The efficiency of the pump set at duty point shall not be less than 60% of
the maximum efficiency for the pump.
The bearings shall be of the rotating element type, grease packed and sealed
for life.
The pump shall have two mechanical seals. The seals shall work
independently of each other, one to seal off the motor, one to seal off the
pumped fluid. An oil chamber shall act as a buffer between the seals and a
coolant for the seals. A moisture detection probe in the oil chamber shall
detect the presence of water in the chamber and thus the deterioration of
the lower seal. The probe shall operate a remote alarm.
A lifting chain with shackles, rings etc. shall be fitted to each pump, which
shall support the weight of the pumps during installation and removal from
the sump. The chain shall comply with BS 1663 and be hot-dipped
galvanized.
Pump Specification :
The waste water and sewage pump in cast iron execution must be designed
for permanent submerged installation. Super Vortex impeller with
minimum 80mm of solid handling size, Pumps to be of EU origin only.
Motor to be built of IE 3 components only. Primary Seal to be Sic/Sic &
Secondary Seal to be Carbon/Ceramic. Pump outside to be powder coated
with minimum thickness 100μm. Motor cable to be have minimum 10m
and to be water tight and of stainless steel. Thermal switches to be
incorporated in the motor windings to protect the motor against
overheating. Motor Speed to be 2 pole with Class H insulation. Pumps to be
installed with auto coupling and guide rail.
There shall be duplicated pump sets in the system, one duty and one
standby. The pumps shall be automatically controlled to maintain the water
pressure in the system as indicated on the Drawings.
The pump control shall have the following features:
For the two-pump arrangement, one pump shall act as duty and the other one as
standby. The pumps shall be automatically controlled to transfer the soil and /
or waste water to the manhole or the nearest drainage pipe connections.
Automatic controls shall be of float - type mercury switches suitable for use
with soil or waste water. Each pit shall be fitted with four switches at different
levels to correspond with the required depths of water and to initiate the
relevant controls to operate the pump and / or raise the alarm suitably.
When the water level in the sump pit reaches the first pre-determined high
level, the duty pump shall be started and continue to run until the water level
falls back to the low level.
For duplicated pump sets, if the water level continues to rise to the second pre-
determined level, the second pump shall also be called to operate in parallel
with the first pump. The pumps shall only be stopped when the water level
drops back to the low level.
Automatic and manual change-over facilities shall be provided for the pumps.
A lead / lag selection and an automatic alternation facility shall be provided.
After one pump has finished one operation, the second pump shall act as duty
pump for the next cycle.
An extra high level alarm shall be provided at the vicinity of the pit or one of
the control panels, when the water raises up to the extra high level, an audible
and visual alarm shall be raised.
Vertical Multistage Pump with Cast Iron parts to be CED coated. The
primary seal should be SiC/SiC and secondary to be EPDM only. Impeller
shaft to be of Stainless steel only with minimum IE 3 motor. Motors to be
Thermostat in motor windings. Pump efficiency need to be at least 60%
at duty point.