Professional Documents
Culture Documents
ASPE Grease Interceptors
ASPE Grease Interceptors
Interceptors
CEU 313
November 2022
Note: In determining your answers to the CE questions, use only the material presented in the corresponding continuing education article. Using information from other
materials may result in a wrong answer.
Grease Interceptors
Reprint from Plumbing Engineering Design Handbook, Volume 4 – Chapter 8.
All rights reserved.
The purpose of a grease interceptor is to intercept and collect free-floating fats, oils, and grease (FOG) from a commercial or institutional
kitchen’s wastewater discharge, thereby preventing the deposition of pipe-clogging FOG in the municipal sanitary drainage system. Grease
interceptors are required to receive the drainage from fixtures and equipment with FOG-laden wastes, including but not limited to pot sinks,
soup kettles or similar devices, wok stations, floor drains or sinks into which kettles are drained, automatic hood-wash units, pre-rinse sinks,
and dishwashers without grinders. Residential dwellings seldom discharge FOG in such quantities as to warrant a grease interceptor.
Grease interceptors typically come in one of two basic types. The first type is called a hydromechanical grease interceptor (HGI), previously
referred to as a grease trap. These are typically thermoplastic (such as high-density polyethylene [HDPE], low-density polyethylene [LDPE],
or polypropylene), fiberglass (FRP), coated steel, or stainless-steel manufactured units, predominately located indoors at a centralized location
in proximity to the fixtures served or at the discharging fixture point of use. They are relatively compact in size and utilize hydraulic flow
characteristics, internal baffling, air entrainment, and the difference in the specific gravities between water and FOG to separate and retain
FOG from the fixture waste stream. HGIs are specified by flow in gallons per minute (gpm) or liters per second (L/s) and generally require
an external or integral flow control device (vented or non-vented) to prevent the incoming flow from exceeding the rated flow for the
interceptor. The standards governing the installation, testing, and maintenance of HGIs are PDI G101: Testing and Rating Procedure for
Grease Interceptors, ASME A112.14.3: Grease Interceptors, and CSA B481: Grease Interceptors.
The second type is the gravity grease interceptor (GGI). These may be manufactured from fiberglass, coated prefabricated steel, or
thermoplastics or are engineered, prefabricated concrete-constructed units. (Larger units may be field-fabricated.) They typically are located
outside due to their large size and receive FOG discharge waste from all required fixtures within a given facility. GGIs use Stokes’ law of
gravity separation to separate FOG from the facility’s waste stream prior to it entering the municipal drainage system. GGIs are specified by
volume, typically 300 gallons (1,136 L) or larger, and do not require a flow control device. The standard for the design and construction of
gravity grease interceptors is IAPMO/ANSI Z1001: Prefabricated Gravity Grease Interceptors.
Other FOG retention and removal devices are categorized as either grease removal devices (GRDs) or FOG disposal systems (FDSs).
Technically, these are considered hydromechanical grease interceptors since they also utilize flow controls.
Note: It is important to understand that FOG retention and removal are a continuing evolution of technology. The types of interceptors
currently on the market are proprietary and may include features specifically inherent to one particular manufacturer. The purpose of the
equipment descriptions contained in this chapter is to expose the designer to the basic types of FOG treatment equipment presently available
as currently defined and listed within the model codes and relevant product standards.
PRINCIPLES OF OPERATION
Grease interceptors operate on the principle of separation by flotation alone over time or by fluid mechanical forces in conjunction with
flotation according to Stokes’ law. Generally, FOG globules have a specific gravity in the range of 0.87 to 0.93, whereas water has a specific
gravity of 1.0.
All interceptor designs employ the difference between the specific gravity (density) of water and that of the FOG. If the specific gravity
of the FOG is close to that of water, the globules will rise more slowly. If the specific gravity difference between the grease and the water is
larger, the rate of separation will be faster.
The rise rate of a FOG globule is inversely proportional to the viscosity of the wastewater. The rate of ascension will be faster when the
carrier fluid is less viscous and vice versa. FOG globules rise more slowly at lower temperatures and more rapidly at higher temperatures. FOG,
especially when hot or warm, has less drag, is lighter than water, and does not mix well with water. The final velocity for a spherical particle,
known as its floating velocity, may be calculated using Newton’s equation for frictional drag with the driving force, shown in Equation 8-1:
Equation 8-1
Cd A w v2
Fd = =( p – w )gV
2
This yields the following mathematical relationship:
Equation 8-2
4 g ( – )
√
w p x
v= x x
3 Cd w
D
where
Fd = Drag force, pound-force or Newtons (Note: 1.0 pound-force = 1.0 slug-foot/sec/sec. 1.0 Newton =
1.0 kilogram-meter/sec/sec.)
Cd = Drag coefficient, dimensionless
A = Projected area of the particle, D2/4 for a sphere (not the surface area)
v = Relative velocity between the particle and the fluid, feet per second (m/s)
w = Mass density of water, 1.94 slug per cubic foot (1,000 kg/m ) (Note: 32.2 pound-mass = 1 slug.)
3
Experimental values of the drag coefficient have been correlated with the Reynolds number, a dimensionless term expressing the ratio of
inertia and viscous forces. (Note: Equation 8-2 applies to particles with diameters of 0.4 inch [10 mm] or smaller and involving Reynolds numbers
(Re) less than 1. For larger diameters, there is a transition region; thereafter, Newton’s law applies.) The expression for the Reynolds number
(Re = w v D/µ) contains, in addition to the parameters defined above, the absolute viscosity. The drag coefficient has been demonstrated to
equal 24/Re (Stokes’ law). When this value is substituted for Cd in Equation 8-2, the result is the following (Reynolds number <1):
Equation 8-3
g( w – ) D2
p
v=
18µ
The relationship of differential densities in Equation 8-3, which identifies the principle of separation in a grease interceptor, has been
verified by a number of investigations for spheres and fluids of various types. An examination of this equation shows that the vertical velocity
of a FOG globule in water depends on the density and diameter of the globule, the density and viscosity of the water, and the temperature
of the water and FOG material. Specifically, the FOG globule’s vertical velocity is highly dependent on the globule’s diameter, with small
globules rising much more slowly than larger ones. Thus, larger globules have a faster rate of ascension.
The effect of shape irregularity is most pronounced as the floating (vertical) velocity increases. Since FOG particles in sanitary drainage
systems have slow floating velocities, particle irregularity is of lesser importance than particle diameter.
Figure 8-1 shows the settling velocities of discrete spherical particles in still
water. The heavy lines are for settling values computed using Equation 8-3 and for FIGURE 8-1
Rising and Settling Rates in Still Water
drag coefficients depending on the Reynolds number. Below a Reynolds number
of 1, the settlement is according to Stokes’ law. As noted above, as particle 0.4
SG = 0.85
sizes and Reynolds numbers increase, there is first a transition stage, and then 0.33
Newton’s law applies. At water temperatures other than 50°F (10°C), the ratio 0.3
Rise Rate (ft/min)
Retention Period
The retention period (P) is the theoretical time that a particle of wastewater is held in the grease interceptor. The volume of the tank for the
required retention period can be computed as follows:
Equation 8-4
V = QP/7.48 SI: V = QP/1,000
As an example, for a retention period (P) equal to 30 minutes and a flow rate (Q) of 35 gpm, the tank volume is V = 35 × 30 = 1,050
gallons. (Divide by 7.48 to find the cubic feet [140.37 ft3].) For a flow rate (Q) of 132 liters per minute (Lpm), the tank volume is V = 132 ×
30 = 3,960 L. (Divide by 1,000 to find the cubic meters [3.96 m3].) Keep in mind that gravity grease interceptors are rated on normal liquid
volumes (gallons or liters).
Retention periods should be based on the peak flow during the retention period.
Retention periods can vary according to interceptor design and volume and can range from one to five minutes up to 30 minutes or more.
Flow-Through Period
The actual time required for the water to flow through an existing tank is called the flow-through period. How closely this flow-through
period approximates the retention period depends on the tank. A well-designed tank should provide a flow-through period nearly equal to
the required retention period.
Equation 8-5
V = QT
where
V = Volume of basin, gallons (L)
Q = Design flow, gpm (Lpm)
T = Retention time, minutes
As previously noted, particles that rise to the surface of a liquid are said to possess rise rates, while particles that settle to the bottom
exhibit settling rates. Both types obey Stokes’ law, which establishes the theoretical terminal velocities of rising and/or settling particles. With a
value of 150 micron for the diameter (D) of the globule, the rate of rise of oil globules in wastewater may be expressed in feet per minute as:
Equation 8-6
0.0241 (Sw – 0.735 (Sw –
Vt = So) (Vt = So) )
SI:
μ µ
where
Vt = Rise rate of oil globule (150 micron in diameter) in the wastewater, ft/min (cm/min)
Sw = Specific gravity of wastewater at the design temperature of flow
So = Specific gravity of oil in the wastewater at the design temperature of
flow TABLE 8-1 Travel Time for a Droplet to Rise
3 inches (7.6 cm) at 68°F (20°C)
µ = Absolute viscosity of the wastewater at the design temperature, poises
Droplet Diameter, Rise Time of Oil, SG =
Example 8-1 microns 0.87, hr:min:sec
The following example illustrates the application of the above equations for the design of a 300 0:00:17
grease interceptor.
Without additional data describing the distribution of oil droplets and their diameters within 150 0:00:53
a representative wastewater sample, it is not possible to quantitatively predict the effect that 125 0:01:16
increased interceptor size or reduced flow and the subsequent increased retention time within 90 0:02:23
the grease interceptor will have on the effluent concentration of the interceptor. However, 60 0:05:22
experimental research on oil droplet rise time (see Table 8-1) illustrates the effect that increased
interceptor size or reduced flow and the subsequent increased retention time within the grease 50 0:07:44
interceptor will have on oil droplet removal. Following the logic in Table 8-1 allows the designer 40 0:12:05
to improve grease interceptor performance by increasing the interceptor volume or reducing 30 0:21:28
flow and subsequently lowering horizontal velocity and increasing retention time. 20 0:48:19
Other data for this example is as follows:
• Specific gravity of grease/oil in wastewater: 0.9 (average) 15 1:25:53
• Temperature of wastewater and oil mixture: 68°F (20°C) (average) 10 3:13:15
• Rate of rise of oil globules in the wastewater: use Equation 8-6 5 12:52:58
• Dimensions of a typical 20-gpm-capacity grease interceptor: 24 inches long, 14 inches 1 322:04:22
wide, 20 inches high (76-Lpm-capacity grease interceptor: 61.0 cm long, 35.6 cm wide,
50.8 cm high) Droplet Diameter, Rise Time of Oil, SG =
microns 0.90, hr:min:sec
• Capacity: 23.27 gallons (88.17 L)
• Fluid level: 16 inches (40.6 cm) 300 0:00:21
• Flow rate: 20 gpm (76 Lpm) 150 0:01:09
• Inlet/outlet: 2 inches (DN-50) 125 0:01:36
• The grease interceptor will operate when completely full and in a horizontal position.
90 0:03:06
• Inlet and outlet pipes are running full, and the interceptor is fully charged.
• FOG globules must rise a minimum distance of 3 inches (7.6 cm) from a point at the 60 0:06:59
bottom of the inlet head of the interceptor to a point directly below the interceptor 50 0:10:03
effluent outlet. 40 0:15:42
To solve, first determine the rate of rise of the oil globules: 150 micron = 0:01:09 minutes.
30 0:27:55
Then determine the wastewater flow rate through a 20-gpm (76-Lpm) capacity grease
interceptor: 20 1:02:48
• Vh = L/T = 24 in. × 1.0 ft/12 in./1.15 minutes = 1.74 fpm 15 1:51:39
(Vh = L/T = 61.0 cm/1.15 minutes = 53.2 cm/min) 10 4:11:13
• Wetted cross-sectional area of the separation basin:
5 16:44:52
W × H = 14 in. × 16 in. = 224 in.2 × (1 ft2/144 in.2) = 1.56 ft2
(W × H = 35.6 cm × 40.6 cm = 1,445 cm2) 1 418:41:41
PRACTICAL DESIGN
While acquaintance with the theory of flotation is important to the engineer, several factors have prevented the direct application of this theory
to the design of grease interceptors. Some turbulence is unavoidable at the inlet end of the tank. This effect is greatly reduced by good inlet
design (including baffling) that distributes the influent as uniformly as practicable over the cross-section of the tank. The streamline flow at the
outlet also encounters some interference, but this condition is less pronounced than the inlet turbulence and is reduced only by using overflow
weirs or baffles. Density currents are caused by differences in the temperature, the density of the incoming wastewater, and the interceptor’s
contents. Incoming water has more suspended matter than the partially clarified contents of the tank. Therefore, the influent tends to form a
relatively rapid current along the bottom of the tank, which may extend to the outlet. This condition is known as short-circuiting and occurs
even with uniform collection at the outlet end.
Flocculation of suspended solids has been mentioned. Its effects, however, are difficult to predict.
In general, the engineer depends on experience as well as the code requirements of the various local health departments for the preferred
retention and overflow rates. Depth already has been discussed as having some effect on the tank’s efficiency—a smaller depth provides a
shorter path for the rising particles to settle.
The tank’s inlets and outlets also require careful consideration by the designer. The ideal inlet reduces the inlet velocity to prevent the
pronounced currents toward the outlet, distributes the inlet water as uniformly as practical over the cross-section of the tank, and mixes the
inlet water with the water already in the tank to prevent the entering water from short-circuiting toward the outlet.
FOOD DISPOSERS
The code does not prohibit the discharge from a food waste disposer from connecting downstream of a grease interceptor (of either the
hydromechanical or gravity type). However, there are mixed opinions concerning where food waste disposer discharges should be connected.
Because studies have indicated that dishwasher pre-rinse (food scrap) sinks are a significant source of grease wastewater and that many food
waste disposer installations receive the waste from pre-rinse sinks, the disposer discharge should go through the grease interceptor. However,
since a food waste disposer operates best with cold water flow and chops the food waste (and the grease contained within) into solidified
particles, the particles will readily flow in the sewer system without the congealing problems associated with hot or warm grease-laden wastewater
discharges. Manufacturers of food waste disposers understandably find the requirement for a solids interceptor for the disposer discharge
illogical, especially where jurisdictions require them for gravity-type grease interceptors. Ultimately, the code official or the public sewer system
operator will make the decision on where the food waste disposer should be connected. (See the 2015 IPC commentary on Section 1003.3.2.)
INSTALLATION
Most local administrative authorities require water from FOG-producing food service fixtures and equipment to discharge into an approved
interceptor before entering the municipality’s sanitary drainage system. Pretreatment regulations, with pretreatment coordinators having the
final word, may include all kitchen discharges, including floor drains. If floor drains are connected to an interceptor, the interceptor must be
recessed or below the floor.
It is recommended to locate the interceptor as close to the grease-producing fixtures as possible. Under-the-counter or above-slab
interceptor installations are often possible adjacent to the grease-producing fixtures. This arrangement may combine venting of the fixtures
with a common vent and trap downstream of the grease interceptor. Flow control air inlets are commonly connected to the building vent.
Proper trapping is required because interceptors do not contain interior water seals to serve as a gas trap.
Some practical considerations are important if an interceptor will be located near the fixtures it serves. For instance, if the interceptor is
an under-the-counter, above-the-slab device, the engineer must leave space above the interceptor cover to allow FOG removal.
If the grease interceptor is located far from the fixtures it serves, the grease can cool and collect in the waste lines upstream of the
interceptor, causing clogging conditions and requiring more frequent cleaning of the waste lines. However, in some cases a heat trace system
can be installed along the main waste line that is routed to the inlet side of the interceptor to minimize the potential for FOG to solidify
before it enters the interceptor.
Some ordinances do not allow the installation of interceptors where the surrounding temperatures under normal operating conditions
are less than 40°F (4.4°C).
Some administrative authorities prohibit the discharge of food waste disposers through interceptors because of the accumulation of
food particles. Other jurisdictions allow this setup, provided that a solids interceptor or strainer basket is installed upstream to remove food
particulates prior to the waste stream entering the interceptor. When allowed by the AHJ, connecting food waste disposers to HGIs and
GRDs (in conjunction with a solids strainer) is recommended due to the fact that disposer waste discharge is a prime carrier of FOG-laden
FLOW CONTROL
Flow controls are best located immediately downstream of the last drain of the fixtures served prior to the interceptor. Flow control fittings
are not commonly applied to floor drains or for fixtures that could flood.
Attention to the manufacturer’s instructions is necessary for the proper application of flow controls. The purpose of air-injecting flow
controls is to cause air to be drawn into the flow downstream of the orifice, thereby promoting air-entrained flow at the interceptor’s rated
flow. It has been stated that the air entrained through the flow control aids FOG flotation by lifting and FOG particle agglomeration, but this
should not to be confused with specifically designed “DAF” units that promote particle floatation through dissolved air floatation.
The air intake (vent) for the flow control, required by interceptors certified to PDI G101, CSA B481.1, and ASME A112.14.3 Type A, may
terminate above the flood line of the sink as high as possible to prevent overflow, or it may terminate in a return bend at the same height on
the outside of the building. A flow control air intake may connect to the vent stack if the fixtures are properly trapped. Illustrations of the
correct placement of air-injecting flow controls appear in the appendix of the applicable standard.
Interceptors certified to ASME A112.14.3 Type B have an unvented external flow control. Interceptors certified to ASME A112.14.3 Types
C and D do not have a vented or unvented external flow control fitting. Engineers should consult the manufacturer’s installation instructions
regarding the use, location, and installation of flow controls that are a part of a unit’s certification type.
Hydromechanical Grease Interceptors a. The maximum allowable DFUs plumbed to the kitchen drain lines that will be connected to
the grease interceptor
The following sizing procedure for HGIs may be used as method to calculate b. This size is based on DFUs, the pipe size from UPC Table 703.2 (2018 UPC), and useful
the flow rate in gpm or L/s for the connected fixtures and equipment. tables for flow in half-full pipes. Based on a 30-minute retention time. Rounded up to the
nominal interceptor volume.
c. Where the flow rate of directly connected fixture(s) or appliance(s) have no assigned DFU
values, the additional grease interceptor volume shall be based on the known flow rate
multiplied by 30 minutes.
Source: 2018 UPC Table 1014.3.6
Example 8-2
Assume a single-fixture installation. Size the grease interceptor for a three-compartment pot (scullery) sink, with each compartment being 18
× 24 × 12 inches (457 × 610 × 305 mm).
1. Determine the sink volume:
• Cubic contents of one sink compartment = 18 × 24 × 12 = 5,184 in.3 (457 × 610 × 305/1,000,000 = 85 L)
• Cubic contents of three sink compartments = 3 × 5,184 = 15,552 in.3 (3 × 85 = 255 L)
• Contents expressed in gallons = 15,552 in.3/231 = 67.3 gal (255 L)
2. Add the total potable water supply that could be discharged independent of the fixture calculated above, including manufacturer-rated
appliances such as water wash exhaust hoods.
3. Determine the fixture load. A sink (or fixture) seldom is filled to the brim, and dishes, pots, or pans displace approximately 25 percent
of the water. Therefore, 75 percent of the actual fixture capacity should be used to establish the drainage load: 0.75 × 67.3 gal = 50.8
gal (0.75 × 255 L = 191 L).
4. Calculate the flow rate based on drain time, typically one or two minutes. Flow rate is calculated by dividing the drainage load in gallons
by the drain time in minutes. Therefore, the flow for this example would be 50 gpm (3.19 L/s) for one-minute drainage or 25 gpm (1.59
L/s) for two-minute drainage.
5. Select a hydromechanical interceptor with a certified, rated capacity of 50 gpm (3.19 L/s) for one-minute flow or 25 gpm (1.59 L/s)
for two-minute flow.
Sizing a hydromechanical grease interceptor by flow rate according to Example 8-2 is mandatory, yielding many options for grease interceptors
that are certified at the calculated flow rate but also are certified at the minimum grease storage capacity. Selecting an HGI that can only store
the minimum required amount of FOG may be problematic in that the food service establishment could be required to conduct maintenance
on a biweekly, weekly, or even daily basis. In those cases, it may be more appropriate to choose a lower-maintenance gravity grease interceptor
(GGI) or to select one of the new generation high-capacity HGIs on the market.
The following optional selection method for HGIs allows an engineer to calculate the potential daily grease load that may be anticipated
from a given food service establishment to select an interceptor that meets the minimum code-required flow rate previously established, but
with a larger grease-holding storage capacity. Keep in mind that FOG stored in an interceptor becomes very corrosive to the interceptor and
the downstream collection system in less than 30 days.
Example 8-3
To calculate a food service facility’s daily potential grease load, multiply the number of meals (customers) per day by the grease production
value per meal. Note, this calculation is applicable to both HGIs and GGIs.
0.035 lbs (15.876 g)/meal (no flatware) Full-fare family, fast-food hamburger, hamburger bar and grill,
High grease producer
0.0455 lbs (20.638 g)/meal (with flatware) German, Italian, fast-food Mexican
0.058 lbs (26.308 g)/meal (no flatware) Full-fare BBQ, fast-food fried chicken, full-fare Mexican, steak and
Very high grease producer
0.075 lbs (34.019 g)/meal (with flatware) seafood, Chinese, Hawaiian
Assume the food service facility is a full-fare family Italian restaurant serving approximately 300 meals per day on washable dishes and
flatware. Select the grease production value for high grease production with flatware from Table 8-3 and then calculate the daily grease load
as follows: 300 × 0.0455 = 13.65 lbs (300 × 20.638/1,000 = 6.191 kg) of grease per day.
Next, select an interceptor based on its certified grease storage capacity and the desired maintenance frequency as follows:
• Weekly maintenance: 7 days × 13.65 lbs per day = 95.55 lbs (7 days × 6.191 kg per day = 43.34 kg) of grease storage capacity required
• Monthly maintenance: 30 days × 13.65 lbs per day = 409.5 lbs (30 days × 6.191 kg per day = 185.7 kg) of grease storage capacity required
• Bimonthly maintenance: 60 days × 13.65 lbs per day = 819 lbs (60 days × 6.191 kg per day = 371.5 kg) of grease storage capacity required
• Quarterly maintenance: 90 days × 13.65 lbs per day = 1,228.5 lbs (90 days × 6.191 kg per day = 557.2 kg) of grease storage capacity
required
The engineer should work closely with the owner to determine the maintenance frequency that best suits their particular project.
CODE REQUIREMENTS
The necessity to verify all state and local jurisdictional requirements prior to the startup of any food service facility design cannot be emphasized
enough. Although state and model plumbing codes provide information with respect to interceptor requirements and regulations, local health
departments and administrative AHJs have likely established their own guidelines and requirements for interceptors and, therefore, also should
be consulted at the start of the design. It is up to the plumbing engineer to pull together the various agency requirements to design a code-
compliant system while incorporating any additional governing requirements and regulations.
The code-referenced standards do not provide any mandatory sizing methods for hydromechanical grease interceptors or automatic
grease removal devices. Some of these standards provide a sizing method in a non-mandatory appendix of each standard. Sizing methods for
grease interceptors have been debated for decades. Although there is most likely a point at which a grease interceptor that is too small does
reduce the removal efficiency under ideal conditions (i.e., just cleaned), there is no penalty (other than initial cost) for the selection of a unit
larger than required. A larger unit than “required by the numbers” might cost only slightly more, with the benefit of less-frequent cleanings
(cleaning being a cost as well). Thus, Table 8-3 provides a method for the plumbing engineer to oversize the FOG storage compartment in
grease interceptors or to compare alternate grease interceptor products.
Gravity grease interceptors are nominally sized to allow approximately 25 percent of the volume taken up by solids and FOG as the
interceptor loads with non-water flow. The calculation in Table 8-3 can be used to consider enlargement of the grease interceptor to reduce
the required frequency of cleanout.
Following are itemized lists incorporating the major provisions of the model plumbing codes and are included herein as an abbreviated
design guide for the engineer when specifying sizing. It is important to review the applicable code in effect in the area for any variation from
this generalized list.
General
1. Grease interceptors are not required in individual dwelling units or residential dwellings. (1014.1)
2. Water closets, urinals, and other plumbing fixtures conveying human waste shall not drain into or through any interceptor. (1014.1)
3. Each fixture discharging into an interceptor shall be individually trapped and vented in an approved manner. (1014.1.1)
4. An approved type of grease interceptor(s) in accordance with ASME A112.14.3, ASME A112.14.4, CSA B481, PDI G101, or PDI G102,
and sized in accordance with Section 1014.2.1 or Section 1014.3.6, shall be installed in accordance with the manufacturer’s installation
instructions to receive the drainage from fixtures or equipment that produce grease-laden waste located in areas of establishments where
food is prepared, or other establishments where grease is introduced into the drainage or sewage system in quantities that can affect line
stoppage or hinder sewage treatment or private sewage disposal systems. (1014.1)
5. The grease collected from a grease interceptor must not be introduced into any drainage piping or public or private sewer (1014.1.2).
6. Unless specifically required or permitted by the AHJ, no food waste disposal unit or dishwasher shall be connected to or discharge into
any grease interceptor. Commercial food waste disposers shall be permitted to discharge directly into the building’s drainage system.
(Exception: Food waste disposers shall be permitted to discharge to grease interceptors that are designed to receive the discharge of
food waste.) (1014.1.3)
TABLE 8-4 UPC Hydromechanical Grease Interceptor Sizing Using Gravity Flow Rates
Size of Grease Interceptor
Diameter of Grease Waste Maximum Full Pipe Flow, Maximum Capacity of
Pipe, in. (DN) gpm (L/min)a One-Minute Drainage Two-Minute Drainage Connected Fixtures, gal (L)
Period, gpm (Lpm) Period, gpm (Lpm)
2 (50) 20 (75.7) 20 (75.7) 10 (37.9) 50 (189)
3 (80) 60 (227) 75 (284) 35 (132) 150 (568)
4 (100) 125 (473) 150 (568) 75 (284) 313 (1,183)
5 (125) 230 (871) 250 (946) 125 (473) 575 (2,176)
6 (150) 375 (1,419) 400 (1,514) 200 (757) 938 (3,548)
a. ¼ inch slope per foot (20.8mm/m) based on Manning’s formula with friction factor
N = 0.012 and flowing 100% full
Source: 2018 UPC Table 1014.2.1 and paragraph 1014.2.1