You are on page 1of 6

SIMATIC 55_SERIES_WITH_VACUUM\SIMATIC 08/12/2013 02:43:29 PM

300 Station\CPU 315-2 DP(1)\...\OB35 - <offline>

OB35 - <offline>
"ANALOG" Cyclic Interrupt 5
Name: Family:
Author: Version: 0.1
Block version: 2
Time stamp Code: 08/09/2013 08:01:37 AM
Interface: 07/26/2009 04:38:23 PM
Lengths (block/logic/data): 00896 00750 00032

Name Data Type Address Comment


TEMP 0.0
OB35_EV_CLASS Byte 0.0 Bits 0-3 = 1 (Coming event), Bits 4-7 = 1 (Event class 1)
OB35_STRT_INF Byte 1.0 16#36 (OB 35 has started)
OB35_PRIORITY Byte 2.0 Priority of OB Execution
OB35_OB_NUMBR Byte 3.0 35 (Organization block 35, OB35)
OB35_RESERVED_1 Byte 4.0 Reserved for system
OB35_RESERVED_2 Byte 5.0 Reserved for system
OB35_PHASE_OFFSET Word 6.0 Phase offset (msec)
OB35_RESERVED_3 Int 8.0 Reserved for system
OB35_EXC_FREQ Int 10.0 Frequency of execution (msec)
OB35_DATE_TIME Date_And_Time 12.0 Date and time OB35 started
TEMP0 Word 20.0 Ret_Val bit

Block: OB35 "Cyclic Interrupt"

Network: 1 Analog Conversion for Bookcell DC Amps

SCALES BOOKCELL AMPS FROM 0-100 ADC

FC105
Read Analog Value
464-2
"Read Analog Value
464-2"
EN ENO

PIW258 #TEMP0
"Bookcell_ Ret_Val
DC_Amps" IN bit
RET_VAL #TEMP0
1.000000e+
002 HI_LIM MD500
"HMI_
0.000000e+ Bookcell_
000 LO_LIM OUT Amps_Real"

M15.4
"Not_
Bipolar" BIPOLAR

Page 1 of 6
SIMATIC 55_SERIES_WITH_VACUUM\SIMATIC 08/12/2013 02:43:30 PM
300 Station\CPU 315-2 DP(1)\...\OB35 - <offline>

Network: 2

SCALES BOOKCELL DC VOLTS 0-200 VDC

FC105
Read Analog Value
464-2
"Read Analog Value
464-2"
EN ENO

PIW256 #TEMP0
"Bookcell_ Ret_Val
DC_Volts" IN bit
RET_VAL #TEMP0
2.000000e+
002 HI_LIM MD560
"HMI_
0.000000e+ Bookcell_
000 LO_LIM Volts_
OUT Real"
M15.4
"Not_
Bipolar" BIPOLAR

Network: 3

SCALES EC REACTOR AMPS 0-50 ADC

FC105
Read Analog Value
464-2
"Read Analog Value
464-2"
EN ENO

PIW262 #TEMP0
"EC_Cell_ Ret_Val
DC_Amps" IN bit
RET_VAL #TEMP0
5.000000e+
001 HI_LIM MD570
"HMI_EC_
0.000000e+ OUT Amps_Real"
000 LO_LIM

M15.4
"Not_
Bipolar" BIPOLAR

Page 2 of 6
SIMATIC 55_SERIES_WITH_VACUUM\SIMATIC 08/12/2013 02:43:30 PM
300 Station\CPU 315-2 DP(1)\...\OB35 - <offline>

Network: 4

SCALES EC REACTOR VOLTS TO 0-200 VDC

FC105
Read Analog Value
464-2
"Read Analog Value
464-2"
EN ENO

PIW260 #TEMP0
"EC_Cell_ Ret_Val
DC_Volts" IN bit
RET_VAL #TEMP0
2.000000e+
002 HI_LIM MD510
"HMI_EC_
0.000000e+ Volts_
000 LO_LIM OUT Real"

M15.4
"Not_
Bipolar" BIPOLAR

Network: 5

FLOW TRANSMITTER SCALED 0-200 LITERES PER MINUTE

FC105
Read Analog Value
464-2
"Read Analog Value
464-2"
EN ENO

PIW304 #TEMP0
"FT_FLOW_ Ret_Val
RAW_INPUT" IN bit
RET_VAL #TEMP0
2.000000e+
002 HI_LIM MD580
"HMI_FT_
0.000000e+ SCALED_
000 LO_LIM OUT FLOW_REAL"

M15.4
"Not_
Bipolar" BIPOLAR

Page 3 of 6
SIMATIC 55_SERIES_WITH_VACUUM\SIMATIC 08/12/2013 02:43:30 PM
300 Station\CPU 315-2 DP(1)\...\OB35 - <offline>

Network: 6

V1 LEVEL TRANSMITTER SCALED 0-100 %

FC105
Read Analog Value
464-2
"Read Analog Value
464-2"
EN ENO

PIW308 #TEMP0
"V1_LEVEL_ Ret_Val
RAW_INPUT" IN bit
RET_VAL #TEMP0
1.000000e+
002 HI_LIM MD584
"HMI_V1_
0.000000e+ LEVEL_
000 LO_LIM SCALED_
OUT REAL"
M15.4
"Not_
Bipolar" BIPOLAR

Network: 7

CLARIFIER LEVEL TRANSMITTER SCALED 0-100 %

FC105
Read Analog Value
464-2
"Read Analog Value
464-2"
EN ENO

PIW310 #TEMP0
"CLARIFIER Ret_Val
_RAW_ bit
LEVEL" IN RET_VAL #TEMP0

1.000000e+ MD588
002 HI_LIM "HMI_CLAR_
LEVEL_
0.000000e+ OUT SCALED_RE"
000 LO_LIM

M15.4
"Not_
Bipolar" BIPOLAR

Page 4 of 6
SIMATIC 55_SERIES_WITH_VACUUM\SIMATIC 08/12/2013 02:43:30 PM
300 Station\CPU 315-2 DP(1)\...\OB35 - <offline>

Network: 8

BLACK WATER TANK LEVEL TRANSMITTER SCALED 0-100 %

FC105
Read Analog Value
464-2
"Read Analog Value
464-2"
EN ENO

PIW312 #TEMP0
"BLACK_ Ret_Val
WTR_TNK_ bit
RAW_LVL" IN RET_VAL #TEMP0

1.000000e+ MD776
002 HI_LIM "HMI_BLK_
WTR_LVL_
0.000000e+ OUT SCALED"
000 LO_LIM

M15.4
"Not_
Bipolar" BIPOLAR

Network: 9

GRAY WATER TANK LEVEL TRANSMITTER SCALED 0-100 %

FC105
Read Analog Value
464-2
"Read Analog Value
464-2"
EN ENO

PIW314 #TEMP0
"GRAY_WTR_ Ret_Val
TNK_RAW_ bit
LVL" IN RET_VAL #TEMP0

1.000000e+ MD780
002 HI_LIM "HMI_GRAY_
WTR_LVL_
0.000000e+ OUT SCALED"
000 LO_LIM

M15.4
"Not_
Bipolar" BIPOLAR

Page 5 of 6
SIMATIC 55_SERIES_WITH_VACUUM\SIMATIC 08/12/2013 02:43:30 PM
300 Station\CPU 315-2 DP(1)\...\OB35 - <offline>

Network: 10

RUNG RELAYS THE GRAY WATER TANK LEVEL TO CUSTOMER


SCALED 0-100% INPUT AND IS SCALED TO COUNTS OUTPUT

FC106
Read Analog Value
466-1
"Read Analog Value
466-1"
EN ENO

MD780 #TEMP0
"HMI_GRAY_ Ret_Val
WTR_LVL_ bit
SCALED" IN RET_VAL #TEMP0

1.000000e+ PQW258
002 HI_LIM "GRAY_WTR_
TNK_LVL_
0.000000e+ OUT TO_CUST"
000 LO_LIM

M15.4
"Not_
Bipolar" BIPOLAR

Network: 11

EC REACTOR CURRENT CONTROL OUTPUT TO TRANSMITTER


TECH SHOULD CALIBRATE TRANSMITTER SO THAT RANGE WILL BE 8-25 ADC. 7-31-2012 SD

FC106
Read Analog Value
466-1
"Read Analog Value
466-1"
EN ENO

MD100 #TEMP0
"HMI_EC_ Ret_Val
REACTOR_ bit
AMPS_SET" IN RET_VAL #TEMP0

2.500000e+ PQW256
001 HI_LIM "EC_Cell_
Current_
0.000000e+ OUT Control"
000 LO_LIM

M15.4
"Not_
Bipolar" BIPOLAR

Page 6 of 6

You might also like