Professional Documents
Culture Documents
L DESIGN 1
THIS COURSE DEALS WITH THE STUDY OF ELECTRICAL SYSTEM
DESIGN, INSTALLATION AND COST ESTIMATION FOR SINGLE AND
MULTI-FAMILY DWELLING UNITS GUIDED BY THE PROVISIONS OF
THE PHILIPPINE ELECTRICAL CODE (PEC) AND OTHER RELEVANT
LAWS AND STNDARDS.
[
FULL LOAD CURRENT IN AMPERES
SINGLE PHASE ALTERNATING - CURRENT MOTORS
(Table 4.1)
FULL-LOAD
CURRENT
TWO- PHASE
ALTERNATING
CURRENT
MOTORS (4-
WIRE)
(Table 5.1)
FULL-LOAD CURRENT
THREE-PHASE ALTERNATING-CURRENT
MOTORS
(Table 6.1)
CONVERSION TABLE OF LOCKED-ROTOR CURRENTS
FOR SELECTION OF DISCONNECTING
MEANS AND CONTROLLERS
AS DETERMINED FROM HORSEPOWER AND
VOLTAGE RATING
(Table 7.1)
ALLOWABLE
AMPACITIES OF SINGLE INSULATED
CONDUCTORS, RATED 0-2000VOLTS, IN FREE AIR
BASED ON AMBIENT AIR TEMPERATURE OF 30ºC
(Table 11.1)
AMPACITY CORRECTION FACTORS
(Table 12.1)
(Table 14.1)
ALLOWABLE AMPACITIES FOR SINGLE INSULATED
CONDUCTORS, RATED 0-2000VOLTS, 150º TO 250ºC, IN
FREE AIR BASED ON AMBIENT AIR
TEMPERATURE OF 40ºC
(Table 15.1)
AMPACITY CORRECTION FACTORS
(Table 16.1)
(b) Dwelling units. In every kitchen, family room, dining room, breakfast
room, living room, parlor, library, den, sun room, bedroom, recreation room,
or similar rooms, receptacle outlets shall be installed so that no point along
the floor kine in any wall space is more than 1800 mm, measured
horizontally, from an outlet in that space, including any wall space 600 mm
or more in width and the wall space occupied by sliding panels in exterior
walls. The wall space afforded by fixed room dividers, such a free-standing
bar type counters, shall be included in the 2 meter measurement.
Outlets in other section of the dwelling unit for special appliances, such as
laundry equipment, shall be placed within 1800 mm of the intended location
of the appliance.
At least one receptacle outlet shall be installed for the laundry.
4.In other than one-family dwellings where laundry facilities are not be
installed or permitted, a laundry receptacle shall not be required.
(a) Dwelling units: At least one wall switch controlled lighting outlet shall be
installed in every habitable room, in bathrooms, hallways, stairways and
attached garage: and at outdoor entrances
FEEDERS:
Minimum size or rating. Feeder conductors shall have an ampacity not lower
than required to supply the load . The minimum sizes shall be as specified in
(a) and (b) below under the conditions stipulated. Feeder conductors for a
one family dwelling or amobile home need not be larger than service
entrance conductors.
(a) For specified circuits. The feeder conductors shall not be smaller than 5.5
square mm where the load supplied consists of the following number and
types of circuits: (1) Two or more 2-wire branch circuits supplied by a 2-wire
feeder. (2) MOre than two 2-wire branch circuits supplied by a 3-wire feeder
(3) Two or more 3-wire branch circuits supplied by a 3-wire feeder
(c) Overload feeders. Where at any time feeder conductors are or will be
overloaded the feeder conductors shall be increased in ampacity to
accommodate the ctual load served.
EXCEPTION: When the computed load for multifamily dwelling under the
section without cooking load exceeds that computed under this section for
the identical load plus electric cooking exceeds that computed for the
identical load plus the electric cooking, the lesser of the loads may be used.
(3) Each dwelling unit is equipped with either electric space heating or air
conditioning or both
Feeders and service-entrance conductors whose demand load is determined
by this optional calculation shall be permitted to have the neutral load
determined by this section
the connected load to which the demand factors apply shall include the
following:
(1)1500 watts for each 2-wire, 20 A small appliance branch circuit and each
laundry branch circuit
(2) 24 watts per square meter for general lighting and general use
receptacles
(3) The nameplate rating of all appliances that are fastened in place,
permanently connected or located to be on a specific circuit, ranges, wall
mounted ovens, counter-mounted cooking units, clothes dryer, water heaters
and space heaters
If water heater elements are so interlocked that all elements cannot be used
at the same time, the maximum possible load shall be considered the
nameplate load.
(4)The nameplate A or kVA rating of all motors and of all low-power factor
load.
(5) The larger of the air conditioning load or the space heating load.