Professional Documents
Culture Documents
com
VOLTAGE DROP
COMPENSATORS
FOR LONG CABLE
RUNS
WHITE PAPER
OVERVIEW
CONTENTS
WHAT ARE VOLTAGE DROPS? 01
What factors affect Voltage Drop? 01
CONCLUSION 14
REFERENCES 15
Besides the resistivity which is constant, below is a As can be seen, resistivity has a great impact on
list of some of the factors that lead to voltage drop. resistance and voltage drop.
Factor Effect
Type Of Conductor Material The resistivity value of each material is different. Some
materials have lower resistivity than others. Copper has a
lower resistivity compared to Aluminum, hence a more efficient
conductor. Conductors with higher resistivity, the higher the
voltage drops.
Current Carried By The Conductor With the resistance held constant, an increase in current
(Ampere Load) flowing through the circuit will result in more voltage drop.
Procedure
Step 1: Take the value from the volt drop table 4E4B
(mV/A/m) for the cable cross-section area you want
to use.
Step 2: Multiply the actual current the cable will
deliver (do not use the cable rating).
Step 3: Multiply by the length of cable run in meters.
Step 4: Divide results by 1,000 (to convert millivolts
to volts)
The NEC recommends a maximum combined For Commercial and Industrial Installations, the
voltage drop of 5% for both feeder and branch circuits. supply voltage can vary between statutory limits of
According to the NEC 210.19(A)(1) Informational +10% to –6%. [3]
Note No. 4, the voltage drop for branched circuits is
limited to 3% of the applied voltage. This allows a 2%
Voltage Drop limits in Australia
drop in the feeder. [1]
The maximum permissible voltage drop between the
point of supply and any point of the installation is as
Voltage Drop limits in Europe follows: Any low voltage Electrical installation must
not exceed 5% voltage drop and where a substation
In Europe, the maximum permitted voltage drop is
is located on-premises, must not exceed 7% voltage
3% for lighting or 5% for other uses. This is for low
drop. [4]
voltage installations supplied directly from a public
LV distribution system. For low voltage installations
supplied from private LV Supply, the limits are 6% for Voltage Drop limits in Singapore
lighting and 8% for other uses.
Voltage drop at consumer final sub-circuit should
be kept at below 4% – Under normal conditions, the
Voltage Drop limits in the U.K. voltage drop at the terminals of any fixed current-
using equipment such as switch socket outlet
For Consumer’s Installations, the maximum should not exceed 4% of the nominal voltage of the
permitted voltage drop is 3% for lighting or 5% for supply. [5]
Flickering of lights – Voltage drops may cause flickering of lights which may
2.
eventually lead to damage of the lights as well as a human health issue.
Reduced motor torque and efficiency – A 10% voltage drop reduces torque by
4. about 18%. Increased heating also occurs due to increased current drawn to
supplement the voltage drop.
Failed motor startup: - Motor startup requires higher in-rush current levels,
5.
which will be limited if the voltage drop is significant.
Where the Voltage drop is persistent over long periods, the low voltage and
8. increased resistance will pose a fire risk due to increased heating and heat
dissipation.
In cases where the long cable runs are used for communication transmission
14. systems and security systems, unplanned interruptions of these critical
services may have a negative ripple effect.
There are a few proven solutions for reducing voltage If the load is relatively non-essential such as lighting
drops and their effects on long cable runs and and pumps, the solution to voltage drop issues
installation. The choice of a suitable solution may should be one that does not strain the available
vary according to the specific situation and there is a finances. However, for critical loads, it is important
need to consider some critical factors. to deploy a cost-effective and reliable solution that
prevents the negative effects of the voltage drop at a
Generally, the main factors include length and cross- reasonable budget.
section area of the conductor, type of conductor
used, the load current, connections, and temperature. Based on the issues that result in voltage drops,
there are conventional methods that work by
In most instances, the length of the cable will remain limiting the contributing factors hence preventing
constant and there is little to do on this unless the occurrence. At the same time, there are adaptive
changing the route or design, which may not be methods that help to reduce voltage drops and are
possible. Load is something that requires proper therefore suitable when it is impossible to stop them.
consideration if there is going to be a long cable run.
Conventional Methods
The conventional methods include: VD = 1.10 * 100 * 1500
__________________ = 165V
1000
1. Using Larger Cross-sectional
Sized Cables Using the Voltage drop calculation formula above,
with the (mV/A/m) constant for the cable as 1.10,
the Voltage drop for this setup will be 165V which is
equal to 41% Voltage Drop.
To find out the cable size that will reduce this voltage
drop to less than 4%, which is 16V, we will make the
(mV/A/m) constant the subject of the formula, and it
will then become:
2. Increasing the Number of the current capacity ignoring the voltage drop issue.
If we increase the number of conductors to 12
Transmission Cables
conductors, the current will be shared hence each
Increased transmission current leads to an increase However, delivering higher voltages is costly since it
in voltage drop. Using higher transmission voltages requires a step-up transformer at the sending end. It
can also reduce voltage drops for a given amount of will also require another step-down transformer at the
power transmitted. destination end to lower the voltage to the standard
Power (P) = Voltage (V) * Current (I). level. Unfortunately, adding the transformers may
increase the cost of transmission significantly when
For the same power being transmitted, an increase in dealing with the much higher voltages.
voltage leads to a reduction in the current to transmit.
In practice, the compensator continuously monitors • Reduces the need for extensive cable sizing
and adjusts the voltage to maintain it constantly that would have been required to compensate
and within stipulated levels. It can as well compen- for voltage drop regulation in the conventional
sate for any fluctuations in the utility mains supply. method, hence saving on cable costs and cable
installation requirements.
CONCLUSION
Voltage drops are very common where long protection features that ensure the protection of your
transmission cables are used. As an engineer or loads and power system. These include input circuit
electrical consultant, this is one factor you have to breaker overcurrent protection, inbuilt high overload
consider while designing and implementing projects capability, transient voltage surge suppression as
with long cable runs. As highlighted, there are several well as lightning surge arrestors. This way loads
solutions one can employ to reduce the voltage drop are guaranteed to receive the recommended and
issues in your projects. stable voltage, hence improving the overall efficiency
and performance while minimizing unforeseen
The use of Voltage Drop Compensators in your downtime.
project is one of the most reliable and cost-effective
approaches, especially when powering up non- To ensure safety and avoid financial loss, voltage
essential loads. This way you will reduce financial drop regulation is key, particularly for facilities that
expenses on extra electrical cables required to use long transmission cable lines. Is your facility or
compensate for the high voltage drops. The smaller electrical system in need of an effective voltage drop
cable size used becomes also advantageous in the solution?
cable installation process.
Get in touch with us at sales@ashleyedison.com
Voltage Drop Regulators also come with additional and our consultants will be happy to speak to you.
Email us at sales@ashleyedison.com
or call us at the following:
Website: www.ashleyedison.com
References
1. Snyder, D., 2014. Voltage drop calculations ( Formulas. Phasor Diagram and Real-world examples).
[online] https://electrical-engineering-portal.com/. Available at: <https://electrical-engineering-portal.com/download-
center/books-and-guides/electrical-engineering/voltage-drop> [Accessed 17 November 2021].
2. Locke, D., 2008. Guide to the Wiring Regulations 17th Edition IEE Wiring Regulations (BS 7671: 2008). 1st ed. Oxford:
John Wiley & Sons Ltd, p.50.
3. Legislation.gov.uk. 2003. The Electricity Safety, Quality and Continuity Regulations 2002. [online] Available at:
<https://www.legislation.gov.uk/uksi/2002/2665/regulation/27/2003-01-31> [Accessed 17 November 2021].
4. ELEK Software. 2021. Voltage drop limits for Low Voltage installations - ELEK Software. [online] Available at:
<https://elek.com.au/articles/voltage-drop-limits-for-low-voltage-installations/> [Accessed 17 November 2021].