You are on page 1of 7

C-FIX 1.121.0.

0
Database version
2023.12.14.12.55
Date
19/01/2024

Grow Vertex Co., Ltd.

1 Empire Tower Fl. 47th Unit 4703


(River 38)
South Sathorn Rd., Yannawa, Sathorn,
Bangkok 10120
Phone: +66 2 6863461
Fax: +66 2 0266874
info@growvertex.co.th
www.growvertex.co.th

Design Specifications
Anchor
Anchor system fischer Bolt Anchor FAZ II Plus
Anchor Bolt Anchor FAZ II Plus 16/60 R,
stainless steel
Calculated anchorage 125 mm
depth
Design Data Anchor design in Concrete according European Technical
Assessment ETA-19/0520, Option 1,
Issued 24/05/2023

Geometry / Loads / Scale units


mm, kN, kNm

Value of design actions (including

partial safety factor for the load) Static

Not drawn to scale

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 1
C-FIX 1.121.0.0
Database version
2023.12.14.12.55
Date
19/01/2024

Input data

Design method TR055/ETAG 001, Annex C, Method A


Base material Customized, Test specimen: Cylinder 150 x 300 mm,
Compressive strength = 32.0 N/mm²
Concrete condition Cracked, dry hole
Reinforcement No or standard reinforcement. No edge reinforcement. With
reinforcement against splitting
Drilling method Hammer drilling
Installation type Pre-positioned installation
Annular gap Annular gap not filled
Type of loading Permanent-Transient/Static
Base plate location Base plate flush installed on base material
Base plate geometry 350 mm x 400 mm x 20 mm
Profile type Square tube hot formed (QSH 180x5)

Design actions *⁾
# NSd VSd,x VSd,y MSd,x MSd,y MT,Sd Type of loading
kN kN kN kNm kNm kNm
1 -4.90 6.00 0.00 0.00 17.50 0.00 Permanent-Transient/Static

*⁾ The required partial safety factors for actions are included

Resulting anchor forces


Tensile action Shear Action Shear Action x Shear Action y
Anchor no. kN kN kN kN
1 19.98 1.00 1.00 0.00
2 0.00 1.00 1.00 0.00
3 19.98 1.00 1.00 0.00
4 0.00 1.00 1.00 0.00
5 19.98 1.00 1.00 0.00
6 0.00 1.00 1.00 0.00

max. concrete compressive strain : 0.16 ‰


max. concrete compressive stress : 5.2 N/mm²
Resulting tensile actions : 59.93 kN , X/Y position ( -125 / 0 )
Resulting compression actions : 64.83 kN , X/Y position ( 154 / 0 )

Resistance to tension loads

Action Capacity Utilisation βN


Proof kN kN %
Steel failure * 19.98 59.29 33.7
Pullout failure * 19.98 22.68 88.1
Concrete cone failure 59.93 76.56 78.3

* Most unfavourable anchor

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 2
C-FIX 1.121.0.0
Database version
2023.12.14.12.55
Date
19/01/2024

Steel failure

( NRd,s )

NRk,s γMs NRd,s NSd βN,s


kN kN kN %
83.00 1.40 59.29 19.98 33.7

βN,s
Anchor no. % Group N° Decisive Beta
1 33.7 1 βN,s;1
2 0.0 2 βN,s;2
3 33.7 3 βN,s;3
4 0.0 4 βN,s;4
5 33.7 5 βN,s;5
6 0.0 6 βN,s;6

Pullout failure

( NRd,p )

NRk,p Ψc γMp NRd,p NSd βN,p


kN kN kN %
34.02 1.260 1.50 22.68 19.98 88.1

The given Psi,c-factor may has been determined by interpolation.

βN,p
Anchor no. % Group N° Decisive Beta
1, 3, 5 88.1 1 βN,p;1

Concrete cone failure

( NRd,c )

Eq. (5.2)

Eq. (5.2a)

Eq. (5.2c)

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 3
C-FIX 1.121.0.0
Database version
2023.12.14.12.55
Date
19/01/2024

Eq. (5.2d)

Eq. (5.2e)

NRk,c γMc NRd,c NSd βN,c


kN kN kN %
114.84 1.50 76.56 59.93 78.3

βN,c
Anchor no. % Group N° Decisive Beta
1, 3, 5 78.3 1 βN,c;1

Resistance to shear loads

Proof Action Capacity Utilisation βV


kN kN %
Steel failure without lever arm * 1.00 56.88 1.8
Concrete pry-out failure 6.00 408.31 1.5

* Most unfavourable anchor

Steel failure without lever arm

( VRd,s )

VRk,s γMs VRd,s VSd βVs


kN kN kN %
71.10 1.25 56.88 1.00 1.8

βVs
Anchor no. % Group N° Decisive Beta
1 1.8 1 βVs;1
2 1.8 2 βVs;2
3 1.8 3 βVs;3
4 1.8 4 βVs;4
5 1.8 5 βVs;5
6 1.8 6 βVs;6

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 4
C-FIX 1.121.0.0
Database version
2023.12.14.12.55
Date
19/01/2024

Concrete pry-out failure

( VRd,cp )

Eq. (5.6)

Eq. (5.2)

Eq. (5.2a)

Eq. (5.2c)

Eq. (5.2d)

Eq. (5.2e)

VRk,cp γMc VRd,cp VSd βV,cp


kN kN kN %
612.47 1.50 408.31 6.00 1.5

βV,cp
Anchor no. % Group N° Decisive Beta
1, 2, 3, 4, 5, 6 1.5 1 βV,cp;1

Utilization of tension and shear loads

Tension loads Utilisation βN Shear Loads Utilisation βV


% %
Steel failure * 33.7 Steel failure without lever arm * 1.8
Pullout failure * 88.1 Concrete pry-out failure 1.5
Concrete cone failure 78.3
* Most unfavourable anchor

Resistance to combined tensile and shear loads


Eq. (5.8a)
Proof successful Eq. (5.8b)

Eq. (5.8c)

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 5
C-FIX 1.121.0.0
Database version
2023.12.14.12.55
Date
19/01/2024

Base plate thickness


Stress distribution pattern within the Base plate details
anchor plate
Anchor plate thickness t = 20 mm
Base plate material S 275
E-modulus E = 210,000 N/mm²
Yield strength Rp,0,2 = 275 N/mm²
Safety factor γM = 1.0
Poisson's ratio ν = 0.3
Utilisation η = 79 %

Profile type Square tube hot formed (QSH


180x5)

Technical remarks
All data and information in the software is based on fischer products and common engineering knowledge. Please
check all the proof results against local valid standards and approvals.
As fischer is not the design office, the attached is no guarantee for incorrect input or assumptions. Any
recommendations have to be approved by the building-authority or project engineer. Results are valid only for
anchor system calculated in the attached. If any part of the system is changed, it will invalidate this report and new
calculations would be required. The calculation was done under the assumption that a sufficient
splitting reinforcement is available. In this case the spliiting
failure can be omitted.
The transmission of the anchor loads to the supports of the concrete member shall be shown for the ultimate limit state and
the serviceability limit state; for this purpose, the normal verifications shall be carried out under due consideration of the
actions introduced by the anchors. For these verifications the additional provisions given in the current design method shall
be taken into account.
As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate (if present) must
be sufficiently stiff. The C-Fix anchor plate design is based on a proof of stresses and does not allow a statement about the
stiffness of the plate. The proof of the necessary stiffness is not carried out by C-Fix.

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 6
C-FIX 1.121.0.0
Database version
2023.12.14.12.55
Date
19/01/2024

Installation data
Anchor
Anchor system fischer Bolt Anchor FAZ II Plus
Anchor Bolt Anchor FAZ II Plus 16/60 R, Art.-No. 564629
stainless steel

Accessories Blow-out pump ABG big Art.-No. 567792


SDS Plus-V II 16/160/210 Art.-No. 531827

Installation details
Thread diameter M 16
Drill hole diameter d0 = 16 mm
Drill hole depth h1 = 148 mm
Calculated anchorage hef = 125 mm
depth
Installation depth hnom = 143 mm
Drilling method Hammer drilling
Borehole cleaning Clear the borehole with a hand
blower.
Installation type Pre-positioned installation
Annular gap Annular gap not filled
Installation torque Tinst = 110.0 Nm
Socket size 24 mm
Base plate thickness t = 20 mm
Total fixing thickness tfix = 20 mm
Tfix,max tfix, max = 20 mm

Base plate details


Base plate material S 275
Base plate thickness t = 20 mm
Clearance hole in base df=18 mm
plate

Attachment
Profile type Square tube hot formed
(QSH 180x5)

Anchor coordinates

x y
Anchor no. mm mm
1 -125 150
2 125 150
3 -125 0
4 125 0
5 -125 -150
6 125 -150

The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty in
the license agreement of the Software.

Page 7