Professional Documents
Culture Documents
Load Flow Calculations
Load Flow Calculations
• Evaluate the ability of the system to adequately supply the loads while remaining within
the required voltage and current ranges
• Evaluate the operating characteristics of the power system for a given load and generator
power and voltage conditions
• Design and plan of the power system and check for the expansions
• Provide guidelines for the optimum operation of power system
Q1. Find the real and reactive power supplied by the generator, power dissipated in the
feeder and voltage at the generator.
Take common base as 132kV, 100MVA Load
𝑃 = 𝑆𝑐𝑜𝑠 𝜃
0.07∗100
Per unit impedance of transformer 2 = = 0.14𝑝𝑢
50
𝑃 40
𝑆= = = 50𝑀𝑉𝐴
cos(𝜃) 0.8
Feeder
50
𝑆𝑝𝑢 = = 0.5𝑝𝑢
2
𝑉𝑏 1322 100
𝑍𝑏𝑎𝑠𝑒 = = = 174Ω
𝑉𝐴 100 𝑆𝑝𝑢 = 𝑉𝑝𝑢 ∗ 𝐼𝑝𝑢
8 + 𝑗30 𝐼𝑝𝑢 = 0.5𝑝𝑢
𝑍𝑝𝑢 = = 0.0459 + 𝑗0.172
174 𝑄 = 𝑆𝑠𝑖𝑛 𝜃 = 50 ∗ 0.6 = 30
30
𝑄𝑝𝑢 = = 0.3𝑝𝑢
100
j0.1 j0.12 0.0459 j0.172 j0.14
Generator voltage
𝑆 2 = 𝑃2 + 𝑄 2
𝑆 2 = 0.41152 + 0.43322
S = 0.597pu
S=V*I
0.597
𝑉𝑝𝑢 = = 1.195
0.5
Generator voltage = 1.195*20= 23.9kV
Q2. Find the real and reactive power supplied by the generator, power dissipated in the
feeder.
Load 50MW at
0.85power
factor lagging
0.1Ω/km
30km
Take common base as 220kV, 600MVA Load
𝑃 = 𝑆𝑐𝑜𝑠 𝜃
0.35∗600
Per unit impedance of generator= = 2.1𝑝𝑢
100
𝑃 50
0.05∗600 𝑆= = = 58.82𝑀𝑉𝐴
Per unit impedance of transformer 1= = 0.2𝑝𝑢 cos(𝜃) 0.85
150
2
𝐼𝑝𝑢 = 0.098𝑝𝑢
𝑉𝑏 2202
𝑍𝑏𝑎𝑠𝑒 = = = 80.66Ω 𝑄 = 𝑆𝑠𝑖𝑛 𝜃 = 58.82 ∗ 0.5267 = 30.98
𝑉𝐴 600
30.98
(0.1 ∗ 30) + 𝑗(0.25 ∗ 30) 𝑄𝑝𝑢 = = 0.0516𝑝𝑢
600
𝑍𝑝𝑢 = = 0.037 + 𝑗0.093
80.66
j2.1 j0.2 0.037 j0.093 j0.1
𝑋𝑡𝑜𝑡𝑎𝑙 = 2.1 + 0.2 + 0.093 + 0.1 = 𝑗2.493 Reactive power (per unit) = 𝐼2 𝑋 + 𝑄𝑙𝑜𝑎𝑑
Dissipated power (per unit)= 𝐼2 𝑅 = 0.0982 ∗ 0.037 = 0.00035 = 0.0982 ∗ 2.493 + 0.0516 = 0.075
• The stability of an interconnected power system is its ability to maintain acceptable operating
conditions under normal operation and after being subjected to a disturbance
• Capability to return to the original or new equilibrium state on occurrence of disturbances
Rotor angle stability
• Ability of the interconnected synchronous machines in a power system to remain in synchronism
• Small signal stability
• The ability of the power system to maintain synchronism under small disturbances like small
variations in loads and generation
• Transient stability
• The ability of the power system to maintain synchronism under severe disturbances like loss of large
generation, load or transmission line
Voltage stability
• The ability of the power system to maintain steady acceptable voltages at all the busses in the system
under normal operating conditions and after being subjected to a disturbance
Classification of buses
• Bus is defined as a node where many transmission lines, generators and loads are connected
• Bus is indicated by a vertical line where these components are connected
• Mainly there are three types of buses
• Load bus
• A bus where the active and reactive power are specified
• Most common type in power systems (around 80%)
• Voltage controlled bus/Generator bus
• Always connected with the generator
• Slack bus
• The bus which doesn’t carry any load
AC generators which produce constant frequency, constant voltage output
are called as “synchronous generators”
𝟏𝟐𝟎𝐟
𝐍=
𝐏
P = no. of poles on the rotor
f = frequency
N = rpm speed of the rotor
Method of excitation
▪ To supply DC current to the rotor(field) winding
▪ Control the magnitude of direct current
• Using external DC source
• Using self generated DC
• Using self generated AC plus rectification
Φ=Power factor angle
δ = Load angle/ Rotor angle
P = 𝑉𝑎 𝐼𝑎 cos 𝜃
Q = 𝑉𝑎 𝐼𝑎 sin 𝜃
𝑉𝑎 𝐸𝑎 sin 𝛿
P=
𝑋𝑠
𝑉𝑎 (𝐸𝑎 cos 𝛿 − 𝑉𝑎 )
Q=
𝑋𝑠
Synchronization
▪ When a live generator is connecting to a live bus bar there’s a process called
synchronization.
▪ There are essential conditions for connecting.
▪ The generator and bus bar should have
• Same frequency
• Same line-line voltage
• Same phase sequence
• Same phase instant
Real Power sharing/ Parallel operation of generators
Q. Two generators A and B, with rated power of 500MW and 300MW and governor
droops of 3% and 4% are operating in parallel. The combination delivers a total power of
600MW at 50Hz with generator A taking 65% share. The rated frequency is 50Hz.
Find,
i. The maximum total power that the combination can deliver without overloading any
generator
ii. The frequency of operation after the load power goes down from 600MW to
200MW.
𝑓1 − 𝑓3
= 0.03
50
𝑓1 − 𝑓3 500
50 =
𝑓1 − 50 390
𝑓1 = 51.17Hz
𝑓3 = 49.67Hz
𝑓2 − 𝑓4
= 0.04
For generator A; 50
𝑓2 − 𝑓3
𝑃𝐵 = 300
𝑓2 − 𝑓4
51.4−49.67
𝑃𝐵 = 300 = 259.5MW
51.4−49.4
𝑓4 = 49.40Hz 𝑓5 = 50.827Hz
Real power (P) and Reactive power (Q)
P = 𝑉𝑎 𝐼𝑎 cos 𝜃
Q = 𝑉𝑎 𝐼𝑎 sin 𝜃
𝑉𝑎 𝐸𝑎 sin 𝛿
P=
𝑋𝑠
𝑉𝑎 (𝐸𝑎 cos 𝛿 − 𝑉𝑎 )
Q=
𝑋𝑠
Power/ rotor-angle curve for a synchronous generator