B RESPONSE SCHEDUE TO REV.

02
FOR ARUP’S COMMENTS

ITEM DESCRIPTION RESPONSE OPEN / CLOSED


Page 36&48: Comment#1, ARUP (20231223):
Support types 6.2 and 6.8 are to L2 150thk
Page All: Anchor positions are cleared
bondek slabs, not RC slabs. Connection
from the steel decking rib which will be
1 details would have to cater for the presence Closed
made sure by site surveying of HEXACON
of 1mm thk steel decking ribs. Please ensure
and Seiko’s coordination
cast-in bolts do not interfere with the ribs
and only go between the ribs.