You are on page 1of 67

PT.

PERTAMINA (Persero) RU II DUMAI

Pemasangan 38 Unit MOV di Pertamina Dumai

Factory Acceptance Test (FAT) Procedure for System

.+

18 Nov 2022
4

REV DESCRIPTION PREPARED CHECKED APPROVED COMPANY

STATUS CODE : 1 = Issued for Approval - 2 = Issued for Construction - 3 = As Built

PT. PERTAMINA (Persero) RU II DUMAI


PT. ATHAYA ABBAS MANDIRI
CONTRACT NO. DOCUMENT NO. REV.

21.0006552 870-SYS-FAT-1001
TABULATION OF REVISED PAGES
REVISIONS REVISIONS
SHEET 1 2 3 4 5 SHEET 1 2 3 4 5
1 51
2 52
3 53
4 54
5 55
6 56
7 57
8 58
9 59
10 60
11 61
12 62
13 63
14 64
15 65
16 66
17 67
18 68
19 69
20 70
21 71
22 72
23 73
24 74
25 75
26 76
27 77
28 78
29 79
30 80
31 81
32 82
33 83
34 84
35 85
36 86
37 87
38 88
39 89
40 90
41 91
42 92
43 93
44 94
45 95
46 96
47 97
48 98
49 99
50 100

Pemasangan 38 Unit MOV di Pertamina Dumai Document :


PT. PERTAMINA (PERSERO) RU II Dumai Revision :
Date :
APPENDIX

FAT DOCUMENT LIST

NO DESCRIPTION

1 APPENDIX

2 ATTENDANCE LIST

3 FAT PROCEDURE

4 FACTORY ACCEPTANCE TEST

4.1 MATERIAL CHECK


4.2 PHYSICAL CHECK
4.3 FUNCTION TEST
4.4 PUNCH LIST

5 DRAWING

5.1 PANEL LAYOUT


PROJECT DESCRIPTION

PROJECT NAME Pemasangan 38 Unit MOV di Pertamina Dumai

END USER PT. PERTAMINA (PERSERO) RU II DUMAI

CONTRACTOR PT. ATHAYA ABBAS MANDIRI

ATTENDANCE LIST

DATE NAME COMPANY NAME SIGNATURE


PT. ATHAYA ABBAS MANDIRI DATE SHEET

Pemasangan 38 Unit MOV di Pertamina Dumai

FACTORY ACCEPTANCE TEST PROCEDURE

FAT Tools :

1. Multitester
2. Screw driver
3. etc

FAT Procedure :

1. Material Check
In Material Check, we will check materials prepared by contractor and
compared them with required materials listed in KAK (Kerangka Acuan
Kerja) document and approved document by the end user by availability
and quantity.

2. Physical Check
In Physical Check, we will check materials prepared by contractor and
compared them with required materials listed in KAK (Kerangka Acuan
Kerja) document and approved document by the end user by quality.

3. Function Test
In Function Test, we will test materials prepared by contractor and note
the result and quality of the result as to make sure materials work as they
should.
PT. ATHAYA ABBAS MANDIRI Date Sheet

Pemasangan 38 Unit MOV di Pertamina Dumai

MATERIAL CHECK

ITEM DESCRIPTION QTY UNIT CHECK

MASTER CONTROL STATION (PUMP HOUSE)

CABINET MASTER CONTROL RITTAL


01 1 ea
Size : 2000 mm (H) x 810 mm (W) x 810 mm (D)

02 SIMA2 MASTER STATION 1 ea

03 ACCESSORIES CABINET :
- MCB (1P) 2 ea
- MCB (2P) 1 ea
- Thermostat 1 ea
- Stop Kontak 1 Phase 1 ea
- Lampu T5 1 ea
- Exhaust Fan 1 ea
- Limit Switch 1 ea
- Terminal Block 1 ea
- Busbar Grounding 2 ea
- Tag Panel 1 ea
- Air Intake Filter 1 ea

Prepared By Checked By

Date : Date :
PT. ATHAYA ABBAS MANDIRI Date Sheet

Pemasangan 38 Unit MOV di Pertamina Dumai

MATERIAL CHECK

ITEM DESCRIPTION QTY UNIT CHECK

MASTER CONTROL STATION (CONTROL BLENDING ROOM)

CABINET MASTER CONTROL RITTAL


01 1 ea
Size : 2000 mm (H) x 810 mm (W) x 810 mm (D)

02 SIMA MASTER STATION 1 ea

03 ACCESSORIES CABINET :
- MCB (1P) 2 ea
- MCB (2P) 1 ea
- Thermostat 1 ea
- Stop Kontak 1 Phase 1 ea
- Lampu T5 1 ea
- Exhaust Fan 1 ea
- Limit Switch 1 ea
- Terminal Block 1 ea
- Busbar Grounding 2 ea
- Tag Panel 1 ea
- Air Intake Filter 1 ea
04 PC Engineering 1 set

Software untuk monitoring healthiness dan torque


05 curve secara remote ke PC Engineering yang terdapat 1 ea
di Blending Control Room

Prepared By Checked By

Date : Date :
PT. ATHAYA ABBAS MANDIRI Date Sheet

Pemasangan 38 Unit MOV di Pertamina Dumai

PHYSICAL CHECK

RESULT
NO DESCRIPTION NOT
GOOD
GOOD

PANEL MASTER CONTROL STATION MOV PUMP HOUSE CONTROL ROOM

Verify quality of cabinet master control station


01
(ensure the dimensions according to GA drawing)
Verify installed material
02
(ensure compatibility with GA drawing)
Verify the strength of cable connection toward components
03
(ensure cables are connected properly)
Verify grounding components
04
(ensure all have been installed properly)
Verify existence of name tag of cabinet master control station
05
(ensure name tag is attached properly)
Verify existence of cabinet keys
06
(ensure door clamps and keys installed properly)
Verify the cleanliness of panel
07
(ensure the inside of the panel is vacuumed and outside polished)

PANEL MASTER CONTROL STATION MOV BLENDING CONTROL ROOM

Verify quality of cabinet master control station


08
(ensure the dimensions according to GA drawing)
Verify installed material
09
(ensure compatibility with GA drawing)
Verify the strength of cable connection toward components
10
(ensure cables are connected properly)

Prepared By Checked By

Date : Date :
PT. ATHAYA ABBAS MANDIRI Date Sheet

Pemasangan 38 Unit MOV di Pertamina Dumai

PHYSICAL CHECK

Verify existence of name tag of cabinet master control station


11
(ensure name tag is attached properly)
Verify existence of cabinet keys
12
(ensure door clamps and keys installed properly)
Verify the cleanliness of panel
13
(ensure the inside of the panel is vacuumed and outside polished)

MASTER STATION AND PC ENGINEERING

Verify master station connection and operation


14
(ensure master station’s power and ability to connect)
Verify master station’s ability to operate MOV remotely
15
(ensure the remote function open-close of AUMA actuators)
Verify master station’s connection to PC Engineering
16
(ensure connection and data read with PC Engineering)
Verify software for monitoring healthiness and torque curve
17
(ensure layout display according to approval document)
Verify software’s function to operate MOV remotely, read MOV
18 status, and display ongoing torque curve
(ensure function according to approval document)

Prepared By Checked By

Date : Date :
PT. ATHAYA ABBAS MANDIRI Date Sheet

Pemasangan 38 Unit MOV di Pertamina Dumai

FUNCTION TEST
Please provide the procedure for
PT. ATHAYA ABBAS MANDIRI item list:
1. Testing a new PC engineering
CLIENT : PT. PERTAMINA (Persero) RU II Dumai for RAID 1 configuration
PROJECT TITLE : Pemasangan 38 Unit MOV di Pertamina Dumai 2. Testing using Modbus Simulator
for command actuator
1. SIMA MASTER STATION

NO DESCRIPTION RESULT REMARK


Connect actuators in a loop to the master station and turn on
01
the power.
Switch the master station ON and turn actuator's black
selector switch to REMOTE.

02

Check that the actuators are connected properly from master


station's touch panel

03

Press OPEN command. Percentage of open position can be


seen on the panel.

04
Press CLOSE command. Running progress can be seen on the
panel in percentage.

05

Actuator will run (open/close) with SETPOINT command by


inputting the position %.

06

1. SOFTWARE PC ENGINEERING
NO FUNCTION RESULT REMARK

Local Operation Detection

01

Remote Operation Command


• Open

02
• Close

Healthiness Monitoring
• Normal Status

• Moving Status
03

• Fault Status
Torque Curve (1 Hour Range)

04

Alarm Log

05

Event Log

06

Notes :

Checked and Tested by Approved by

Date : Date :
PT. ATHAYA ABBAS MANDIRI Date Sheet

Pemasangan 38 Unit MOV di Pertamina Dumai

PUNCH LIST

COMMENTS / TARGET DATE


NO. DESCRIPTION SIGNATURE
OUT STANDING CLOSE DATE CLEARED
NO COMPONENT NAME TYPE or P/N Manufacture Qty

01 MCB (1P) SCHNEIDER 3

02 MCB (2P) SCHNEIDER 1

03 THERMOSTAT 3110.000 RITTAL 1

04 STOP KONTAK 1 PHASE 1

05 LAMPU T5 1

06 EXHAUST FAN 3243.10 RITTAL 1

07 LIMIT SWITCH 1

08 MASTER STATION SIMA 2 SIMA 1

09 TERMINAL BLOCK FORT 1

10 BUSBAR GROUNDING IMPORT 2

11 TAG PANEL - 1

12 AIR INTAKE FILTER 3243200 RITTAL 1

REVISION
GENERAL ARRANGEMENT PT. ATHAYA ABBAS MANDIRI NO. DD/MM/YYYY REMARKS
6. 21/09/2022 Issued for Approval

870-ELE-GA-1001 7. 07/10/2022 Issued for Approval

Master Control Station 8. 15/11/2022 Issued for Approval

di Pump House
NO COMPONENT NAME TYPE or P/N Manufacture Qty

01 MCB (1P) SCHNEIDER 3

02 MCB (2P) SCHNEIDER 1

03 THERMOSTAT 3110.000 RITTAL 1

04 STOP KONTAK 1 PHASE 1

05 LAMPU T5 1

06 EXHAUST FAN 3243.10 RITTAL 1

07 LIMIT SWITCH 1

08 MASTER STATION SIMA 2 SIMA 1

09 TERMINAL BLOCK FORT 1

10 BUSBAR GROUNDING IMPORT 2

11 TAG PANEL - 1

12 AIR INTAKE FILTER 3243200 RITTAL 1

REVISION
GENERAL ARRANGEMENT PT. ATHAYA ABBAS MANDIRI NO. DD/MM/YYYY REMARKS
6. 21/09/2022 Issued for Approval

870-ELE-GA-1001 7. 07/10/2022 Issued for Approval

Master Control Station di 8. 15/11/2022 Issued for Approval

Pump House Control Room


PT. PERTAMINA (Persero)
RU II DUMAI

Pekerjaan Pemasangan 38 Unit MOV


di Tank Farm OM (Tahap 1)

HMI SCREEN DESIGN

4 1 Issued for Approval Rizky Setiawan Shirley


REV DESCRIPTION PREPARED CHECKED APPROVED
STATUS CODE : 1 = Issued for Approval - 2 = Issued for Construction - 3 = As Built
PT. PERTAMINA (Persero) RU II DUMAI
PT. ATHAYA ABBAS MANDIRI

PROJECT NO. DOCUMENT NO. REV

21.0006552 870-SYS-WOW-1001 3
ALARM EVENT
610-TK-203 INLET 610-TK-207 INLET 610-TK-211 INLET

610-TK-203 OUTLET 610-TK-207 OUTLET 610-TK-211 OUTLET

610-TK-204 INLET 610-TK-208 INLET 610-TK-212 INLET

610-TK-204 OUTLET 610-TK-208 OUTLET 610-TK-212 OUTLET

610-TK-205 INLET 610-TK-209 INLET

610-TK-205 OUTLET 610-TK-209 OUTLET

610-TK-206 INLET 610-TK-210 INLET

610-TK-206 OUTLET 610-TK-210 OUTLET


945-T-07 INLET 945-T-12 INLET 945-T-29 INLET

945-T-07 OUTLET 945-T-12 OUTLET 945-T-29 OUTLET

945-T-09 INLET 945-T-14 INLET

945-T-09 OUTLET 945-T-14 OUTLET

945-T-10 INLET 945-T-15 INLET

945-T-10 OUTLET 945-T-15 OUTLET

945-T-11 INLET 945-T-28 INLET

945-T-11 OUTLET 945-T-28 OUTLET


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-203 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 10 OPEN CLOSE
STEM DIAMETER (MM) : 36,2
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M250X-F14
RANGE TORQUE (NM) : 25 - 250
MOTOR TYPE : BDX0090-2-1,40
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-203 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 36 OPEN CLOSE
STEM DIAMETER (MM) : 77,5
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M500X + GK30.2
RANGE TORQUE (NM) : 400 - 4000
MOTOR TYPE : BDX0090-2-3,30
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-204 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 10 OPEN CLOSE
STEM DIAMETER (MM) : 36,2
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M250X-F14
RANGE TORQUE (NM) : 25 - 250
MOTOR TYPE : BDX0090-2-1,40
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-204 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 36 OPEN CLOSE
STEM DIAMETER (MM) : 77,5
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M500X + GK30.2
RANGE TORQUE (NM) : 400 - 4000
MOTOR TYPE : BDX0090-2-3,30
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-205 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 12 OPEN CLOSE
STEM DIAMETER (MM) : 39,8
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M500X-F14
RANGE TORQUE (NM) : 50 - 500
MOTOR TYPE : BDX0090-2-3,30
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-205 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 36 OPEN CLOSE
STEM DIAMETER (MM) : 77,5
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M500X + GK30.2
RANGE TORQUE (NM) : 400 - 4000
MOTOR TYPE : BDX0090-2-3,30
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-206 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 8 OPEN CLOSE
STEM DIAMETER (MM) : 32,3
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M120X-F10
RANGE TORQUE (NM) : 12 - 120
MOTOR TYPE : BDX0071-2-0,70
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-206 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 24 OPEN CLOSE
STEM DIAMETER (MM) : 62
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M250X + GK25.2
RANGE TORQUE (NM) : 200 - 2000
MOTOR TYPE : BDX0090-2-1,80
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-207 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 8 OPEN CLOSE
STEM DIAMETER (MM) : 31,8
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M120X-F10
RANGE TORQUE (NM) : 12 - 120
MOTOR TYPE : BDX0071-2-0,70
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-207 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 24 OPEN CLOSE
STEM DIAMETER (MM) : 58,1
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M1000X-F16
RANGE TORQUE (NM) : 100 - 1000
MOTOR TYPE : BDX0112-2-5,00
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-208 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 6 OPEN CLOSE
STEM DIAMETER (MM) : 30,1
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M120X-F10
RANGE TORQUE (NM) : 12 - 120
MOTOR TYPE : BDX0071-2-0,70
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-208 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 24 OPEN CLOSE
STEM DIAMETER (MM) : 58,1
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M1000X-F16
RANGE TORQUE (NM) : 100 - 1000
MOTOR TYPE : BDX0112-2-5,00
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-209 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 6 OPEN CLOSE
STEM DIAMETER (MM) : 30,3
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M120X-F10
RANGE TORQUE (NM) : 12 - 120
MOTOR TYPE : BDX0071-2-0,70
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-209 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 24 OPEN CLOSE
STEM DIAMETER (MM) : 58,1
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M1000X-F16
RANGE TORQUE (NM) : 100 - 1000
MOTOR TYPE : BDX0112-2-5,00
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-210 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 6 OPEN CLOSE
STEM DIAMETER (MM) : 30,3
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M120X-F10
RANGE TORQUE (NM) : 12 - 120
MOTOR TYPE : BDX0071-2-0,70
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-210 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 24 OPEN CLOSE
STEM DIAMETER (MM) : 58,1
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M1000X-F16
RANGE TORQUE (NM) : 100 - 1000
MOTOR TYPE : BDX0112-2-5,00
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-211 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 6 OPEN CLOSE
STEM DIAMETER (MM) : 30,3
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M120X-F10
RANGE TORQUE (NM) : 12 - 120
MOTOR TYPE : BDX0071-2-0,70
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-211 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 8 OPEN CLOSE
STEM DIAMETER (MM) : 31,8
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M120X-F10
RANGE TORQUE (NM) : 12 - 120
MOTOR TYPE : BDX0071-2-0,70
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-212 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 6 OPEN CLOSE
STEM DIAMETER (MM) : 30,3
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M120X-F10
RANGE TORQUE (NM) : 12 - 120
MOTOR TYPE : BDX0071-2-0,70
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 1 HEALTHINESS STATUS

TAG NUMBER 610-TK-212 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 8 OPEN CLOSE
STEM DIAMETER (MM) : 31,3
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M120X-F10
RANGE TORQUE (NM) : 12 - 120
MOTOR TYPE : BDX0071-2-0,70
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-07 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 4 OPEN CLOSE
STEM DIAMETER (MM) : 25,5
RATING (ANSI) : 300 # RF
POSITION (%)
MOV TYPE : TR-M60X-F10
RANGE TORQUE (NM) : 10 - 60
MOTOR TYPE : BDX0063-2-0,40
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-07 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 6 OPEN CLOSE
STEM DIAMETER (MM) : 30,3
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M120X-F10
RANGE TORQUE (NM) : 12 - 120
MOTOR TYPE : BDX0071-2-0,70
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-09 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 4 OPEN CLOSE
STEM DIAMETER (MM) : 25,5
RATING (ANSI) : 300 # RF
POSITION (%)
MOV TYPE : TR-M60X-F10
RANGE TORQUE (NM) : 10 - 60
MOTOR TYPE : BDX0063-2-0,40
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-09 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 10 OPEN CLOSE
STEM DIAMETER (MM) : 36,2
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M250X-F14
RANGE TORQUE (NM) : 25 - 250
MOTOR TYPE : BDX0090-2-1,40
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-10 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 4 OPEN CLOSE
STEM DIAMETER (MM) : 25,5
RATING (ANSI) : 300 # RF
POSITION (%)
MOV TYPE : TR-M60X-F10
RANGE TORQUE (NM) : 10 - 60
MOTOR TYPE : BDX0063-2-0,40
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-10 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 10 OPEN CLOSE
STEM DIAMETER (MM) : 36,2
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M250X-F14
RANGE TORQUE (NM) : 25 - 250
MOTOR TYPE : BDX0090-2-1,40
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-11 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 10 OPEN CLOSE
STEM DIAMETER (MM) : 36,2
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M250X-F14
RANGE TORQUE (NM) : 25 - 250
MOTOR TYPE : BDX0090-2-1,40
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-11 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 30 OPEN CLOSE
STEM DIAMETER (MM) : 70,2
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M250X + GK25.2
RANGE TORQUE (NM) : 200 - 2000
MOTOR TYPE : BDX0090-2-1,80
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-12 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 10 OPEN CLOSE
STEM DIAMETER (MM) : 36,2
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M250X-F14
RANGE TORQUE (NM) : 25 - 250
MOTOR TYPE : BDX0090-2-1,40
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-12 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 30 OPEN CLOSE
STEM DIAMETER (MM) : 70,2
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M250X + GK25.2
RANGE TORQUE (NM) : 200 - 2000
MOTOR TYPE : BDX0090-2-1,80
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-14 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 10 OPEN CLOSE
STEM DIAMETER (MM) : 34,8
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M250X-F14
RANGE TORQUE (NM) : 25 - 250
MOTOR TYPE : BDX0090-2-1,40
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-14 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 30 OPEN CLOSE
STEM DIAMETER (MM) : 70,2
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M250X + GK25.2
RANGE TORQUE (NM) : 200 - 2000
MOTOR TYPE : BDX0090-2-1,80
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-15 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 10 OPEN CLOSE
STEM DIAMETER (MM) : 36,2
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M250X-F14
RANGE TORQUE (NM) : 25 - 250
MOTOR TYPE : BDX0090-2-1,40
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-15 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 30 OPEN CLOSE
STEM DIAMETER (MM) : 70,2
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M250X + GK25.2
RANGE TORQUE (NM) : 200 - 2000
MOTOR TYPE : BDX0090-2-1,80
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-28 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 10 OPEN CLOSE
STEM DIAMETER (MM) : 26,2
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M250X-F14
RANGE TORQUE (NM) : 25 - 250
MOTOR TYPE : BDX0090-2-1,40
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-28 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 30 OPEN CLOSE
STEM DIAMETER (MM) : 70,2
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M250X + GK25.2
RANGE TORQUE (NM) : 200 - 2000
MOTOR TYPE : BDX0090-2-1,80
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-29 INLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 10 OPEN CLOSE
STEM DIAMETER (MM) : 36,2
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M250X-F14
RANGE TORQUE (NM) : 25 - 250
MOTOR TYPE : BDX0090-2-1,40
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


TANK NUMBER TANK FARM 2 HEALTHINESS STATUS

TAG NUMBER 945-T-29 OUTLET


OPERATION STATUS

REMOTE LOCAL FAULT MOVING GOOD


TYPE AND SPECIFICATION
VALVE SIZE (INCH) : 30 OPEN CLOSE
STEM DIAMETER (MM) : 70,2
RATING (ANSI) : 150 # RF
POSITION (%)
MOV TYPE : TR-M250X + GK25.2
RANGE TORQUE (NM) : 200 - 2000
MOTOR TYPE : BDX0090-2-1,80
POWER : 380VAC/50HZ/3PH
TORQUE CURVE

120

80

40

-40

-80

-120

12:00 12:12 12:24 12:36 12:48 13:00


ALARM LOG
2022/10/13 09:55:15
EVENT LOG
2022/10/13 09:55:15 OPERATION LOCAL CLOSE
Data Sheet for PC and Wifgasindo Doc. No :
Monitor -

PEMASANGAN 38 UNIT MOV DI PT.PERTAMINA Rev : 0 Date : June 07, 2022


RU II DUMAI Page 1 of 1

PT. ATHAYA ABBAS MANDIRI


GENERAL

1, Tag Numbers To be update with order


2, Qty
3, Equipment Type 1 set

PC

SPECIFICATION
4, Processor Intel Processor Xeon W-2225 4.1GHz 4.6GHz,

5, RAM 4 Core , 16GB (2x8GB) DDR4 RDIMM ECC 2,5”,


6, Disk 512GB SSD + 2TB SATA 7200Rpm, DVDRW Optical Drive
7, Monitor Dell 24” P2422H Monitor

8, VGA Nvidia Quadro A2000, 6GB,Intel Dual Wireless AC 8265 (802.11ac) 2x2

9, Accessories Bluetooth moduleUSB Optical Mouse MS116 & USB Keyboard KB216

10, O/S Windows 10/11 Profesional 64Bit (Includes Windows 11 Pro License) English

11, Service ProSupport and Next Business Day Onsite Service Initial, 3 Years Onsite Service

12, RAID 1

SELECTION
13, Manufacturer Dell
14, Model Number
Precision 5820 Tower MT
PRECISION 5820 TOWER

Big power in an innovative


compact design.

POWERFUL PERFORMANCE LATEST TECHNOLOGY


The Dell Precision 5820 Tower delivers high performance for your Ready for complex projects, including artificial intelligence and
most demanding applications with the latest Intel® Xeon® virtual reality workflows, with next generation Radeon™ Pro and
and Core® X Series processors and up to 512GB of fast 2666MHz NVIDIA Quadro® professional graphics, with support for up to 600W
memory. In addition, every Dell Precision comes with the exclusive of graphics power. Front access FlexBays provide outstanding
Dell Precision Optimizer, which automatically tunes your workstation storage expandability, up to 60TB with SATA, SAS and PCIe M.2/U.2
to run some of the most popular (ISV) applications at the fastest NVMe solid state drives, featuring hot-swap access, so you never
speeds possible. DPO Premium is a new AI-based version which have to stop creating.
optimizes your workstation, based upon how you use it, providing
true customization.

INNOVATIVE DESIGN
The front FlexBay design supports a range of modules from scalable
OUTSTANDING RELIABILITY
storage to security options, you can build the workstation designed The revolutionary multichannel thermal design delivers advanced
for your creative expertise. Secure your data with the optional cooling and acoustics so you can enjoy longer productivity under
Smart Card (CAC/PIV) reader, hot swap NVMe SSDs and heavy workloads. Precision workstations are tested and are
lockable hard drive carriers. The best-in-class smart design Independent Software Vendor certified to ensure the high-
includes integrated front and rear handles for easy deployment performance applications you rely on every day run smoothly.
and moves, and an externally accessible tool-less (lockable)
power supply for superior serviceability.
Essential Accessories
PRECISION 5820 TOWER

Dell Canvas Dell Wireless Premium Keyboard Dell 27 UltraSharp Monitor


Bring your ideas to life with a 27-inch & Mouse Combo | KM717 with PremierColor | UP2716D
workspace that empowers natural Enhance productivity and enjoy its elegant Expect vivid, accurate color precision, ultra-
digital creation. Featuring a precise design that will fit into virtually any thin bezels and ideal color coverage to suit your
EMR pen, totem, and touch surface. workspace. For increased productivity professional needs with the Dell UltraSharp 27
you can simultaneously pair up to two Monitor.
compatible devices with Bluetooth LE.

Jabra Evolve 75 3Dconnexion SpaceMouse Wireless X-Rite Colorimeter i1Display Pro


With the ambient noise cancellation SpaceMouse Pro Wireless handles 3D navigation The i1Display Pro ensures a perfectly calibrated
feature of this wireless headset you can for a revolutionary two-handed work style preferred and profiled display while delivering the speed,
hear every word clearly on your next call. by the world’s top 3D professionals. Intuitively options and flexibility needed to maintain
This easy to carry device is certified for examine and analyze your designs from every angle. color accuracy.
Microsoft Skype for Business.
Built for business

Dell Technologies Unified Workspace


Dell Technologies Unified Workspace is the most comprehensive solution to deploy, secure, manage and
support virtually all devices from the cloud. We designed this revolutionary solution with intelligence and
automation providing you with visibility across the entire endpoint environment. We help you save time,
improve user experience, optimize resources and strenthen security.

Our modern deployment solution, ProDeploy in the Unified Workspace allows


you to revolutionize the way deployment gets done. By spending just one
hour for set up , IT can then hand deployment to Dell and have preconfigured
systems shipped directly to the end users--wherever they are.
DEPLOY

Dell Endpoint Security for the Unified Workspace helps you manage growing
cyber risks while embracing workforce transformation. With Dell SafeGuard
and Response powered by Secureworks, you gain actionable insight to help
you quickly and efficiently prevent, detect and respond to cyber-attacks -
keeping your environment free from harm.
SECURE

We integrated our hardware management solution Dell Client Command


Suite with VMware Workspace ONE, allowing you to take advantage of
unified endpoint management (UEM) and manage the firmware, operating
system and applications for all devices from the Workspace ONE console.
MANAGE UEM simplifies the management of the entire environment saving IT time
from having to work between separate consoles for PCs and phones.

ProSupport Plus continues to be the only predictive and proactive support


in the market. When compared to key competitors, ProSupport Plus with
SupportAssist reduced time to resolve a failed hard drive with up to 11x
faster time to resolution*
SUPPORT

Based on a Principled Technologies test report, “Spend Less Time and Effort Troubleshooting Laptop Hardware Failures” dated April 2018. Testing ommissioned
*

by Dell, conducted in the United States. Actual results will vary. Full report: http://facts.pt/L52XKM
Features & Technical Specifications
PRECISION 5820 TOWER

Feature Precision 5820 Tower Feature Precision 5820 Tower


Technical Specifications Technical Specifications
Processor Intel® Xeon® Processor W-2000 Family and Storage PCIe backplane chassis with integrated Intel controller
Options Core X Series CPUs with up to 18 cores and Intel Options2 and up to 4 with MegaRAID 9460* NVMe hardware
Advanced Vector Extensions, Intel Trusted Execution RAID controller option - see controller section
Technology, Intel AES New instructions, Optimized Note: Precision PCIe FlexBay backplane and single
Intel Turbo Boost and optional Intel vPro™ technology M.2 Module (incl. 1 M.2 PCIe/NVMe carrier) kits are
(Xeon W CPUs only) (Important Note: Features and available for customers to convert standard FlexBays*
Supported Configurations will differ between 5820 to support Intel and MegaRAID NVMe controller
Tower Workstations with Intel® Xeon® W Processors options. (different kits) Only 1 front accessible M.2
and 5820 Tower Workstations with Intel® Core™ NVMe PCIe SSD is supported, due to reduced PCIe
X Processors. Please see systems on Dell.com/ lane support on Core X I9 and I7 Series CPUs
Precision for specific configuration details.) NVMe RAID 0,1 option (Intel RSTe vROC).*
Up to 4 x M.2 NVMe PCIe SSDs via 1 x Dell Ultra-
Operating Windows 10 Pro for Workstations (up to 4 Cores) Speed Drive Quad x16 card. NVMe RAID 0,1,10 option
System Windows 10 Pro for Workstations (4 Cores Plus) (Intel RSTe vROC).
Options Windows 10 Pro - for Core X Series CPUs
Red Hat Enterprise Linux 8.0 M.2 NVMe PCIe SSDs
Ubuntu Linux 18.04 Up to 4 x 2TB drives on 1 Dell Precision Ultra-Speed
Suse Linux (SLES 12 SP2) supported* Drive Quad x16 card.
NeoKylin 6.0 SP5 (China only) * Front FlexBay M.2/U.2 NVMe PCIe SSDs
Up to 4 x 2TB M.2 drives
Chipset Intel® C422 (Skylake/Cascade Lake W) ;
Intel® Optane™905P SSDs
Intel X299 (Skylake/Cascade Lake X)
Up to 4 x 960GB drives
Memory Four channel memory up to 512GB 2666MHz and up 2.5” SATA SSD
Options1 to 256GB 2933MHz DDR4 (RDIMM) ECC memory. Up to 6 x 1.9TB drives
(Up to 256GB 2666MHz DDR4 (UDIMM) Non-ECC
2.5” SATA 7200 RPM
memory) 8 DIMM slots.
Up to 6 x 1TB drives
Note: Memory speed is dependent on specific Intel
Xeon or Core X Processor installed. 3.5” SATA 7200 RPM Hard Drives
Up to 5 x 12TB Enterprise Drives
Graphics Support for 2 PCI Express® x16 Gen 3 graphics card -
2.5” SAS SSD
Options1 up to 600W with maximum of up to 2 x 300W double
Up to 6 x 800GB drives
width graphics cards.
Not all graphics card offerings are available with 3.5” SAS 7200 RPM 12Gb/s
Core X I9 and I7 Series CPUs Up to 5 x 4TB
2.5” SAS 10K RPM 12Gb/s
High end 3D cards:
Up to 6 x 1.8TB
Radeon™ Pro WX 9100
Radeon™ Pro SSG 2.5” SAS 15K RPM 12Gb/s
NVIDIA Quadro GV100 Up to 6 x 600GB
NVIDIA Quadro P6000 M.2 PCIe SED SSD
NVIDIA Quadro P5000 512GB and 1TB
Nvidia Quadro RTX 8000 Not all storage offerings (including SAS drives)
Nvidia Quadro RTX 6000 are available with Core X Series CPUs
Nvidia RTX 5000 Storage Integrated: Intel® chipset SATA controller (6Gb/s)
Mid-range 3D cards: Controller with 6 SATA ports plus 2 dedicated ports for optical
Radeon™ Pro WX 7100 drives. Intel RSTe software RAID 0,1,5,10*
Radeon™ Pro WX 5100 Intel RSTe (vROC) software RAID 0,1,10 option
Radeon™ Pro WX 4100 (motherboard activation key) for M.2 NVMe PCIe
NVIDIA Quadro P4000 SSDs on Dell Ultra-Speed Drive Quad card, Duo x8
NVIDIA Quadro P2000 card (RAID 0,1) and for 2 x front FlexBay M.2/U.2
NVIDIA Quadro P2200 NVMe PCIe SSDs* (RAID 0,1) or front FlexBay NVMe
NVIDIA Quadro RTX 4000 PCIe SSDs (RAID 0,1)
Entry 3D cards: Customer kit available for Intel RSTe (vROC)
Radeon™ Pro WX 3200 motherboard activation key for NVMe RAID support.
Radeon™ Pro WX 2100 Optional: Broadcom MegaRAID® SAS 9440-8i 12Gb/s
NVIDIA Quadro P1000 SAS (6Gb/s SATA) PCIe controller, 8 ports, Software
NVIDIA Quadro P620 RAID 0,1,5,10.*
NVIDIA Quadro P400 MegaRAID® SAS 9460-16i 12Gb/s SAS (6Gb/s SATA)
Professional 2D cards: PCIe controller (4GB cache with Flash module/Super
NVIDIA NVS 310 Cap backup) Hardware RAID 0,1,5,10.*
MegaRAID 9460* controller NVMe option supports
Storage Front accessible FlexBays support up to 4 x 2.5”/3.5” up to 4 front FlexBay M.2/U.2 NVMe PCIe SSDs
Options2 SATA HDD/SSDs and up to 6 x 2.5” and 5 x 3.5” with Hardware RAID 0,1,5,10
drives with 5.25” bay populated.
Up to 2 front accessible (hot plug) M.2/U.2 NVMe
PCIe SSDs are supported in FlexBay 1 on enabled
Features & Technical Specifications
PRECISION 5820 TOWER

Feature Precision 5820 Tower Feature Precision 5820 Tower


Technical Specifications Technical Specifications
Communications Integrated: Intel® i219 Gigabit Ethernet controllers Security Options Trusted Platform Module (TPM 2.0); Optional
with Intel Remote Wake UP, PXE and Jumbo (Check regional CAC/PIV card reader for slimline bay, chassis
frames support availability) Intrusion switch; Setup/BIOS Password; I/O
Optional: Intel® i210 10/100/1000 single port PCIe Interface Security; Kensington® lock slot, Padlock
(Gen 3 x1) gigabit network card, Intel® X550-T2 ring, lockable power supply; Optional hard drive
10GbE dual port PCIe (Gen 3 x4) network card locking sleds (key lock), Dell Data Guardian, Dell
Endpoint Security Suite Enterprise, Lockable front
Audio Controller Integrated Realtek ALC3234 High Definition Audio bezel (covers FlexBays), Front FlexBay NVMe
Codec (2 Channel) drives are removable (hot swap).
Speakers Internal Speaker; Optional Dell 2.0 stereo speaker Manageability3 AMT or vPro with DASH support*
systems available and Dell sound bar for select Dell vPro Enhancements (Grasslake)*
flat-panel displays SNMT/CIM vis OMCI
Add-in cards Optional: Dell Precision Ultra-Speed Drive Duo Dell Command Suite
(HH/HL,x8) & Ultra-Speed drive Quad (FH/FL,x16) Regulatory and Energy Star® configurations available* including 80
with active cooling. Support for up to 2 and 4 M.2 Environmental PLUS® registered Gold power supplies; EPEAT®
PCIe NVMe SSDs respectively. registered (see epeat.net for specific registration
Optional USB 3.1 (Gen 2) 10Gb/s Type C card (2 rating/status by country); China CECP; GS
ports) 1 DP pass-through port Mark. For a complete listing of declarations &
Optional dual & quad display Teradici PCoIP remote certifications, see Dell’s regulatory & compliance
workstation host PCIe cards homepage at dell.com/regulatory_compliance
Optional Thunderbolt 3 PCIe Card (2 ports) 1 DP
pass-through port Warranty & 3-Year Limited Hardware Warranty and 3-year
Optional Serial Port PCIe Card Support NBD On-Site Service after Remote Diagnosis
Services4 Optional: Dell ProSupport is designed to rapidly
I/O Ports Front
respond to your business’s needs, help protect
2 – USB 3.1 Gen 1 Type A
your investment and sensitive data, and provide
2 – USB 3.1 Gen 1 Type C
enhanced proactive support services to help
1 – Universal Headphone Jack
reduce risk and complexity within your IT
Internal environment
1 – USB 2.0 Type A
1 – 2 x 5 USB 2.0 header. (requires 3rd party splitter
cable to support 2 x USB 2.0 Type A ports)
6 – SATA @6Gb/s plus 2 for optical
Rear
6 – USB 3.1 Gen 1 Type A
(6th port supports Power Delivery)
1 – Serial
1 – RJ45 Network
2 – PS2
1 – Audio Line out
1 – Audio Line in/Microphone
Chassis HxWxD: 16.45” (417.9 mm) | Width: 6.95”
(176.5 mm) | Depth: 20.4” (518.2 mm) |
Starting at weight 34lb/15.4kg
Bays: (2) FlexBays can support up to 2x 3.25” or
2.5” drives each and (1) 5.25” HDD/SSD drives as
factory option or customer kit.
(1) Slimline optical bay; (1) SD slot UHS ll Class 3
with read only support (SW enabled)
Available PCIe backplane FlexBay chassis
supporting 1 - 4 x M.2/U.2 PCIe NVMe SSDs.
Slots: All slots PCIe Gen 3: (2) PCIe x16, (1) PCIe
x16 wired as x8, (1) PCie x16 wired as x4, (1) PCIe
x16 wired as x1, 1 PCI 32/33
Power Supply: 425W* or 950W (input voltage
100VAC - 240VAC) –90% efficient (80PLUS Gold
Certified) Externally accessible/removable/lockable

Storage devices Slimline Bay Options: DVD-ROM; DVD+/-RW, CAC/


PIV card reader. 5.25” Bay
Options: BD, DVD+/-RW; Standard: SD slot UHS ll
Class 3 with read only support
PRECISION 5820 TOWER

Create without limits

*
Not available on the 5820 Tower with Core X I9 and I7 CPUs.

ISV certification applies to select configurations:


1 System memory may be used to support graphics, depending on system memory size and other factors.
2 Hard Drive capacity varies with preloaded material and will be less.
3 Systems Management Options: Intel® vPro Technology - Fully vPro-capable at point of purchase; the vPro systems management option requires vPro processors. Includes support for
Intel Advanced Management Technology (AMT) 9.x. Intel® Standard Manageability - Fully enabled at point of purchase, the Intel Standard Management option is a subset of the AMT
features. ISM is not upgradeable to vPro technology post-purchase. No Out-of-Band Systems Management - This option entirely removes Intel out of band systems (OOB)
management features. The system can still support in band management. OOB management support through AMT cannot be upgraded post-purchase.
4 Availability and terms of Dell Services vary by region. For more information, visit Dell.com/servicecontracts/global; Limited Hardware Warranty available by writing Dell USA LP, Attn:
Warranties, One Dell Way, Round Rock, TX 78682 or see www.dell.com/warranty; Onsite Service after Remote Diagnosis: Remote Diagnosis is determination by online/phone
technician of cause of issue; may involve customer access to inside of system and multiple or extended sessions. If issue is covered by Limited Hardware Warranty