Design Queries Knowledgebase: Protection of MV cables in Basement

RefNo PAW-DQ-1179

Subject Protection of MV cables in Basement

Consultant Perkins_Will

Discipline EL

Date 17/03/2010

Parcels 4.01; 4.10; 2.11

Query Item Kindly advise if any specific protection from physical damage (ex. L-shaped
concrete attic) is required at basement levels for the protection of the MV cable
trays routed inside the basement, specifically above car parks and circulation
areas.
Response 1) Routing from the manhole, outside the parcel, to the SEC room: A closed
concrete trench in basement 1 ceiling is to be provided along with side
openings for access every 5-10 m .
2) Routing from SEC room to RMUs: Cable tray (horizontal routing) , and
cable ladder (vertical routing).

Content Type: Query


Created at 18/03/2010 12:52 PM by Ghassan Chkaiban
Last modified at 18/03/2010 12:52 PM by Ghassan Chkaiban