You are on page 1of 39

USER’S MANUAL

REF. CHATO4S-T6

1
WARNING

THE USE OF THIS MATERIAL MUST BE IN ACCORDANCE WITH THE PROVISIONS OF


THE LABOUR LAW.

USE 4MM SAFETY CABLES WITH DOUBLE-INSULATION FOR THE CONNECTION OF


THE ELECTRICAL APPLIANCES

PRECAUTIONS BEFORE USE

- Ensure that no water leak occurs in the tanks or piping.

PRECAUTIONS FOR INSTALLATION

- Place the CHATO in a place lit in accordance with the provisions of the labour law (500 lux
minimum).
- The electrical supplies must be protected in accordance with the standards in force.
- The operator must have a power shut-off device within reach.
- The CHATO must be placed on a flat and even floor.
- Check the proximity of an emergency stop device.

PRECAUTIONS FOR USE

- Do not use the CHATO if even the slightest leak occurs.


- When using the features, always ensure that the door of the CHATO electrical switchgear
cabinet is properly closed.
- The pumps must not operate without water for over 45 seconds.
- The pumps must not operate with their manual valve closed for over 45 seconds.
- Only authorised persons may use the CHATO with its electrical switchgear cabinet door
open.

PRECAUTIONS FOR CONSIGNMENT

Secure the machine in the event of a defect according to the procedure below:

- Cut off the power supply to the CHATO.


- Disconnect all the connector parts of the CHATO.
- Isolate and lock up the apparatus presenting the defect in an isolated room locked with a
key. Only a person responsible for the equipment should have this key.
- Place a notice on the apparatus clearly indicating its being secured against use.
- Have the defective apparatus repaired by a qualified person.
- Release the apparatus (this operation must be effected by the person who secured the
apparatus).

CHATO MAINTENANCE

- Drain the 150-litre tank if the system is not used for over 60 days.
- Clean the sides of the tanks with a cotton cloth.
- The motorised pumps do not require any maintenance.
2
NOTE ABOUT THE ROUTE TAKEN BY AND TREATMENT OF WATER FOR
CONSUMPTION
(example for an overseas pumping station)

Water is pumped from a river or water table by sets of electrical pumps.


It is then filtered in a settling tank using successive layers of sand and gravel.
This clean water is then treated with chemicals against organic impurities and algae and with
calcium hydroxide to rectify the pH, or in other words to decrease the acidity of the water.
Next, the clean water is moved towards a water tower by means of motorised pumps and pipes
The water tower will then supply water at a constant pressure for users.

The CHATO system enables students to simulate this entire circuit, from the stage
where water is pumped from rivers to the stage where it arrives in people’s homes.

3
WATER FLOW IN THE CHATO
(Model shown without electrical switchgear cabinet)

In the settling tank:

- Filling by means of the three-phase or single-


phase motorised pump depending on the option
selected
- Draining by means of a manual valve

In the water tower:

- Filling by means of the three-phase motorised


pump

- Draining by means of a valve

4
PRESENTATION OF THE PUMPING SYSTEM: CHATO 4

- Test cabinet : holds the wired student grid.


- Power console: houses the electrical protective devices and
power source (400V three-phase and 24V AC) which enable the
model to operate. .
- Control console: comprises control components for testing the
student grid.
- Level sensors: total of 6 (3 per tank): for differentiating water
levels in the tanks
- Water tower: 60-litre tank simulating a water tower.
- Settling basin: 60-litre tank simulating a water tower.
- River: 150-litre tank simulating a water table or river.
- Valve: simulates domestic water consumption.
- High indication: indicates the presence of the three-phase 400V.
- Low indication: indicates the presence of the three-phase 24V.

5
COMPONENTS AT THE REAR OF THE CHATO:

SPHERICAL PLUG VALVE:

The spherical plug valve, or ball valve, consists of a sphere with a hole pierced in its diameter. It rotates
around an axis perpendicular to the hole’s axis.

- Manual valve for draining the settling basin

- 2 motorised pumps: 1 or 2 three-phase 400V and/or 1 single-phase 230V power supply, depending
on the selected option.
- 1 valve for adjusting the flowrate of the water at the output of each motorised pump

6
COMPONENTS AT THE FRONT OF THE CHATO-IDF:

CHATO tank fitted with a valve

Tap simulating domestic water consumption.

7
ELECTRICAL PROPERTIES OF THE CHATO-IDF COMPONENTS:

MOTORISED PUMPS:

Self-priming pump with STAINLESS STEEL body. Class F IP4 totally-enclosed motor. Max.
pressure = 6 bars

Hydraulic properties:

8
Identification plate of the single-phase and triple-phase motorised pump:

Type Rated power Power I(A) Flowrate (m³/h – l/min)


1~ 3~ consumption 0.6 1.2 1.8 2.4 3.0
single three- kW HP 1~ 3~ 1x230 3x400 10 20 30 40 50
- phase V V
phase 50 Hz 50 Hz Manometric height (m)
JX10 JX105 T 0.75 1.0 1.10 1.10 5.2 2.2 42 36 31.5 27.5 24
5

Coupling of the three-phase motorised pump:

V A Hz min-1 kW L/Min
400 2,2 50 2850 0,75 40
230 3,8 50 2850 0,75 40

- Exploded view of a single-phase motorised pump

9
- Exploded view of the hydraulic part of the single-phase motorised pump using the solid
Works software:

Key: 3-D view

No. of parts Designation


1 Pump body
2 Motor support
4 Motor rotor
5 Turbine
6 Diffuser
11 Venturi tube
13 Retaining spring
14 Motor stator
15 Motor cover
16 Fan
17 Fan guard
18 Motor terminal
19 Motor terminal cover
20 Centring part
22-23 Bearings
24 Spring washer
25 Tightening stud
26 Capacitor
27 Capacitor support
28-29 Screwable sealing plugs
31 O-ring seal
31 Seal
45 Tightening screw
48 Metal sealing washer
63 Feet

10
LEVEL SENSORS:

Form of NO or NC contact
The switching action (for example, changing the NO contact to NC) can be reversed by rotating
the sensor through 180°C. This operation must be performed when the power is off and
the tanks are empty.

- Unscrew the two fastening screws from the level sensors guard.
- Remove the guard.
- Slightly unscrew the fastening nut on the sensor.
- Pivot the sensor through 180°.

Sensor for the water level in the tank:

- Without water (not operating): it has a normally open «NO» contact

- With water (operating): it has a switched contact

- Same level sensor after a 180° rotation

- Without water (not operating): its contact is normally closed «NC»

-
-

-
- With water (operating): it has an open contact

PP PPS Nylon Equipment


Colour Black Opaque Grey
Temperature °C -20 / +75 -20 / +100 -10 / +120*
Min. liquid density 0.85
Degree of closure (d=1) 18mm
Degree of opening (d=1) 42mm
Max. current: 5A
Max. voltage: 30V

NB: A 24 Volt AC power supply (generated through the wiring in the student grid) is required for
the operation of the board which controls the level sensors. This board is fixed in the console
on the chato and comprises fuses which protect the various sensors.

11
CONTROL CONSOLE:

Unwired equipment:

- One emergency stop system (palm-button)


- One double On/Off push-button with lamp
- Three 24V lamps
- One key switch
- One 3-position switch
- Three free spaces for the addition of DIAM 22mm control accessories

POWER CONSOLE:

Consisting of:

- One circuit breaker switch


- One differential circuit breaker
- One magneto-thermal circuit breaker for the three-phase 400V
- One magneto-thermal circuit breaker for the single-phase 24V
- One general On/Off push-button
- One emergency stop circuit breaker

The fully-wired console is ready to protect the user and provide the necessary power
sources for the proper operation of the CHATO

12
Options for the console:
Option: GD
A special key switch and an indication lamp can be added to unlock the open
door protection system. In fact, this system allows an AUTHORISED person to
measure the electrical values on the grid wiring with the cabinet door open.
Please be warned that this operation must only be performed by an
AUTHORISED person or with the help of IP2X equipment.

OTHER OPTIONS:

- 4-20mA sensor for sensing the flowrate of water at the output of the motorised pump.

- Display showing the flowrate of water at the output of the motorised pump. This
display requires the flow sensor option (above).

Through programming, the display parameters can be locked. (the programming keys are no longer
enabled).
Press DSP until PRO3 is displayed. Then press the PAR key and you will be able to modify
programme 3.
PROGRAMME 3 – LOC

Displayed magnitudes and locking

DISPLAY PARAMETER RANGE AND UNIT COMMENTS


HI Max. value display LOC – locked Display options for the acquired
LO Min. value display rEd – display of the acquired value
tOt Counter display value
SP-1 Set point No.1 LOC – locked Options for the «settings
SP-2 Set point No. 2 rEd – - read only protection» mode
SP-3 Set point No. 3 ENt – reading and entry of a
SP-4 Set point No. 4 value
CodE Security code 0 to 250 Codes:
If other than 0: the settings are
locked
If 222: general unlocking

13
PREPARATION FOR THE COMMISSIONING OF THE CHATO MODEL

Note: The 150-litre tank should be filled ONLY when the unit is POWERED OFF

Filling the tank: - - Using a watering can or a hosepipe, fill the water tank
(river) via the specially-provided orifice.

- Fill the tank to the level of the handle

Note: if a water leak is noticed in the tanks


or piping, the CHATO system MUST be
secured.

Checking the manual valves:

Check that the manual valve and the drain tap are closed.
Check that the two manual valves for adjusting the flowrate of water at the output of the
motorised pump are open.

14
Connecting the sensor and water flow sensor display (optional):

- Connect the flow sensor at the output of the motorised pump.

- Connect the flow sensor lead to the rear of the display unit.

- Connect the unit’s power supply to the 220V socket behind the power console. A green lamp
indicates that a voltage is present.

The flowrate display is ready for operation.

Note on the flowrate:


- This is the quantity of water (volume in cubic metres) which flows into a container for each
unit of time (in seconds).
The symbol for the flowrate is the letter Q. The legal unit is m³/s (cubic metres per second).

Measuring the flowrate:


A flowmeter is used (also known as a flow regulator). When moving across the flowmeter,
the liquid causes the vane to rotate. This generates a current of between 4 and 20mA inclusive,
depending on the flowrate of the water.

Electrical connection:
The three-phase plug can then be connected to the network.
The power console’s circuit breaker switch must be set to position «0».

The CHATO system is ready for operation.

15
OPERATION OF THE CHATO MODEL

Students can come and test their wiring grids in the electrical switchgear cabinet at any
time.

Note:
Only an AUTHORISED person may carry out operations in the electrical switchgear
cabinet when it is switched on.

PRESENTATION OF THE ELECTRICAL SWITCH GEAR CABINET:

Disconnect the 4 quick connectors. The


student grid can be removed very easily from
the cabinet without the need for any tools.
Slide the grid upwards by a few centimetres
and then remove the bottom of the grid from
the notch.

Identifying the wired connectors in the electrical switchgear cabinet:

HARTING CONNECTOR B1 (per cable) 16 female pins (power supplies)

Number of pins Identification Designation


1 not specified
2 Neutral
3 not specified
4 Phase 1
5 not specified 400V three-phase
6 Phase 2
7 not specified
8 Phase 3
9 not specified
10 not specified
11 not specified
12 Neutral
13 not specified 24V single-phase
14 Phase
15 not specified
16 not specified
16
HARTING CONNECTOR B2 (per cable) 16 male pins (power for motorised pump)

Number of pins Identification Designation


1 U
Three-phase motorised
2 V
pump 1
3 W
4 not specified
5 Neutral Single-phase motorised
6 Phase pump
7 not specified or
8 not specified
9 U
Three-phase motorised
10 V
pump 2
11 W
12 not specified
13 not specified
14 not specified
15 not specified
16 not specified

HARTING CONNECTOR B3 (per cable) 24 male points (level sensors)

Number of pins Identification Designation


1 brown
LOW level
2 brown/green
3 white
AVERAGE level
4 white/green
TANK level sensors
5 grey/pink
HIGH level
6 grey/brown
7 not specified
8 not specified
9
Flow sensor contact «CO-DEB» option
10
11 not specified
12 not specified
13 red
LOW level
14 red/blue
15 pink
AVERAGE level
16 pink/white WATER TOWER level
17 yellow sensors
HIGH level
18 white/yellow
19 not specified
20 not specified
21 not specified
22 not specified
23 not specified
24 not specified

17
HARTING CONNECTOR B4 (per cable) 24 male pins (door control components)

Number of pins Identification Designation


1
UNWIRED (to be wired by the
student)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24

18
PRESENTATION OF THE STUDENT GRID:

Identifying the connectors on the student grid: (earth connected to the unit)

HARTING CONNECTOR B1 (on grid) 16 male pins (Power supplies)

Number of pins Identification Designation


1 not specified
2 Neutral
3 not specified
4 Phase 1
5 not specified 400V three-phase
6 Phase 2
7 not specified
8 Phase 3
9 not specified
10 not specified
11 not specified
12 Neutral
13 not specified 24V single-phase
14 Phase
15 not specified
16 not specified

19
HARTING CONNECTOR B2 (on grid) 16 female pins (Power supply for motorised
pumps)
Number of pins Identification Designation
1 U
Three-phase motorised
2 V
pump
3 W
4 not specified
5 Neutral Single-phase motorised
6 Phase pump
7 not specified
8 not specified
9 not specified
10 not specified
11 not specified
12 not specified
13 not specified
14 not specified
15 not specified
16 not specified

HARTING CONNECTOR B3 (on grid) 24 female pins (Level sensors)

Number of pins Identification Designation


1
LOW level
2
3
AVERAGE level
4
TANK level sensors
5
HIGH level
6
7 not specified
8 not specified
9 not specified
10 not specified
11 not specified
12 not specified
13
LOW level
14
15
AVERAGE level
16 WATER TOWER level
17 sensors
AVERAGE level
18
19 not specified
20 not specified
21 not specified
22 not specified
23 not specified
24 not specified

20
HARTING CONNECTOR B4 (on grid) 24 female pins (Door control components)

Number of pins Identification Designation


1
UNWIRED (to be wired by the
student)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24

21
PLACING THE STUDENT’S WIRED GRID IN THE CABINET:

Once the grid has been wired, it can be installed in the electrical switchgear cabinet for a test.
- The wired grid is fixed in the cabinet using the quick locking rails.

- Once the grid has been installed, connect the various connectors to the grid.
- Close the door of the cabinet.

- Engage the circuit breaker switch and the various circuit breakers.
- Press the door’s control components.
- Manipulate the manual valves and the water valve to develop the tests.

If electrical measurements need to be taken in the cabinet whilst the unit is switched on,
flick the key-operated switch (version with GD option: override of the safety system
preventing the door being opened during use). The door can then be opened without
cutting off the power to the cabinet.

Note: this operation must absolutely


be carried out by an experienced
person or using IP2X equipment.

22
CHATO TUTORIAL

The three tutorials presented on the following pages are examples of the CHATO system’s
operating cycles, but we should remember that other electrical wiring configurations are
possible.

Tutorial no.1) (simulation for filling the tank with water after a maintenance procedure).

- Activation of cycle using On/Off push-button and shown by an indication lamp.


- Filling the TANK to the high level.
- Indication by means of a lamp of the tank pump operation.
- If the water level in the tank is lower than the high level, the motorised tank pump is engaged by the
push-button.

- Draw the wiring schematic for the power and the control of the CHATO
- Establish the list of material necessary for the tutorial.
- Fix the various control and protection equipment as well as the ducts on the wiring grid.
- Carry out the wiring of the elements.
- Carry out the test and the start-up of the system.

Tutorial no. 2) (simulation of the operation of a drinking water distribution plant).

- Activation of cycle using On/Off push-button and shown by an indication lamp.


- Filling the TANK to the high level.
- Indication by means of a lamp of the tank pump operation.
- Filling the WATER TOWER when the water level reaches the average level of the tank.
- Indication by means of a lamp of the water tower pump operation.
- The tank pump will operate again when the water level reaches the low level.
- The water tower pump regulates the water level at the average level.
- Cycle stopped by pressing the STOP push-button.

- Draw the wiring schematic for the power and the control of the CHATO
- Establish the list of material necessary for the tutorial.
- Justify the coupling of the coils of the motorised pump according to the network voltage.
- Represent the wiring of the coils of the motorised pump according to the coupling selected.
- Fix the various control and protection equipment as well as the ducts on the wiring grid.
- Carry out the wiring of the elements.
- Carry out the test and the start-up of the system.
- Record the value of the intensity absorbed by the gear motor. Compare the value with that screen-
printed onto the console.
Note: this operation must absolutely be carried out by an experienced person or using IP2X
equipment.

23
REFERENCE TO THE SCHEMATIC OF THE CIRCUITS IN
DEVELOPED FORM

Definition of a schematic:
An electrical schematic is a symbolic and conventional representation of electrical installations.
It represents the various links between the elements of an installation, a set of apparatus or a
single piece of apparatus.
General layout of representation:
In the upper part of the schematic of the power circuits, the horizontal lines
represent the network. The various motors of the receiving apparatus are placed on shunts.
The control schematic is developed between two horizontal lines representing the two polarities.
Representation of the power circuits:
These are represented either in a unifilar form for simple cases (direct starting, etc…) or in a
multifilar form (star triangle starter, reverser...)
In the case of a unifilar representation, it is the number of oblique lines across the line
representing the connection which indicates how many similar conductors there are in the circuit
represented, for example two for a single-phase network, three for a three-phase network (cf. figure 1).
In order to allow the user to determine the section of the conductors, the electrical
characteristics of each receiver are indicated either in the schematic if it is simple, or in a key.
The various elements constituting the apparatus (coils, poles, auxiliary contact, etc ….) are not
represented on the schematic close to one another as they are in reality in the apparatus, but are
separated and are placed according to a layout which facilitates the comprehension of the operation.
Without exception, no link (interrupted line) must be reproduced on the schematic between
elements of the same apparatus.
To improve the clarity of the circuit schematics, letters and figures representing the identification
references which specify the nature of the apparatus are written on the left or at the bottom while the
identification of its terminals is indicated on the right or at the top (cf. figure 1).

1 2
3 4
5 6 (figure 1)

KM1

Representation of the control and indication circuits:

On the schematic of the control and indication circuits, the symbols of the control elements of
the contacts, the relays and other electrically controlled apparatuses, are laid out one after the
other, as far as possible in the order corresponding to their supply during normal operation.
Two horizontal lines or a "common conductor" represent the supply. The coils of the various
conductors and receivers, lamps, warning devices, clock, etc… are connected directly to the lower
conductor.

Other elements:
- auxiliary contacts,
- external control apparatus (button, mechanical control contacts, etc….), as well as the connection
terminals are represented at the top of the control unit.

24
NOTE
NOTE ONONTHE
THEROTATING
ROTATING CONTACT
CONTACT

Poles
1. Mobile contacts support of pole
2. Mobile contact of pole "F"
3. Auxiliary mobile contact "O"
4. Poles unit and chambers to cut arcing
5. Power supplies connection
6. Fixed contact of pole "F"
7. Fixed contact of pole "O"

Electromagnet
8. Base
9. Shock absorber of the electromagnet
10. Fixed part of the electromagnet
11. Dephasing rings
12. Attraction coil
13. Spring of the moving part of the
electromagnet 15. Slide allowing the addition of instantaneous
14. Moving part of the electromagnet and time-lag auxiliary contacts

Operating Principle

The contactor is in the detente position. The clearance distance between the poles and the fixed and mobile magnetic circuits is maximum.
The apparatus is energized. The mobile magnetic circuit moves towards the fixed magnetic circuit taking the mobile poles with it.
The fixed and mobile poles come into contact. At this moment, there remains an air-gap whose dimension e1 is called the clearance
dimension.
Apparatus under power. The final movement of the mobile magnetic circuit compresses the springs of the mobile poles to obtain strong
pressure of these against the fixed poles.
At the end of the movement of the mobile circuit, there remains an air-gap "e2" on the median branch making it possible to avoid staying in
a closed position due to a remnant flow when switching off the power.

25
The instantaneous contact blocks have 2 or
4 "O" or "F" contacts.
 They are fixed by a simple click to
the front face of the auxiliary
contacts, automatic locking
facilitates the assembly and
disassembly and ensures the
resistance to shocks and vibration.
 They are common to all the contact
sizes of the series 9-12-16-25-40-63.
 Their self-cleaning friction contacts
ensure good contact reliability.

1. Contact fixed on opening


2. Contact fixed on closing
3. Stirrup and captive screw
4. Locking latch
5. Box for 2 contacts
6. Mobile contact support
7. Spring recess for "O" contact
8. Mobile contact on opening
9. Guide for the contacts
10. Mobile contact on closing
11. Closing contact spring

Principle of automatic locking.

Principle of operation of the auto-cleaning contacts

1. With the apparatus at rest, the mobile contacts are at the bottom of the guide and displaced with respect to the fixed
contacts.
2. When the electromagnet closes, the mobile contacts come to rest against the fixed contacts in the same position as
previously.
3. The electromagnet finishes its movement by compressing the mobile contacts, by following the guide, effecting a movement
upwards leading to the friction on the fixed contacts.

26
COMPOSITION OF THE CONTACT:

1) The electromagnet:

The electromagnet is the ‘driving’ element of the contact.


Essentially, it has a magnetic circuit and a coil.
A slight air-gap is included in the magnetic circuit in the closed position to avoid any risk of
remanence. It is constructed either by removal of metal or by insertion of a magnetic material.

- AC type magnetic circuit:

- silicon steel sheet assembled with rivets to avoid losses due to hysteresis.
- laminated circuit in order to reduce eddy currents which occur in any metallic mass subject to an
alternating current.
- One or two dephasing rings to create a flux in the fixed part of the magnetic circuit which is
displaced with respect to the main flux to prevent cancellation of the force of attraction and thus
vibrations.

- D.C. type magnetic circuit:

There is no disadvantage in using a contact with D.C. current. On the other hand, the coil must
be different. As there is no formation of eddy current, it is thus preferable to use a massive steel
magnetic circuit.

2) The coil:

It creates the magnetic flux necessary for the attraction of the mobile armature.
It is made of enamelled copper wire.

3) The poles:

They are designed to establish or interrupt the current in the power circuit. They are equipped
with stainless material contacts whose mechanical resistance and resistance to arcing are very
good. They are often supplemented by an electric anti-arcing device.

4) Auxiliary contacts:

They ensure auto-supply, locking, controls, indication, etc.


There are two different types:

Type 'F' 3 1 Type 'O'

4 2

One can also find supplementary units including this type of contact and time-lag supplementary
units.

27
CARRYING OUT PRACTICAL WORK

KEY FOR THE PLATE + STUDENT GRID

Diagram Designations Qty Item reference


identification
Addition on S NEUTRAL addition for 25 to 40A circuit breaker 1 VZ-11
Addition on S Auxiliary contacts for circuit breaker 1 VZ-7
Aux KM1 Addition for 2F contact 1 LADN20
H1 + H2 + H3 GREEN-topped lamp for LED 3 ZB5AV033
H1 + H2 + H3 24V GREEN-bodied lamp with integrated LED 3 ZB5AVB3
KA1 + KA2 + KA3 2"o" + 3"c" auxiliary contact BOB 24V 3 CA2D32B7
KM1 + KM2 3kW/220V three-pole contact and 5.5kW/380V BOB 24V 3 LC1DT25B7
Lamp H11 16x35 lamp BA 15d 255V 5W 1 118920
Lamp H12 16x35 lamp BA 15d 24V 5W ref. B3524 1 118903
H11 + H12 light Indicator light 1 LT220-2
S1 Red key-operated emergency stop – diam. 40mm 2 XB5AS142
S2 Black-topped push-button 1 ZB5AA2
S2 «F" contact body 1 ZB5AZ101
S3 Red-topped push-button 1 ZB5AA4
S3 «O» contact body 1 ZB5AZ102
Raceway (m) 40mm (width) x 60mm (height) – with strips 2 36207
551 x 750mm grid 1 55456
Black plug for 22.5 drilling 4 ZB5SZ3
Unmarked label holder – yellow/white 7 ZBY4101
Circular «Emergency stop» label 1 ZBY9130

28
Tutorial no.1) (simulation for filling the tank with water after a maintenance procedure).
- Activation of cycle using On/Off push-button and shown by an indication lamp.
- Filling the TANK to the high level.
- Indication of tank pump operation by means of a lamp.
- If the water level in the tank is lower than the high level, the motorised tank pump is engaged by the
push-button.

Identifying the control components and level detectors


Stage of operation Identification letter
Low water level in the tank Nbb
Average water level in the tank Nbm
High water level in the tank Nbh
Emergency stop button S1
General operation S2
General shutdown S3
Motorised tank pump on S4
General on lamp H1
Motorised pump on lamp H2

29
Alim. Monophasé 230V Protection M/A général Détection du niveau HAUT Moto pompe BASSIN Alim. Monophasé 230V Moto pompe monophasée
230V 5,2A 50Hz 0,75KW
x12 13 Q1 14 1 F1 2 x3
L x2
N
1 x4
L
S1
2

x4

3 13
13 23
S2 KA1
4 14
KM1
14 33
x5

30
1 3 1 x5 x6

S3 Nbh KA2 KA2


2 4 2
x7
1

S4
2

x6 x8 x9

PE
A1 X1 A1 A1 X1

H1 H2
x14 A2 X2 A2 A2 X2
N
KA1 KA2 KM1
Alim. Monophasé 230V Protection M/A général Détection du niveau HAUT Moto pompe BASSIN Alim. Triphasée 400V Moto pompe triphasée

x12 13 Q1 14 1 F1 2 x3
L
1 x4
L3
S1 x6
L2
2
x8
L1
x4

3 13

S2 KA1
4 14

13 23 33

x5
SYSTEME CHATO EQUIPE D'UNE POMPE TRIPHASE
KM1
14 24 34

31
1 3 1

S3 Nbh KA2 KA2


2 4 2
x7 x1 x2 x3

Couplage Triangle
S4
2
Réseau 230V
I: 3,8A
x6 x8 x9 n : 2850tr/min
P : 0,75KW
50Hz

A1 X1 A1 A1 X1
Couplage Etoile
H1 H2
x14 A2 X2 A2 A2 X2 Réseau 400V
I: 2,2A PE
N n : 2850tr/min
KA1 KA2 KM1 P : 0,75KW
50Hz
Caption:

- Q1: Isolator
- F1: Fuse
- KA1: Main relay
- KA2: High level sensor relay
- KM1: Motorised pump power contact

Operation:

- Once the emergency protections and emergency stop are engaged, press S2, relay KA1 closes and
lamp H1 lights up.
- The motorised pump is engaged and lamp H2 lights up.
- The water level in the TANK rises to the HIGH level.
- When it reaches this level, relay KA2 is engaged, cuts the power to KM1 and the motorised pump
stops.
- As soon as the level falls below the HIGH level, by pressing push-button S4 the motorised pump will
be engaged and will stop again at the HIGH level.
- At any moment, pressing button S3 stops the cycle.
- In the event of a problem, pressing the emergency stop button S1 stops the cycle.

Handling:

- Check that the time taken for the TANK to fill with water varies depending on the position of the
valve on the motorised pump outlet.

- Measure different values of the electric current consumed by the motorised pump depending on a
variation in the position of the valve. This manipulation is only possible if the GD option (override of
the safety system preventing the door being opened during use) has been selected. Note: this
operation must absolutely be carried out by an experienced person or using IP2X equipment.
- When the TANK is filling, measure the load characteristic of the motorised pump (I = f(Q), where Q
is the flowrate in m³/h). This measurement is possible if the flow sensor has been selected.

32
Tutorial no. 2) (simulation of the operation of a drinking water distribution plant).
- Activation of cycle using On/Off push-button and shown by an indication lamp.
- Filling the TANK to the high level.
- Indication of tank pump operation by means of a lamp.
- Filling the WATER TOWER when the water level reaches the average level of the tank.
- Indication by means of a lamp of the water tower pump operation.
- The tank pump will operate again when the water level reaches the low level.
- The water tower pump regulates the water level at the average level.
- Cycle stopped by pressing the STOP push-button.

Identifying the control components and level detectors


Stage of operation Identification letter
Low water level in the tank Nbb
Average water level in the tank Nbm
High water level in the tank Nbh
Low water level in the water tower Ncb
Average water level in the water tower Ncm
High water level in the water tower Nch
Emergency stop button S1
General operation S2
General shutdown S3
General on lamp H1
Motorised tank pump on lamp H2
Motorised water tower pump on lamp H3

33
Alim. Monophasé 230V Protection M/A général Détection du niveau HAUT Moto pompe BASSIN Moto pompe CHATEAU D'EAU Alim. Triphasée 400V Moto pompe triphasée Moto pompe monophasée
230V 5,2A 50Hz 0,75KW
x12B1 13 Q1 14 1 F1 2 x5B4
L
1 x4
L3
S1 x6
2
L2
x8
L1
x6B4 x2
N

3 13

S2 KA1
4 14

13 23 33 13 23

x2B4

34
KM2 KM1
14 24 34 14 33

1 3 1 3 13

S3 Nbh KA2 KA2 Nbm KA3 KA3


2 4 2 4 14
x1B3 x4B3 x15B3 x1 x2 x3 x5 x6

Nbb Ncm Couplage Triangle

Réseau 230V
I: 3,8A
x3B4 x6B3 x15B4 x16B4 n : 2850tr/min
P : 0,75KW
50Hz

A1 X1 A1 A1 X1 A1 A1 X1
Couplage Etoile
H1 H2 H3
x14B1 x17B4 A2 X2 A2 A2 X2 A2 A2 X2 Réseau 400V
N I: 2,2A PE PE
n : 2850tr/min
KA1 KA2 KM1 KA3 KM2 P : 0,75KW
50Hz
Alim. Monophasé 230V Protection M/A général Détection du niveau HAUT Moto pompe BASSIN Moto pompe CHATEAU D'EAU Alim. Triphasée 400V Moto pompe triphasée Moto pompe triphasée

x12B1 13 Q1 14 1 F1 2 x5B4
L
1 x4
L3
S1 x6
2
L2
x8
L1
x6B4

3 13
SYSTEME CHATO EQUIPE DE 2 POMPES TRIPHASES
S2 KA1
4 14

13 23 33 13 23 33

x2B4
KM2 KM1
14 24 34 14 24 34

1 3 1 3 13

S3 Nbh KA2 KA2 Nbm KA3 KA3

35
2 4 2 4 14
x1 x2 x3 x4 x5 x6
x1B3 x4B3 x15B3

Nbb Ncm Couplage Triangle

Réseau 230V
I: 3,8A
x3B4 x6B3 x15B4 x16B4 n : 2850tr/min
P : 0,75KW
50Hz

A1 X1 A1 A1 X1 A1 A1 X1
Couplage Etoile
H1 H2 H3
x14B1 x17B4 A2 X2 A2 A2 X2 A2 A2 X2 Réseau 400V
N I: 2,2A PE PE
n : 2850tr/min
KA1 KA2 KM1 KA3 KM2 P : 0,75KW
50Hz
Caption:

- Q1: Isolator
- F1: Fuse
- KA1: Main relay
- KA2: Motorised TANK pump power management relay
- KM1: Motorised TANK pump power contact
- KA3: Motorised WATER TOWER pump power management relay
- KM2: Motorised WATER TOWER pump power contact

Operation:

For efficient operation, the manual flowrate adjustment valve at the output of the motorised
WATER TOWER pump must be set to a flowrate slightly above that of the water evacuation
valve.
The level sensor Ncm must be rotated through 180° so that its contact opens when the water
reaches its level. To do this, slightly unscrew the plastic nut on the outside of the tank from the
sensor and rotate it through 180°. Retighten the nut. This operation must be performed when
the power is off and the tank empty.

- Once the emergency protections and emergency stop are engaged, press S2, relay KA1 closes and
lamp H1 lights up.
- Contact KM1 fixes and controls the motorised TANK pump and lamp H2 lights up.
- The water level in the TANK increases and when it reaches the average level it engages relay KA3
which controls contact KM2. The motorised WATER TOWER pump and the lamp are then powered.
- When the water level reaches the HIGH level, relay KA2 is engaged, cuts the power to KM1 and the
motorised TANK pump stops.
- When the water level in the tank reaches the LOW level, relay KA2 is cut and contact KM1 is
engaged again and it controls the motorised TANK pump.
- The water level in the WATER TOWER is maintained at the average level regardless of the valve's
water flow setting.
- At any moment, pressing button S3 stops the cycle.
- In the event of a problem, pressing the emergency stop button S1 stops the cycle.

Handling:
- Check that the time taken for the TANK to fill with water varies depending on the position of the
valve on the motorised pump outlet.
- Measure different values of the electric current consumed by the motorised TANK pump depending
on a variation in the position of the valve. This manipulation is only possible if the GD option
(override of the safety system preventing the door being opened during use) has been selected.
Note: this operation must absolutely be carried out by an experienced person or using IP2X
equipment.
- Measure different values of the electric current consumed by the motorised WATER TOWER pump
depending on a variation in the position of the valve. This manipulation is only possible of the GD
option has been selected. Note: this operation must absolutely be carried out by an
experienced person or using IP2X equipment.
- When the TANK is filling, measure the load characteristic of the motorised pump (I = f(Q), where Q
is the flowrate in m³/h). This measurement is possible if the flow sensor has been selected.
- When the TANK is filling, measure the load characteristic of the motorised pump (I = f(Q), where Q
is the flowrate in m³/h). This measurement is possible if the flow sensor has been selected.

36
PROCEDURE FOR A SIMPLE WIRING REPAIR ELECTROTECHNICS ON A GRID

A) ANALYSIS OF REASONS FOR FAULTS:


Despite the very large number and broad variety of possible disturbances, they may be attributed to:
- a complete power outage in the circuit,
- a "bad contact" which causes resistance in the circuit,
- accidental contact between two resistors.
These faults may occur together, or one may be caused by the other.

B) EXAMPLES OF «CLASSIC» FAULTS THAT BE ENCOUNTERED IN


ELECTROTECHNICAL WIRING:

ANOMALIES MAIN POSSIBLE CAUSES MAIN FINDINGS


- Receiver damage. - Equipment stops operating if powered by two
- Control contact damage. conductors
- Blown fused circuit breakers or - Partial or unbalanced stoppage of phases in
Power cut in the circuit
triggering of the circuit breaker. the case of a three-phase power supply.
- Connection error.
- Broken conductor.
- Loose connections. - Voltage decrease at the receiver terminals
Bad contact» The circuit - Oxidation of contacts. (intermittent operation).
is not completely - Overheating of a terminal - Major overheating due to the joule effect and
broken: a contact connection which is too small. sparking at the contact point.
resistance has been - Poor welding (typical in - Production of interference waves.
introduced electronic wiring) - Contact damage and oxidation.

- Insulation damage: - Triggering of protection devices.


a) through overheating - Damaged control device contacts.
b) through mechanical stress. - Involuntary outage of power to conductors.
Contact between two
- Connection errors.
conductors subjected to
- Bad connections (conductors
different potentials.
too stripped).
- Contact with a metal foreign
body.
- Modification of receiver operation, in other
words:
Contact between two
a) due to a complete shutdown.
conductors subjected to - ditto.
b) due to an operation limited to some of
equal potentials.
the functions to perform.

- Insulation fault due to: - triggering of the protection device if there is


a) assembly fault. complete contact between phase and earth.
Earthing b) Insulation damage: - voltage decrease on the receiver terminals.
c) Moisture. - Live metal parts (risk of serious accidents).
d) Conductive dust

37
4°) Harting connectors and additional grid for pupil:

Example of equipment for a pupil:

QT Designation Reference

4) Plastic base plates Réf. : HA-GR1

1) Male connector 16 pins Réf. : HA-M16

1) Female connector 16 pins Réf. : HA-F16

2) Female connector 24 pins Réf. : HA-F24

Removable grid
1) (Dimension up to 725 X 525mm Réf. : Nous consulter

38
CEM COMPLIANCE DECLARATION
EQUIPMENT: CHATO / CHATO ECO / CHATO3 / CHATO4

THE ABOVE EQUIPMENT SATISFIES THE FOLLOWING CEI STANDARDS

DIRECTIVES
89/336/CEE
92/31/CEE
93/68/CEE

ELECTROMAGNETIC COMPATIBILITY
GENERIC STANDARD CONCERNING EMISSION EN50081-1 (1992)
PART 1: LIGHT INDUSTRY, COMMERCE, RESIDENTIAL USE
RADIO EMISSION EN55022 GRADE B
HARMONICS EN61000-3-2 1995
VOLTAGE VARIATION EN61000-3-3 1987
LOW VOLTAGE DIRECTIVE EN61010-1 1993

ELECTROMAGNETIC COMPATIBILITY
GENERIC STANDARD CONCERNING IMMUNITY EN50082-1 (1992)
PART 1: LIGHT INDUSTRY, COMMERCE, RESIDENTIAL USE
ELECTROSTATIC IEC 1000-4-2 1995
DISCHARGE
IMMUNITY TO RADIATION IEC 1000-4-3 1995
RAPID TRANSIENTS IEC 1000-4-4 1995
IMMUNITY TO IEC 1000-4-5 1995
OVERVOLTAGES
MAINS POWER IEC 1000-4-11 1994
INTERRUPTION

CEM COMPLIANCE DECLARATION

I declare that the CHATO products “all extensions” were produced in compliance with the product
technical specifications and comply in all respects with EC norms and standards, in particular with
IEC1010 / NF-C15-100 / decree 88-1056 / order dated 13-12-88.

Gradignan France

M. LABORDE
Technical Operations Manager

39

You might also like