Professional Documents
Culture Documents
August 2000
PIP VECV1001
Vessel/S&T Heat Exchanger Design Criteria
ASME Code Section VIII, Divisions 1 and 2
PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES
In an effort to minimize the cost of process industry facilities, this Practice has
been prepared from the technical requirements in the existing standards of major
industrial users, contractors, or standards organizations. By harmonizing these
technical requirements into a single set of Practices, administrative, application, and
engineering costs to both the purchaser and the manufacturer should be reduced. While
this Practice is expected to incorporate the majority of requirements of most users,
individual applications may involve requirements that will be appended to and take
precedence over this Practice. Determinations concerning fitness for purpose and
particular matters or application of the Practice to particular project or engineering
situations should not be made solely on information contained in these materials. The
use of trade names from time to time should not be viewed as an expression of
preference but rather recognized as normal usage in the trade. Other brands having the
same specifications are equally correct and may be substituted for those named. All
Practices or guidelines are intended to be consistent with applicable laws and
regulations including OSHA requirements. To the extent these Practices or guidelines
should conflict with OSHA or other applicable laws or regulations, such laws or
regulations must be followed. Consult an appropriate professional before applying or
acting on any material contained in or suggested by the Practice.
This Practice is subject to revision at any time by the responsible Function Team
and will be reviewed every 5 years. This Practice will be revised, reaffirmed, or
withdrawn. Information on whether this Practice has been revised may be found at
http://www.pipdocs.org.
PIP VECV1001
Vessel/S&T Heat Exchanger Design Criteria
ASME Code Section VIII, Divisions 1 and 2
Table of Contents
5.2 MAWP and Coincident Maximum
1. Introduction .................................. 3 Temperature .................................... 10
1.1 Purpose ............................................. 3 5.3 Minimum Design Metal Temperature
1.2 Scope................................................. 3 and Coincident Pressure ................. 11
5.4 External Pressure Design ................ 11
2. References ................................... 4 5.5 Cyclic Service .................................. 11
2.1 Process Industry Practices ................ 4 5.5.1 Number of Cycles........................12
5.5.2 Fatigue Analysis ..........................12
2.2 Industry Codes and Standards .......... 4
5.5.3 Fatigue Loading Data ..................12
2.3 Other References .............................. 5
5.6 Welded Pressure Joint
2.4 Government Regulations ................... 6
Requirements .................................. 12
5.7 Postweld Heat Treatment ................ 14
3. Definitions .................................... 6 5.8 Wind Load ....................................... 15
5.8.1 User Selections from ASCE 7 .....15
4. General ......................................... 7 5.8.2 Determination of Wind-Induced
4.1 Applicable PIP Documents ................ 7 Forces .........................................17
4.2 ASME Code Requirements................ 7 5.9 Seismic Loads ................................. 17
4.2.2 Applicable Code Scope 5.9.1 General Requirements and Data
Exemptions ................................... 7 from ASCE 7 ...............................17
4.2.3 Waste Heat Recovery Vessels ..... 7 5.9.2 Seismic Loads for Ground-
4.3 National Board Registration............... 7 Supported Equipment..................18
4.4 Jurisdictional Compliance .................. 7 5.9.3 Seismic Loads for Structure-
4.5 Units of Measurement ....................... 8 Mounted Equipment ....................18
4.6 Language........................................... 8 5.10 Design Loads and
4.7 Documentation to be Provided to the Load Combinations.......................... 19
5.10.1 Dead Load...................................19
Manufacturer...................................... 8 5.10.2 Operating Live Load ....................19
5.10.3 Pressure Load .............................19
5. Design........................................... 8 5.10.4 Thermal Load ..............................19
5.1 Design Pressure and Temperature ... 8 5.10.5 Test Load ....................................20
5.10.6 Wind Load ...................................20
5.10.7 Seismic Load...............................20
1. Introduction
Note to Readers: This Practice contains design criteria for pressure vessels and shell-and-
tube heat exchangers. Corresponding subject matter for pressure vessels and shell-and-tube
heat exchangers is covered by paragraphs identically numbered. Paragraphs pertaining to
pressure vessels are preceded by [V]. Paragraphs pertaining to shell-and-tube heat
exchangers are preceded by [E]. Paragraphs pertaining to both are preceded by [V/E]. In
addition, ASME Boiler and Pressure Vessel Code, Section VIII, Division 2 requirements are
shown in braces { }.
This Practice should be used for pressure vessels built to Division 1 or Division 2 of the
ASME Boiler and Pressure Vessel Code, henceforth referred to as the Code. Shell-and-tube
heat exchangers are limited to Division 1 in this Practice.
1.1 Purpose
[V] The primary focus of this Practice is to communicate vessel design criteria and
methodology from the User to a Designer. This Practice is also intended as guidance
for the development of purchase specifications covering the construction of new
pressure vessels which meet the philosophy and requirements of Section VIII,
Division 1 {or 2} of the Code.
[E] The primary focus of this Practice is to communicate vessel design criteria and
methodology from the User to a Designer. This Practice is also intended as guidance
for the development of purchase specifications covering the construction of new
shell-and-tube heat exchangers which meet the philosophy and requirements of
Section VIII, Division 1 of the Code and TEMA Standards of the Tubular
Exchangers Manufacturers Association.
1.2 Scope
1.2.1 [V/E] This Practice must be used in conjunction with PIP VEDST003,
PIP VEDV1003, PIP VEFV1100, and PIP VESV1002 in order to comprise a
complete vessel purchase specification.
1.2.2 [V/E] Many recognized and generally accepted good engineering
construction practices are included herein. However, in light of the many
diverse service applications of Code vessels, these practices must be
employed with engineering judgment and supplemented as appropriate with
requirements related to specific materials of construction, service fluids,
operating environments, and vessel geometries. Accordingly, provisions of
this Practice may be overridden or supplemented by an Overlay
Specification.
1.2.3 [V/E] Standardized pre-designed (off-the-shelf) vessels and heat exchangers
are not within the scope of this Practice, but are covered in PIP VESSM001.
2. References
The following documents are only those specifically referenced in this Practice. In
applications where laws or regulations issued by municipal, state, provincial, or federal
authorities cover pressure vessels, those laws or regulations should be reviewed prior to the
initiation of design work since the requirements may be different or more restrictive than
those covered in this Practice. Short titles will be used herein when appropriate.
3. Definitions
Code: ASME Boiler and Pressure Vessel Code Section VIII, Division 1{or 2}. References to
Division 2 are identified in braces { }.
Designer: The party responsible for defining and specifying the mechanical design
requirements (e.g., Vessel Drawing/Data Sheet {User’s Design Specification}) consistent
with User criteria for use by the Manufacturer. The Designer is frequently an engineering
contractor, but could be the User, third party consultant, or the Manufacturer. The Designer
is also considered the thermal Designer with respect to heat exchanger design.
Manufacturer: The party entering into a contract with the Purchaser to construct a vessel in
accordance with the purchase order
National Board: The National Board of Boiler and Pressure Vessel Inspectors, an
organization comprised of chief inspectors of various governmental jurisdictions in the
United States and Canada. Vessels meeting requirements of the Code, except those stamped
with the Code “UM” symbol, may be registered with the National Board.
User: The party responsible for establishing construction criteria consistent with the Code
philosophy and service hazards. “User” refers to the owner and/or operator of the equipment.
Vessel: This term may be used as a non-specific reference to a pressure vessel or a shell-and-
tube heat exchanger.
4. General
4.6 Language
[V/E] The language of all documents shall be either English or include the English
translation.
5. Design
• Normal shutdown
• Startup following a turnaround or an emergency shutdown
• Cleaning, steam out, and decontamination
• Upset conditions
• Environmental restraints on relief venting
• [E] Tube failure [Code Paragraph UG-133(d)]
[V/E] The margin above the maximum anticipated operating pressure selected to
establish the design pressure and coincident maximum metal temperature must be
carefully considered for each vessel component as a function of the overall objective
with respect to pressure relief, coupled with the uncertainties in determining what
actual pressures will be developed. For example, where minimization of severely
flammable or acutely toxic environmental hazards is a controlling design
requirement, the establishment of a design pressure and associated Maximum
Allowable Working Pressure (MAWP) {MAWP replaced by Design Pressure in
Division 2, AD-121.1} that will provide containment without actuation of the
pressure relief device may be a consideration.
[V/E] As will be noted with reference to Appendix A, this margin is also dependent
upon the operational characteristics of the pressure relief device. For example, when
the maximum anticipated operating pressure of a gas/vapor service can be identified
with confidence, and when metal-seated, direct spring-operated valves will be used,
the design pressure is frequently established by dividing the maximum anticipated
operating pressure by 0.90. However, when a pilot-operated pressure relief device is
used, the design pressure is sometimes established by dividing the maximum
anticipated operating pressure by a factor as high as 0.98.
[V/E] Refer to the Overlay Specification for any margins to be applied to the
maximum operating pressure(s) and coincident temperature(s).
[V/E] Also use of Code Case 2211, entitled “Pressure Vessels with Overpressure
Protection by System Design, Section VIII, Divisions 1 and 2,” may be an
appropriate option. Note that prior jurisdictional acceptance may be required and that
this Code Case Number shall be shown on the Manufacturer’s Data Report.
Likewise, with permission from the authority having legal jurisdiction over the
installation of pressure vessels (should one exist), the advantages of using the
provisions of Code Case 2203, entitled “Omission of Lifting Device Requirements
for Pressure Relief Valves on Air, Water over 140° F, or Steam Service, Section
VIII, Divisions 1 and 2,” should be considered.
[E] The shell side and tube side design pressures and temperatures shall be reviewed
to determine extreme conditions that may be encountered. During transients (startup,
pressure relief, or shutdown, etc.), the shell side or tube side fluid may be absent, not
flowing, or auto-refrigerating with design pressure in the other chamber. For
components subjected to both shell side and tube side conditions, the more severe
condition shall control. The following additional conditions shall be considered:
5.1.1 [E] The exchanger shall be designed for full pressure on either side with
atmospheric (or full vacuum if specified) on the other side. If an exchanger
is designed for differential pressure, the Data Sheet and nameplate shall so
indicate.
5.1.2 [E] Fixed tubesheet exchangers cannot generally be operated at the
coincident nameplate temperature-pressure conditions. The basis for
differential thermal expansion used in the design shall be defined and shall
become a fabrication drawing requirement. (See PIP VEDST003.)
frequently fall into this category. The following guidelines {AD-160} are
recommended as a starting point when determining if cyclic analysis will be
required. The need for a fatigue analysis by the Manufacturer shall be stated on the
Data Sheet by the Designer.
5.5.1 Number of Cycles {See AD-160.2}
[V/E] Code vessels should be considered to be in cyclic service when the
total number of cycles in the following three items (1.+2.+3.) exceed 1000
cycles in the desired design life of the vessel:
1. The expected number of full range (design) pressure cycles, including
startups and shutdowns
2. The expected number of operating pressure cycles in which the range
of pressure variation exceeds 20% of the design pressure
3. The expected number of thermal cycles where the metal temperature
differential between any two adjacent points exceeds 50ºF (For a
definition of adjacent points, see Code Section VIII, Division 2,
Paragraph AD-160.2, footnote 3.)
5.5.2 Fatigue Analysis
[V/E] In cases where the preliminary guidelines in Section 5.5.1 indicate that
a fatigue analysis may be required, the rules in Code Section VIII, Division
2, Paragraph AD-160, “Fatigue Evaluation,” are recommended for use with
sound engineering judgment as a guideline for establishing further action. A
fatigue analysis shall always be performed for agitator mounting nozzles and
their attachment to the vessel. (See Sections 5.12.2 and 5.14.1.)
5.5.3 Fatigue Loading Data
[V/E] The applicable fatigue loading conditions shall be stated on
PIP VEDV1003 and PIP VEDST003.
5.7.2 [V/E] PWHT provides reduction of residual stresses due to forming and
welding and softens heat-affected zones. Some steels can be damaged within
certain temperature zones below PWHT temperature. A materials engineer
shall be consulted regarding the need for PWHT beyond the requirements of
the Code and dependent on service conditions. The resulting
recommendation shall be included on the Data Sheet, PIP VEDV1003, or
PIP VEDST003.
Vessel Description Cf
A. For all horizontal vessels and for vertical 0.5
vessels having an h/D ratio not greater
than 1
B. For vertical vessels having an h/D ratio See Table 6-7 for
greater than 1 (applies to that portion moderately smooth
of vessel without spoilers) surfaces
C. For that portion of vertical vessels See Table 6-7 for very
provided with spoilers as recommended rough surfaces
in Section 5.11.2.1 or 5.11.2.2 of this
Practice
0.06 sec, storage tanks, and irregular equipment structures. The designer
shall be responsible for such special analysis and design requirements.
5.9.3 Seismic Loads for Structure-Mounted Equipment
[V/E] For equipment mounted in a structure above grade, the governing
equation for seismic force is:
Fp = 4.0 Ca Ip Wp
where:
Ca = seismic coefficient
Ip = component importance factor = 1.5
Wp is the operating weight of the equipment.
Fp is the horizontal seismic force applied at the center of gravity of the
equipment and in the direction causing the highest stresses.
If the above method of calculating the floor-mounted equipment seismic
force is too conservative, the alternate method may be used. See equations
9.3.1.2-2 through -5 in ASCE 7. Note that this method requires the
calculation of the fundamental period T of the structure that the equipment is
mounted in.
5.13.3.3 [V/E] Design flanges not only for the design pressure, but also for
other loadings that will be applied to the joints during the project
life (e.g., externally applied bending moment and axial thrust
loadings.) [See Section 5.13.3.1(d).]
5.13.3.4 [V/E] Select flange thickness so that, considering all loadings that
will be applied [see Section 5.13.3.1(d)], the Rigidity Index as
defined in Appendix S-2 {Appendix M} of the Code is ≤ 1.0,
based on the recommended value of KL of 0.2 or K1 of 0.3, as
applicable.
5.13.3.5 [V/E] Flange bolts shall not be less than 3/4 inch nominal
diameter. Flange bolt holes shall be 1/8 inch larger than the
diameter of the bolts.
5.13.3.6 [V/E] Nubbins are permitted only by agreement with the User.
5.13.4 Custom-Designed Lap Joint Flanges
[V/E] Practices relative to lap joint flanges that experience has shown will
result in a level of damage tolerance, leak-tightness integrity, and gasket
replacement capability equivalent to the welding neck style are as follows:
flange and the nominal diameter at the toe of the lap ring attachment
weld at the back of the lap ring shall be 1/8 inch (+1/16 inch, -0).
5.13.5 Lap Joint Flanges NPS 24 and Smaller
[V/E] When ASME B16.5 lapped flanges are specified, the User is
cautioned to make the checks/inspections necessary to ensure that the
flanges actually are ASME B16.5 lapped flanges.
[V/E] For certain of the smaller sizes in each pressure class, the length-
through-hub (dimension Y) of the slip-on flange and the lapped flange are
the same. (This is true through NPS 12 for Class 150, through NPS 8 for
Class 300, etc.) Accordingly, since the slip-on flange is more commonly
used, flange manufacturers typically modify the small slip-on flanges to
make the lapped style. This modification consists of machining the corner
radius of the bore as specified in ASME B16.5 (dimension r) and removing
the raised face. The latter change is permitted in Interpretation 3-5 of
ASME B16.5, provided the resulting flange meets the requirements for a
lapped flange, including flange thickness, or a length-through-hub
dimension.
[V/E] The caution is focused on larger sizes where the length-through-hub
(dimension Y) for lapped flanges is greater than that of the slip-on style.
Some flange manufacturers have furnished the modified versions of these
slip-on flanges as lapped flanges, calling them short-hubbed lapped flanges.
These flanges do not comply with ASME B16.5 and, as a result, do not
comply with either the Code or OSHA when Code construction is mandated.
The strength of the short-hubbed flanges cannot generally be justified by
Code calculations.
5.13.6 Slip-on Flanges
[V/E] Slip-on flanges are limited to use under the following conditions:
1. [V/E] ASME B16.5 standard forged flanges for design pressures
and coincident temperatures not exceeding the pressure-
temperature ratings for Class 150 flanges as specified in
ASME B16.5, except that the maximum design temperature shall
not exceed 650°F
2. [V/E] {Not Division 2 Applicable} Custom-designed flanges per
Code Figure 2-4(8), (8a), (9), (9a), (10), or (10a) for design
temperatures not exceeding 650ºF; and for flange thickness not
exceeding 3 inches
3. [V/E] Corrosion allowance does not exceed 1/16 inch (1.6 mm)
4. [V/E] Carbon or low-alloy steel flanges attached to solid high-
alloy necks are limited to design temperatures no higher than
450ºF, unless a higher temperature is justified by a complete stress
analysis and approved by the User
5. [V/E] MDMT is not colder than minus 20ºF for carbon and low-
alloy steels
6. [V/E] Vessel is not for lethal service (Code requirement)
7. [V/E] Vessel or nozzle is neither for cyclic pressure or
temperature service nor subjected to cyclic loadings from
associated equipment
8. [V/E] For vessels not in hot hydrogen service (Hot hydrogen
service is defined as hydrogen partial pressure exceeding 100 psia,
with a corresponding coincident temperature exceeding 400ºF.)
5.13.7 Threaded and Socket Weld Flanges
[V/E] Threaded and socket weld flanges shall not be used. (See Section
5.13.9.)
5.13.8 Flange Facing and Surface Finish
5.13.8.1 [V/E] Flanges, except for lapped flanges, shall either have a raised
face or shall have a construction that provides outer confinement
to the gasket if required by Section 5.13.8.3. The height of a raised
face shall be 1/16 inch or a greater height when required by
ASME B16.5 or ASME B16.47, or as specified by the User. For
some User-designated services, flat-face flanges or ring joint
facings may be required.
5.13.8.2 [V/E] Standard flanges and factory-made lap joint stub ends shall
have a surface finish in accordance with ASME B16.5 or
ASME B16.47, as applicable. For standard flanges in services
requiring special consideration (e.g., hydrogen) and for custom
flanges and shop-fabricated lap joint stub ends, the gasket contact
surface shall have either a serrated concentric or serrated spiral
finish having a resultant surface finish from 125 - 250 µ inch
average roughness.
5.13.8.3 Confined Joints
[V/E] For any of the following conditions, gasketed flange joint
designs (body flange and nozzle joints) larger than NPS 24 shall
provide outer confinement of the gasket:
• Design pressure 300 psi or higher
• Design temperature hotter than 500°F
• MDMT colder than minus 20°F
• Cyclic pressure or temperature service
• Joint requires metallic gasket
Note: Robust metal reinforced gaskets (e.g., spiral-wound with
outer gauge ring, double-jacketed corrugated metal gaskets with
a corrugated metal filler, etc.) are exempted.
5.14 Nozzles
5.14.1 [V/E] Nozzles supporting agitators, pumps, or other mechanical equipment
shall be suitably reinforced to withstand the mechanical loadings specified
by the device manufacturer. Likewise, nozzles for pressure relief devices
shall be designed and reinforced for thrust reaction. Use of heavier nozzle
necks, conventional reinforcing pads with properly contoured fillet welds,
and formed heads of appropriate stiffness are the elements that result in a
design suitable for an infinite number of cycles. Gussets shall not be used to
strengthen, stiffen, or reinforce nozzles, unless demonstrated by calculations
to be suitable for the specified cyclic life or thermal condition.
For such nozzles, consideration shall be given to the dimensional
requirements of the device as supplied by the device manufacturer (e.g.,
tolerances).
5.14.2 [V/E] Surface-attached nozzles as shown in Code Figures UW-16.1(a),
(a-1), (a-2), (a-3), and (b) {Figures 610.1(a) and (b)}, and those with internal
reinforcing pads, are not permitted.
5.14.3 [V/E] Nozzle locations (including manways) and their reinforcing pads, if
necessary, shall preferably not interfere with or cover pressure vessel weld
seams [see PIP VESV1002, Section 5.2.2(c)]. When located in heads other
5.15 Manways
[V/E] The location, quantity, and size of manways and internal ladder rungs shall be
specified to ensure that all interior areas are accessible as required. Minimum
requirements regarding manway and inspection openings are covered in Code
Paragraph UG-46 {Article D-10}, “Inspection Openings.”
5.15.1 [V/E] Service conditions, size, and configuration of the vessel may justify
manways other than (or in addition to) those mandated by the Code.
5.15.1.1 [V] Vessels with mixers/agitators shall be provided with at least
one manway that does not require removal of the mixer/agitator.
5.15.1.2 [V] Unless other provisions (e.g., body flanges) are made for tray
removal, trayed towers shall have at least two manways, one at the
top and one at the bottom. Additional manways shall be as
specified by the User.
5.15.2 [V/E] Manways shall be usable from a ladder, platform, or grade.
5.15.3 [V] Vessels smaller than 3 feet ID that are subject to internal corrosion,
erosion, or mechanical abrasion shall be equipped with inspection openings
as described in Code Paragraph UG-46 {Article D-10}. Vessels in this size
category may justify the use of body flanges.
5.15.4 [V] Vessels 3 feet ID and larger that are subject to internal corrosion,
erosion, or mechanical abrasion shall be equipped with one or more flanged
and blinded manways.
5.15.5 [V/E] The nominal recommended manway size is NPS 24 with a finished ID
not less than 23 inches. Manways shall not be smaller than NPS 18 or have a
finished ID of less than 17 inches. Larger diameter manways should be used
to satisfy additional needs such as, but not limited to, installation of
internals/catalyst, packing, maintenance requirements, long projection due to
thick insulation, etc.
5.15.6 [V/E] To provide utility for entry and exit, vessel geometry, and location of
access platforms shall be considered when locating manways. Internal
ladders or grab rungs may be needed at manway locations for entry and exit.
5.15.7 [V/E] Provisions shall be made for lifting devices (fixed or portable) at
manways for personnel rescue as described in OSHA 29 CFR 1910.146.
5.15.8 [V/E] Manways shall be equipped with either a davit or a hinge to facilitate
handling of the blind flange. Manways oriented with the nozzle neck axis in
a horizontal plane shall be equipped with a hinge in accordance with
PIP VEFV1116 or a davit in accordance with PIP VEFV1117. Attach the
davit-socket bracket to the nozzle neck when lap joint flanges are employed.
Manways on the top of vessels oriented with a vertical nozzle neck axis shall
be equipped with a davit in accordance with PIP VEFV1118.
5.15.9 [V/E] Consideration may be given for use of suitable process connections as
manways and handholes. (Consider both size and location.)
5.15.10 [V/E] When approved by the User, flanges and their pressure-retaining
covers for manways may be custom-designed, with due consideration being
given to providing a Rigidity Index in accordance with the recommendations
in Code Appendix S-2 {Appendix M}. A detail sketch describing the flange,
cover, bolting, and gasket, as well as Code calculations supporting the
design, shall be provided.
Higher values may be used consistent with the ulitmate strength chosen (if
known) and other provisions of state-of-the-art concrete foundation design.
The design loadings for anchor bolts embedded in concrete may be
determined by either the simplified method (neutral axis of bolt pattern at
centerline of vessel) or the shifted neutral axis method (See Section 2.3,
Brownell and Young). However, the use of the latter method is
recommended for large vertical vessels because of the economic benefit.
Note: The neutral axis shift method does not apply for vessels supported
by steel structures.
5.16.5 [V/E] Anchor bolts embedded in concrete foundations shall be zinc-coated
(hot dip galvanized or mechanically zinc-coated) so that the addition of a
corrosion allowance is not required.
5.17 Internals
[V/E] Functional design of trays and other removable internals are outside the scope
of this Practice.
5.17.1 [V/E] Removable internals shall be sized to pass through designated vessel
openings. On vessels with internals where a vessel manway is not located in
the top head, internal rigging clips shall be provided to facilitate handling of
the internals.
5.17.2 [V/E] Vessel internals such as distributors, dip tubes, baffles, and
thermowells should not be located near manways in a manner that would
interfere with personnel access or rescue. Special consideration should be
given to the area directly below manways and to head knockers above
manways. In some circumstances, the addition of grab rungs may be
necessary.
5.17.3 [V/E] In services the User has defined as corrosive, welding of vessel
internals attached to a pressure boundary component shall be continuous on
all surfaces in order to eliminate corrosion pockets. All seams and corner
joints shall be sealed.
5.17.4 [V/E] Internal piping and baffles shall be mounted in a manner that will not
unduly restrict thermal expansion. Consideration shall be given to vibration
and the possibilities of fatigue failure. Where vibration and fatigue are
governing design requirements, internal non-pressure parts (e.g., baffles that
may be subject to vibration or cyclic loading) shall be continuously welded.
5.17.5 [V/E] Internal bolting in vessels, especially where vibration is expected
(e.g., where agitators are installed), shall either be double nutted, tack-
welded to the clip (or baffle), or have a lock wire placed in the nut/bolt or
other supports.
5.17.6 [V/E] The nominal chemical composition of internal non-pressure piping
shall be compatible with that of the inside surface of the vessel and the
process. Flanges for internal non-pressure piping may be fabricated from
plate but must conform to ASME B16.5 Class 150 bolting dimensions.
5.17.7 [V/E] Vessel internals and all portions of each vessel shall be self-draining
to ensure complete elimination of liquid from the vessel when drained.
5.17.8 [V/E] For integrally clad and/or weld overlayed vessels, lightly loaded (as
defined in Code Section VIII, Division 2, Paragraph AD-912, footnote 4)
supports, such as those for trays, baffles, etc., may be welded directly to the
alloy clad or weld overlay. Where supports are carrying an appreciable load
(> 25% of the allowable stress for fillet welds), such as packing bed support
rings, the Designer shall determine and specify whether the support shall be
welded directly to the base metal.
5.20.4.2 [E] Two phase flows, in general, are to have the hot stream
(condensing) flow downward and the cold stream (boiling)
upward. Exceptions are “falling film evaporation” and “reflux
condensation,” which will have downward liquid and upward
vapor flows. Mist flow may warrant flow in either direction.
5.20.4.3 [E] Gases may flow down or up consistent with the Log Mean
Temperature Difference (LMTD) calculation.
5.20.5 Tube Selection
(See Section 5.19.1 for additional information.)
5.20.5.1 Diameter
[E] The preferred tube size for use in heavy tube side fouling (dirty
service) (0.002 hr ft2 °F/BTU or greater) is 1 inch OD. For light
tube side fouling (clean service), 3/4 inch OD tubes are preferred.
5.20.5.2 Length
[E] Specify commonly used tube lengths, if practical.
5.20.5.3 [E] Recommended Tubewall Thickness
• Tube side inlet temperatures are well above the shell side
stream pour-point temperature.
• Surface tension will not “hold” the condensate in the fins.
• Tube external corrosion is not expected.
5.20.6 Bundle Design and Tube Layout
5.20.6.1 Tube Layout
5.20.6.1.2 [E] Triangular pattern can be used for clean shell side
services, independent of whether the bundle is
removable or not. An expanded pitch triangular design
can be used in dirty services only when sufficient
cleaning lanes are provided by the tube layout and
when approved by User.
5.20.6.2 Baffles
5.20.6.2.3 [E] Special baffle designs (e.g., rod, disk and donut,
longitudinal, spiral baffles, etc.) require User’s
approval.
5.20.6.2.5 [E] Tie rods and spacers: Peripheral tie rods and
spacers for positioning baffles shall be located so that
the outside of the spacers coincides with the outer
periphery of the baffles. The ID of the spacer shall not
be greater than the OD of the tie rod plus 1/8 inch.
5.20.7 Thermal Performance
5.20.7.1 [E] Condensing Heat Transfer
For accurate condenser design, the temperature difference should
be calculated incrementally. The temperature and heat transfer of
the condensing vapor mixtures will vary with the fraction
condensed. Even with pure components, the condensing
temperature will not be constant if there is significant pressure
drop. The effect of delta P on delta T should be checked, especially
if the overall delta T is small.
For rough calculations, a straight line temperature may be used for
the condensing zone. For final design, the results should always be
checked using stepwise increments. When the vapor entering a
condenser is superheated (temperature above the dew point) or
when the condensate is subcooled (temperature below the bubble
point), special considerations are required.
If the temperature of the heat transfer surface (tube wall
temperature) encountered is less than the dew point of the vapor,
the vapor will begin to condense on contact and a wet wall
condition will occur. In such cases, a condensing heat transfer
coefficient is used (just as in the case of saturated vapor) and the
Mean Temperature Difference (MTD) is based on the dew point
temperature rather than the superheated vapor temperature.
If the tube wall temperature is greater than the dew point of the
vapor, a dry wall condition occurs. In such cases, the single phase
gas heat transfer coefficient is used and the actual vapor
5.20.9 Vibration
[E] The Designer shall include a check for flow-induced tube vibration. The
method of vibration analysis shall be acceptable to the User. The vibration
analysis shall consider, as a minimum, vortex shedding, fluid elastic
instability, turbulence excitation (buffeting), and acoustic resonance.
Generally, the natural frequency (or harmonics) of the tubes should not be
within 20% of the predicted flow vibration frequency produced by any
excitation mode, unless the vibration amplitude is within accepted practices.
6. Materials
• Addition of a welded wear plate with the intent that the plate is
sacrificial
Note: Use caution when using this method in hydrogen service.
• Internal refractory linings, if appropriate
• Increase of inlet nozzle size
6.4 Gaskets
[V/E] In no case shall the nominal thickness of sheet or laminate service gasketing
be greater than 1/16 inch.
7. Testing
[V/E] All new pressure vessels shall be pressure tested prior to being placed in service. The
following paragraphs provide guidance and references to design and execution
considerations relative to hydrostatic and pneumatic pressure testing.
8.4 Welds
[V/E] Shear stresses for fillet welds on the lifting attachments to the vessel
shell/head shall not exceed 0.55 times the Code-allowable stress {design stress
intensity} at 100ºF for the material selected.
General Considerations
for
Pressure Relief Valve Application
PIP VECV1001 REVISION
Vessel/S&T Heat Exchanger Design Criteria August 2000
ASME Code Section VIII, Divisions 1 and 2
A general comparison of operational characteristics is given for the different types of pressure relief
valves in common industrial use. The influence on operating margin, from set pressure, is
considered.
The point where leakage begins to be a concern when using direct spring-operated valves
depends on the disk seat design. Metal-to-metal contact seats will begin to leak at about 90% of
set pressure. O-ring soft seat disk type direct spring-operated valves will not leak below 95% of
set pressure. Pilot-operated valves will not leak below 98% of set pressure. The recommended
maximum equipment operating pressure is slightly below, but many times considered to be equal
to, the start-to-leak limit for the valve.
Welded Pressure
Joint Requirements Form
PIP VECV1001 REVISION
Vessel/S&T Heat Exchanger Design Criteria August 2000
ASME Code Section VIII, Divisions 1 and 2
DESIGN BASIS
SHELL AND CONE THICKNESS BASED ON: DISHED HEAD THICKNESS BASED ON:
JOINT EFFICIENCY E = _________ JOINT EFFICIENCY E = _________
HEAD -TO-SHELL
CATEGORY B TYPE NO. (1) OF TABLE UW-12
OTHER
BODY FLANGES
CATEGORY C
NOZZLE FLANGES FIGURE 2-4
GENERAL NOTES:
1) Unless otherwise indicated, all references on this form are to ASME Code paragraphs, tables, and figures. All nondestructive examination
shall be performed per Code methods.
2) Joints supplied shall be either detailed or identified by use of standard AWS welding symbols on the vessel Manufacturer's drawings.
3) Permanent weld joint backing strips are not permitted.
4) Separate internal nozzle reinforcing plates are not permitted.
5) The flat plate from which formed heads are to be made shall be either seamless or made equivalent to seamless in which all Category A
welds are Type (1) and fully radiographed per UW−51 before forming. After forming, the spin hole, if it remains in the final construction, shall
be closed with a metal plug which is butt-welded in place with the weld meeting the Category A weld joint requirements shown in the table.
6) Category D welds shall be per Figure UW-16.1 using full penetration welds through vessel wall and through inside edge of external
reinforcing plates, when used. Nozzle necks designated to extend beyond the inside surface of the vessel wall shall have a fillet weld at the
inside corner.
WELDED PRESSURE
JOINT REQUIREMENTS
ITEM NUMBER: ____________________________________ PRESSURE VESSELS
EXCLUDING HEAT EXCHANGERS
PAGE 1 OF 2
A. Full radiography shall be per Paragraph UW-51. For welded pipe components, this applies
only to Categories B and C butt joints. For exclusions, see Paragraph UW-11(a)(4).
B. Spot radiography shall be per Paragraph UW-52. For welded pipe components, this applies
only to Categories B and C butt joints. For exclusions, see Paragraph UW-11(b).
C. Spot radiography shall be per Paragraph UW-52. Rules of UW-11(a)(5)(b) must be satisfied.
The Manufacturer is cautioned to select the appropriate increments of weld for establishing
the spot radiography requirements for the vessel. [See UW-52(b)(4).]
General Note: Notes D through H are examples of user options that are sometimes
selected for critical services. Other options may be provided as appropriate.
D. When joint thickness exceeds 2 inches, examine (using MT or PT) the root pass after back-
chipping to sound metal and all accessible surfaces of completed welds of Categories A, B,
C, and D butt type joints.
E. When design is based on a joint efficiency of 1.00, examine (using MT or PT) Categories C
and D non-butt type joints after back-chipping or gouging root pass to sound metal and
accessible surfaces of completed weld.
F. When nozzles are attached with a full penetration weld through the nozzle wall, the cut edge
of the opening in vessel walls thicker than 1/2 inch shall be examined using MT or PT. The
examination shall be made before nozzle attachment and a re-examination shall be made
after attachment, when accessible.
G. Examination (using MT or PT) of completed welds shall be made after PWHT for the
following:
1. Vessels or vessel parts for which impact testing is required
2. Welds joining non-impact tested low-alloy steels thicker than 1-1/4 inches
3. Welds joining carbon steels thicker than 2 inches
4. When required by Code
H. Butt welds exempt from radiography by Paragraph UW-11(a)(4) shall have accessible
surfaces of completed welds MT or PT examined. (Only applies to designs employing impact-
tested steels when Category A joints are based on a joint efficiency of 1.00.)
Item Number:
PAGE 2 OF 2
EXAMPLE
DESIGN BASIS
SHELL AND CONE THICKNESS BASED ON: DISHED HEAD THICKNESS BASED ON:
JOINT EFFICIENCY. E = __0.85_______ JOINT EFFICIENCY. E = __0.85_______
HEAD -TO-SHELL
CATEGORY B TYPE NO. (1) OF TABLE UW-12 B
OTHER
B
BODY FLANGES
CATEGORY C --
GENERAL NOTES:
1) UNLESS OTHERWISE INDICATED. ALL REFERENCES ON THIS FORM ARE TO ASME CODE PARAGRAPHS.
TABLES AND FIGURES. ALL NONDESTRUCTIVE EXAMINATION SHALL BE PERFORMED PER CODE METHODS.
2) JOINTS SUPPLIED SHALL BE EITHER DETAILED OR IDENTIFIED BY USE OF STANDARD AWS WELDING
SYMBOLS ON THE VESSEL MANUFACTURER'S DRAWINGS.
3) PERMANENT WELD JOINT BACKING STRIPS ARE NOT PERMITTED.
4) SEPARATE INTERNAL NOZZLE REINFORCING PLATES ARE NOT PERMITTED.
5) THE FLAT PLATE FROM WHICH FORMED HEADS ARE TO BE MADE SHALL BE EITHER SEAMLESS OR MADE
EQUIVALENT TO SEAMLESS IN WHICH ALL CATEGORY A WELDS ARE TYPE (1) AND FULLY RADIOGRAPHED
PER UW−51 BEFORE FORMING. AFTER FORMING, THE SPIN HOLE, IF IT REMAINS IN THE FINAL
CONSTRUCTION, SHALL BE REPAIRED WITH A METAL PLUG THAT IS BUTT-WELDED IN PLACE WITH THE
WELD MEETING THE CATEGORY. A WELD JOINT REQUIREMENTS SHOWN IN THE TABLE.
6) CATEGORY D WELDS SHALL BE PER FIG. UW-16.1 USING FULL PENETRATION WELDS THROUGH VESSEL
WALL AND THROUGH INSIDE EDGE OF EXTERNAL REINFORCING PLATES WHEN USED. NOZZLE NECKS
DESIGNATED TO EXTEND BEYOND THE INSIDE SURFACE OF THE VESSEL WALL SHALL HAVE A FILLET WELD
AT THE INSIDE CORNER.
WELDED PRESSURE
JOINT REQUIREMENTS
ITEM NUMBER: ________PIP 123456___________________ PRESSURE VESSELS
EXCLUDING HEAT EXCHANGERS
DRAWN BY CHECKED BY DATE DRAWING NUMBER
VESSEL ASSEMBLY DWG.: ___PIP 123456______________
PAGE 1 OF 2
Welded Pressure
Joint Requirements Form
PIP VECV1001 REVISION
Vessel/S&T Heat Exchanger Design Criteria August 2000
ASME Code Section VIII, Divisions 1 and 2
SHELL HEAD-TO-SHELL
CATEGORY B TYPE NO. (1) OF TABLE UW-12
SIDE OTHER
TUBE HEAD-TO-CHANNEL
CATEGORY B TYPE NO. (1) OF TABLE UW-12
SIDE OTHER
CATEGORY C
GENERAL NOTES:
1) Unless otherwise indicated, all references on this form are to ASME Code paragraphs, tables, and figures. All nondestructive examination shall
be performed per Code methods.
2) Joints supplied shall be either detailed or identified by use of standard AWS welding symbols on the vessel Manufacturer's drawings.
3) Permanent weld joint backing strips are not permitted.
4) Separate internal nozzle reinforcing plates are not permitted.
5) The flat plate from which formed heads are to be made shall be either seamless or made equivalent to seamless in which all Category A welds
are Type (1) and fully radiographed per UW−51 before forming. After forming, the spin hole, if it remains in the final construction, shall be
closed with a metal plug which is butt-welded in place with the weld meeting the Category A weld joint requirements shown in the table.
6) Category D welds shall be per Figure UW-16.1 using full penetration welds through vessel wall and through inside edge of external reinforcing
plates, when used. Nozzle necks designated to extend beyond the inside surface of the vessel wall shall have a fillet weld at the inside corner.
WELDED PRESSURE
JOINT REQUIREMENTS
ITEM NUMBER: ____________________________________ SHELL AND TUBE HEAT EXCHANGERS
PAGE 1 OF 2
B. Spot radiography shall be per Paragraph UW-52. For welded pipe components, this applies
only to Categories B and C butt joints. For exclusions, see Paragraph UW-11(b).
C. Spot radiography shall be per Paragraph UW-52. Rules of UW-11(a)(5)(b) must be satisfied.
The Manufacturer is cautioned to select the appropriate increments of weld for establishing
the spot radiography requirements for the vessel. [See UW-52(b)(4).]
General Note: Notes D through L are examples of user options that are sometimes
selected for critical services. Other options may be provided as appropriate.
D. When joint thickness exceeds 2 inches, examine (using MT or PT) the root pass after back-
chipping to sound metal and all accessible surfaces of completed welds of Categories A, B,
C, and D butt type joints.
E. When design is based on a joint efficiency of 1.00, examine (using MT or PT) Categories C
and D non-butt type joints after back-chipping or gouging root pass to sound metal and
accessible surfaces of completed weld.
F. When nozzles are attached with a full penetration weld through the nozzle wall, the cut edge
of the opening in vessel walls thicker than 1/2-inch shall be examined (using MT or PT). The
examination shall be made before nozzle attachment and a re-examination shall be made
after attachment, when accessible.
G. Examination (using MT or PT) of completed welds shall be made after PWHT for the
following:
1. Vessels or vessel parts for which impact testing is required
2. Welds joining non-impact tested low-alloy steels thicker than 1-1/4 inches
3. Welds joining carbon steels thicker than 2 inches
4. When required by Code
H. Butt welds exempt from radiography by Paragraph UW-11(a)(4) shall have accessible
surfaces of completed welds MT or PT examined. (Only applies to designs employing impact-
tested steels when Category A joints are based on a joint efficiency of 1.00.)
L. Clad tubesheet material shall be ultrasonically examined after cutting to final size per
ASME SA-578 Acceptance Level 1, Supplementary Requirement S7 (applies to clad material
of any thickness).
Item Number:
PAGE 2 OF 2
Equivalent Pressure Formulas for Bending Moment and Axial Tensile Load
When sustained bending moments or axial thrust loadings are applied to the flanged joint during
operation in sufficient magnitude to warrant consideration in the flange design, the design
pressure, P, used in the calculation of total hydrostatic end load, H, in the flange design
calculations should be replaced by the following design pressure:
PFLG = P + PEQ
16M 4F
PEQ = +
πG3 πG2
Where:
M= Sustained bending moment applied across full section at flange during the design
condition, in-lb
F= Sustained axial tensile force applied at flange, lb
G= Diameter at location of gasket load reaction, in (See Appendix 2 {Appendix 3} of the
Code for full definition.)
Note: Experience has shown that axial tensile forces resulting from a properly designed
piping system have no significant effect on the flange design and hence are typically not
included in the PEQ determination.
Therefore, the hydrostatic end load, H, used in the flange calculations is determined as follows:
2
H = 0.785 G PFLG
8M
PEQ =
πG3
Where:
M= Bending moment, as defined above, but including dynamic bending moment (e.g.,
seismic moment) applied across full section at flange during the design condition,
in-lb