NOTES:

1. ALL DIMENSIONS ARE IN MILIMETRES & LEVELS IN METRES.

2. THIS DWG SHALL NOT BE SCALED, ONLY WRITTEN DIMENSIONS

TO BE FOLLOWED.

3. USE CONCRETE GRADE M25 (DESIGN MIX) UNLESS SPECIFIED

4. MINIMUM CLEAR COVER TO REINFORCEMENT

FOOTINGS: 50 (TO OUTERMOST BARS), COLUMNS: 40 (TO MAIN BARS)

BEAMS: 25 (TO STIRRUPS), SLABS: 25 (TO OUTERMOST BARS)

1500MM OR EQUAL TO THE LENGTH OF THE CANTILEVER BEAM(L2) WHICH EVER IS MORE 5. LAP LENGTH SHALL BE AS FOLLOWS
OR AS SHOWN IN DETAILED DRG
FOR COLUMNS 40d, OTHERS 50d (d IS BAR DIA)

6. THIS DWG SHALL BE READ IN CONJUCTION WITH RELEVANT

ARCHITECTURAL DWG.

7. ANY DISCREPANCY SHALL BE DISCUSSED WITH THE

CONSULTANT BEFORE THE WORK IS EXECUTED.


TOP REINFORCEMENT
TOP REINFORCEMENT 8. MINIMUM DEPTH OF EXCAVATION IS 1200mm FROM NGL
L2
9. SBC ASSUMED 250KN/M2

10. STEEL GRADE TO BE Fe500

STIRRUPS SPACING AS PER DETAILED DWG.


STIRRUPS SPACING AS PER DETAILED DWG. FOR EXECUTION
L1/8 L1/8
(L2) BOTTOM REINFORCEMENT (L1)
BOTTOM REINFORCEMENT

L1
L1 L2

SINGLE SPAN BEAM


SINGLE SPAN BEAM WITH CANTILEVER ON ONE SIDE

SUPPORT REINFORCEMENT SUPPORT REINFORCEMENT

TOP REINFORCEMENT TOP REINFORCEMENT TOP REINFORCEMENT


L1/3 L2/3 L2/3 L1/3
PROJECT:

SURAJ SINGH
RESIDENTIAL BUILDING
STIRRUPS SPACING AS PER DETAILED DWG STIRRUPS SPACING AS PER DETAILED DWG STIRRUPS SPACING AS PER DETAILED DWG
ARCHITECTS:

L1/8 L1/8 L2/8 L2/8 L1/8 L1/8 UNIKNOWN ARCHITECTS


BOTTOM REINFORCEMENT BOTTOM REINFORCEMENT BOTTOM REINFORCEMENT
(LAYER 1) (LAYER 1) (LAYER 1)
BOTTOM REINFORCEMENT BOTTOM REINFORCEMENT BOTTOM REINFORCEMENT CONSULTANT:
(LAYER 2) (LAYER 2) (LAYER 2)
VIRAJ KUNKOLIENCAR
B.E. (Civil), AMIE, AIV
L1 L2 L1

CONTINUOUS BEAM S. K. ASSOCIATES


A-11, SIXTH FLOOR, SILVIO HEIGHTS, ST. INEZ,
PANAJI - GOA 403001.
(M): +91-9765848536 (E): viraj@sk-associatesgoa.com

SHEET CONTENT: GAD-BEAM DETAILS

CLIENT: SURAJ SINGH

DRAWN: OMKAR CHECKED: VIRAJ

DATE: 14.12.2023 SCALE: N.T.S.

DRAWING NO: SKA/51/01 REV NO: R0