of plastic is being fed into the mold
100% and to maintain even pressures for
consistent flow. in the extruders, the
37 kW DOL
speed control can lead to average
SCIM-IE2
Gear Box
Driveshaft savings of 15% [18].
in grain storage silos, it is also
Disk Coupling Disk Coupling possible to save a significant amount
of energy by controlling the speed of
the dehumidification system blower
Savings Variable Speed Fixed Speed Savings (which blows air into the bottom of
47% 5.5% the tank/silo) as a function of the
(a)
hygrometric state of the air in the
top of the tank. typically, the blow-
29% Time Share: 100% Flow 100% ers are operated at a constant speed,
Output Flow Flow
71% Time Share: 90, 80, 70, 60, 50% Flow regardless of the actual humidity
225–112.5 r/min 225 r/min
level of the stored grains, which is a
Fan
quite inefficient strategy.
Input Power
53% 94.5% Combined Efficient Technology
and Process Control
VSD a good example of the combined
PMSM
Stored Stored
0.6 Kinetic 0.6 0.6 Kinetic
Energy Energy
(Area) Stored (Area)
Kinetic
0.4 0.4 Energy 0.4
(Area)
Rotor and Rotor
Stator and
Joule Losses Stator
0.2 0.2 Rotor and 0.2
(Curve) Joule
Stator
Losses
Joule Losses
(Curve)
(Curve)
0.0 0.0 0.0
0 0.5 1 0 0.5 1 0 0.5 1
Speed (p.u.; ωNas Reference) Speed (p.u.; ωNas Reference) Speed (p.u.; ωNas Reference)
(a) (b) (c)
6.0
Power (p.u.; DOL Starting Losses as Reference)
1.0 1.0
5.0
0.8 0.8
Two
Speed
4.0
0.6 0.6
Stored Stored
Kinetic Kinetic 3.0 Soft
Energy Energy Starter
0.4 (Area) 0.4 (Area)
Start-
2.0 Delta
Rotor and Stator
0.2 Joule Losses 0.2 VSD
(Curve) Rotor and Stator 1.0
Joule Losses
(Curve)
0.0 0.0 0.0
0 0.5 1 0 0.5 1 0 0.5 1
Speed (p.u.; ωNas Reference) Speed (p.u.; ωNas Reference) Speed (p.u.; ωNas Reference)
(d) (e) (f)
FIGURE 10. The approximate variation of the SCIM joule losses (p.u., DOL starting losses as reference) and line current (p.u., nominal current
as reference), as a function of the motor speed (p.u., nominal speed ~ N as reference), during the starting period, for different starting
methods: (a) DOL, (b) star-delta, (c) two-speed constant-torque Dahlander winding, (d) soft starter, (e) VSD, and (f) motor line current.
1.1
1.5
2.2
3
5.5
7.5
9.2
11
15
15
18.5
22
or batteries for further use. these
solutions can be combined. the first Rated Power (kW)
and second solutions are depicted
in figure 13. FIGURE 12. The minimum steady-state time to justify the investment in a high-efficiency SCIM
the first solution is widely used, with higher rotor inertia [29].
and the amount of regenerated
energy is limited by the maximum
power/current that can be handled Common
ac Grid
by the regenerative drive and the ac R ST
dc Bus
Losses
grid in the point of connection. for + –
a given amount of stored energy, the Power Flow
average power to be injected into
dc-Bus
VSI
Regenerative
VSI
dc-Bus
VSI
VSI
M2 Trunk Saw
M2 Trunk Jsaw
M2 Trunk M2
J2
Carriage Loading System
Trunk M2
Carriage Carriage Starting:
v Backward m F m1 Forward v, F Driving Mode
1
Braking Driving Stopping:
M1 M1
J4 J1 J4 J1 Braking Mode
be saved. however, as previously mentioned, the maxi- during the heavily loaded downward movement can be
mum power that can be injected into the ac grid may reused to simultaneously supply the translation motor
force the user to extend the deceleration period (to ^M 1 h through a common dc bus. if possible, it can also
reduce the injected power) and/or install a braking be used to partially supply the motors of another lightly
resistor in the dc bus to dissipate
the part of the energy that cannot
be injected into the ac grid. the
first option leads to an increase in m1 Braking
the carriage returning time. the F
M2
second option lowers the energy J2
Regenerated v
saving potential associated with
Energy
Regenerated
m1
systems can easily be implemented.
F, v mc m4
in descendant escalators, the friction loss share is typi-
v
Braking
Braking
m2 m F, v
F mc c F general, the higher the overall power efficiency of escala-
v tors, the higher the energy savings associated with regener-
m3 mc ation. the drive system speed and/or on/off/standby control
as a function of people upon or approximating the escalator
System with Multiple Elevators
also has a significant impact on its energy consumption.
the same principles apply to hoists and cranes, except
FIGURE 16. A system with multiple elevators (four-quadrant operation). that there is no moving counterweight and energy regen-
eration is only possible when the
handled load is moving downward.
in large cranes (a two-quadrant
operation), some manufacturers are
ac Grid or dc Bus already offering integrated regenera-
tive drives for the downward move-
ments in two different forms: 1)
Regenerated Regenerated regenerative braking for energy stor-
Energy Energy ing in supercapacitors, to be used
Second
Floor in the next driving mode operation,
M2 M3 and 2) regenerative braking for ener-
J2 J3 gy injection directly into the ac grid.
F, v F
Driving First Floor Braking v the first strategy is quite interest-
M1 M4 ing because it saves energy and, at
J1 J4
F
same time, shaves the motor-starting
F, v
Driving Ground Floor Braking v peak power in the very beginning
of the upward movement operation,
System with Multiple Escalators
which can be an issue when mul-
tiple cranes are operating simultane-
FIGURE 17. A system with multiple escalators (one- or two-quadrant operation). ously, as happens in large harbors