Professional Documents
Culture Documents
WOODINVILLE, WA
MANUAL
2. Relay Output
2
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
TABLE OF CONTENTS
TROUBLESHOOTING............................................................................................................................................ 25
SPECIFICATIONS................................................................................................................................................... 27
3
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
LIST OF FIGURES
FIGURE 1 SLC4000 ASSEMBLY..................................................................................................................19
FIGURE 2 REMOTE INDICATOR PANEL BOARD LAYOUT..................................................................20
FIGURE 3 REMOTE INDICATOR PANEL MOUNTING HOLES..............................................................20
FIGURE 4 FIELD WIRING DIAGRAM ........................................................................................................23
LIST OF TABLES
TABLE 1 SWITCH SETTINGS FOR VARIOUS COMMAND INPUT TYPES ............................................8
TABLE 2 GENERAL PURPOSE SET POINT CONTROLLER - SENSOR INPUT ......................................9
TABLE 3 SWITCH POSITION FOR PROGRESSIVE OR LINEAR..............................................................9
TABLE 4 SWITCH COMBINATIONS FOR MASTER AND EXPANSION UNIT CONFIGURATION.....9
TABLE 5 SWITCH POSITION FOR THE OPERATIONAL AND TEST MODE .........................................9
TABLE 6 SWITCH POSITION FOR ON DELAY ........................................................................................10
TABLE 7 SWITCH POSITION FOR OFF DELAY.......................................................................................10
TABLE 8 SWITCH POSITION FOR DEFINING QUANTITY OF RELAYS TO USE...............................10
TABLE 9 HONEYWELL-SELECTRONIX TERMINAL DESIGNATION CROSS-REFERENCE ............12
TABLE 10 LOAD LIMIT OR SHUTDOWN INPUT WIRING.....................................................................13
TABLE 11 SWITCH POSITION FOR PROGRAMMING THE USER-DEFINED VALUES .....................14
TABLE 12 USER-DEFINED PROPORTIONAL OPTIONS .........................................................................15
TABLE 13 USER-DEFINED ALTERNATE-CHOICE OPTIONS................................................................15
TABLE 14 STATUS LED INDICATIONS AND FLASH RATES................................................................18
TABLE 15 TROUBLESHOOTING ................................................................................................................25
TABLE 16 ELECTRICAL AND PHYSICAL SPECIFICATIONS................................................................27
4
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
GENERAL INFORMATION
Introduction
An LED illuminates in proportion to the
The SELECTRONIX, INC. SUPERSTEP SERIES fractional unit-step load output
4000 controllers are all solid-state, microcontroller-
based, proportional load controllers for use in staged • A ‘Test Up’ and ‘Test Dn’ Pushbutton provide
electric heating, cooling, or other HVAC systems. It for rapid startup and troubleshooting tests. The
provides multi-stage relay contact closures in Operational Test Mode operates the relays for a
proportional response to a slidewire sensor, short time interval before returning to the
potentiometer, voltage, or current inputs. The controller normal control mode, while the Dedicated Test
is also suitable for many other general purpose control Mode keeps the unit in a constant test
applications requiring proportional deadband closed-loop configuration. The Test Mode is selected by an
control. on-board switch.
• Units may be connected together to provide a • A multi-color LED indicates operational status,
maximum of 32 stages. as well as annunciating several error conditions.
• A single board size accommodates from 1 to 8 • All outputs are pilot relay contacts, intended to
relay stages, using on-board switches to control interposing relays or contactors of less
configure the actual desired quantity. Standard than 125 VA burden. The relays are
configurations are SLC4000-4 which has 4 conservatively rated for this application. (They
relays, while SLC4000-8 has 8 relays. carry a UL rating of 8A resistive @ 125/250
VAC). Each output stage has an LED indicator
• The Master Unit is compatible with a number of to show output operation.
different input signal types, including, 0-5VDC,
0-10VDC, 2-10VDC, 4-20 maDC, ohmic • Step timing is adjusted by a combination of on-
slidewire, and a user-defined input range. The board switches and a potentiometer for On-
input signal type is selected with on-board delay timing of up to 8 minutes. A single
switches. switch provides a selection between 2 and 5
second ‘Off delay’.
• Integral Load Limit Input provides for local or
remote control of the maximum quantity of • Many built-in failsafe features including input-
loads to energize, for control of peak demand signal range-checking and detection of loss of
charges. communication with master unit.
• 2200 Ohm Thermistor / Set Point Adjuster • The Master Unit is provided with standoffs
Control Input Configuration provides suitable for mounting to chassis panels using 4 -
proportional control for series-connected #6 machine screws. A NEMA 4X enclosure is
thermistor/Set Point Adjusters. The deadband available as an option.
width is field programmable.
• The Superstep Series 4000 controllers are
• General Purpose Set Point Control Input Recognized under the UL Component's
Configuration provides additional flexibility for Program in accordance with UL873
proportional deadband control interfacing with Temperature Indicating and Regulating
various command input and sensor signals. Equipment (CCN: XAPX2) and are intended
The deadband width is field programmable. for use by Original Equipment Manufacturers
(OEM) who will seek overall UL approval for
• An integral 0-10 VDC vernier output provides a the end-item system. File Number E124742.
signal to control an SCR module or other
proportional control devices. A field-
programmable ratio allows vernier loads
between 1 to 2 times the unit-step load.
5
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
6
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
The SLC4000 has 2 standard configurations, which Sequencing and output proportionality of the added
contain either 4 or 8 relays, however any amount of stages are maintained without any additional
output stages between 1 and 8 may be special-ordered. adjustments or calibration of the additional units.
The Control Unit provides an output compatible with the The Master Unit also provides an integral vernier output
SLC2170-xx Remote Indicator Panel. to control an SCR or other proportional control devices
for accurate 0-100% fractional control of between 1 to 2
The SLC4000 may be configured as a Master Unit, and unit-loads.
connected to other SLC4000s configured as Expansion
Units, by using Cascading Cables. Up to 4 units may be The Master Unit maintains independent communication
cascaded together, to provide up to 32 stages. Dual-port with each Expansion Unit, such that if a single
cascading connectors are provided on the SLC4000, Expansion Unit were to fail, the other Expansion Units
providing an easy method to interconnect additional continue to operate. The Expansion Units continually
units in a daisy-chained fashion. Either connector port verify communication with the Master Unit, so that in
may be used to connect to the next cascaded unit. This the event of a loss or communication, all outputs on the
provides the OEM with the flexibility of purchasing a affected Expansion Unit sequence off.
single unit which can be used individually or in multiples
to accommodate larger systems. These units include the flat-cable header connector to
attach the optional Remote Indicator Panel, enabling
remote viewing of the relay output status..
7
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
UNIT CONFIGURATION
Note 1: SW1-1 ON connects a 62 ohm resistor to circuit common, for use with current loop inputs.
Note 2: SW1-2 ON attenuates the input signal by 25%. Resistor divider of 5.9K and 2.0K.
Note 3: 20% Offset Option for Load Limit Input (Default is No Offset)
Note 4: Vernier Load/Unit Load Ratio 100% to 200% (100% is Default)
Note 5: See ‘Programming The User-Defined Levels or Options’
Note 6: Direct Acting control is when the sensor level is above the set point, results in more stages added
Note 7: The sensor is connected to this input. See Table 2 for applicable settings
8
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
0-10 VDC Off On None TB2(+) TB3(-) Connect Ext 7.87K ohm 1%, 1/4w
resistor in series with input signal
and TB2
4-20ma On Off None TB2(+) TB3(-) Default DirectActing
For ReverseActing use User-
defined option
Thermistor Off Off Ext resistor with Thermistor
DirectActing ohms close to set
Control pt R of thermistor
Thermistor Off Off Thermistor Ext resistor with ohms
ReverseActing close to set pt R of
Control thermistor
100 ohm RTD Off Off 100 ohm, 1%, 100 ohm RTD
DirectActing 1/4W Resistor
Control
100 ohm RTD Off Off 100 ohm RTD 100 ohm, 1%, 1/4W
ReverseActing Resistor
Control
9
For systems requiring additional output stages, simply
Table 6 Switch Position for On Delay
cascade of up to 3 additional SLC4000 units.
Note: The total On Delay time is the total of the minute
delay setting + the On Delay Seconds potentiometer AnyOn Alternate Function – Relay #8
setting.
This relay turns on whenever there is one or more
Signal Type SW2-2 SW2-3 SW2-4 operational relays on, and is available when the
0 Minutes OFF OFF OFF ‘Quantity of Relays To Use’ is 7 or less. See Table
1 Minute Off Off On 8, above for 7 relay setting. This could be used to
2 Minutes Off On Off signal or operate a circulating pump or drive an
3 Minutes Off On On external indicator, for instance.
4 Minutes On Off Off
5 Minutes On Off On AllOff Alternate Function – Relay #7
6 Minutes On On Off This relay turns on whenever there no operational
7 Minutes On On On relays on, and is available when the ‘Quantity of
Relays To Use’ is 6 or less. The AnyOn Alternate
function for relay #8 is also enabled. . See Table
Table 7 Switch Position for Off Delay 8, above for 6 relay setting. This output could be
used to signal a Building Automation System, or to
Description SW2-5 drive any external indicator or alarm.
2 Seconds ON
5 Seconds off System Fault Alternate Function – Relay #6
This relay turns on whenever there is a detected
Table 8 Switch Position for Defining Quantity of system fault, and is available when the ‘Quantity of
Relays To Use Relays To Use’ is 5 or less. See the on-board
Status Led to determine the actual detected fault.
Description SW2-6 SW2-7 SW2-8 The AnyOn and AllOff Alternate functions for
8 Relays or OFF OFF OFF relays #8 and #7, respectively, are also enabled.
All See Table 8, above for 5 relay setting. This output
Available could be used to signal a Building Automation
1 Relay Off Off On System, or to drive any external indicator or alarm.
2 Relays Off On Off
3 Relays Off On On
4 Relays On Off Off
5 Relays On Off On
6 Relays On On Off
7 Relays On On On
Contact Closure
• A contact closure may be used to provide
all-on or all-off operation.
• Connect a 10K external resistor
betweenTB2 and TB3 or connect DPST
contacts with the NC contact between TB2
and TB3 and the NO contact between TB1
and TB2.
11
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
The primary type of interface used with the Superstep • Honeywell Model P7810B, Pressure Controller
Series 4000 is one which can provide a voltage, current, using 4-20ma output.
or an Ohmic Slide-Wire Resistance. This can be
electronic controllers, temperature sensors, pressure • Resistance inputs provided by any
sensors, or a manual potentiometer. potentiometer or slidewire device between 0
ohms to anything between 100 to 5K ohms are
Suitable sensors are manufactured by Honeywell and acceptable.
other environmental control manufacturers.
• Voltage Inputs of 0-5 VDC. 0-10VDC, 2-
Set the Input Configuration switches according to “Table 10VDC
1 - Switch Combinations for Various Command Input
Types”. • Current Input of 4-20 ma
• Honeywell Model T775E, T775F • Dry Contact for All-On or All-Off operation
• Honeywell Model T991A Temperature Sensor • Voltage or Current compatible with the User-
(Use Ohmic configuration) Defined Input Limits
Controllers which provide simulated 135 ohm outputs, which are usually used to control valve and
damper motors are not recommended for use as the 135 ohm input to the Superstep Series 4000
controllers. Use a device which provides a compatible voltage or current output.
12
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
The Load Limiting feature limits the output to a proportional percentage of the full output capability. For instance
if the load limit setting is 50% on a 16 step system, then the maximum stages that will be energized with a
maximum input signal will be 8 steps.
• *1 CW terminal measures 0 ohms between it and the wiper terminal, when the potentiometer knob is turned full
clockwise
• *2 CCW terminal measures 0 ohms between it and the wiper terminal, when the potentiometer knob is turned
full counterclockwise
• See Figure 4 Field Wiring Diagram
• Any signal between 0 and 1.24VDC may be used at TB5, referenced to TB6.
• For use with a 4-20 ma signal, connect a 61.9 Ohm 1% resistor between TB5 and TB6, and program the 20%
offset option.. See ‘20% Offset (4-20ma) Option for Load Limit Input
The Load Limit Input may also be used either separately or simultaneously as a Shutdown Input, or a Low Water
Shutdown.
• Connect an external relay
• Connect the Normally Open contact between TB4 to TB5.
• Connect the Normally Closed contact to the Load Limit signal, which may be an external potentiometer, a
Building Automation system, or Direct Digital Control
• Closing the Normally Open contact will turn all outputs off.
13
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
• Apply control power, and verify the status LED is flashing Red, then Grn, at 1 Hz, indicating the
programming mode.
• Set the Input voltage, current, or other value for the User-Defined Upper Limit
• To Program an Upper Limit Value: Press and hold the Test Up pushbutton for greater than 1 second, until
the status LED turns off, then cycles Grn, Org, and Red. It returns to flashing Red and Grn.
• Set the Input voltage, current, or other value for the User-Defined Lower Limit
• To Program an Lower Limit Value: Press and hold the Test Dn pushbutton for greater than 1 second, until
the status LED turns off, then cycles Grn, Org, and Red. It returns to flashing Red and Grn.
• Turn off control power
• Set the Input Configuration switches to the desired setting.
• Re-connect the normal sensor inputs, as required.
• Test and verify the User-Defined levels or options are as desired
14
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
• If a potentiometer is being used as the Set Point Control, simply switching the CW with the CCW terminals, will
switch the control sense.
• If the sensor is either an RTD or a thermistor, then switching the connections with the fixed resistor, will switch
the control sense.
Valid Input Configurations Proportional Option Default Full CCW Full CW Pgm Using
Std voltage, Std current, or Vernier Load/Unit- 100% 100 % 200% Test Up
ohmic Load Ratio
Thermistor Control, General Deadband Width Most Most Least Test Up
Purpose Set Point Control sensitive sensitive Sensitive
15
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
A load of up to 2 times the unit-step load may be Cable Adapter, RS-485 to Pigtail
controlled by the vernier output. For loads larger than a For use in making discrete connections to the RS-485
unit-step load, the user must program the ratio into the bus, such as adding the RS-232 to RS-485 Converter.
User-Defined Upper Limit, using a potentiometer
method of programming. Remote Indicator Panel Cable SLC2197
The Remote Indicator Panel Cable is a 6' 14-conductor
The inter-step modulation is scaled by this value to flat cable with strain-relieved connectors at each end. It
maintain a unit-step equivalent output until all the steps is used to connect the Remote Indicator Panel to a
are on. When all the relays are turned on, the vernier Master Unit.
output is set to full on. A 6' cable is included with the Remote Indicator Panel
option.
An LED illuminates in proportion to the vernier output.
Resistor Adapter Assemblies
The connections are TB7 (+), also labeled ‘V’ and TB8
(-), also labeled ‘X’. Resistor adapter assemblies with different resistor values
are available for applications that require an externally
mounted resistor. The resistors are supplied with female
Remote Indicator Panel SLC2170-xx quick-connect terminals and an insulated male quick-
connect tab for the field connection. Also included are 2
A Remote Indicator Panel provides LED indications of quick-connect terminal adapters that provide 2 male
output stage status at a remote location. connections for the single male tab, for a choice of field
wiring preferences.
The Panel consists of a printed wiring board and an
acrylic plastic cover suitable for mounting behind a
cutout on the control cabinet. The Panel is available
with up to 8 LED’s to match the quantity of stages
located on the attached Control or Expansion Unit. A
6 foot flat cable is included with the Remote Indicator
Panel.
16
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
Operating Modes
• The Status LED on the Master Unit flashes
Operational - Normal Proportional Output identically to the Normal Proportional Output
Mode mode.
• The Status LED on the Master Unit flashes: For additional information using this option, see
• Green, at a 1 Hz rate to indicate that the system SLC4000Addendum120.pdf available at
is in a balanced or quiescent state. www.selectronix.us.
• Green, at a 4 Hz rate to indicate that the system
is in the timing mode before changing the Operational – General Purpose Set Point
quantity of output stages.
Control Output Mode
Some features that apply when expansion units are used The General Purpose Set Point control configuration
in a system: provides a closed-loop, deadband control, with a field
• If the Expansion unit detects a loss of programmable deadband or sensitivity width. The
communications with the Master Unit, it control accepts a number of different sensor outputs,
sequences its own relays off in a graceful including 0-5 VDC, 4-20 ma, RTD, thermistor, and 0-
shutdown, turns on the flashing red status 1.24 V.
indication, then waits for resumption of Master The Set Point input, connects to TB4, TB5, and TB6,
Unit messages. If communications are restored, may be a potentiometer or 0-1.24 VDC signal.
the Expansion Units will gracefully resume
normal operation. As with the thermistor Input Configuration, the quantity
• Expansion Units detect loss of communications of output relays to activate is determined by sensing the
within approximately 10 seconds. imbalance of the sensor input with that of the set point
adjuster input.
17
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
Operational – Transient Test Mode an additional stage for each press of the applicable
pushbutton. If the pushbutton is held down continuously
The Master Unit may be put in a timed test mode by
for more than 2 seconds, the Master Unit enters an
pressing either the Test Up or Test Dn pushbutton. Each
automatic Test Up mode, where the stages turn on
time either the Test Up or Test Dn pushbutton is pressed,
sequentially, with no further pushbutton presses, until all
a one minute timer is started. For each press of the Test
the stages are on. Likewise if the Test Dn pushbutton is
Up pushbutton, an additional stage is turned on, and for held continuously for more than 2 seconds, the Master
each press of the Test Dn pushbutton, a stage is turned Unit enters an automatic Test Dn mode, where the stages
off, until no stages remain on. When the Master Unit is are sequentially turned off, until all the stages are off.
in the Operation Test Mode, the status LED indicator
blinks orange. The blink rate increases, as the time
moves closer to the unit returning to the normal Status LED
operating mode. Additional presses of either Test Up or
Test Dn pushbuttons, reset the Test Mode timer. A single led capable of displaying green, orange, and red
indicates various operating conditions.
Dedicated Test Mode
SW2-5 in the OFF position is used to select the
Dedicated Test Mode. The dedicated test mode turns on
18
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
19
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
20
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
INSTALLATION
• Review all installation and wiring instructions • Verify that only 1 of the units is configured
thoroughly before proceeding. as a Master, and the remaining units are
configured as Expansion Units. Each
• Inspect all SLC4000 units for any physical Expansion Unit must be configured with a
damage. unique unit number using the on-board
configuration switches. Do not have line
• Verify that the operating ambient temperatures power applied, while configuring or
will be within 0 to 60 degrees C. (32 to 140 connecting the units!
degrees F).
• Verify that all interconnecting wiring is sized
• Mount the Master Unit by using 6-32 machine and installed in conformance with the National
screws in the standoffs provided. See Figure 1 Electrical Code (NEC) and other applicable
for the physical mounting dimensions. It is local codes.
recommended that the lower left standoff be
connected to earth ground, for best EMI • Connect the appropriate sensor or input signal
rejection. This standoff is connected to the to the Master unit per the wiring diagram shown
circuit common through a 1 meg ohm resistor. in Figure 3 being careful to observe polarity.
See the shielding and grounding considerations
• Mount the Remote Indicator Panel behind a 2" in the section ‘Field Wiring’.
x 4" rectangular cutout, using the six #6 holes
provided. See Figure 3 for the physical • Connect the Vernier Output (optional) to an
mounting dimensions. SCR module, being careful to observe polarity.
• Verify the proper setting of all switches on the • Connect the cable from any Remote Indicator
controller. See section ‘Unit Configuration’ Panels, if used.
21
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
Field Wiring
Vernier Wiring
Input Terminal Designations Connect the integral vernier output to a suitable SCR
See Table 9 for important wiring details and cross- power module or any other device which accepts 0-10
referencing to other popular controller terminal VDC, being careful to observe correct polarity. Refer to
designations. Figure 4, Field Wiring Diagram.
Grounding
The low voltage circuit common on the Selectronix
Superstep controllers is TB3, and TB6. It is connected
through a 1 Meg ohm resistor to the lower left standoff.
This provides a high impedance reference to chassis
ground, for rejection of electromagnetic interference.
22
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
OPERATING INSTRUCTIONS
• If Expansion Units are used in the system, verify
Startup and Adjustments that the Master Unit’s Status LED blinks Green/Off.
Verify the Expansion Unit’s status LED blinks
• Verify that all configuration switches are set as Green/Orange.
desired.
• The Test Up pushbutton may be operated to turn on
• Verify that the wiring is in accordance with Figure the relays, and the Test Dn pushbutton may be
4, Field Wiring Diagram. operated to turn off the relays.
• Verify that the On Delay Timing switches are set as • Verify the operation of the input signal by
desired, along with the OnDelaySeconds simulating the signal or by stimulating the
Adjustment RV1, and Off Delay Timing Switch. transducer to produce a test output.
• Make all RS-485 connections while the AC power is • Turn the line power off.
OFF.
• Apply line power to the Control System. • A Littelfuse 312002 or Bussman AGC 2A are
suitable replacements
24
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
TROUBLESHOOTING
Table 15 Troubleshooting
SYMPTOM POSSIBLE CAUSE REMEDY
Output stages do not turn on, On Time delay set too long Select the desired delay by setting
but Status LED flashing 4 Hz the applicable switches and
green. OnDelaySecs potentiometer
Output stages do not turn on, Input is out-of-range Verify that the sensor is providing
but Status LED flashing 2 Hz the correct input voltage or current.
red.
Output stages do not turn on, Sensor not wired correctly, or sensor not Wire sensor per Figure 4, and
and Status LED flashing 1 providing appropriate signal verify that the sensor output is
Hz green sufficient to activate the output
Output stages do not turn off Sensor not wired correctly, or sensor not Wire sensor per Figure 4, and
and Status LED flashing 1 providing appropriate signal verify that the sensor output is
Hz green appropriate for the desired output
level
All stages do not turn on at Signal source is not producing the full Configure the Master Unit to utilize
maximum command range expected by the controller the User-defined range
Input configuration switches incorrectly Verify Set the configuration
set switches
All stages turn on before Signal source is producing higher than Configure the Control Unit to
maximum command the full range expected by the controller utilize the User-defined range
All stages do not turn off at Signal source has an offset that keeps Adjust the offset of the control
the minimum command some of the outputs on. signal or configure the Master Unit
to utilize the User-defined range
Status LED is flashing 4 Hz A fault has been detected. Cycle incoming power to the
red SLC4000. If indication persists, the
unit must be replaced.
Status LED is flashing 1 Hz Communication with the master has Cycle incoming power to all the
red on an Expansion Unit been interrupted. SLC4000 units. If indication
persists, disconnect the faulty unit’s
power and cascading cables. Re-
connect cascading cables to any
remaining good units. It is then
possible to continue operating with
the remaining units without any re-
configuration , with a diminished
temporary capacity.
25
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
Troubleshooting Tips
• Verify that the problem is not in the field wiring If the trouble appears to be in the controller or
to the controller by verifying that the signal at any attached expansion units, isolate the
the sensor is the same as at the controller problem to being a Master or Expansion unit
terminals. problem. Turn off the power, and then
disconnect the cascading cable to the Expansion
• Isolate the source of the problem to being either Units. Test the Master Unit as a stand-alone
internal or external to the controller by controller. If the unit operates normally, then
disconnecting the external wiring, and driving the problem is in the communication link or in
the controller with a local input source. one of the Expansion Units.
• Temporarily change the Input Configuration Connect a single Expansion unit to the Master,
switches for ohmic, if not already using this and retest. Repeat for all Expansion Units to
configuration. isolate between individual units, and individual
cables.
• Connect a Test potentiometer with a total
resistance value of between 100 and 5000 If the problem is isolated to a specific cable or
ohms, 1/2 watt or greater. Connect the CW unit, re-configure the Master Controller for the
terminal of the pot to TB1 (1.24 volt reference), applicable Input Configuration. Re-connect any
the wiper to TB2, and the CCW terminal of the functional Expansion Units. The system may
pot to TB3 (circuit common). still be operated in the stand-alone mode or with
a partial amount of Expansion Units, until the
• Turn on the AC power. Rotate the defective parts are repaired or replaced.
potentiometer and monitor the quantity of relays
and LEDs, which are activated. The quantity of
LEDs should be proportional to the input signal.
T2 may be monitored for a voltage between 0
and 1.24 VDC, which indicates the proportional
amount of output stages to be activated.
26
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
SPECIFICATIONS
• Closed contact
FIELD WIRING: • 1/4" quick-connect male terminals provided for all connections.
• RJ-45 type connectors are used for interconnections between Master and
Expansion Units.
STEP TIME: • On Delay, Adjustable from ½ sec to 8 minutes, programmed by on-board switches
for integral minutes from 0-7, and a potentiometer to provide the fine adjustment
for seconds, which are added to the minutes delay.
• Off Delay, selectable between either 2 or 5 seconds using an on-board switch.
SIZE: Master Unit is: 5.50" height by 5.25" width by 2" max.
27
Selectronix, Inc. Superstep Series 4000 Installation & Operating Manual
___________________________________________________________________________________________
28