You are on page 1of 2

®

DSEULTRA
®

STARTING
WITH
QUALITY. SPECIFICATION

DC SUPPLY

DSE4410 & DSE4420 DC SUPPLY


AUTO START & AUTO MAINS (UTILITY) FAILURE CONTROL MODULES 8V to 35V Continuous

CRANKING DROPOUTS
Able to survive 0V for 50mS, providing supply
was at least 10V before dropout and supply
recovers to 5V. This is achieved without the
need for internal batteries. LEDs and backlight
will not be maintained during cranking.

MAXIMUM OPERATING CURRENT


TBC

MAXIMUM STANDBY CURRENT


TBC

GENERATOR INPUT RANGE


15V to 333V AC (L-N) absolute maximum
50Hz - 60Hz (min 15V AC)

CHARGE FAIL/EXCITATION RANGE


0V to 35V

MAGNETIC PICKUP

VOLTAGE RANGE
0.5V RMS minimum

The DSE4410 is an Auto Start FEATURES OPERATION FREQUENCY RANGE


Control Module and the DSE4420 is • PC and front panel configurable The module is operated using the 10,000 Hz (max)
an Auto Mains (Utility) Failure CAN and magnetic pick-up versions front STOP/RESET, MANUAL, AUTO
• Six digital inputs OUTPUTS
Control Module for single gen-set and START push buttons.
applications. Both modules have • Six outputs (all six configurable on
CANbus version, four configurable OUTPUT A (FUEL)
been designed to work with Two additional push buttons next to 2 Amp DC at supply voltage
electronic and non electronic on magnetic pick-up version) the LCD screen are provided to
engines providing advanced engine • Automatic mains (utility) supply scroll through the modules’ metering OUTPUT B (START)
monitoring (DSE4420 only) 2 Amp DC at supply voltage
monitoring and protection features. displays and to access the event log.
• Event log
The modules are available in AUXILIARY OUTPUTS C,D
• 50/60 Hz calibration setting
magnetic pick-up and Canbus OVERSPEED PROTECTION 2 Amp DC at supply voltage
• Configurable timers
versions. • Automatic shutdown or warning The engine over speed trip setting
when fault conditions are detected can be calibrated for 50Hz or 60Hz MAINS (UTILITY) SENSING INPUT RANGE
(DSE4420 ONLY)
The modules include a back-lit • Manual and remote start nominal operation During engine
LCD display which clearly show the • Engine pre-heat cranking and for a user configurable 15V to 333V AC (L-N) absolute maximum
status of the engine at all times. • Protected Solid State Outputs time after the engine starts running, 25V to 576V AC (L-L) absolute maximum
They monitor frequency, voltage, (PSS) all alarm conditions are suspended 50Hz - 60Hz (min 15V AC)
current, oil pressure, coolant • Advanced metering capability to allow the engine to reach its
• Front panel mounting DIMENSIONS
temperature and fuel level. The optimum running speed.
modules have also been designed • Front panel programming
• Engine hours counter OVERALL
to display the warning and CONFIGURATION 180mm x 116mm x 42mm
shutdown status of the engine. • LED indicators The modules can be configured 7.1” x 4.6” x 1.7”
• Back-lit LCD display using the front panel or by remote
PANEL CUT-OUT
Both modules include six digital PC using a USB connection lead 154mm x 98mm
BENEFITS and the DSE Configuration Suite PC
inputs and six outputs. Four 6” x 3.9”
• Transfers between mains (utility) software.
outputs are configurable on the
and generator power MAXIMUM PANEL THICKNESS
magnetic pick-up version and six (DSE4420 only) 8mm (0.3”)
are configurable on the Canbus ELECTRONIC ENGINE
• Hours counter provides accurate COMPATIBILITY
version. The modules can either information for monitoring and
be programmed using the front • CAT
maintenance periods • Cummins
panel or by using the DSE • User-friendly set-up and button • Deutz
Configuration Suite PC software. layout. Multiple engine parameters • John Deere
are monitored simultaneously • MTU
• Module can be configured to suit • Perkins
individual applications. Wide range • Scania
of engines can be specified • Volvo
IP65/NEMA 12 rating offers • Generic
advanced resistance to water • Plus additional manufacturers
ingress
• License free PC software
DEEP SEA ELECTRONICS PLC TELEPHONE EMAIL ®
Highfield House +44 (0)1723 890099 sales@deepseaplc.com
Hunmanby Industrial Estate
Hunmanby, North Yorkshire FACSIMILE WEBSITE
YO14 0PH England +44 (0)1723 893303 www.deepseaplc.com

Registered in England & Wales No.01319649 VAT No.316923457

DEEP SEA ELECTRONICS INC TELEPHONE EMAIL


3230 Williams Avenue +1 (815) 316 8706 sales@deepseausa.com
Rockford
IL 61101-2668 USA FACSIMILE WEBSITE
+1 (815) 316 8708 www.deepseausa.com

TESTING STANDARDS
DSE4410 & DSE4420
ELECTRICAL SAFETY/
ELECTROMAGNETIC COMPATIBILITY
TO LOAD
DSE4420 ONLY
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
L1 L1

TEMPERATURE (OPERATING)
BS EN 60068-2-2
L2 L2
Test Ab to +70oC 60067-2-2 Hot
Test Ab to -30oC 60068-2-1 Cold
FROM L3 L3
FROM
GENERATOR MAINS VIBRATION
(UTILITY) BS EN 60068-2-6
N N Ten sweeps in each of three major axes
5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn
APPROPRIATE

APPROPRIATE
MAG PICK UP VERSION ONLY
FUSE

FUSE
2 AMP FUSES

2 AMP FUSES
HUMIDITY
BS 2011 part 2.1 60068-2-30
GBCR MBCR
Test Cb Ob Cyclic
93% RH @ 40oC for 48 hours
*
MPU
SHOCK
CON 1 CON 2
DO NOT
BS EN 60068-2-27
CONNECT
THE
Three shocks in each of three major axes
SCREEN
TO ENGINE
15gn in 11mS
15 16 12 13 14 17 18 19 20
U
L1
N
+ -
GEN VOLTS MPU TESTING STANDARDS
USB
SENDER COMMON

MODULE 4410/4420 PROGRAMMING PORT ENVIRONMENTAL


CRANK
O/P B
O/P A
FUEL

FUEL SENDER

4 FET OUTPUTS
PLANT +VE PLANT +VE ENGINE ECU
BATTERY 6 INPUTS
BS EN 61000-6-2
-VE

+VE

EMC Generic Emission Standard for the


H

1 2 3 4 5 10 11 21 22 23 24 25 26 6 7 8 9 14 12 13 Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the
FUEL

USER CONFIGURABLE +VE OUTPUT E

USER CONFIGURABLE +VE OUTPUT F


USER CONFIGURABLE OUTPUT C GEN BREAKER CLOSE

USER CONFIGURABLE OUTPUT D MAINS BREAKER CLOSE

CONNECT THE
SCREEN TO
Industrial Environment
RECOMMENDED THAT
EMERGENCY STOP BREAKS THE
FUEL AND CRANK OUTPUTS

ENGINE ONLY
USER CONFIGURABLE -VE INPUT E

INSTRUMENTATION AND ALARMS


INPUT A CONFIGURED FOR EMSTOP

USER CONFIGURABLE -VE INPUT F


MIN 2 AMP MAX 20 AMP
ANTI-SURGE FUSE

† The DSE4410 and DSE4420 both provide


USER CONFIGURABLE -VE INPUT B

comprehensive metering and alarm indications:


USER CONFIGURABLE -VE INPUT C

NOTE 1 Generator frequency


Under/over speed
Generator volts (L-L, L-N)
Engine oil pressure
USER CONFIGURABLE -VE INPUT D

Engine coolant temperature


Fuel level (warning or shutdown)
BATTERY

WL
CHARGE
ELECTRONIC ENGINE VERSION ONLY
FUEL ALT
Hours run counter
* †
Battery volts
MBCR NOTE 2. 120 R TERMINATING RESISTOR
CRANK
MAY BE REQUIRED EXTERNALLY Fail to start/stop
SEE ENGINE MANUFACTURERS LITERATURE Emergency stop
GBCR
Failed to reach loading voltage/frequency
Charge fail
Low DC voltage
BATTERY NEGATIVE MUST BE GROUNDED NOTE 1. THESE GROUND CONNECTIONS MUST BE ON THE EN- CAN diagnostics
GINE BLOCK, AND MUST BE TO THE SENDER BODIES. Mains volts 3 phase (DSE4420 only)
TERMINALS SUITABLE FOR 22-16 AWG (0.6mm - 1.3mm )
FIELD WIRING * NOTE 3. MAINS BREAKER CLOSED OUTPUT SHOULD BE AMF indications (DSE4420 only)
CONFIGURED FOR DE-ENERGISE CLOSE MAINS, AND USE THE
TIGHTENING TORQUE = 0.8Nm (7lb-in) NORMALLY CLOSED CONTACTS OF MBCR.

RELATED MATERIALS
TITLE PART NO’S
DSE4410 Manual 057-092
DSE4420 Manual 057-093
DSE Configuration Suite PC Software Manual 057-101
DSE4410 Installation Instructions 053-056
DSE4420 Installation Instructions 053-057
PENDING

DEEP SEA ELECTRONICS maintains a policy of continuous development and reserves the right to
change the details shown on this data sheet without prior notice. The contents are intended for guidance only.

This data sheet is printed on 9lives 55 Silk, which is produced with 55% recycled fibre
from both pre and post-consumer sources, together with 45% virgin ECF fibre.
055-068/11/08 (1)