PT. TRAFOINDO PRIMA PERKASA Spec. No. PT.

TRAFOINDO PRIMA PERKASA

7. APPROXIMATE WEIGHT AND DIMENSION WITHOUT PACKING : to be informed later on


7-1 The outline drawing of the transformer will be submited to customer

SPECIFICATION FOR TRANSFORMER


8. ACCESSORIES : The transformer will be furnished with all necessary accessories as follow :
To. Date
Spec No. GENERAL ACCESSORIES SPECIAL ACCESSORIES
- HV Porcelain Bushing on Cover Ö Plug in Bushing 50 mm2 c/w Straight Connector on Cover
1. TYPE ONAN : Oil immersed self cooled / in / out door use / step-up / step-down / hermetically sealed Ö LV Porcelain Bushing on Cover
distribution transformer - Oil Level Indicator w/o Contact Ö Integrated Safety Device c/w Contact
- Thermometer w/o Contact - Magnetic Oil Level Gauge c/w Alarm Contact
2. SERVICE CONDITION : The transformer will be installed at the altitudes below 1.000 meters and the maximum Ö Manual Off-Load Tap Changer - Dial Thermometer c/w Alarm & Trip Contact
ambient temperature does not exceed
o
40 C Ö Name Plate - Buchholz Relay c/w Alarm & Trip Contact
Ö Earth Terminal - Conservator c/w Sampling Valve
3. STANDARD : The transformer is designed, manufactured and tested in accordance with : Ö Radiator - Breather c/w Silicagel
IEC 600-76 Ö Drain Valve - Air-filled LV Junction Box
- Sampling Valve - HV/LV Cable Box
4. RATING Ö Lifting Lug - N2 Filling Valve
4-1 Number of Phase : 3 phase 4-2 Frequency : 50 Hz - Jacking Lug - Pressure Vacuum Gauge c/w Bleeder
4-3 Primary Voltage : 20 kV 4-4 Secondary Voltage : 400/231 Volt Ö Roller - Pressure Relief Valve w/o Contact
Winding Connection : DELTA Winding Connection : WYE - Square Hole - Pressure Relief Device c/w Alarm Contact
4-5 Rated Capacity (total) : 500 kVA - Skid Base ( Pad Mounted ) - Radiator Fans
Incase of double primary voltage, capacity will be : - Hanger ( Pole Mounted ) - Radiator Valves
at : - kV Rated Capacity : - kVA Ö Oil Filter Valve - Terminal Control Box
at : - kV Rated Capacity : - kVA - Voltage Change Over Board - Neutral CT
Incase of double secondary voltage, capacity will be : - Thermometer Pocket
at : - V Rated Capacity : - kVA - Winding Thermometer c/w Alarm & Trip Contact
at : - V Rated Capacity : - kVA - CT for Winding Thermometer
4-6 Additional Taps on High Voltage : +/- 2.5 % & +/- 5 % ( 5 Taps ) - Sudden Pressure Rise Relay + Seal in Relay c/w Alarm & Trip Contact
9. ADDITIONAL INFO : - Ladder
5. POLARITY AND PHASOR RELATIONSHIP : The transformer will be subtractive polarity for single phase and
phasor relationship for three will be Dyn 5 DESCRIPTION

6. ELECTRIC PERFORMANCE :
Primary Voltage Secondary Voltage
6-1 Insulation Class : 24 kV 1.1 kV
6-2 Basic Impulse Level : 125 kV - kV
6-3 Applied Voltage Test During 1 Minute : 50 kV 3 kV
6-4 Induced Voltage Test : Apply 2 times of the rate voltage at 350 cycles per second for 18 second
o
6-5 Temperature Rise : The coil temperature rise measured by resistance method will not exceed 65 C
o
and the oil temperature rise will not exceed 60 C
6-6 Losses at Rated Voltage 20 / 0.4 kV 10. NOTE :
No Load Losses : 1,000 Watt
Load Losses ( at 75 oC ) : 5,800 Watt
Total Losses : 6,800 Watt
6-7 Efficiency at % Rated Capacity : 100 75 50 25 %
at P.F. = 1,0 : 98.66 98.88 99.03 98.92 %
6-8 Exciting Current : 1.90 % Date of Approval :
6-9 Percent Impedance : 4.00 % PROPOSER :
6 - 10 Voltage Regulation at P.F. = 1,0 : 1.23 %
Voltage Regulation at P.F. = 0.8 : 3.25 % mi