USER MANUAL

AUTOMATIC POWER FACTOR RELAY ‘B 6220’

This unit is applicable to single phase power factor correction. In case, the supply available is
three phase , any of the phase connected to the unit CT is to be connected in the same phase
from which supply is given to the unit.

The power factor controller measures the power factor of the AC supply and switches the
adequate amount of capacitors from the capacitor bank, to maintain the power factor to the
desired power factor value set in the controller.

PROGRAM SETTINGS:
The unit has 4 switches: Mode, Select, Up , Down

MODE SELECT SWITCH: When pressed, this gives the following modes in a sequential way
AUTO POWER FACTOR HIGH POWER FACTOR LOW DELAY ON DELAY OFF
DELAY START STAGE MANUAL TEST

AUTO: This is the power up default mode. The power factor measured by Relay is displayed in
display in this mode.

1|P a g e www.runcon.co.in
PF h: Set the upper threshold power factor target value in the range from Lag 0.50 To Lead
0.50 The default value in this mode is Lead 0.95

PF L: Set the lower threshold power factor target value in the range from Lag 0.50 To Lead
0.50 The default value in this mode is Lag 0.99

DELAY ON: This can program the delay time between any two sequential relay getting on. The
time is adjustable from 1 to 60 seconds (The display shows dLon)

DELAY OFF: This can program the delay time between any two sequential relay beinf put off.
The time is adjustable from 1 to 60 seconds (The display shows dLof)

DELAY START: This indicated the time after which the first relay would be put on.The time is
adjustable from 1 to 60 seconds(The display shows dt)

STAGE: The number of capacitor banks to be operated can be selected by this stage selector
mode. (The display shows StG)

MANUAL: In this mode, the number of capacitor banks can be selected by the customer as
desired and all other controls are bypassed.

TEST: In this mode, all the relays start getting on in a sequential order and then off in the same
order. This is in a cyclic manner indefinitely.

IMPORTANT INSTRUCTIONS:
1. Always install C/T on Maximum Load Current & connect on same phase
2. When unit is switched on and the displays shows ‘Ct’ ,the connection to the current
transformers has to be reversed.
3. Always install capacitor in increasing order as given in table:
Stage 1 2 3 4 5
KVAR 1 2 4 8 15
4. Install C/T before APFC panel & factory load
5. When load is less than 1%, the display will shows ‘LOC’ and unit will not function. If the load
is less than 1% power factor correction is not required.
6. Fix capacitors on LT Side of Transformer for Transformer PF Compensation (If Energy Meter is
installed on HT Line)

2|P a g e www.runcon.co.in
CONNECTION DIAGRAM:

Thanks for using our APFC Relay ‘B 6220’.

M AU RY A EN T ERPRI SES
ADD: 7 5 A M AI N 6 0 FEET ROAD V I SH WASH N AGAR SH AH DARA DELH I -1 1 0 0 3 2
Mfg APFC RELAY MDI CONTROL RELAY PHASE SEQUENCE REALY ENGINE RELAY
CAPACITORS APFC PANELS ELECTRICAL PANELS Etc

Mob +91 9717152559, 9310821045


Email runconcapacitor011@gmail.com , sunil.morrya@gmail.com
Web: www.runcon.co.in , www.runcon.in

3|P a g e www.runcon.co.in

You might also like