Subject: Deviation letter

Dear Mrs. Fitri Karyanti

Herewith we would like to inform you that we have finished the following test with unfavorable
result:

Product: MCB
Type & rating: HDB3wN
1P, 1P+N, 2P, 3P, 3P+N, 4P
240 / 415 Vac for 1P, 240 Vac for 1P+N, 415 Vac for 2P, 3P, 3P+N, 4P
In: 1,2,3,4,5,6,10,13,16,20,25,32,40,50,63 A(1P,2P,3P,4P);
10,13,16,20,25,32,40,50,63A (1P+N,3P+N) B, C, D type
Ics = Icn = Icn1 = 6 kA

Standards:
IEC 60898-1:2015+A1:2019

1. Test item: Clause 9.12.11.4.2 – Service short-circuit capacity (Ics)


HDB3wN / 1P / D1:
105#,106#,107# - The sample are not conductive after “O” test.
109# - The sample can’t be closed after “O” test.
HDB3wN / 2P / D1:
114#,115#,116# - The sample are not conductive after “O” test.
HDB3wN / 4P / D1:
129#,130# - The sample can’t be closed after “O” test.
131# - The sample are not conductive after “O” test.

Please provide us with your improvement report ASAP, after checking it we can determine the
samples and cost for re-testing and continue the test schedule accordingly.

Kind regards,

Project Engineer

Baker Zhang