Safety with or without

standard PLC ?

Intern © Siemens AG 2016 siemens.com/simatic-safety


Agenda

1 What the standards says

2 The result of a risk analysis

3 Some examples with standard components

Intern © Siemens AG 2016


DF FA S MP PLC 2
Risk assessment / risk reduction according to ISO 12100

Risk assessment Describe the machine Identify the hazards Evaluate the risks

Define and
evaluate Design the architecture Implement a safety concept and
Risk reduction the safety measures of the safety functions put it into operation
(3-level method)

Prove compliance with the


Document the
Proof measures
Carry out a validation directive
Affix the CE marking

Intern © Siemens AG 2016


Define and evaluate the safety measures
The 3-level method according to EN ISO 12100 Ch. 6

Risk reduction
START

1 Safe mechanical design

YES No PLC
Risk reduced appropriately?
NO
needed
2 Technical measures

YES
Risk reduced appropriately?
NO

3 User information about residual risks

YES
Risk reduced appropriately?
NO

Renewed risk assessment END

Intern © Siemens AG 2016


Relation of PL and Cat

PL a
Standard MTTFd

components PL b low
medium
high

WELL tried PL c

components !!
PL d

PL e

Cat. B Cat. 1 Cat. 2 Cat. 3 Cat. 4


DCavg= 0 0 low medium low medium high
CCF >= 65 pts

Intern © Siemens AG 2016


Possible architectures according to ISO 13849-1
Categories from B to 2

Standard
components

WELL tried
components !!

Intern © Siemens AG 2016


Requirements starting from category 1

Intern © Siemens AG 2016


What are well tried components ?

Intern © Siemens AG 2016


Safety Evaluation Tool
Safety loop with standard components PLb

Detection Evaluation Reaction

Standard CPU Switchgear


E-STOP
Well proven Well proven

Intern © Siemens AG 2016


SRP-CS E-STOP

Intern © Siemens AG 2016


DF FA S MP PLC 2
SRP-CS Contactor

Intern © Siemens AG 2016


DF FA S MP PLC 2
SRP-CS: standard PLC??

??
Intern © Siemens AG 2016
DF FA S MP PLC 2
With Sistema PL can be calculated

STD CPU
STD DI
STD DO

Intern © Siemens AG 2016


DF FA S MP PLC 2
Result : a low PL is reached

Detection Evaluation Reaction

Standard CPU Switchgear


E-STOP
Well proven Well proven

Intern © Siemens AG 2016


DF FA S MP PLC 2
Differentiation of the use of IEC 62061 – ISO 13849

IEC 62061
• applicable for all electrical and electronical systems with any architecture.
• SIL 1 up to 3
• programmable logic controller (PLC etc) have to fulfil IEC 61508

EN ISO 13849-1
• applicable for hydraulic, pneumatic and electromechanical systems without
restrictions.
• applicable for programmable electronic only with restrictions
• certain architecture
• up to PL d resp. SIL 2
• programmable logic controller for PL e (SPS etc) have to fulfil
IEC 61508
• calculation concept of ISO 13849-1 based on predefined architectures

Intern © Siemens AG 2016


Safety Evaluation Tool
With certified components

Detection Evaluation Reaction

3SE6315 CPU 1500F 2x 3RT switchgears


RFID safety switches With F-DI and F-DO
Ple PFH 2,7e-10

Ple PFH 1e-9


Ple PFH 2e-9
Ple PFH 2e-9

Ple PFH 2e-8


TOTAL = Ple PFH 2,52e-8

Intern © Siemens AG 2016


Safety switch off of voltage on standard components

1. The safety system is Ple


2. The feedback of the contactors is taken in
consideration
3. The MTTFd of each module and each contactor
has to be taken in consideration.

Intern © Siemens AG 2016


DF FA S MP PLC 2
SIMATIC Safety Integrated
… System Solutions for Safety-Related Automation

+ Integrated product portfolio


Detection – evaluation – responding
Consistent product Functional Safety siemens.com/safety-integrated-products
portfolio
services & training
+ Support and Consulting
by Siemens safety experts
http///support.industry.siemens.com

Consulting + Prefabricated solutions on the basis


Safety Evaluation of practice-oriented functional examples
Tool SET siemens.com/safety-functional-examples

+ SET for the assessment of your machine's safety


functions
Function siemens.com/safety-evaluation-tool
examples + Training and support regarding standards, risk
assessment
siemens.be/sitrain

Intern © Siemens AG 2016


Thank you very much for your attention