Professional Documents
Culture Documents
CONTENTS
Scope 5
Executive Summary 6
Section 4: Using Test Results to Select the Right Device for each Design 17
References 31
D2: Conclusion 43
E4: Conclusion 58
TABLES
Table 1: Summary of Test Protocols 11
CHARTS
Chart 1: Comparison of Sediment Gradation for the BW
CoP, NJCAT and DIBt Test Protocols, Benchmarked against
the ISO14688-1 Soil Classifications 13
SCOPE
This document only applies to Manufactured Treatment Devices (MTDs) designed
for the treatment of stormwater (not simply attenuation or conveyance devices)
that have been tested in accordance with one of the protocols detailed in
Section 2. The guide defines a process and consistent data set that allows
manufacturers to provide mitigation indices for use in The SuDS Manual Simple
Index Approach (SIA) as defined in The SuDS Manual (C753) (Woods Ballard, et
al., 2015)- Section 26.7. The requirements of the The SuDS Manual (C753) takes
precedence over this document. For more detailed risk assessments, advice
from the approving authority and manufacturer should be sought.
Pollution hazard indices are presented in Table 26.2 of the SuDS manual. Indices range from 0 to 1.
Step 2 – Select SuDS/MTD with a total pollution mitigation index that equals or exceeds the pollution hazard index.
Total SuDS mitigation index ≥ pollution hazard index (per contaminant type)
Where the mitigation index of a single component is insufficient, two (or more) components in series will be required, where:
Total SuDS mitigation index = Mitigation index of first component + 0.5 (mitigation index of second component)
CONTAMINANTS/POLLUTANTS:
Mitigation indices for MTDs should be declared according to the British Water Code of Practice (BW CoP). The basis on which
they are derived is as follows:
Where:
Particulate fraction reduction = Sediment removal efficiency x Particulate fraction
Dissolved fraction reduction = Dissolved metal removal efficiency x Dissolved fraction
Use of internationally recognised declared testing, certification or verification programmes is acceptable, but it will be
necessary to correct the net annual removal efficiencies under these to UK rainfall patterns and convert to a Metals
Mitigation Index.
Continued.
Where:
Particulate fraction reduction = Sediment removal efficiency x Particulate fraction
Free Phase fraction reduction = Free Phase hydrocarbon removal efficiency x Free Phase fraction
Use of internationally recognised testing, certification or verification programmes is acceptable, but it will be necessary
to correct the net annual removal efficiencies declared under these to UK rainfall patterns and convert to a Hydrocarbon
Mitigation Index
Step 3 – Where the discharge is to protected surface waters or groundwater, consider the need for a more
precautionary approach
Reference to local planning documentation should be considered to identify any additional protection requirements due to
habitat conservation or areas with environmental designations, such as Sites of Special Scientific Interest (SSSI) sites.
In England and Wales additional treatment components must be provided where discharge is to protected surface waters or
groundwater. This provides an additional level of protection in the event of an unexpected pollution event, system failure or
poor system performance.
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
9
STORMWATER TREATMENT DEVICES
SECTION 1.
PROTECTING THE WATER ENVIRONMENT
FROM POLLUTION
Chapter 4 and Chapter 26 of The SuDS Manual (C753) both provide information about
the sources of pollution in surface water runoff, the risks to the aquatic environment
presented by these contaminants and the general approaches to water quality risk
management. Annex 1 of Chapter 26 of C753 provides an outline of the typical
contaminants in urban runoff and their potential toxicity. These values were used as
the basis for the definition of the pollution hazard indices used in the Simple Index
Approach (SIA) (see Table 26.2 of C753) and the SIA Tool developed by HR Wallingford
on behalf of the Scottish Environmental Protection Agency (SEPA):
There are other, more complex risk assessment methods, such as those also covered
in Chapter 26 of C753 and in Design Manual for Roads and Bridges (DMRB HD33/16)
HD45. These methodologies are outside the scope of this guidance document and
advice should be sought from the approving / adopting body (where relevant) and
supplier.
SECTION 2.
TEST PROTOCOLS
Whilst there is currently no British, European or International Standard that applies to
proprietary (or manufactured) devices for the treatment of surface water run-off, there
are now a number of recognised testing methods both in the UK and internationally.
Whilst these have often been developed independently of each other, there are
noticeable similarities across them.
Some of the most widely recognised are specifically referenced in this guide:
British Water Assessment of MTDs Designed to Treat Surface Water Runoff – BW CoP
(see Appendix A1)
New Jersey Corporation for Advanced Technology - NJACT Verification Programe
(see Appendix A2)
National Technical Approval Granted by the German Institute of Building Technology/
Deutsches Institut für Bautecknik - DiBt (Appendix A3)
Separator Systems for Light Liquids (e.g., oil and petrol) – BS EN 858 (Appendix A4)
These test methods are summarised in Table 1, and discussed fully in the relevant
appendices. BS EN 858-1:2002 is not included in Table 1, as testing of free phase
hydrocarbons is not directly covered in the BW CoP. Chart 1 also contains a comparison
of the sediments used to represent typical urban Total Suspended Solids (TSS) size
distributions in the test protocols.
The NJCAT testing protocols are designed to assess the annual capture rate of
sediments from runoff in a typical urban setting. This is in recognition that the majority
of pollutants in runoff will be associated with the sediments (rather than dissolved).
The annual sediment capture performance required to gain NJCAT approval is 50% for
sedimentation (settling) systems and 80% for filter systems.
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
10
STORMWATER TREATMENT DEVICES
The German DIBt testing protocol is a stringent approval protocol for treating runoff in
high-risk scenarios. The focus is primarily on reducing pollutant loads from metal roofs
and highly trafficked road runoff, which is partly related to German building practices.
The DIBt requirements are only applied for areas with > 300 Average Daily Traffic (ADT)
and where the discharge is infiltrated to groundwater. The test protocol assesses annual
capture rate of sediment, dissolved metals and hydrocarbons, where the approval
requirements are:
This guidance is not intended to be all encompassing as it is recognised that there are
an increasing number of test methods being developed or in use around the world.
Use of other methodologies to evaluate the performance of proprietary or MTDs
should follow the principles set out here where practical.
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
11
STORMWATER TREATMENT DEVICES
Applicable Devices Various treatment devices as covered in C753 Separate test methods for: Filtration systems for drained areas of up to
Chapter 14 • Hydrodynamic Sedimentation 2000m² and prior to discharge to earth or
• Filtration Systems groundwaters
Quality Assurance Witnessed by a United Kingdom Accreditation Tests at independent facility or supervised by Testing must be carried out at an approved
Services (UKAS) accredited expert at an accredited person 3rd party laboratory
manufacturer facilities or suitable 3rd party
laboratory
Sediment Particle Size Distribution (PSD) 2 to 400 microns 2 to 1000 microns 2 to 400 microns
for removal efficiency D 50 = 63 microns D50 = 75 microns D 50 = 63 microns
Sediment Particle Size Distribution (PSD) 2 to 400 microns 50 to 1000 microns 2 to 400 microns
for retention efficiency D 50 = 63 microns D50 = 200 microns D 50 = 63 microns
Sediment influent load (mg/l) 200 200 Based off 50 g/m² of connected area size:
seen to be approximately equal to the
annual load
Sediment Pass / Fail Criteria None – informative only Hydrodynamic Separator Devices (HDS) must >92% retention
achieve a minimum net annual 50% TSS
reduction; all HDS results are rounded down to
50%
Filtration devices must achieve a minimum net
annual 80% TSS removal; all Filtration device
results are rounded down to 80%
Metals Capture Assessed? Yes – Dissolved metals (Copper & Zinc) No Yes – Dissolved metals (Copper & Zinc)
(optional) (mandatory)
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
12
STORMWATER TREATMENT DEVICES
Metals Pass / Fail Criteria None – informative only n/a Effluent concentrations:
Copper ≤ 144 µg/l (80% retention)
Zinc ≤ 1875 µg/l (70% retention)
Hydrocarbons test fluid n/a n/a Heating oil to Deutsches Institut für Normung
(DIN) 51603
Hydrocarbon Pass / Fail Criteria n/a n/a Effluent concentration ≤ 20% of 0.68 g/m2 of
connected area
Treatment Flow Rates A mean flow rate resulting from a 1 Maximum Treatment Flow Rate (MTFR), n/a.
year 15-minute (M1:15) rainfall event which is defined as the highest flow rate that Performance is declared based on the
(determined by HR Wallingford as 27 mm/hr can be conveyed through the device while maximum connected area that can be
as an appropriate UK average) for a stated both achieving a performance claim based treated.
catchment area shall be declared by the on the TSS removal efficiency testing and,
manufacturer as the device Treatment Flow for filtration systems, allowing for sufficient
Rate (TFR). operational longevity.
Typical Rainfall Intensity for Treatment A mean flow rate resulting from a 1 Weighted efficiency determined based 3 test flow rates are determined based on the
Design year 15-minute (M1:15) rainfall event on typical annual New Jersey rainfall connected area and each represent 1/3 of the
(determined by HR Wallingford as 27 mm/hr characteristics annual rainfall run-off for Germany: 2.5l/s/ha,
as an appropriate UK average) for a stated 6l/s/ha and 25l/s/ha. An exceedance test at
catchment area shall be declared by the 100 l/s/ha is applied to test for retention of
manufacturer as the device TFR. captured material under heavy rainfall
Maximum Flow Rate (Hydraulic Capacity) Capability to safely pass a maximum A Maximum Hydraulic Flow Rate (MHFR) An exceedance test at 100 l/s/ha is applied to
capacity flow rate equivalent to a 1:30 year is also declared for HDS devices, which is test for retention of captured material under
rainfall event (90mm/hr), utilising bypass as defined as the highest flow rate that can heavy rainfall
appropriate be conveyed through the device with a
manufacturer specified head loss.
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
13
STORMWATER TREATMENT DEVICES
Chart 1 Comparison of sediment gradation for the BW CoP, NJCAT and DIBt
Test Protocols, benchmarked against the ISO14688-1 Soil Classifications.
(Note: the BW CoP and DIBt sediment gradations are identical)
Coarse
Clay Fine Silt Med. Silt Coarse Silt Fine Sand Med. Sand Sand
100
KEY
90 NJDEP
BW CoP/DiBt
80
70
Percent finer than (%)
60
50
40
30
20
10
0
1 10 100 1000
Particle size (microns)
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
14
STORMWATER TREATMENT DEVICES
SECTION 3.
USE OF MANUFACTURED STORMWATER TREATMENT
DEVICES WITHIN A SuDS MANAGEMENT TRAIN
The following represents general guidance on the most appropriate location for
manufactured devices within a SuDS Management Train (Table 2). This guidance is not
considered comprehensive and the design for each site should be considered based on
local factors such as pollution sources, topography, rainfall, existing infrastructure and
services, and space constraints. Where in doubt, advice from the manufacturer on the
most appropriate device and location should be sought, for consideration by the design
engineer.
Settling: Suitable for removal of denser, readily settable sediments and trash. Removal
rate decreases with increasing flow-rate.
Floatation: Suitable for removal of less dense (specific gravity < 1.0) readily floatable
oils and trash. Removal rate decreases with increasing flow-rate.
Physical treatment mechanisms are also present in green infrastructure systems, and
their capability to remove pollutants reflected in observed performance. For example,
a detention basin provides settling and has an expected mitigation index of 0.5 for TSS,
whereas a bioretention system provides filtration and adsorption and has an expected
mitigation index of 0.8 for TSS (CIRIA C753 Table 26.2). Test standards for manufactured
devices set similar expectations for settling and filtration.
The US NJCAT protocol and German federal regulations for stormwater treatment (DWA
A102) both require 50% annual load reduction of TSS when settling is applied as the
treatment mechanism. US NJCAT and German DIBt approvals for filters require 80% and
92% removal of TSS respectively.
Read and use in conjunction with Table 14.1 and Table 26.7 of The SuDS Manual
(C753). Proprietary systems, vegetative & other SuDS components can be used
independently or collectively as part of an overall Management Train.
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
15
STORMWATER TREATMENT DEVICES
Table 2: Use of Manufactured Stormwater Treatment Devices within a SuDS Management Train
TREATMENT2
Proprietary Yes4 Yes Yes No
Bioretention /
Biofiltration
Treatment Yes4 Yes5 No No
Channels
Hydrodynamic No Yes Yes3 No
or Vortex
Separators
Proprietary No Yes5 Yes5 Yes5
Filtration
Systems
Oil Separators No Yes5 Yes5 No
Multi-Process Dependant on the nature of the system and the individual
elements combined to create the multi-process system
NOTES:
1. The prevention of runoff from the site for the majority of small (frequent) rainfall events is called interception and is a vital part
of treatment design that should be incorporated into many SuDS designs. Interception components are also normally a treatment
component.
2. “Primary”, “Secondary” and “Tertiary” treatment defined as per the The SuDS Manual (C753), noting that the definitions here are
different from conventional wastewater / water treatment.
3. Primary treatment mechanism is sedimentation; therefore, these components will generally be at their most effective when used
as the first treatment stage.
4. Where volume reduction through filter media, soil, or vegetation (where applicable) can be demonstrated or where used as part
of an infiltration system.
5. These remove coarse sediments, but their use for this purpose could have implications with respect to maintenance
requirements. Coarse sediment should be removed upstream unless they are specifically designed to retain sediment as
a separate part of the component. See also Box 1.
The steps taken in assessing a SuDS Management Train that incorporates MTDs, in
accordance with the SIA design process are shown in Table 3 Steps in assessing a SuDS
Management Train . This also contains, a simple example and supporting information to
demonstrate the process being applied.
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
16
STORMWATER TREATMENT DEVICES
Review C753 Section 26.7.1 to establish For a residential development the following hazards
Determine suitable hazard indices for discharges to indices would apply (low hazard level):
appropriate hazard surface water bodies or see alternative table
TSS = 0.5
indices for site for groundwater discharges if required.
Metals = 0.4
conditions based
Hydrocarbons = 0.4
on land.
Total SuDS mitigation index ≥ pollution Check BW CoP tested devices list online and
hazard index manufacturers datasheets to select an appropriate
MTD or combination of SuDS devices to give suitable
Total SuDS mitigation index = mitigation
mitigation indices:
index1 + 0.5 mitigation index2
Select MTD and/
Mitigation index check:
or other treatment Example of MTD mitigation indices:
approaches to TSS = 0.5 POLLUTANT HAZARD MITIGATION DESIGN
satisfy pollution Metals = 0.4 INDEX INDEX CHECK
Select a suitable unit capacity from For 1 ha site, a 2.4 m diameter unit would be
manufacturers’ equipment range. required from the example table.
Peak flow-rate requirements are generally Assuming a peak rainfall intensity of 90 mm/hr (250
dictated by the requirement to pass a l/s/ha) for a 15min 1:30 yr event, the flow-rate can
15min 1:30yr event. This must be checked be derived from (where C=1 for impervious):
against the manufacturer’s datasheet.
SECTION 4.1.
FLOW RATES
It is best practice to size the MTD
installation so that the design flow of
the unit is equal to the runoff from the
peak annual rainfall intensity (e.g., 1 year,
15-minute rainfall event). This makes
MTDs less sensitive to local rainfall
variations, as the majority of runoff occurs
at low flow-rates, below the operating limit
of the MTD.
Table 4 Test flow-rates to assess capture efficiency for the typical sub-annual rainfall volume percentile
Selection and sizing of an MTD should be based on the following treatment flow-rate
requirement derived from the rational method:
Q = CIA
Where Q is the treatment flow-rate of the device, C is the runoff coefficient, I is the
rainfall intensity (in this case 75 l/s/ha or 27mm/hr), and A is the drained area in ha.
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
19
STORMWATER TREATMENT DEVICES
The correlation of these test flow-rates against the average English rainfall distribution is
shown in Chart 2 (McPherson, 2019). Rainfall intensities below 2mm/hr are discounted from
analysis due to the negligible amount of runoff that is generated in this rainfall intensity range.
100%
KEY
70%
Cumulative rainfall (%)
60%
50%
40%
30%
20%
10%
0
0 5 10 15 20 25 30 35 40
Rainfall intensity (mm/hr)
Chart 2 Distribution of annual rainfall in England and test flow-rates in the BW CoP.
These flow-rates and rainfall distributions are used in the next section to derive the
net annual removal rate and mitigations indices for each pollutant.
An example of how the peak annual rainfall intensity (27mm/hr) may be applied to
calculate the treatment flow-rate from the drained area is shown in Box 2.
Typical peak annual rainfall (e.g., 1 year, 15-minute rainfall event) for England is
given as 27mm/hr (75 l/s/ha) in the BW CoP.
Calculating the runoff rate from Q=CiA (with an example runoff coefficient of C=0.8)
gives the following:
Therefore, in this example the required treatment flow-rate of the MTD is ≥ 75 l/s.
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
20
STORMWATER TREATMENT DEVICES
100
KEY
90
USGS (2011)
80 - Highway runoff
WRC/EA (2003)
70
- Highway runoff
50
Zanders (2005)
40 - Road sweepings
Morgan (2013)
30
- Road sweepings
20
10
0
1 10 100 1000 10000
Particle Size (microns)
Comparison of the road runoff samples, with the test sediments used in the methods
described in Section 2, shows that the test methods use PSDs with finer particles (or
smaller D50 values). As larger / heavier particles will settle more readily than lighter
/ smaller particles the efficiencies shown by the tests detailed above are likely to
underpredict performance for removal of sediment from road runoff.
It is therefore considered that the test methods outlined above are fully representative
of the sediment loading and particle size distribution typically seen on UK developments.
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
21
STORMWATER TREATMENT DEVICES
Net annual performance is the pollutant removal rate of an MTD or SuDS component
over a typical annual period. This can be calculated from the runoff rate distribution
from a site and a pollutant removal rate of a device. This calculation weights importance
of the MTD performance at a given flow rate by the volume of flow that will be
generated at this flow-rate (due to the rainfall distribution).
Σ
n
µAnnual = (V i – Vi – 1 ) * µi
Vn
i1
Where:
µ is the TSS removal rate at a given flow-rate
V is the cumulative runoff volume at a given runoff rate (percentile)
i is a given runoff rate (percentile)
For the SIA, the net annual sediment removal efficiency declared under the BW
CoP and convert directly to a TSS Mitigation Index.
In the case of the BW CoP the test flow-rates have been selected to relate directly to
English rainfall distributions and allow the net-annual removal efficiency to be derived
from the following relationship, which also considers the contribution of pollutant
washout (see BW CoP for full details):
Mout = Vfr 1 C1 + Vfr 2 C2 + Vfr 3 C3 + Vfr 4 C4 + Vfr 5 C5
M
out Total mass of non-retained sediment, in mg
V
fr 1 Supply volume for test flow rate "n", in 1
Cn Averaged sediment concentration in discharge for test flow rate "n", in mg/1
Mout
µ= 1 – –––––– .100
Min
Min Total input mass, in mg, of sediment delivered over all test flow-rates
For example, a sediment removal efficiency of 55% declared under the BW CoP
Assessment method can be converted directly to a TSS Mitigation Index of 0.55.
This mitigation index will apply assuming that the device is sized based on the
declared TFR.
Use of the NJCAT or DIBt methodologies will require the performance to be adjusted
to suit UK rainfall. Use of other methods and, especially, narrow spectrum PSDs (such
as OK-110, which is commonly used in some US territories) are a representative of the
materials commonly found in typical stormwater runoff. Tests carried out on narrow
spectrum PSDs can, however, still be useful and applicable for more detailed design
methods where the precise PSD of the sediment for any given site has been assessed
(see Section 7).
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
22
STORMWATER TREATMENT DEVICES
SECTION 4.3:
METALS REMOVAL AND RETENTION
Chart 4 below shows the percentage of different pollutant types associated with the
dissolved and particulate fractions in Stormwater runoff. The values are derived from
Wilson, Bray & Cooper (2004), Colwill, Peters & Perry (1984) and Crabtree, Dempsey,
Moy, Song & Brown (2008). The values show that, with the exception of Nitrogen, an
excess of 70% of the total mass of priority pollutants are associated with the particulate
material carried within the flow.
100%
90% KEY
80%
% Pollutant Mass
70% Dissolved
60% Particulate
50%
40%
30%
20%
10%
0%
us
nc
ad
er
n
on
ge
pp
or
Zi
Le
PA
rb
ro
ph
Co
ca
it
os
N
ro
Ph
yd
H
Of particular interest here are the metals, of which 75% to 90% are associated with
the particulate material and 25% to 10% are dissolved.
In the UK it can be considered best practice to assume that 75% of the metals are
associated with the particulate phase in the runoff. Where a high proportion of metals
may be present, specific mitigation indices should be derived on a case-by-case basis.
The BW CoP and DIBt test methods only directly measure the removal of the dissolved metal
fraction. In order to provide a mitigation index applicable to total metals it is necessary to
consider both the dissolved and particulate fraction.
The calculation of the metals mitigation index for a particular device can therefore be
calculated as follows (with a worked example shown in Box 4):
Note that for devices tested under the DIBt and NJCAT method, correction of the annual
efficiencies to reflect UK rainfall will be required (see Sections 4.1. & 4.2.).
Whereas a filtration device might be expected to remove 80% of TSS and might achieve dissolved metals efficiencies of 90%
in the BW CoP testing.
Therefore, the metal mitigation index for a filtration device could be as follows:
Particulate fraction reduction = 80% x 75% = 0.6
Dissolved fraction reduction = 90% x 25% = 0.225
Total Metals Mitigation Index = 0.6 + 0.225 = 0.825
The NJCAT test method may be used to derive the particulate fraction reduction but does
not cover dissolved metal removal. Therefore, the dissolved metal removal efficiency for
devices tested under this method would have to be assumed as being zero, unless valid
justification or evidence of higher dissolved pollutant removals can be provided.
SECTION 4.4:
LIQUID HYDROCARBON REMOVAL AND RETENTION
Testing of free phase hydrocarbons is not covered in the BW CoP or NJCAT but can be
assessed under BS EN 858-1:2002 or DIBt.
The hydrocarbon hazard factor used in the SIA was assumed by the authors to represent the
level of hydrocarbon-based pollutants present both in liquid / free-phase form and sorbed to
suspended solids.
Dissolved, emulsified or saponified hydrocarbons are not considered within the SIA.
Similarly, for metals, the calculation of the composite hydrocarbon mitigation index for a
particular device can be calculated as follows (with a worked example shown in Box 5):
For devices assessed under the DIBt method, the net annual removal efficiency can be
converted to a liquid hydrocarbon mitigation index but would need to be corrected to
account for the differences in the German and UK rainfall intensities.
Whereas a filtration device might be expected to remove 80% of TSS and might also achieve free phase hydrocarbon
efficiencies of 80%.
Therefore, the composite hydrocarbon mitigation index for a filtration device in an urban area would be as follows:
Particulate fraction reduction = 80% x 90% = 0.72
Table 6 Order of magnitude of mitigation provided during the site trials recorded in the US BMP database
Further comparison of the median effluent values recorded in the US BMP Database for
the different device types against the Environmental standards provided in Annex 1 of
Chapter 26 of C753 (Table 7), demonstrate that these devices can be expected to reduce
concentration levels in many cases far beyond the desired environmental standard.
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
26
STORMWATER TREATMENT DEVICES
Table 7 Comparison of the median effluent values recorded in the US BMP Database for the different
device types against the Environmental Standards provided in Annex 1 of Chapter 26 of C753
Filter systems can provide both physical interception of particles and sorption
processes. To ensure the efficacy of these mechanisms are similar at all device sizes,
both the flow velocity through the filter and the flow contact time of the filter should
remain similar. This is achieved by scaling filter components based on surface-loading
rate, similar to settling devices, with the exception that the filter depth should (typically)
remain constant across all unit sizes to give a constant contact time. This also prevents
unduly increasing system head loss with increased filter depths.
Where a manufacturer does not conform to these scaling protocols, the manufacturer
should provide test results for multiple unit sizes to verify alternative scaling protocols.
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
28
STORMWATER TREATMENT DEVICES
REFERENCES
Bathi, J. R., Pit, R. E., & Clark, E. S. (2012). Polycyclic Aromatic Hydrocarbons in Urban
Stream Sediments. Advances.
Colwill, D., Peters, C., & Perry, R. (1984). Water Quality of Motorway Runoff
Supplementary Report 823. TRRL.
Crabtree, B., Dempsey, P., Moy, F., Song, M., & Brown, C. (2008). Improved determination
of pollutants in highway runoff – phase 2. Report No.: UC7697. Swindon: WRc.
McPherson, N. (2019). Characterisation of rainfall data for the design of SuDS in
England. School of Water, Energy And Environment. MSc Thesis. Cranfield
University.
Morgan, D., Johnston , P., Gill , L., Collins , P., & Osei , K. (2013). Event-based
characterisation of surface water runoff from an urban residential sewer
separation scheme. 7th International Conference on Sewer Processes and
Networks. Sheffield, UK.: IWA.
Pittner, C., & Allteron, G., (2009). SuDS for Roads. Edinburgh: WSP.
Stone, M., & Marsalek, J. (1996). Trace metal composition and speciation in street
sediment: Sault Ste. Marie, Canada. Water, Air, and Soil Pollution Volume 87,
149-169.
Wilson, S., Bray, R., & Cooper, P. (2004). Sustainable drainage systems. Hydraulic,
structural and water quality advice (C609B). London: CIRIA.
Woods Ballard, B., Wilson, S., Udale Clarke, H., Illman, S., Scott, T., Ashley, R., & Kellagher,
R. (2015). The SuDS Manual. London: CIRIA.
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
32
STORMWATER TREATMENT DEVICES
A mean flow rate resulting from a 1 Tests are carried out on full scale,
year 15-minute (M1:15) rainfall event commercially available devices. For
(determined by HR Wallingford as 27 mm/ filtration devices that consist of multiple
hr as an appropriate UK average) for a cartridges or modular filter components,
stated catchment area shall be declared by tests may be carried out on a single
the manufacturer as the device TFR. This cartridge / component as long as it is
originates from the requirement for the representative of the complete system.
treatment device to treat all rainfall events
with a sub-annual rainfall intensity. Quality Assurance:
The verification process is administered
A2: PROCEDURE FOR OBTAINING by NJCAT, who will appoint a Technical
Expert to assess the quality of data
VERIFICATION OF A STORMWATER submitted by applicants or independent
MTD FROM NEW JERSEY 3rd parties. Tests must either be carried
CORPORATION FOR ADVANCED out at an independent facility or at the
TECHNOLOGY (NJCAT) manufacturer’s facility under direct
supervision of an independent 3rd
The NJCAT administer the verification of MTDs party observer.
based on laboratory and analytical tests prior
to approval of MTDs by the NJDEP. Details Verifications are internally checked
of the verification and approval process, and approved by NJCAT Executive or
along with a full list of verified and approved Technical Director and peer reviewed by
products can be found on the State of New a review panel consisting of 20 persons
Jersey’s Department of Environmental experienced and learned in the science
Protection Treatment Webpage. of stormwater treatment.
140%
KEY
120% BW CoP
NJCAT
100%
DIBt
Cumulative Volume
80%
60%
40%
20%
0%
0 10 20 30 40 50
Rainfall or Runoff Intensity (mm/hr)
Scope:
BS EN 858-1 covers the following areas:
Materials
Water tightness and joints
Structural Stability
Labelling and marking
Determination of Nominal Size
and Class (Oil removal)
Determination of Storage Volumes
(Oil and Sediment)
Closure devices
Risk of infrequent Risk of regular Drainage will also Fuel oils are Very low risk of oil
light contamination contamination of contain dissolved delivered to and contamination
and potential for surface water run oils, detergents or dispensed on site e.g. roof water
small spills only off with oil and/ degreasers such as e.g. retail fuel
e.g. car park or risk of larger vehicle wash water forecourts
spills e.g. vehicle and trade effluents
maintenance e.g. industrial
YES
area, Goods sites
Vehicle parking YES
or vehicle
Source control
manoeuvring5
SUDS must be
considered and
incorporated YES
where suitable Separator not
YES
required
If not suitable YES
By-pass separator Full retention Trade effluents Full retention Clean water should
with alarm separator with must be directed 'forecourt' not be passed
required. alarm required. to the foul sewer.1 separator with through the
Class 1 if discharge It may need to alarm required. separator unless
Class 1 if discharge
to surface water2,3 pass through the size of the
to surface water2 Class 1 if discharge
Class 2 if discharge a separator to unit is increased
to surface water2
to foul sewer.1 Class 2 if discharge remove free oils accordingly
to foul sewer1 before discharge Class 1 or 2 if
to sewer. discharge to foul
sewer1, 4
Source control
SUDS should be
The use of SUDS should be considered at all sites and they should be incorporated where suitable. considered where
SUDS can be used to polish the effluent from these separators before it enters the environment.6 possible
Applicable Devices:
BS EN858:1-2002 is specific to devices designed to separate light liquids, i.e., petrol
interceptors / oil separators from water by means of gravity and / or coalescence.
However, the test methodology can be applied to surface water treatment devices in
order for manufacturers to be able to declare an equivalent performance. It should be
noted that surface water treatment devices can only be classified as petrol interceptors
/ oil separators if they meet all of the requirements of BS EN 858.There are two classes
of separator defined under the standard:
Quality Assurance:
As these systems fall under the Construction Products Regulations, the manufacturer
or agent established in the European Economic Area (EEA) shall prepare and retain
a declaration of conformity which authorises the affixing of Conformité Européene
(CE) marking. Evaluation of conformity is therefore a mandatory requirement, and it is
recommended that this should be undertaken by a 3rd party (i.e., regular factory audits
/ inspections and witnessing of type testing). (CE) marking for the European Union and
The UKCA (UK Conformity Assessed) marking for goods being placed on the market in
Great Britain (England, Wales and Scotland).
Pollutants Covered:
BS EN 858-1:2002 only covers the removal of liquid hydrocarbons (e.g., oil and petrol). It
defines oils as “a light liquid with a density no greater than 0.95 g/cm³, which is actually
or practically insoluble and unsaponifiable”. Dissolved or sediment bound hydrocarbons
are not covered within BS EN 858-1:2002.
The standard does not apply to stable emulsions, solutions of light liquids and water,
grease and oils of vegetable and animal origin.
However, some of the units on the UK market have additional sediment storage capacity
and can retain over 5m3 of sediment. Theoretically, an oil separator could be tested for
sediment removal using the BW CoPractice in order to publish mitigation indices for TSS
alongside those for hydrocarbons.
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
39
STORMWATER TREATMENT DEVICES
Flow Rates:
Within the two classes, there are two types of system based on incoming and outgoing
flows:
Full retention units which are generally sized to fully treat all of the flow generated
by a 65mm/hr rainfall intensity event.
Bypass separators, which are generally sized to treat all flows generated by rainfall
events of up to 6.5mm/hr.
The choice of separator is generally related to the risk associated with spillage events.
A Nominal Size (NS) or Nominal Size before Bypass (NSB) is declared as the highest flow
rate at which the Class I or Class II effluent standard is achieved.
For example:
an NS 10 Class I Full Retention Separator will achieve an effluent concentration
<5mg/l for all flow rates up to and including 10 l/s. Higher flows should not be
connected.
an NSB 10 Class II Bypass Separator will achieve an effluent concentration <100mg/l
for all flow rates up to and including 10 l/s. Higher flows will bypass.
Class 1 oil separators will be expected to achieve an effluent level of less than 5mg/l of
oil under standard test conditions.
Class 2 oil separators will be expected to achieve an effluent level of less than 100mg/l
of oil under standard test conditions.
Annex 1 of Chapter 26 of The SuDS Manual (C753) states that, under normal conditions,
oil levels for urban catchments in the UK are typically 2-5 mg/l for residential areas,
5-25mg/l for general areas and 200 mg/l for main roads (Mitchell, 2005).
Class 1 oil separators (or devices shown to provide an equivalent performance) = 0.8
to 0.975 (based on a reduction level under normal conditions from 25 mg/l or 200
mg/l down to <5mg/l)
Class 2 oil separators (or devices shown to provide an equivalent performance) = 0
to 0.5 (based on a reduction level under normal conditions from 200 mg/l down to
100 mg/l).
It is important to note that these devices will still also provide critical environmental
protection for spillage events.
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
40
STORMWATER TREATMENT DEVICES
The following steps detail the process for deriving device performance values that
correlate to the BW CoP flow-rates from the NJCAT test data listed in Table D.1:
1. The 100% MTFR (Maximum Treatment Flow Rate) for NJCAT is first correlated to
the 1:1 yr 15min rainfall intensity of 27mm/hr (or 75l/s/ha) to adjust the
performance expectations to align with UK rainfall distributions.
This gives the following range of rainfall intensities against the NJCAT MTFR values:
54.8 – 61.8
–––––––––---------- * (11.3 – 6.75) + 61.8 = 57.1
13.5 – 6.75
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
42
STORMWATER TREATMENT DEVICES
3. Where performance data is not available and cannot be linearly interpolated (i.e.,
at the lower flow-rate range) the 25% MTFR performance value should be used.
The 25% MTFR performance is selected for lower flow-rates as a conservative
measure so as not to overestimate device performance:
4. The particle retention efficiency is then taken from the scour concentration measured
in the NJCAT test. In this example case a value of 7mg/l is used, but the NJCAT test
protocol allows up to a 20mg/l washout rate.
5. The annual TSS removal rate (µTSS) can then be calculated from the derived BW CoP
performance values and the washout rate according the to the following equation:
µTSS = Mout
1 – ––––-
Min
Min is the input mass over all flow-rates tested. In this case the calculation can be
simplified by weighting the input concentrations by the number of volume exchanges
during the test:
Min = R 1 * V * C1 + R2 * V * C2 + R3 * V * C3 + R4 * V * C4 + R5 * V * C5
Assessment 1 Assessment 2 Assessment 3 Assessment 4 Assessment 5
Min = 10V * 200 mg.l--1 + 10V * 200 mg.l--1 + 10V * 200 mg.l--1 + 10V * 200 mg.l--1
Assessment 1 Assessment 2 Assessment 3 Assessment 4
Mout is the total mass lost by the system for capture and particle retention tests. In this
case the calculation can be simplified by weighting the outlet concentrations by the input
flow volume exchanges during the test
Mout = R 1 * V * C1 + R2 * V * C2 + R3 * V * C3 + R4 * V * C4 + R5 * V * C5
Assessment 1 Assessment 2 Assessment 3 Assessment 4 Assessment 5
10V * 200 mg.l--1 * (1 _ 0.618) + 10V * 200 mg.l--1 * (1 _ 0.571) + 20V * 7 mg.l--1 = 3290mg.l--1.V
Assessment 3 Assessment 4 Assessment 5
µ CoP = 3290mg.l--1.V
1 – –––––––––-------------- = 58.9%
8000mg.l--1.V
D2 CONCLUSION
The example above shows that for an NJCAT removal rating of 54.74% and a scour
rate of 7mg/l, the derived BW CoP performance rating is 58.9%. This is a slightly higher
performance value than the NJCAT testing and is expected due to the lower rainfall intensity
distributions in the UK.
The BW CoP rating is translated directly into an SIA mitigation index, resulting in a TSS
mitigation index for this device of 0.59.
The treatment device in this example calculation has a treatment flow-rate of 25.2 l.s--1
resulting in an allowable connected area of 0.34 ha (25.2 l.s--1 / 75 l.s--1.ha--1).
Where this supporting calculation is not available for a treatment device, the NJCAT
performance rating may be used as the SIA rating directly, as this is considered a
conservative design approach.
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
44
STORMWATER TREATMENT DEVICES
TEST PART RAINFALL FLOW ADDITION VOLUME DURATION DISCHARGE OF TSS PERMISSIBLE
INTENSITY IN IN L/S OF TSS IN L IN MIN TSS
L/(S X HA) IN KG IN G IN % DISCHARGE
RATE IN %
The following steps detail the process for deriving device performance values that
correlate to the BW CoP flow-rates from the DIBt test data listed in Table E.1.:
1. The data required for the derivations is extracted from Table E.1 and
summarised below:
2. Measured removal efficiencies from the DIBt testing should then be linearly
interpolated (or linearly extrapolated in the case of 31.5 l/s/ha) to match the BW CoP
rainfall intensities:
i) For 5 l/s/ha:
3–0.8
6–2.5 * (5 – 2.5) + 0.8 = 2.4%
7.3–3
25–6 * (10 – 6) + 3 = 3.9%
7.3–3
25–6 * (15 – 6) + 3 = 5.0%
7.3–3
25–6 * (31.5 – 6) + 7.3 = 8.8%
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
46
STORMWATER TREATMENT DEVICES
3. For the washout flow of 110 l/s/ha the 100 l/s/ha concentration measured in the DIBt
test shall be used. In this example, a value of 172mg/l is used. The DIBt test protocol
allows up to an 8% cumulative washout mass across all tests.
4. The annual TSS removal rate (µTSS) can then be calculated from the derived BW CoP
performance values and the washout rate according the to the following equation:
µTSS = Mout
1 – ––––-
Min
Min is the input mass over all five flow-rates tested in the BW CoP assessment process.
In this case the calculation can be simplified by weighting the input concentrations by
the number of volume exchanges during the test:
Min = 10V * 200 mg.l--1 + 10V * 200 mg.l--1 + 10V * 200 mg.l--1 + 10V * 200 mg.l--1
Assessment 1 Assessment 2 Assessment 3 Assessment 4
Mout is the total mass lost by the system for capture and particle retention tests. In this
case the calculation can be simplified by weighting the outlet concentrations by the
input flow volume exchanges during each test:
Where: Coutn is the outlet concentration of TSS, derived from multiplying the inlet
flow volume by the average outlet concentration for each flow-rate tested,
apart from in the case of assessment 5 where the concentration value
is used directly.
Mout = 10V * (200 mg.l--1 * 0.024) + 10V * (200 mg.l--1 * 0.039) + 10V * (200 mg.l--1 * 0.050)
Assessment 1 Assessment 2 Assessment 3
So, the final BW CoP performance rating for TSS removal is:
µ TSS = 3842mg.l--1.V
1 – –––––––––-------------- = 52.0%
8000mg.l--1.V
TEST PART RAINFALL FLOW HYDRO- VOLUME DURATION SAMPLE DISCHARGE PERMISSIBLE
INTENSITY IN L/S CARBONS IN L IN MIN IN G
IN IN G IN MG/L IN G
L/(S X HA)
1 2,5 0.15 136 3.150 350 1a < 0,1 < 0,315 54,4
1b < 0,1 < 0,315 54,4
2 6,0 0,36 136 3.150 146 2a < 0,1 < 0,315 54,4
2b < 0,1 < 0,315 54,4
3 25,0 1,5 136 3.150 35 3a < 0,1 < 0,315 54,4
3b < 0,1 < 0,315 54,4
4 100 6,0 0 5.400 15 4a < 0,1 < 0,540 -
4b < 0,1 < 0,540 -
Total 408 14.850 < 2,97 81,6
* Where measured values are below the detection limit, the detection limit is used.
The following steps detail the process for deriving device performance values that
correlate to the BW CoP flow-rates from the DIBt test data listed in Table E.3. and
flow-rates remain the same as in Table E.2:
1. The data required for the derivations is extracted from Table E.3. and
summarised below:
2. Measured removal efficiencies from the DIBt test should then be linearly interpolated
(or linearly extrapolated in the case of 31.5 l/s/ha) to match the BW CoP rainfall
intensities:
v) For 5 l/s/ha:
0.23–0.23
6–2.5 * (5 – 2.5) + 0.23 = 0.23%
0.23–0.23
6–2.5 * (10 – 6) + 0.23 = 0.23%
0.23–0.23
6–2.5 * (15 – 6) + 0.23 = 0.23%
0.23–0.23
6–2.5 * (31.5 – 6) + 0.23 = 0.23%
3. For the washout flow of 110 l/s/ha the 100 l/s/ha concentration measured in the DIBt
test shall be used. In this example a value of 0.1mg/l is used. The DIBt test protocol
allows up to an 20% cumulative washout mass across all tests.
4. The annual hydrocarbon removal rate (µHC) can then be calculated from the derived
BW CoP performance values and the washout rate according the to the following
equation:
µHC = Mout
1 – ––––-
Min
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
52
STORMWATER TREATMENT DEVICES
Min is the input mass over all five flow-rates tested. In this case the calculation can be
simplified by weighting the input concentrations by the number of volume exchanges
during the test:
Min = 10V * 43.2 mg.l--1 + 10V * 43.2 mg.l--1 + 10V * 43.2 mg.l--1 + 10V * 43.2 mg.l--1
Assessment 1 Assessment 2 Assessment 3 Assessment 4
Mout is the total mass lost by the system for capture and particle retention tests. In this
case the calculation can be simplified by weighting the outlet concentrations by the
input flow volume exchanges during each test:
Where: Coutn is the outlet concentration of hydrocarbons, derived from multiplying the
inlet flow volume by the average outlet concentration for each flow-rate tested,
apart from in the case of assessment 5 where the concentration value is
used directly.
10V * (43.2 mg.l--1 * 0.0023) + 10V * (43.2 mg.l--1 * 0.0023) + 20V * 0.1 mg.l--1 = 6mg.l--1.V
Assessment 3 Assessment 4 Assessment 5
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
53
STORMWATER TREATMENT DEVICES
So, the final BW CoP performance rating for hydrocarbon removal is:
µHC = 6mg.l--1.V
1 – –––––––––-------------- = 99.7%
1728mg.l--1.V
Total 720
* Where measured values are below the detection limit, the detection limit is used.
The following steps detail the process for deriving device performance values that
correlate to the BW CoP flow-rates from the DIBt test data listed in Table E.4.
1. The data required for the derivation is extracted from Table E.4. and
summarised below:
2. Measured removal efficiencies from the DIBt test should then be linearly
interpolated (or linearly extrapolated in the case of 31.5 l/s/ha) to match
the BW CoP rainfall intensities:
14.1–2.0 0.7–0.7
Zn: 6–2.5 * (5 – 2.5) + 2 = 10.6% Cu: 6–2.5 * (5 – 2.5) + 0.7 = 0.7%
x) For 10 l/s/ha:
11.1–14.1 0.7–0.7
Zn: 25–6 * (10 – 6) + 14.1 = 13.5% Cu: 25–6 * (10 – 6) + 0.7 = 0.7%
11.1–14.1 0.7–0.7
Zn: 25–6 * (15 – 6) + 14.1 = 12.7% Cu: 25–6 * (15 – 6) + 0.7 = 0.7%
11.1–14.1 0.7–0.7
Zn: 25–6 * (31.5 – 6) + 14.1 = 10.1% Cu: 25–6 * (31.5 – 6) + 0.7 = 0.7%
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
55
STORMWATER TREATMENT DEVICES
3. For the metal retention under the influence of salt influence, the value measured
for 25 l/s/ha from the DIBt test shall be used.
1. The annual dissolved metals removal rate (µMetals) can then be calculated from the
derived
2. BW CoP performance values and for zinc (µZn) and copper (µCu) according to the
following equation:
µMetals = µ Zn + µCu
1 – –––-------------
2
µZn = Mout
1 – ––––-
Min
µCu = Mout
1 – ––––-
Min
Min is the input mass over all four flow-rates tested. In this case the calculation can be
simplified by weighting the input concentrations by the number of volume exchanges
during the test:
Min = 10V * 6.25 mg.l--1 + 10V * 6.25 mg.l--1 + 10V * 6.25 mg.l--1 + 10V * 6.25 mg.l--1
Assessment 1 Assessment 2 Assessment 3 Assessment 4
Min = 10V * 0.72 mg.l--1 + 10V * 0.72 mg.l--1 + 10V * 0.72 mg.l--1 + 10V * 0.72 mg.l--1
Assessment 1 Assessment 2 Assessment 3 Assessment 4
Mout is the total mass lost by the system for capture and particle retention tests. In this
case the calculation can be simplified by weighting the outlet concentrations by the
input flow volume exchanges during each test:
Where: Coutn is the outlet metal concentration, derived from multiplying the
inlet flow volume by the outlet concentrations for each flow-rate tested.
10V * (6.25 mg.l--1 * 0.127) + 10V * (6.25 mg.l--1 * 0.101) + 10V * 0.077 = 30.07mg.l--1.V
Assessment 3 Assessment 4 Assessment 5
10V * (0.72 mg.l--1 * 0.007) + 10V * (0.72 mg.l--1 * 0.007) + 10V * 0.005 = 0.252mg.l--1.V
Assessment 3 Assessment 4 Assessment 5
So, the final BW CoP performance rating for the metals removal are:
30.07mg.l--1.V 0.252mg.l--1.V
µ Zn = 1 – –––––––----------- = 88.0% µCu = 1 – –––––––----------- = 99.1%
250mg.l .V
--1
28.8mg.l .V
--1
E4 CONCLUSION
The example calculations above show that from the DIBt test data the following BW CoP
removal rates are derived:
µTSS = 52%
µHC = 99.7%
µMetals = 93.6%
The BW CoP removal rates are translated directly into SIA mitigation indices, resulting
in a TSS and hydrocarbon index of 0.52 and 0.997 respectively. The metals removal rate
only relates to the dissolved fraction and therefore must be combined with the solid
removal rate, as described in section 4.3 to calculate the SIA mitigation index for total
metals.
The treatment device in this example calculation has a treatment flow-rate of 6 l.s-1
resulting in an allowable connected area of 0.08 ha (6 l.s-1 / 75 l.s-1.ha-1, where 75 l/s/
ha is the peak annual rainfall rate, equivalent to 27 mm/hr).
HOW TO GUIDE: APPLYING THE CIRIA SUDS MANUAL (C753) SIMPLE INDEX APPROACH TO PROPRIETARY / MANUFACTURED
59
STORMWATER TREATMENT DEVICES
DMRB: Design Manual for Roads and Bridges TFR: Treatment Flow Rate
DIN: Deutsches Institut für Normung UKAS: United Kingdom Accreditation Service
CONTRIBUTORS
Provides a broad range of surface water Stormwater Shepherds is an
management systems designed to provide international not-for-profit committed
the optimum solution in storm water to restoring health to our waterways.
control and sustainable drainage systems. Stop urban and plastic pollution!
This document has been reviewed and is deemed to be in line with CIRIA C753 The SuDS Manual.
The British Water ‘How to guide’ working group are grateful to Bridget Woods Ballard, HR Wallingford, Steve Wilson,
Environmental Protection Group and Mark Goodger Caerphilly County Borough Council for the valuable
input and contribution as reviewers of this code of practice.
Subject as stated below, no responsibility, duty of care or liability whatsoever (whether in contract or tort or otherwise
including, but not limited to, negligence) is or will be accepted by British Water, its officers, employees, agents or
members to any user of this guidance or any other person in connection with or in relation to this guidance. Subject
as stated below, British Water, its officers, employees, agents and members do not accept any responsibility or liability
for any loss or damage caused to any person who acts or refrains from acting as a result of anything contained in
or omitted from this guidance or in reliance on the provisions of or material in this guidance, whether such loss or
damage is caused by negligence or otherwise.
Nothing in this disclaimer shall be construed as excluding or limiting the liability of British Water or any of its officers,
employees, agents or members for death or personal injury resulting from the negligence of such persons or for
fraud. This guidance does not constitute legal, technical or other advice and it should not be regarded as such. Anyone
requiring advice on any of the matters referred to in this guidance, including on how to ensure compliance with any
relevant legal or regulatory requirements, should consult their legal or other appropriate professional advisers.
Nothing in this guidance is intended to be or should be construed as advice on the merits of, or a recommendation in
relation to, any particular product or product provider and no representation is made that any member of British Water
operates or will operate in accordance with this guidance. Each part of this disclaimer shall be construed as a separate
and severable part, and if one or more parts is held to be invalid, unlawful or otherwise unenforceable, the remaining
parts shall remain in full force and effect.
We champion collaboration,
channel innovation and
promote future thinking.
www.linkedin.com/company/british-water
#bwconnect
#bwnetworking www.twitter.com/British_Water