You are on page 1of 208

ID Câble Résumé Limite Longueur Marge de Sécurité Date / Heure

R.5 H1-A/01 CORRECT TIA Cat 6A Perm. Link 72.2 m 2.9 dB (NEXT) 20/05/2023 17:04
R.5 H1-A/02 CORRECT TIA Cat 6A Perm. Link 72.0 m 4.7 dB (NEXT) 20/05/2023 17:05
R.5 H1-A/04 CORRECT TIA Cat 6A Perm. Link 72.2 m 3.2 dB (NEXT) 20/05/2023 17:06
R.5 H1-A/05 CORRECT TIA Cat 6A Perm. Link 66.8 m 4.1 dB (NEXT) 20/05/2023 17:02
R.5 H1-A/06 CORRECT TIA Cat 6A Perm. Link 64.9 m 2.9 dB (NEXT) 20/05/2023 17:09
R.5 H1-A/07 CORRECT TIA Cat 6A Perm. Link 64.7 m 1.2 dB (NEXT) 20/05/2023 17:10
R.5 H1-A/08 CORRECT TIA Cat 6A Perm. Link 64.7 m 2.6 dB (NEXT) 20/05/2023 17:10
R.5 H1-A/09 CORRECT TIA Cat 6A Perm. Link 66.8 m 3.8 dB (NEXT) 20/05/2023 17:07
R.5 H1-A/13 CORRECT TIA Cat 6A Perm. Link 62.5 m 1.9 dB (NEXT) 20/05/2023 17:17
R.5 H1-A/14 CORRECT TIA Cat 6A Perm. Link 61.6 m 3.7 dB (NEXT) 20/05/2023 17:12
R.5 H1-A/16 CORRECT TIA Cat 6A Perm. Link 51.4 m 4.4 dB (NEXT) 20/05/2023 17:20
R.5 H1-A/18 CORRECT TIA Cat 6A Perm. Link 51.4 m 3.7 dB (NEXT) 20/05/2023 17:19
R.5 H1-A/19 CORRECT TIA Cat 6A Perm. Link 48.1 m 1.9 dB (NEXT) 20/05/2023 17:21
R.5 H1-A/20 CORRECT TIA Cat 6A Perm. Link 48.1 m 3.5 dB (NEXT) 20/05/2023 17:22
R.5 H1-A/21 CORRECT TIA Cat 6A Perm. Link 44.3 m 5.4 dB (NEXT) 20/05/2023 17:30
R.5 H1-A/22 CORRECT TIA Cat 6A Perm. Link 44.3 m 2.0 dB (NEXT) 20/05/2023 17:31
R.5 H1-A/23 CORRECT TIA Cat 6A Perm. Link 49.0 m 3.0 dB (NEXT) 20/05/2023 17:32
R.5 H1-A/24 CORRECT TIA Cat 6A Perm. Link 48.1 m 3.9 dB (NEXT) 20/05/2023 17:27
R.5 H1-B/01 CORRECT* TIA Cat 6A Perm. Link 44.3 m 0.2 dB (NEXT) 20/05/2023 17:45
R.5 H1-B/02 CORRECT TIA Cat 6A Perm. Link 44.3 m 1.3 dB (NEXT) 20/05/2023 17:46
R.5 H1-B/03 CORRECT TIA Cat 6A Perm. Link 44.3 m 4.2 dB (NEXT) 20/05/2023 17:46
R.5 H1-B/05 CORRECT TIA Cat 6A Perm. Link 39.8 m 3.5 dB (NEXT) 20/05/2023 17:41
R.5 H1-B/06 CORRECT TIA Cat 6A Perm. Link 40.3 m 3.7 dB (NEXT) 20/05/2023 17:51
R.5 H1-B/07 CORRECT TIA Cat 6A Perm. Link 40.0 m 3.3 dB (NEXT) 20/05/2023 17:52
R.5 H1-B/08 CORRECT TIA Cat 6A Perm. Link 40.3 m 4.5 dB (NEXT) 20/05/2023 17:50
R.5 H1-B/09 CORRECT TIA Cat 6A Perm. Link 35.3 m 4.5 dB (NEXT) 20/05/2023 17:49
R.5 H1-B/10 CORRECT TIA Cat 6A Perm. Link 36.2 m 4.7 dB (NEXT) 20/05/2023 17:48
R.5 H1-B/11 CORRECT TIA Cat 6A Perm. Link 34.6 m 5.0 dB (NEXT) 20/05/2023 17:55
R.5 H1-B/12 CORRECT TIA Cat 6A Perm. Link 34.6 m 3.8 dB (NEXT) 20/05/2023 17:56
R.5 H1-B/13 CORRECT TIA Cat 6A Perm. Link 34.6 m 3.1 dB (NEXT) 20/05/2023 17:56
R.5 H1-B/14 CORRECT TIA Cat 6A Perm. Link 30.1 m 3.8 dB (NEXT) 20/05/2023 17:53
R.5 H1-B/15 CORRECT TIA Cat 6A Perm. Link 31.3 m 3.5 dB (NEXT) 20/05/2023 17:53
R.5 H1-B/16 CORRECT TIA Cat 6A Perm. Link 27.2 m 2.9 dB (NEXT) 20/05/2023 18:00
R.5 H1-B/17 CORRECT TIA Cat 6A Perm. Link 25.8 m 2.5 dB (NEXT) 20/05/2023 18:02
R.5 H1-B/19 CORRECT TIA Cat 6A Perm. Link 29.8 m 2.1 dB (NEXT) 20/05/2023 18:08
R.5 H1-B/20 CORRECT TIA Cat 6A Perm. Link 30.1 m 4.8 dB (NEXT) 20/05/2023 18:07
R.5 H1-B/21 CORRECT TIA Cat 6A Perm. Link 24.4 m 4.9 dB (NEXT) 20/05/2023 18:12
R.5 H1-B/22 CORRECT TIA Cat 6A Perm. Link 24.4 m 4.0 dB (NEXT) 20/05/2023 18:13
R.5 H1-B/23 CORRECT TIA Cat 6A Perm. Link 21.1 m 3.1 dB (NEXT) 20/05/2023 18:11
R.5 H1-B/24 CORRECT TIA Cat 6A Perm. Link 22.5 m 4.1 dB (NEXT) 20/05/2023 18:10
R.5 H1-C/01 CORRECT TIA Cat 6A Perm. Link 25.1 m 4.8 dB (NEXT) 20/05/2023 18:14
R.5 H1-C/02 CORRECT TIA Cat 6A Perm. Link 26.3 m 4.8 dB (NEXT) 20/05/2023 18:15
R.5 H1-C/03 CORRECT TIA Cat 6A Perm. Link 26.5 m 3.5 dB (NEXT) 20/05/2023 18:16
R.5 H1-C/07 CORRECT TIA Cat 6A Perm. Link 20.6 m 3.3 dB (NEXT) 20/05/2023 18:20
R.5 H1-C/09 CORRECT TIA Cat 6A Perm. Link 26.3 m 3.2 dB (NEXT) 20/05/2023 18:24
R.5 H1-C/11 CORRECT TIA Cat 6A Perm. Link 34.1 m 3.1 dB (NEXT) 20/05/2023 18:29
R.5 H1-F/05 CORRECT TIA Cat 6A Perm. Link 25.3 m 9.9 dB (NEXT) 20/05/2023 18:38
R.5 H1-F/06 CORRECT TIA Cat 6A Perm. Link 24.9 m 7.5 dB (NEXT) 20/05/2023 18:40
R.5 H1-F/07 CORRECT TIA Cat 6A Perm. Link 25.3 m 10.3 dB (NEXT) 20/05/2023 18:39
R.5 H1-F/08 CORRECT TIA Cat 6A Perm. Link 24.6 m 10.6 dB (NEXT) 20/05/2023 18:41
R.5 H1-F/09 CORRECT TIA Cat 6A Perm. Link 14.2 m 9.5 dB (NEXT) 20/05/2023 18:43
R.5 H1-F/10 CORRECT TIA Cat 6A Perm. Link 44.5 m 11.6 dB (NEXT) 20/05/2023 18:52
R.5 H1-F/11 CORRECT TIA Cat 6A Perm. Link 44.5 m 9.5 dB (NEXT) 20/05/2023 18:55
R.5 H1-F/12 CORRECT TIA Cat 6A Perm. Link 44.8 m 9.2 dB (NEXT) 20/05/2023 18:56
R.5 H1-F/13 CORRECT TIA Cat 6A Perm. Link 44.5 m 10.0 dB (NEXT) 20/05/2023 18:54
R.5 H1-F/14 CORRECT TIA Cat 6A Perm. Link 45.2 m 10.8 dB (NEXT) 20/05/2023 18:50
R.5 H1-F/15 CORRECT TIA Cat 6A Perm. Link 46.9 m 11.0 dB (NEXT) 20/05/2023 19:00
R.5 H1-F/16 CORRECT TIA Cat 6A Perm. Link 46.4 m 9.4 dB (NEXT) 20/05/2023 19:04
R.5 H1-F/17 CORRECT TIA Cat 6A Perm. Link 46.2 m 10.3 dB (NEXT) 20/05/2023 19:01
R.5 H1-F/18 CORRECT TIA Cat 6A Perm. Link 47.1 m 10.1 dB (NEXT) 20/05/2023 19:05
R.5 H1-F/20 CORRECT TIA Cat 6A Perm. Link 54.2 m 4.2 dB (NEXT) 20/05/2023 19:12
R.5 H1-F/21 CORRECT TIA Cat 6A Perm. Link 52.6 m 10.8 dB (NEXT) 20/05/2023 19:16
R.5 H1-F/22 CORRECT TIA Cat 6A Perm. Link 54.2 m 9.4 dB (NEXT) 20/05/2023 19:13
R.5 H1-F/23 CORRECT TIA Cat 6A Perm. Link 50.2 m 11.0 dB (NEXT) 20/05/2023 19:17
R.5 H1-F/24 CORRECT TIA Cat 6A Perm. Link 54.2 m 9.3 dB (NEXT) 20/05/2023 19:14
R.5 H1-G/01 CORRECT TIA Cat 6A Perm. Link 56.6 m 10.6 dB (NEXT) 20/05/2023 19:24
R.5 H1-G/02 CORRECT TIA Cat 6A Perm. Link 56.4 m 9.2 dB (NEXT) 20/05/2023 19:25
R.5 H1-G/03 CORRECT TIA Cat 6A Perm. Link 56.4 m 11.4 dB (NEXT) 20/05/2023 19:26
R.5 H1-G/05 CORRECT TIA Cat 6A Perm. Link 53.3 m 11.2 dB (NEXT) 20/05/2023 19:21
R.5 H1-G/06 CORRECT TIA Cat 6A Perm. Link 60.4 m 8.0 dB (NEXT) 20/05/2023 19:36
R.5 H1-G/08 CORRECT TIA Cat 6A Perm. Link 57.8 m 9.4 dB (NEXT) 20/05/2023 19:30
R.5 H1-G/09 CORRECT TIA Cat 6A Perm. Link 57.1 m 9.3 dB (NEXT) 20/05/2023 19:32
R.5 H1-G/10 CORRECT TIA Cat 6A Perm. Link 60.4 m 10.4 dB (NEXT) 20/05/2023 19:37
R.5 H1-G/11 CORRECT TIA Cat 6A Perm. Link 61.1 m 10.4 dB (NEXT) 20/05/2023 19:51
R.5 H1-G/12 CORRECT TIA Cat 6A Perm. Link 60.4 m 10.2 dB (NEXT) 20/05/2023 19:46
R.5 H1-G/13 CORRECT TIA Cat 6A Perm. Link 60.6 m 10.3 dB (NEXT) 20/05/2023 19:49
R.5 H1-G/14 CORRECT TIA Cat 6A Perm. Link 59.2 m 9.2 dB (NEXT) 20/05/2023 19:40

22/05/2023 09:45:32 Page 1


HOPITAL NECKER H6 22 05 2023 correct.flw
ID Câble Résumé Limite Longueur Marge de Sécurité Date / Heure
R.5 H1-G/17 CORRECT TIA Cat 6A Perm. Link 63.0 m 9.5 dB (NEXT) 20/05/2023 19:56
R.5 H1-G/18 CORRECT TIA Cat 6A Perm. Link 66.1 m 10.5 dB (NEXT) 20/05/2023 19:59
R.5 H1-I/21 CORRECT TIA Cat 6A Perm. Link 81.2 m 9.7 dB (NEXT) 20/05/2023 20:44
R.5 H1-I/22 CORRECT TIA Cat 6A Perm. Link 81.5 m 10.7 dB (NEXT) 20/05/2023 20:48
R.5 H1-I/23 CORRECT TIA Cat 6A Perm. Link 75.1 m 9.9 dB (NEXT) 20/05/2023 20:38
R.5 H1-I/24 CORRECT TIA Cat 6A Perm. Link 76.3 m 9.7 dB (NEXT) 20/05/2023 20:41
R.5 H1-J/01 CORRECT TIA Cat 6A Perm. Link 80.5 m 11.6 dB (NEXT) 20/05/2023 20:46
R.5 H1-J/02 CORRECT TIA Cat 6A Perm. Link 75.3 m 9.8 dB (NEXT) 20/05/2023 20:35
R.5 H1-J/03 CORRECT TIA Cat 6A Perm. Link 75.3 m 10.5 dB (NEXT) 20/05/2023 20:32
R.5 H1-J/04 CORRECT TIA Cat 6A Perm. Link 75.3 m 8.9 dB (NEXT) 20/05/2023 20:34
R.5 H1-J/05 CORRECT TIA Cat 6A Perm. Link 72.0 m 12.1 dB (NEXT) 20/05/2023 20:26
R.5 H1-J/06 CORRECT TIA Cat 6A Perm. Link 69.9 m 10.4 dB (NEXT) 20/05/2023 20:29
R.5 H1-J/07 CORRECT TIA Cat 6A Perm. Link 68.9 m 11.0 dB (NEXT) 20/05/2023 20:14
R.5 H1-J/08 CORRECT TIA Cat 6A Perm. Link 76.7 m 9.9 dB (NEXT) 20/05/2023 20:19
R.5 H1-J/09 CORRECT TIA Cat 6A Perm. Link 76.5 m 10.2 dB (NEXT) 20/05/2023 20:22
R.5 H1-J/10 CORRECT TIA Cat 6A Perm. Link 76.7 m 10.4 dB (NEXT) 20/05/2023 20:16
R.5 H1-J/11 CORRECT TIA Cat 6A Perm. Link 70.6 m 10.7 dB (NEXT) 20/05/2023 20:24
R.5 H1-J/12 CORRECT TIA Cat 6A Perm. Link 68.4 m 10.6 dB (NEXT) 20/05/2023 20:10
R.5 H1-J/13 CORRECT TIA Cat 6A Perm. Link 65.1 m 10.4 dB (NEXT) 20/05/2023 20:04
R.5 H1-J/14 CORRECT TIA Cat 6A Perm. Link 67.7 m 9.3 dB (NEXT) 20/05/2023 20:08
R.5 H1-J/15 CORRECT TIA Cat 6A Perm. Link 63.2 m 9.3 dB (NEXT) 20/05/2023 20:06
R.5 H1-J/16 CORRECT TIA Cat 6A Perm. Link 67.5 m 9.3 dB (NEXT) 20/05/2023 20:11
R.5 H1-J/18 CORRECT TIA Cat 6A Perm. Link 23.0 m 9.7 dB (NEXT) 20/05/2023 18:23
R.5 H1-J/19 CORRECT TIA Cat 6A Perm. Link 23.4 m 9.3 dB (NEXT) 20/05/2023 18:26
R.5 H2-A/01 CORRECT TIA Cat 6A Perm. Link 78.9 m 2.8 dB (NEXT) 20/05/2023 15:07
R.5 H2-A/02 CORRECT TIA Cat 6A Perm. Link 78.9 m 4.4 dB (NEXT) 20/05/2023 15:07
R.5 H2-A/05 CORRECT TIA Cat 6A Perm. Link 83.1 m 4.6 dB (NEXT) 20/05/2023 15:10
R.5 H2-A/06 CORRECT TIA Cat 6A Perm. Link 83.1 m 4.0 dB (NEXT) 20/05/2023 15:10
R.5 H2-A/07 CORRECT TIA Cat 6A Perm. Link 81.0 m 3.6 dB (NEXT) 20/05/2023 15:13
R.5 H2-A/08 CORRECT TIA Cat 6A Perm. Link 80.8 m 3.3 dB (NEXT) 20/05/2023 15:12
R.5 H2-A/09 CORRECT TIA Cat 6A Perm. Link 77.2 m 2.7 dB (NEXT) 20/05/2023 15:18
R.5 H2-A/12 CORRECT TIA Cat 6A Perm. Link 77.4 m 3.2 dB (NEXT) 20/05/2023 15:17
R.5 H2-A/13 CORRECT TIA Cat 6A Perm. Link 77.7 m 3.6 dB (NEXT) 20/05/2023 15:20
R.5 H2-A/14 CORRECT TIA Cat 6A Perm. Link 77.7 m 6.5 dB (NEXT) 20/05/2023 15:20
R.5 H2-A/15 CORRECT TIA Cat 6A Perm. Link 77.7 m 3.0 dB (NEXT) 20/05/2023 15:19
R.5 H2-A/16 CORRECT TIA Cat 6A Perm. Link 77.7 m 4.6 dB (NEXT) 20/05/2023 15:19
R.5 H2-A/17 CORRECT TIA Cat 6A Perm. Link 68.9 m 4.2 dB (NEXT) 20/05/2023 15:22
R.5 H2-A/18 CORRECT TIA Cat 6A Perm. Link 68.9 m 5.3 dB (NEXT) 20/05/2023 15:23
R.5 H2-A/20 CORRECT TIA Cat 6A Perm. Link 68.9 m 3.9 dB (NEXT) 20/05/2023 15:22
R.5 H2-A/21 CORRECT TIA Cat 6A Perm. Link 66.8 m 2.5 dB (NEXT) 20/05/2023 15:23
R.5 H2-A/22 CORRECT TIA Cat 6A Perm. Link 66.8 m 6.2 dB (NEXT) 20/05/2023 15:24
R.5 H2-A/23 CORRECT TIA Cat 6A Perm. Link 60.2 m 2.7 dB (NEXT) 20/05/2023 15:25
R.5 H2-A/24 CORRECT TIA Cat 6A Perm. Link 59.9 m 5.6 dB (NEXT) 20/05/2023 15:25
R.5 H2-B/02 CORRECT TIA Cat 6A Perm. Link 59.9 m 3.1 dB (NEXT) 20/05/2023 15:27
R.5 H2-B/03 CORRECT TIA Cat 6A Perm. Link 59.9 m 3.6 dB (NEXT) 20/05/2023 15:28
R.5 H2-B/04 CORRECT TIA Cat 6A Perm. Link 60.9 m 4.7 dB (NEXT) 20/05/2023 15:29
R.5 H2-B/05 CORRECT TIA Cat 6A Perm. Link 60.9 m 5.6 dB (NEXT) 20/05/2023 15:30
R.5 H2-B/06 CORRECT* TIA Cat 6A Perm. Link 57.1 m 0.7 dB (NEXT) 20/05/2023 15:30
R.5 H2-B/07 CORRECT TIA Cat 6A Perm. Link 57.1 m 5.1 dB (NEXT) 20/05/2023 15:31
R.5 H2-B/08 CORRECT TIA Cat 6A Perm. Link 57.1 m 3.7 dB (NEXT) 20/05/2023 15:32
R.5 H2-B/09 CORRECT TIA Cat 6A Perm. Link 57.3 m 3.5 dB (NEXT) 20/05/2023 15:32
R.5 H2-B/10 CORRECT TIA Cat 6A Perm. Link 53.1 m 4.4 dB (NEXT) 20/05/2023 15:35
R.5 H2-B/11 CORRECT TIA Cat 6A Perm. Link 53.3 m 6.1 dB (NEXT) 20/05/2023 15:36
R.5 H2-B/12 CORRECT TIA Cat 6A Perm. Link 50.0 m 2.7 dB (NEXT) 20/05/2023 15:38
R.5 H2-B/13 CORRECT TIA Cat 6A Perm. Link 51.4 m 3.7 dB (NEXT) 20/05/2023 15:37
R.5 H2-B/14 CORRECT TIA Cat 6A Perm. Link 50.4 m 3.7 dB (NEXT) 20/05/2023 15:34
R.5 H2-B/15 CORRECT TIA Cat 6A Perm. Link 48.8 m 1.7 dB (NEXT) 20/05/2023 15:33
R.5 H2-B/16 CORRECT TIA Cat 6A Perm. Link 41.9 m 3.8 dB (NEXT) 20/05/2023 13:38
R.5 H2-B/17 CORRECT TIA Cat 6A Perm. Link 42.2 m 4.2 dB (NEXT) 20/05/2023 13:36
R.5 H2-B/18 CORRECT TIA Cat 6A Perm. Link 51.9 m 2.2 dB (NEXT) 20/05/2023 13:39
R.5 H2-B/19 CORRECT TIA Cat 6A Perm. Link 37.9 m 3.9 dB (NEXT) 20/05/2023 13:29
R.5 H2-B/20 CORRECT TIA Cat 6A Perm. Link 37.9 m 3.4 dB (NEXT) 20/05/2023 13:32
R.5 H2-B/21 CORRECT TIA Cat 6A Perm. Link 31.3 m 2.2 dB (NEXT) 20/05/2023 13:33
R.5 H2-B/22 CORRECT TIA Cat 6A Perm. Link 31.3 m 6.5 dB (NEXT) 20/05/2023 13:33
R.5 H2-B/23 CORRECT TIA Cat 6A Perm. Link 40.0 m 4.3 dB (NEXT) 20/05/2023 13:34
R.5 H2-B/24 CORRECT TIA Cat 6A Perm. Link 39.8 m 3.0 dB (NEXT) 20/05/2023 13:34
R.5 H2-C/01 CORRECT TIA Cat 6A Perm. Link 40.0 m 2.5 dB (NEXT) 20/05/2023 13:35
R.5 H2-C/02 CORRECT TIA Cat 6A Perm. Link 40.0 m 4.6 dB (NEXT) 20/05/2023 13:35
R.5 H2-C/07 CORRECT TIA Cat 6A Perm. Link 28.9 m 3.7 dB (NEXT) 20/05/2023 13:27
R.5 H2-C/08 CORRECT TIA Cat 6A Perm. Link 28.7 m 2.9 dB (NEXT) 20/05/2023 13:27
R.5 H2-C/09 CORRECT TIA Cat 6A Perm. Link 28.4 m 4.4 dB (NEXT) 20/05/2023 13:28
R.5 H2-C/10 CORRECT TIA Cat 6A Perm. Link 78.4 m 2.6 dB (NEXT) 20/05/2023 15:01
R.5 H2-C/11 CORRECT TIA Cat 6A Perm. Link 68.2 m 5.3 dB (NEXT) 20/05/2023 14:54
R.5 H2-C/13 CORRECT* TIA Cat 6A Perm. Link 76.3 m 1.1 dB (NEXT) 20/05/2023 14:49
R.5 H2-C/14 CORRECT* TIA Cat 6A Perm. Link 76.3 m 0.5 dB (NEXT) 20/05/2023 14:49
R.5 H2-C/15 CORRECT TIA Cat 6A Perm. Link 74.6 m 1.9 dB (NEXT) 20/05/2023 14:53
R.5 H2-C/20 CORRECT TIA Cat 6A Perm. Link 74.4 m 4.1 dB (NEXT) 20/05/2023 14:46

22/05/2023 09:45:32 Page 2


HOPITAL NECKER H6 22 05 2023 correct.flw
ID Câble Résumé Limite Longueur Marge de Sécurité Date / Heure
R.5 H2-C/21 CORRECT TIA Cat 6A Perm. Link 74.6 m 2.1 dB (NEXT) 20/05/2023 14:47
R.5 H2-C/22 CORRECT TIA Cat 6A Perm. Link 73.4 m 3.0 dB (NEXT) 20/05/2023 14:47
R.5 H2-C/23 CORRECT* TIA Cat 6A Perm. Link 73.9 m 1.3 dB (NEXT) 20/05/2023 14:48
R.5 H2-D/02 CORRECT TIA Cat 6A Perm. Link 32.0 m 4.4 dB (NEXT) 20/05/2023 13:40
R.5 H2-D/03 CORRECT TIA Cat 6A Perm. Link 33.9 m 4.0 dB (NEXT) 20/05/2023 13:47
R.5 H2-D/05 CORRECT* TIA Cat 6A Perm. Link 71.1 m 0.7 dB (NEXT) 20/05/2023 14:38
R.5 H2-D/06 CORRECT TIA Cat 6A Perm. Link 71.3 m 3.1 dB (NEXT) 20/05/2023 14:44
R.5 H2-D/07 CORRECT TIA Cat 6A Perm. Link 71.3 m 4.7 dB (NEXT) 20/05/2023 14:45
R.5 H2-D/08 CORRECT TIA Cat 6A Perm. Link 70.8 m 3.3 dB (NEXT) 20/05/2023 14:39
R.5 H2-D/09 CORRECT* TIA Cat 6A Perm. Link 68.7 m 1.3 dB (NEXT) 20/05/2023 14:36
R.5 H2-D/10 CORRECT TIA Cat 6A Perm. Link 69.2 m 1.8 dB (NEXT) 20/05/2023 14:37
R.5 H2-D/11 CORRECT TIA Cat 6A Perm. Link 69.2 m 3.4 dB (NEXT) 20/05/2023 14:35
R.5 H2-D/12 CORRECT TIA Cat 6A Perm. Link 68.2 m 2.7 dB (NEXT) 20/05/2023 14:36
R.5 H2-D/13 CORRECT TIA Cat 6A Perm. Link 66.3 m 2.3 dB (NEXT) 20/05/2023 14:34
R.5 H2-D/14 CORRECT* TIA Cat 6A Perm. Link 66.3 m 0.2 dB (NEXT) 20/05/2023 14:34
R.5 H2-D/15 CORRECT TIA Cat 6A Perm. Link 66.3 m 4.1 dB (NEXT) 20/05/2023 14:32
R.5 H2-D/16 CORRECT TIA Cat 6A Perm. Link 66.3 m 3.8 dB (NEXT) 20/05/2023 14:33
R.5 H2-E/09 CORRECT TIA Cat 6A Perm. Link 56.1 m 3.1 dB (NEXT) 20/05/2023 14:30
R.5 H2-E/10 CORRECT TIA Cat 6A Perm. Link 55.4 m 5.1 dB (NEXT) 20/05/2023 14:31
R.5 H2-E/11 CORRECT TIA Cat 6A Perm. Link 54.0 m 4.2 dB (NEXT) 20/05/2023 14:26
R.5 H2-E/12 CORRECT TIA Cat 6A Perm. Link 53.1 m 3.2 dB (NEXT) 20/05/2023 14:25
R.5 H2-E/13 CORRECT TIA Cat 6A Perm. Link 53.1 m 4.1 dB (NEXT) 20/05/2023 14:26
R.5 H2-E/14 CORRECT TIA Cat 6A Perm. Link 53.1 m 5.5 dB (NEXT) 20/05/2023 14:27
R.5 H2-E/15 CORRECT TIA Cat 6A Perm. Link 45.9 m 3.5 dB (NEXT) 20/05/2023 14:13
R.5 H2-E/16 CORRECT TIA Cat 6A Perm. Link 48.8 m 3.8 dB (NEXT) 20/05/2023 14:18
R.5 H2-E/17 CORRECT* TIA Cat 6A Perm. Link 49.0 m 0.7 dB (NEXT) 20/05/2023 14:16
R.5 H2-E/18 CORRECT TIA Cat 6A Perm. Link 49.7 m 4.3 dB (NEXT) 20/05/2023 14:12
R.5 H2-E/19 CORRECT TIA Cat 6A Perm. Link 50.2 m 4.3 dB (NEXT) 20/05/2023 14:21
R.5 H2-E/21 CORRECT TIA Cat 6A Perm. Link 49.7 m 4.7 dB (NEXT) 20/05/2023 14:21
R.5 H2-E/24 CORRECT TIA Cat 6A Perm. Link 50.4 m 2.6 dB (NEXT) 20/05/2023 14:25
R.5 H2-F/01 CORRECT TIA Cat 6A Perm. Link 46.9 m 8.8 dB (NEXT) 20/05/2023 14:09
R.5 H2-F/03 CORRECT TIA Cat 6A Perm. Link 47.6 m 10.8 dB (NEXT) 20/05/2023 14:07
R.5 H2-F/04 CORRECT TIA Cat 6A Perm. Link 47.1 m 9.6 dB (NEXT) 20/05/2023 14:10
R.5 H2-F/05 CORRECT TIA Cat 6A Perm. Link 43.8 m 10.1 dB (NEXT) 20/05/2023 13:49
R.5 H2-F/06 CORRECT TIA Cat 6A Perm. Link 42.2 m 10.3 dB (NEXT) 20/05/2023 13:57
R.5 H2-F/07 CORRECT TIA Cat 6A Perm. Link 41.9 m 10.9 dB (NEXT) 20/05/2023 14:01
R.5 H2-F/08 CORRECT TIA Cat 6A Perm. Link 44.3 m 11.1 dB (NEXT) 20/05/2023 14:04
R.5 H2-F/09 CORRECT TIA Cat 6A Perm. Link 43.1 m 9.3 dB (NEXT) 20/05/2023 14:04
R.5 H2-F/15 CORRECT TIA Cat 6A Perm. Link 29.4 m 8.7 dB (NEXT) 20/05/2023 16:09
R.5 H2-F/16 CORRECT TIA Cat 6A Perm. Link 29.4 m 8.7 dB (NEXT) 20/05/2023 16:08
R.5 H2-F/17 CORRECT TIA Cat 6A Perm. Link 30.3 m 10.8 dB (NEXT) 20/05/2023 16:08
R.5 H2-F/19 CORRECT TIA Cat 6A Perm. Link 35.5 m 9.8 dB (NEXT) 20/05/2023 15:56
R.5 H2-F/20 CORRECT TIA Cat 6A Perm. Link 32.9 m 8.3 dB (NEXT) 20/05/2023 16:52
R.5 H2-F/21 CORRECT TIA Cat 6A Perm. Link 32.2 m 10.4 dB (NEXT) 20/05/2023 15:55
R.5 H2-F/23 CORRECT TIA Cat 6A Perm. Link 28.4 m 8.4 dB (NEXT) 20/05/2023 15:51
R.5 H2-F/24 CORRECT TIA Cat 6A Perm. Link 29.6 m 9.4 dB (NEXT) 20/05/2023 15:54
R.5 H2-G/01 CORRECT TIA Cat 6A Perm. Link 21.3 m 9.7 dB (NEXT) 20/05/2023 13:21
R.5 H2-G/02 CORRECT TIA Cat 6A Perm. Link 21.1 m 10.0 dB (NEXT) 20/05/2023 13:24
R.5 H2-G/03 CORRECT TIA Cat 6A Perm. Link 23.9 m 11.6 dB (NEXT) 20/05/2023 13:25
R.5 H2-G/04 CORRECT TIA Cat 6A Perm. Link 23.9 m 10.0 dB (NEXT) 20/05/2023 13:25

22/05/2023 09:45:32 Page 3


HOPITAL NECKER H6 22 05 2023 correct.flw
Longueur totale 10709.3 m
Nombre de rapports: 204
Nombre de rapports passant: 204
Nombre de rapports en échec: 0
Nombre de rapports avec un avertissement. 0
Pour documentation seulement: 0

22/05/2023 09:45:32 Page 4


HOPITAL NECKER H6 22 05 2023 correct.flw
ID Câble: R.5 H1-A/01 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:04:50 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.9 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 72.2 72.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 329
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 24
Résistance (ohms) [Paire 3,6] 10.18
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 14.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 3,6-7,8 4,5-7,8 MHz


NEXT (dB) 2.9 4.9 5.7 6.0
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 360.0 434.0 467.0 484.0 100 100
Limite (dB) 31.4 28.7 27.6 27.1 80 80
Pire paire 4,5 7,8 3,6 7,8
60 60
PS NEXT (dB) 5.2 7.1 6.2 7.8
Fréq. (MHz) 360.0 210.5 471.0 484.0 40 40

Limite (dB) 28.7 34.0 24.7 24.2 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.9 14.0 13.9 14.0
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 425.0 464.0 425.0 464.0 100 100
Limite (dB) 11.6 10.9 11.6 10.9 80 80
Pire paire 1,2 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.4 15.9 16.9 15.9
40 40
Fréq. (MHz) 1.0 464.0 425.0 464.0
Limite (dB) 61.2 7.9 8.6 7.9 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 12.6 10.8 21.0 21.9 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.1 3.5 474.0 484.0
Limite (dB) 61.8 61.7 -15.0 -15.8 80 80

Pire paire 1,2 1,2 3,6 3,6


40 40
PS ACR-N (dB) 12.5 11.0 20.4 24.0
Fréq. (MHz) 3.3 3.3 471.0 491.0 0 0
Limite (dB) 58.8 58.8 -17.6 -19.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 1,2 4,5 4,5 MHz MHz
RL (dB) 4.6 6.2 8.0 8.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 65.8 44.5 497.0 490.0 100 100
Limite (dB) 15.8 17.5 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 5
ID Câble: R.5 H1-A/02 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:05:24 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.7 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 72.0 72.0 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 328
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 24
Résistance (ohms) [Paire 3,6] 10.11
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 15.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 3,6-7,8 4,5-7,8 MHz


NEXT (dB) 4.7 5.1 7.5 6.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 257.0 196.5 480.0 486.0 100 100
Limite (dB) 35.1 37.1 27.2 27.1 80 80
Pire paire 7,8 4,5 3,6 4,5
60 60
PS NEXT (dB) 6.3 7.4 8.8 9.1
Fréq. (MHz) 257.0 197.0 480.0 486.0 40 40

Limite (dB) 32.5 34.4 24.4 24.2 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.9 13.6 14.7 14.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 298.0 335.0 500.0 458.0 100 100
Limite (dB) 14.7 13.7 10.2 11.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.3 16.3 15.8 17.5
40 40
Fréq. (MHz) 298.0 335.0 500.0 500.0
Limite (dB) 11.7 10.7 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 3,6-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 12.8 14.0 23.1 23.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 22.9 22.9 480.0 500.0
Limite (dB) 43.8 43.8 -15.5 -17.1 80 80

Pire paire 4,5 1,2 3,6 4,5


40 40
PS ACR-N (dB) 13.5 14.3 23.3 25.1
Fréq. (MHz) 22.9 6.0 480.0 500.0 0 0
Limite (dB) 41.4 54.7 -18.4 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 3,6 3,6 MHz MHz
RL (dB) 3.9 5.4 9.4 9.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 6.9 7.1 482.0 489.0 100 100
Limite (dB) 21.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 6
ID Câble: R.5 H1-A/04 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:06:01 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.2 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 72.2 72.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 329
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 24
Résistance (ohms) [Paire 3,6] 10.14
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 14.8 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-3,6 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.2 6.9 7.1 7.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 264.0 281.0 498.0 485.0 100 100
Limite (dB) 34.9 34.5 26.7 27.1 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 5.3 8.8 8.8 9.0
Fréq. (MHz) 264.0 198.5 498.0 485.0 40 40

Limite (dB) 32.3 34.4 23.8 24.2 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.1 12.5 13.1 14.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 471.0 296.0 471.0 471.0 100 100
Limite (dB) 10.7 14.8 10.7 10.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.7 15.5 15.7 17.5
40 40
Fréq. (MHz) 471.0 296.0 471.0 500.0
Limite (dB) 7.7 11.8 7.7 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 11.0 10.9 23.5 23.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.1 4.3 500.0 485.0
Limite (dB) 60.3 60.0 -17.1 -15.9 80 80

Pire paire 3,6 1,2 4,5 4,5


40 40
PS ACR-N (dB) 11.9 12.2 23.9 25.0
Fréq. (MHz) 4.0 4.4 498.0 500.0 0 0
Limite (dB) 58.3 57.5 -19.8 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 1,2 4,5 4,5 MHz MHz
RL (dB) 5.8 5.9 8.3 9.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 6.6 18.1 375.0 444.0 100 100
Limite (dB) 21.0 19.7 8.3 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 7
ID Câble: R.5 H1-A/05 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:02:05 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.1 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 66.8 66.8 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 304
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 22
Résistance (ohms) [Paire 3,6] 9.35
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 17.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 4.1 6.7 4.6 6.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 234.5 499.0 469.0 499.0 100 100
Limite (dB) 35.8 26.7 27.6 26.7 80 80
Pire paire 7,8 4,5 4,5 4,5
60 60
PS NEXT (dB) 6.0 8.7 6.5 8.7
Fréq. (MHz) 288.0 499.0 469.0 499.0 40 40

Limite (dB) 31.7 23.8 24.7 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.7 13.5 14.8 15.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 413.0 232.5 500.0 500.0 100 100
Limite (dB) 11.9 16.9 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.9 15.8 16.9 17.7
40 40
Fréq. (MHz) 412.0 232.0 500.0 500.0
Limite (dB) 8.9 13.9 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 11.7 12.4 22.2 24.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.4 3.5 469.0 499.0
Limite (dB) 61.7 61.7 -14.6 -17.0 80 80

Pire paire 1,2 3,6 4,5 4,5


40 40
PS ACR-N (dB) 13.7 12.9 23.3 26.1
Fréq. (MHz) 15.4 3.6 469.0 499.0 0 0
Limite (dB) 45.7 58.6 -17.4 -19.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 1,2 3,6 4,5 MHz MHz
RL (dB) 7.4 6.7 7.4 10.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 487.0 24.8 487.0 452.0 100 100
Limite (dB) 8.0 19.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 8
ID Câble: R.5 H1-A/06 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:09:37 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.9 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 64.9 64.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 295
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 21
Résistance (ohms) [Paire 3,6] 9.14
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 18.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-4,5 4,5-7,8 1,2-4,5 MHz


NEXT (dB) 2.9 6.4 2.9 6.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 487.0 415.0 487.0 415.0 100 100
Limite (dB) 27.0 29.3 27.0 29.3 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 4.9 7.8 5.2 9.5
Fréq. (MHz) 269.0 415.0 487.0 494.0 40 40

Limite (dB) 32.2 26.5 24.2 23.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.2 12.9 13.3 13.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 475.0 418.0 476.0 425.0 100 100
Limite (dB) 10.7 11.8 10.6 11.6 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.0 14.8 15.0 14.9
40 40
Fréq. (MHz) 475.0 230.0 475.0 425.0
Limite (dB) 7.7 14.0 7.7 8.6 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 4,5-7,8 4,5-7,8 1,2-3,6 MHz MHz
ACR-N (dB) 14.6 13.2 21.9 26.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 15.6 34.8 487.0 495.0
Limite (dB) 47.9 38.9 -16.1 -16.7 80 80

Pire paire 7,8 4,5 4,5 3,6


40 40
PS ACR-N (dB) 14.8 14.5 23.3 27.5
Fréq. (MHz) 15.1 35.0 487.0 495.0 0 0
Limite (dB) 45.8 36.3 -18.9 -19.6
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 3,6 4,5 MHz MHz
RL (dB) 6.7 5.6 8.6 9.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 14.1 14.4 495.0 435.0 100 100
Limite (dB) 20.3 20.2 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 9
ID Câble: R.5 H1-A/07 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:10:14 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 1.2 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 64.7 64.7 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 295
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 22
Résistance (ohms) [Paire 3,6] 9.03
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 18.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 1.2 4.3 4.4 7.2
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 205.0 169.0 480.0 500.0 100 100
Limite (dB) 36.8 38.1 27.2 26.7 80 80
Pire paire 4,5 4,5 7,8 4,5
60 60
PS NEXT (dB) 3.4 6.2 6.2 8.8
Fréq. (MHz) 204.5 169.0 480.0 500.0 40 40

Limite (dB) 34.2 35.5 24.4 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.9 13.7 14.1 13.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 418.0 464.0 466.0 464.0 100 100
Limite (dB) 11.8 10.9 10.8 10.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.0 15.6 16.5 15.6
40 40
Fréq. (MHz) 373.0 464.0 465.0 464.0
Limite (dB) 9.8 7.9 7.8 7.9 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 1,2-3,6 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 10.4 12.5 23.0 26.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 9.6 7.1 480.0 500.0
Limite (dB) 52.7 55.5 -15.5 -17.1 80 80

Pire paire 7,8 3,6 3,6 4,5


40 40
PS ACR-N (dB) 11.9 13.5 25.9 27.2
Fréq. (MHz) 9.5 7.1 500.0 500.0 0 0
Limite (dB) 50.5 53.2 -20.0 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 3,6 MHz MHz
RL (dB) 5.3 6.3 9.1 8.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 92.8 23.8 474.0 437.0 100 100
Limite (dB) 14.3 19.1 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 10
ID Câble: R.5 H1-A/08 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:10:42 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.6 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 64.7 64.7 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 294
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 21
Résistance (ohms) [Paire 3,6] 9.10
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 18.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 2.6 4.2 6.9 4.2
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 221.5 452.0 500.0 452.0 100 100
Limite (dB) 36.2 28.1 26.7 28.1 80 80
Pire paire 4,5 4,5 7,8 4,5
60 60
PS NEXT (dB) 4.5 6.4 8.3 6.4
Fréq. (MHz) 221.5 452.0 500.0 452.0 40 40

Limite (dB) 33.6 25.3 23.8 25.3 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.7 13.5 13.4 14.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 333.0 239.5 485.0 484.0 100 100
Limite (dB) 13.7 16.6 10.5 10.5 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.4 15.6 15.8 16.7
40 40
Fréq. (MHz) 332.0 239.0 485.0 484.0
Limite (dB) 10.8 13.6 7.5 7.5 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 1,2-4,5 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 11.8 12.9 26.2 22.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 16.5 20.1 500.0 452.0
Limite (dB) 47.3 45.2 -17.1 -13.2 80 80

Pire paire 4,5 1,2 4,5 4,5


40 40
PS ACR-N (dB) 13.2 14.6 27.0 24.8
Fréq. (MHz) 47.8 20.5 500.0 464.0 0 0
Limite (dB) 32.4 42.6 -20.0 -17.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 4,5 4,5 MHz MHz
RL (dB) 7.2 7.9 7.5 9.1 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 344.0 14.6 498.0 484.0 100 100
Limite (dB) 8.6 20.2 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 11
ID Câble: R.5 H1-A/09 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:07:36 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.8 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 66.8 66.8 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 304
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 22
Résistance (ohms) [Paire 3,6] 9.46
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 17.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 3,6-7,8 4,5-7,8 MHz


NEXT (dB) 3.8 4.9 8.3 6.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 292.0 157.5 482.0 454.0 100 100
Limite (dB) 34.2 38.6 27.2 28.0 80 80
Pire paire 4,5 4,5 3,6 7,8
60 60
PS NEXT (dB) 6.2 6.8 8.0 9.0
Fréq. (MHz) 292.0 153.0 482.0 454.0 40 40

Limite (dB) 31.6 36.3 24.3 25.2 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.9 13.6 13.4 14.0
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 364.0 362.0 500.0 500.0 100 100
Limite (dB) 13.0 13.0 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.1 15.7 15.6 15.8
40 40
Fréq. (MHz) 364.0 362.0 500.0 499.0
Limite (dB) 10.0 10.0 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 4,5-7,8 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 12.8 12.4 27.0 26.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 15.1 5.3 499.0 491.0
Limite (dB) 48.2 58.2 -17.0 -16.4 80 80

Pire paire 3,6 4,5 3,6 3,6


40 40
PS ACR-N (dB) 14.9 14.0 24.6 28.0
Fréq. (MHz) 15.0 5.3 482.0 491.0 0 0
Limite (dB) 45.9 55.9 -18.5 -19.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 1,2 4,5 4,5 MHz MHz
RL (dB) 5.5 5.6 7.3 8.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 7.3 10.9 480.0 495.0 100 100
Limite (dB) 21.0 20.8 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 12
ID Câble: R.5 H1-A/13 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:17:37 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 1.9 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 62.5 62.5 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 285
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 21
Résistance (ohms) [Paire 3,6] 8.85
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 18.5 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.8 1.9 3.8 1.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 466.0 411.0 466.0 411.0 100 100
Limite (dB) 27.7 29.5 27.7 29.5 80 80
Pire paire 4,5 7,8 4,5 7,8
60 60
PS NEXT (dB) 6.3 4.4 6.3 4.4
Fréq. (MHz) 466.0 411.0 466.0 411.0 40 40

Limite (dB) 24.8 26.7 24.8 26.7 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 12.7 13.2 13.5 14.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 351.0 348.0 451.0 451.0 100 100
Limite (dB) 13.3 13.4 11.1 11.1 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.6 15.9 16.0 16.9
40 40
Fréq. (MHz) 351.0 399.0 451.0 446.0
Limite (dB) 10.3 9.2 8.1 8.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 4,5-7,8 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 11.4 12.3 22.6 25.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 39.3 14.9 466.0 499.0
Limite (dB) 37.4 48.4 -14.3 -17.0 80 80

Pire paire 3,6 4,5 4,5 4,5


40 40
PS ACR-N (dB) 13.8 13.5 24.7 27.2
Fréq. (MHz) 39.3 14.9 466.0 499.0 0 0
Limite (dB) 34.9 46.0 -17.2 -19.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 3,6 MHz MHz
RL (dB) 6.3 7.6 10.2 9.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 9.4 18.9 438.0 489.0 100 100
Limite (dB) 21.0 19.6 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 13
ID Câble: R.5 H1-A/14 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:12:22 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.7 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 61.6 61.6 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 281
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 21
Résistance (ohms) [Paire 3,6] 8.67
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 18.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 5.6 3.7 7.2 3.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 220.0 457.0 453.0 457.0 100 100
Limite (dB) 36.2 27.9 28.1 27.9 80 80
Pire paire 7,8 4,5 3,6 4,5
60 60
PS NEXT (dB) 7.3 6.1 8.4 6.1
Fréq. (MHz) 220.0 457.0 495.0 457.0 40 40

Limite (dB) 33.6 25.1 23.9 25.1 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.4 13.8 13.7 13.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 444.0 444.0 492.0 500.0 100 100
Limite (dB) 11.2 11.2 10.4 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.2 16.3 15.2 16.3
40 40
Fréq. (MHz) 440.0 500.0 440.0 500.0
Limite (dB) 8.3 7.2 8.3 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 13.9 12.0 26.5 22.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 10.1 9.6 477.0 457.0
Limite (dB) 52.2 52.7 -15.2 -13.6 80 80

Pire paire 7,8 1,2 3,6 4,5


40 40
PS ACR-N (dB) 14.8 13.5 27.2 24.3
Fréq. (MHz) 23.5 9.8 495.0 457.0 0 0
Limite (dB) 41.1 50.2 -19.6 -16.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 1,2 4,5 4,5 MHz MHz
RL (dB) 7.9 8.2 7.9 9.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 450.0 17.3 450.0 489.0 100 100
Limite (dB) 8.0 19.8 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 14
ID Câble: R.5 H1-A/16 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:20:27 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.4 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 51.4 51.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 234
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 17
Résistance (ohms) [Paire 3,6] 7.34
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 22.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 4.4 6.9 7.3 8.2
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 261.0 229.5 496.0 497.0 100 100
Limite (dB) 35.0 35.9 26.8 26.7 80 80
Pire paire 4,5 4,5 7,8 4,5
60 60
PS NEXT (dB) 6.7 8.7 9.0 8.8
Fréq. (MHz) 261.0 419.0 500.0 497.0 40 40

Limite (dB) 32.4 26.4 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.4 13.4 14.4 13.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 411.0 406.0 463.0 469.0 100 100
Limite (dB) 11.9 12.0 10.9 10.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.0 15.7 16.5 16.0
40 40
Fréq. (MHz) 351.0 406.0 477.0 470.0
Limite (dB) 10.3 9.0 7.6 7.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 1,2-3,6 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 15.2 15.9 31.4 32.0 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 36.8 8.8 500.0 497.0
Limite (dB) 38.2 53.6 -17.1 -16.9 80 80

Pire paire 1,2 4,5 4,5 4,5


40 40
PS ACR-N (dB) 15.8 16.8 32.7 31.7
Fréq. (MHz) 8.0 10.6 500.0 497.0 0 0
Limite (dB) 52.1 49.4 -20.0 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 4,5 MHz MHz
RL (dB) 5.5 6.4 5.5 8.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 196.5 32.3 196.5 451.0 100 100
Limite (dB) 11.1 18.5 11.1 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 15
ID Câble: R.5 H1-A/18 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:19:06 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.7 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 51.4 51.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 234
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 17
Résistance (ohms) [Paire 3,6] 7.30
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 22.8 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-4,5 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.7 5.5 7.0 5.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 201.5 228.0 474.0 431.0 100 100
Limite (dB) 36.9 36.0 27.4 28.8 80 80
Pire paire 7,8 4,5 7,8 4,5
60 60
PS NEXT (dB) 5.7 7.0 8.4 8.3
Fréq. (MHz) 201.5 228.0 474.0 477.0 40 40

Limite (dB) 34.3 33.4 24.6 24.5 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.7 13.5 13.7 13.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 484.0 480.0 484.0 483.0 100 100
Limite (dB) 10.5 10.6 10.5 10.5 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.5 16.0 16.5 16.1
40 40
Fréq. (MHz) 484.0 480.0 484.0 484.0
Limite (dB) 7.5 7.6 7.5 7.5 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 13.6 13.9 31.6 30.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.6 3.5 499.0 489.0
Limite (dB) 61.4 61.7 -17.0 -16.2 80 80

Pire paire 4,5 7,8 3,6 4,5


40 40
PS ACR-N (dB) 14.4 14.4 32.7 31.0
Fréq. (MHz) 3.8 3.9 500.0 477.0 0 0
Limite (dB) 58.6 58.5 -20.0 -18.1
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 1,2 MHz MHz
RL (dB) 7.9 6.7 10.3 10.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 58.3 18.5 500.0 434.0 100 100
Limite (dB) 16.3 19.7 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 16
ID Câble: R.5 H1-A/19 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:21:41 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 1.9 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 48.1 48.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 219
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 16
Résistance (ohms) [Paire 3,6] 6.83
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 24.3 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 1.9 4.2 3.2 4.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 235.0 394.0 472.0 465.0 100 100
Limite (dB) 35.8 30.1 27.5 27.7 80 80
Pire paire 7,8 4,5 4,5 4,5
60 60
PS NEXT (dB) 3.9 6.0 5.4 6.0
Fréq. (MHz) 235.0 465.0 472.0 465.0 40 40

Limite (dB) 33.2 24.8 24.6 24.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.4 14.4 14.4 15.2
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 449.0 123.5 449.0 500.0 100 100
Limite (dB) 11.1 22.4 11.1 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.7 16.8 17.0 17.4
40 40
Fréq. (MHz) 306.0 306.0 497.0 500.0
Limite (dB) 11.5 11.5 7.3 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 13.9 15.4 28.0 28.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 13.5 12.9 482.0 465.0
Limite (dB) 49.4 49.8 -15.6 -14.2 80 80

Pire paire 7,8 1,2 4,5 4,5


40 40
PS ACR-N (dB) 14.6 16.3 29.8 29.3
Fréq. (MHz) 13.4 4.1 482.0 465.0 0 0
Limite (dB) 47.1 58.0 -18.5 -17.1
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 4,5 MHz MHz
RL (dB) 5.0 5.7 6.9 8.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 144.0 42.3 491.0 480.0 100 100
Limite (dB) 12.4 17.7 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 17
ID Câble: R.5 H1-A/20 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:22:53 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.5 dB (NEXT 3,6-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 48.1 48.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 219
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 16
Résistance (ohms) [Paire 3,6] 6.83
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 24.5 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-7,8 4,5-7,8 3,6-7,8 4,5-7,8 MHz


NEXT (dB) 3.5 4.2 3.5 8.2
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 500.0 273.0 500.0 469.0 100 100
Limite (dB) 26.7 34.7 26.7 27.6 80 80
Pire paire 7,8 4,5 3,6 3,6
60 60
PS NEXT (dB) 5.1 6.3 5.5 10.0
Fréq. (MHz) 446.0 273.0 499.0 496.0 40 40

Limite (dB) 25.5 32.1 23.8 23.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.1 14.3 14.5 14.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 249.0 183.0 435.0 500.0 100 100
Limite (dB) 16.3 18.9 11.4 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.5 16.5 16.5 16.6
40 40
Fréq. (MHz) 498.0 310.0 498.0 500.0
Limite (dB) 7.2 11.4 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 1,2-3,6 3,6-7,8 1,2-3,6 MHz MHz
ACR-N (dB) 13.4 14.1 28.4 34.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 31.5 4.4 500.0 496.0
Limite (dB) 40.1 59.8 -17.1 -16.8 80 80

Pire paire 3,6 1,2 3,6 3,6


40 40
PS ACR-N (dB) 13.6 15.3 29.9 34.3
Fréq. (MHz) 8.0 4.4 499.0 496.0 0 0
Limite (dB) 52.1 57.5 -19.9 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 3,6 4,5 MHz MHz
RL (dB) 5.0 6.2 7.1 8.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 63.0 52.3 323.0 449.0 100 100
Limite (dB) 16.0 16.8 8.9 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 18
ID Câble: R.5 H1-A/21 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:30:24 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 5.4 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 44.3 44.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 201
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 14
Résistance (ohms) [Paire 3,6] 6.29
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 25.8 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 5.9 5.4 7.2 5.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 227.5 474.0 482.0 474.0 100 100
Limite (dB) 36.0 27.4 27.2 27.4 80 80
Pire paire 3,6 4,5 4,5 7,8
60 60
PS NEXT (dB) 7.5 5.8 8.2 7.5
Fréq. (MHz) 431.0 420.0 482.0 477.0 40 40

Limite (dB) 26.0 26.4 24.3 24.5 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-1,2 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.2 14.4 14.5 15.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 402.0 402.0 476.0 482.0 100 100
Limite (dB) 12.1 12.1 10.6 10.5 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.0 16.7 17.2 17.7
40 40
Fréq. (MHz) 333.0 335.0 476.0 482.0
Limite (dB) 10.7 10.7 7.6 7.5 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 11.3 11.5 34.1 31.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 5.4 5.4 500.0 474.0
Limite (dB) 58.0 58.0 -17.1 -15.0 80 80

Pire paire 1,2 1,2 4,5 4,5


40 40
PS ACR-N (dB) 12.8 13.2 33.8 32.9
Fréq. (MHz) 5.4 5.0 482.0 474.0 0 0
Limite (dB) 55.7 56.3 -18.5 -17.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 7,8 3,6 MHz MHz
RL (dB) 6.3 6.3 8.9 9.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 24.0 24.1 490.0 494.0 100 100
Limite (dB) 19.1 19.1 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 19
ID Câble: R.5 H1-A/22 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:31:46 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.0 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 44.3 44.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 201
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 14
Résistance (ohms) [Paire 3,6] 6.22
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 25.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 4.3 2.0 7.3 2.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 188.5 284.0 450.0 423.0 100 100
Limite (dB) 37.4 34.4 28.2 29.1 80 80
Pire paire 4,5 7,8 7,8 7,8
60 60
PS NEXT (dB) 6.0 4.0 7.9 4.9
Fréq. (MHz) 188.5 283.0 450.0 423.0 40 40

Limite (dB) 34.7 31.8 25.3 26.3 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.0 14.3 14.2 14.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 409.0 474.0 476.0 474.0 100 100
Limite (dB) 12.0 10.7 10.6 10.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.4 16.2 16.4 16.8
40 40
Fréq. (MHz) 477.0 343.0 477.0 475.0
Limite (dB) 7.6 10.5 7.6 7.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 14.5 13.5 36.0 31.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 30.5 25.9 500.0 483.0
Limite (dB) 40.5 42.4 -17.1 -15.7 80 80

Pire paire 3,6 3,6 3,6 4,5


40 40
PS ACR-N (dB) 15.3 15.3 35.2 32.7
Fréq. (MHz) 5.5 5.4 489.0 483.0 0 0
Limite (dB) 55.5 55.7 -19.1 -18.6
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 3,6 3,6 MHz MHz
RL (dB) 6.7 4.2 8.8 9.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 26.4 26.9 415.0 444.0 100 100
Limite (dB) 18.9 18.9 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 20
ID Câble: R.5 H1-A/23 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:32:42 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.0 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 49.0 49.0 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 224
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 17
Résistance (ohms) [Paire 3,6] 6.94
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 23.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.3 3.0 5.3 3.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 367.0 232.5 427.0 367.0 100 100
Limite (dB) 31.1 35.9 28.9 31.1 80 80
Pire paire 7,8 7,8 4,5 7,8
60 60
PS NEXT (dB) 5.8 5.0 6.6 9.7
Fréq. (MHz) 367.0 232.5 427.0 500.0 40 40

Limite (dB) 28.4 33.2 26.1 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.6 13.9 13.6 13.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 498.0 495.0 498.0 495.0 100 100
Limite (dB) 10.2 10.3 10.2 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.5 15.7 15.6 15.8
40 40
Fréq. (MHz) 497.0 497.0 498.0 498.0
Limite (dB) 7.3 7.3 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-4,5 1,2-3,6 1,2-4,5 4,5-7,8 MHz MHz
ACR-N (dB) 13.5 14.3 33.2 33.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 23.5 13.6 489.0 500.0
Limite (dB) 43.5 49.3 -16.2 -17.1 80 80

Pire paire 4,5 1,2 3,6 3,6


40 40
PS ACR-N (dB) 14.3 14.9 34.1 34.0
Fréq. (MHz) 23.3 13.4 496.0 496.0 0 0
Limite (dB) 41.2 47.1 -19.7 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 4,5 3,6 3,6 MHz MHz
RL (dB) 6.8 6.5 6.9 9.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 88.0 44.0 334.0 469.0 100 100
Limite (dB) 14.6 17.6 8.8 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 21
ID Câble: R.5 H1-A/24 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:27:27 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.9 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 48.1 48.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 219
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 16
Résistance (ohms) [Paire 3,6] 6.80
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 24.5 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-4,5 4,5-7,8 MHz


NEXT (dB) 5.5 3.9 7.2 6.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 310.0 304.0 424.0 497.0 100 100
Limite (dB) 33.5 33.8 29.0 26.7 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 7.1 5.9 9.1 8.1
Fréq. (MHz) 310.0 304.0 474.0 496.0 40 40

Limite (dB) 30.9 31.2 24.6 23.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.8 12.9 14.4 12.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 184.5 491.0 495.0 491.0 100 100
Limite (dB) 18.9 10.4 10.3 10.4 80 80
Pire paire 3,6 3,6 1,2 3,6
60 60
PS ACR-F (dB) 16.5 15.1 16.8 15.1
40 40
Fréq. (MHz) 304.0 491.0 490.0 491.0
Limite (dB) 11.5 7.4 7.4 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-4,5 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 12.3 14.8 33.9 31.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 5.0 16.3 495.0 497.0
Limite (dB) 58.6 47.5 -16.7 -16.9 80 80

Pire paire 4,5 4,5 3,6 4,5


40 40
PS ACR-N (dB) 13.5 15.4 34.3 32.6
Fréq. (MHz) 4.9 3.9 497.0 496.0 0 0
Limite (dB) 56.6 58.5 -19.7 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 4,5 MHz MHz
RL (dB) 6.0 6.6 8.7 8.1 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 48.3 19.6 489.0 489.0 100 100
Limite (dB) 17.2 19.5 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 22
ID Câble: R.5 H1-B/01 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:45:18 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 0.2 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 44.3 44.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 202
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 15
Résistance (ohms) [Paire 3,6] 6.40
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 25.7 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 0.2 * 3.7 4.6 4.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 281.0 281.0 470.0 447.0 100 100
Limite (dB) 34.5 34.5 27.5 28.3 80 80
Pire paire 4,5 7,8 4,5 4,5
60 60
PS NEXT (dB) 2.6 5.7 6.7 7.0
Fréq. (MHz) 281.0 281.0 470.0 447.0 40 40

Limite (dB) 31.9 31.9 24.7 25.4 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-1,2 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 12.5 13.7 12.5 13.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 478.0 478.0 478.0 478.0 100 100
Limite (dB) 10.6 10.6 10.6 10.6 80 80
Pire paire 3,6 3,6 3,6 1,2
60 60
PS ACR-F (dB) 14.8 16.0 14.9 16.6
40 40
Fréq. (MHz) 475.0 336.0 478.0 478.0
Limite (dB) 7.7 10.7 7.6 7.6 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-4,5 1,2-3,6 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 14.9 15.6 30.0 29.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 8.0 5.9 470.0 447.0
Limite (dB) 54.4 57.2 -14.7 -12.7 80 80

Pire paire 4,5 4,5 4,5 4,5


40 40
PS ACR-N (dB) 14.1 15.3 31.4 34.7
Fréq. (MHz) 8.0 7.9 470.0 500.0 0 0
Limite (dB) 52.1 52.2 -17.5 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 3,6 MHz MHz
RL (dB) 4.6 8.0 8.5 8.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 25.6 103.0 496.0 423.0 100 60
Limite (dB) 19.0 13.9 8.0 8.0 80 50

Conforme aux normes de réseaux: 40


60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

* La marge est dans les limites de précision de l'instrument.

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 23
ID Câble: R.5 H1-B/02 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:46:25 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 1.3 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 44.3 44.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 202
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 15
Résistance (ohms) [Paire 3,6] 6.33
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 25.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.3 1.3 6.0 8.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 354.0 221.5 500.0 482.0 100 100
Limite (dB) 31.6 36.2 26.7 27.2 80 80
Pire paire 4,5 4,5 4,5 3,6
60 60
PS NEXT (dB) 5.3 3.8 8.0 9.1
Fréq. (MHz) 354.0 221.5 500.0 500.0 40 40

Limite (dB) 28.9 33.6 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.8 13.3 13.8 14.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 397.0 336.0 397.0 461.0 100 100
Limite (dB) 12.2 13.7 12.2 10.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.4 15.6 17.8 16.4
40 40
Fréq. (MHz) 397.0 339.0 472.0 461.0
Limite (dB) 9.2 10.6 7.7 7.9 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-4,5 1,2-3,6 4,5-7,8 1,2-3,6 MHz MHz
ACR-N (dB) 14.8 14.0 32.6 35.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 6.9 17.9 500.0 498.0
Limite (dB) 55.8 46.5 -17.1 -16.9 80 80

Pire paire 1,2 1,2 4,5 3,6


40 40
PS ACR-N (dB) 15.0 15.2 34.1 35.0
Fréq. (MHz) 7.3 3.1 500.0 500.0 0 0
Limite (dB) 53.0 58.8 -20.0 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 3,6 4,5 3,6 MHz MHz
RL (dB) 6.5 7.5 7.7 7.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 26.3 470.0 433.0 470.0 100 100
Limite (dB) 18.9 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 24
ID Câble: R.5 H1-B/03 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:46:56 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.2 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 44.3 44.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 201
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 14
Résistance (ohms) [Paire 3,6] 6.33
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 25.5 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 5.7 4.2 6.8 7.2
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 310.0 272.0 486.0 500.0 100 100
Limite (dB) 33.5 34.7 27.1 26.7 80 80
Pire paire 4,5 4,5 3,6 7,8
60 60
PS NEXT (dB) 7.6 6.2 8.2 8.8
Fréq. (MHz) 376.0 272.0 487.0 500.0 40 40

Limite (dB) 28.0 32.1 24.2 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 14.0 14.2 15.1 15.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 343.0 345.0 498.0 498.0 100 100
Limite (dB) 13.5 13.4 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 1,2
60 60
PS ACR-F (dB) 15.9 16.2 17.6 18.5
40 40
Fréq. (MHz) 342.0 348.0 488.0 498.0
Limite (dB) 10.5 10.4 7.4 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 4,5-7,8 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 13.7 13.9 31.8 33.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 18.6 3.5 486.0 500.0
Limite (dB) 46.0 61.7 -16.0 -17.1 80 80

Pire paire 1,2 1,2 3,6 4,5


40 40
PS ACR-N (dB) 14.5 15.0 33.2 35.2
Fréq. (MHz) 5.5 5.5 487.0 500.0 0 0
Limite (dB) 55.5 55.5 -18.9 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 3,6 4,5 MHz MHz
RL (dB) 6.7 7.7 10.1 8.8 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 48.0 29.6 487.0 428.0 100 100
Limite (dB) 17.2 18.6 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 25
ID Câble: R.5 H1-B/05 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:41:17 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.5 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 39.8 39.8 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 181
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 13
Résistance (ohms) [Paire 3,6] 5.64
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 27.6 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 3.5 5.6 7.7 8.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 242.0 242.0 500.0 471.0 100 100
Limite (dB) 35.6 35.6 26.7 27.5 80 80
Pire paire 7,8 4,5 3,6 4,5
60 60
PS NEXT (dB) 5.6 7.5 9.6 8.9
Fréq. (MHz) 242.0 242.0 500.0 471.0 40 40

Limite (dB) 32.9 32.9 23.8 24.7 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.1 13.7 14.8 14.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 291.0 289.0 449.0 443.0 100 100
Limite (dB) 14.9 15.0 11.1 11.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.5 16.3 17.2 16.9
40 40
Fréq. (MHz) 295.0 298.0 450.0 443.0
Limite (dB) 11.8 11.7 8.1 8.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 17.1 15.2 35.3 35.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 16.4 19.6 500.0 471.0
Limite (dB) 47.4 45.4 -17.1 -14.7 80 80

Pire paire 3,6 4,5 3,6 4,5


40 40
PS ACR-N (dB) 17.2 15.1 37.2 35.6
Fréq. (MHz) 16.6 8.9 500.0 471.0 0 0
Limite (dB) 44.8 51.1 -20.0 -17.6
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 4,5 MHz MHz
RL (dB) 7.2 6.3 9.9 10.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 51.3 51.3 394.0 423.0 100 100
Limite (dB) 16.9 16.9 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 26
ID Câble: R.5 H1-B/06 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:51:00 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.7 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 40.3 40.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 183
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 13
Résistance (ohms) [Paire 3,6] 5.72
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 27.5 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.7 4.9 7.5 9.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 276.0 185.5 500.0 495.0 100 100
Limite (dB) 34.6 37.5 26.7 26.8 80 80
Pire paire 7,8 7,8 3,6 4,5
60 60
PS NEXT (dB) 5.6 6.6 8.2 9.5
Fréq. (MHz) 276.0 185.5 472.0 493.0 40 40

Limite (dB) 32.0 34.9 24.6 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.6 14.2 15.0 14.2
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 5.9 458.0 465.0 458.0 100 100
Limite (dB) 48.8 11.0 10.8 11.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.2 16.5 16.5 16.9
40 40
Fréq. (MHz) 372.0 362.0 465.0 466.0
Limite (dB) 9.8 10.0 7.8 7.8 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 3,6-7,8 4,5-7,8 1,2-3,6 MHz MHz
ACR-N (dB) 12.1 12.8 35.7 37.1 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 12.3 12.0 500.0 494.0
Limite (dB) 50.3 50.5 -17.1 -16.6 80 80

Pire paire 3,6 3,6 4,5 4,5


40 40
PS ACR-N (dB) 12.3 12.4 36.6 36.8
Fréq. (MHz) 11.8 11.9 499.0 493.0 0 0
Limite (dB) 48.4 48.3 -19.9 -19.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 3,6 MHz MHz
RL (dB) 1.9 5.2 8.7 9.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 40.3 40.8 495.0 495.0 100 100
Limite (dB) 18.0 17.9 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 27
ID Câble: R.5 H1-B/07 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:52:07 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.3 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 40.0 40.0 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 182
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 13
Résistance (ohms) [Paire 3,6] 5.72
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 27.7 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.3 4.7 3.3 4.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 423.0 481.0 423.0 481.0 100 100
Limite (dB) 29.1 27.2 29.1 27.2 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 5.4 6.9 5.4 6.9
Fréq. (MHz) 423.0 481.0 423.0 481.0 40 40

Limite (dB) 26.3 24.3 26.3 24.3 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.1 14.1 13.1 14.2
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 435.0 438.0 435.0 441.0 100 100
Limite (dB) 11.4 11.4 11.4 11.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.0 16.4 15.3 16.5
40 40
Fréq. (MHz) 364.0 438.0 435.0 439.0
Limite (dB) 10.0 8.4 8.4 8.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 14.4 16.2 33.1 32.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 11.3 8.8 473.0 481.0
Limite (dB) 51.2 53.6 -14.9 -15.6 80 80

Pire paire 1,2 7,8 4,5 4,5


40 40
PS ACR-N (dB) 14.3 16.3 34.2 34.1
Fréq. (MHz) 11.3 10.8 469.0 481.0 0 0
Limite (dB) 48.8 49.3 -17.4 -18.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 7,8 4,5 3,6 MHz MHz
RL (dB) 6.7 7.6 7.6 9.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 224.0 26.4 389.0 493.0 100 100
Limite (dB) 10.5 18.9 8.1 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 28
ID Câble: R.5 H1-B/08 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:50:11 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.5 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 40.3 40.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 183
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 13
Résistance (ohms) [Paire 3,6] 5.72
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 27.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 6.3 4.5 7.2 4.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 389.0 500.0 500.0 500.0 100 100
Limite (dB) 30.3 26.7 26.7 26.7 80 80
Pire paire 4,5 4,5 3,6 4,5
60 60
PS NEXT (dB) 8.0 6.6 8.2 6.6
Fréq. (MHz) 133.0 500.0 490.0 500.0 40 40

Limite (dB) 37.3 23.8 24.1 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.3 14.2 14.3 14.4
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 464.0 300.0 464.0 459.0 100 100
Limite (dB) 10.9 14.6 10.9 11.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.5 16.8 16.5 16.8
40 40
Fréq. (MHz) 463.0 459.0 463.0 459.0
Limite (dB) 7.9 8.0 7.9 8.0 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-4,5 4,5-7,8 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 15.5 16.2 33.9 32.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 11.1 9.4 489.0 500.0
Limite (dB) 51.3 52.9 -16.2 -17.1 80 80

Pire paire 4,5 4,5 3,6 4,5


40 40
PS ACR-N (dB) 16.2 17.0 35.0 34.2
Fréq. (MHz) 10.8 10.0 490.0 500.0 0 0
Limite (dB) 49.3 50.0 -19.2 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 3,6 4,5 3,6 MHz MHz
RL (dB) 8.4 8.8 8.4 8.8 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 56.5 500.0 471.0 500.0 100 100
Limite (dB) 16.5 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 29
ID Câble: R.5 H1-B/09 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:49:10 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.5 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 35.3 35.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 160
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 11
Résistance (ohms) [Paire 3,6] 5.10
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 28.6 40
Fréquence (MHz) [Paire 3,6] 492.0
30
Limite (dB) [Paire 3,6] 43.3
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-4,5 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 5.3 4.5 8.8 4.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 256.0 423.0 498.0 483.0 100 100
Limite (dB) 35.2 29.1 26.7 27.1 80 80
Pire paire 7,8 4,5 3,6 4,5
60 60
PS NEXT (dB) 6.5 6.1 8.5 6.5
Fréq. (MHz) 256.0 423.0 492.0 476.0 40 40

Limite (dB) 32.5 26.3 24.0 24.5 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 13.4 14.1 14.3 15.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 429.0 255.0 500.0 500.0 100 100
Limite (dB) 11.5 16.1 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 1,2
60 60
PS ACR-F (dB) 16.2 16.8 16.4 17.6
40 40
Fréq. (MHz) 429.0 351.0 500.0 500.0
Limite (dB) 8.5 10.3 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-4,5 1,2-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 16.2 16.2 37.8 34.0 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 15.3 15.3 498.0 483.0
Limite (dB) 48.1 48.1 -16.9 -15.7 80 80

Pire paire 4,5 4,5 3,6 4,5


40 40
PS ACR-N (dB) 16.3 16.8 37.1 35.1
Fréq. (MHz) 15.4 15.1 492.0 476.0 0 0
Limite (dB) 45.7 45.8 -19.3 -18.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 4,5 MHz MHz
RL (dB) 5.2 5.3 9.0 9.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 50.5 50.8 486.0 435.0 60 100
Limite (dB) 17.0 16.9 8.0 8.0 50 80
Conforme aux normes de réseaux: 40
60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 30
ID Câble: R.5 H1-B/10 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:48:40 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.7 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 36.2 36.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 166
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 13
Résistance (ohms) [Paire 3,6] 5.14
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 28.6 40
Fréquence (MHz) [Paire 3,6] 496.0
30
Limite (dB) [Paire 3,6] 43.5
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 5.2 4.7 8.3 4.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 340.0 468.0 500.0 468.0 100 100
Limite (dB) 32.2 27.6 26.7 27.6 80 80
Pire paire 7,8 4,5 4,5 4,5
60 60
PS NEXT (dB) 7.6 6.9 9.1 6.9
Fréq. (MHz) 340.0 467.0 500.0 467.0 40 40

Limite (dB) 29.5 24.8 23.8 24.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.2 13.7 14.0 13.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 402.0 162.5 487.0 484.0 100 100
Limite (dB) 12.1 20.0 10.4 10.5 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.3 15.7 16.2 16.6
40 40
Fréq. (MHz) 402.0 405.0 489.0 487.0
Limite (dB) 9.1 9.0 7.4 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 12.2 12.8 37.8 33.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 6.3 6.4 500.0 468.0
Limite (dB) 56.7 56.5 -17.1 -14.5 80 80

Pire paire 3,6 3,6 4,5 4,5


40 40
PS ACR-N (dB) 14.1 14.4 38.2 35.0
Fréq. (MHz) 6.1 6.4 500.0 467.0 0 0
Limite (dB) 54.5 54.2 -20.0 -17.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 4,5 MHz MHz
RL (dB) 6.8 7.5 7.2 8.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 198.5 32.8 449.0 479.0 100 100
Limite (dB) 11.0 18.4 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 31
ID Câble: R.5 H1-B/11 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:55:27 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 5.0 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 34.6 34.6 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 157
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 11
Résistance (ohms) [Paire 3,6] 4.96
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 29.4 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 5.0 5.5 7.2 7.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 319.0 235.5 431.0 467.0 100 100
Limite (dB) 33.1 35.8 28.8 27.6 80 80
Pire paire 4,5 4,5 3,6 4,5
60 60
PS NEXT (dB) 6.6 7.1 9.0 8.5
Fréq. (MHz) 319.0 235.0 489.0 466.0 40 40

Limite (dB) 30.5 33.2 24.1 24.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.2 14.2 14.5 15.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 4.4 351.0 441.0 447.0 100 100
Limite (dB) 51.4 13.3 11.3 11.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.1 15.8 16.3 16.3
40 40
Fréq. (MHz) 431.0 1.5 440.0 429.0
Limite (dB) 8.5 57.7 8.3 8.5 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 3,6-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 14.7 13.5 38.4 36.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 7.1 3.6 491.0 467.0
Limite (dB) 55.5 61.4 -16.4 -14.4 80 80

Pire paire 4,5 4,5 3,6 4,5


40 40
PS ACR-N (dB) 15.1 13.5 38.1 36.8
Fréq. (MHz) 7.1 7.1 491.0 466.0 0 0
Limite (dB) 53.2 53.2 -19.3 -17.2
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 3,6 1,2 4,5 MHz MHz
RL (dB) 4.8 8.3 8.9 8.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 93.0 33.0 466.0 490.0 100 100
Limite (dB) 14.3 18.4 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 32
ID Câble: R.5 H1-B/12 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:56:01 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.8 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 34.6 34.6 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 157
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 11
Résistance (ohms) [Paire 3,6] 4.89
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 29.4 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.8 3.8 7.1 3.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 134.0 482.0 491.0 482.0 100 100
Limite (dB) 39.8 27.2 26.9 27.2 80 80
Pire paire 7,8 7,8 7,8 7,8
60 60
PS NEXT (dB) 6.1 5.8 8.9 6.4
Fréq. (MHz) 134.0 217.5 491.0 482.0 40 40

Limite (dB) 37.2 33.7 24.0 24.3 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 15.1 15.1 16.4 16.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 427.0 343.0 500.0 500.0 100 100
Limite (dB) 11.6 13.5 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.4 17.2 17.5 17.4
40 40
Fréq. (MHz) 427.0 2.4 500.0 500.0
Limite (dB) 8.6 53.7 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-7,8 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 16.2 16.2 36.9 33.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 9.6 33.3 491.0 482.0
Limite (dB) 52.7 39.4 -16.4 -15.6 80 80

Pire paire 7,8 3,6 3,6 4,5


40 40
PS ACR-N (dB) 17.3 16.7 38.6 35.7
Fréq. (MHz) 6.9 10.0 498.0 482.0 0 0
Limite (dB) 53.5 50.0 -19.8 -18.5
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 4,5 7,8 4,5 MHz MHz
RL (dB) 8.2 8.5 8.8 8.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 82.0 496.0 464.0 496.0 100 60
Limite (dB) 14.9 8.0 8.0 8.0 80 50

Conforme aux normes de réseaux: 40


60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 33
ID Câble: R.5 H1-B/13 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:56:30 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.1 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 34.6 34.6 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 157
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 11
Résistance (ohms) [Paire 4,5] 4.90
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 29.2 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 1,2-3,6 MHz


NEXT (dB) 3.1 4.6 4.2 8.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 247.5 303.0 430.0 468.0 100 100
Limite (dB) 35.4 33.9 28.8 27.6 80 80
Pire paire 4,5 4,5 4,5 3,6
60 60
PS NEXT (dB) 5.4 6.7 6.3 9.7
Fréq. (MHz) 247.5 303.0 430.0 495.0 40 40

Limite (dB) 32.8 31.3 26.0 23.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 13.7 14.4 13.7 14.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 446.0 178.0 446.0 446.0 100 100
Limite (dB) 11.2 19.2 11.2 11.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.7 16.1 15.7 16.4
40 40
Fréq. (MHz) 445.0 443.0 445.0 458.0
Limite (dB) 8.2 8.3 8.2 8.0 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-4,5 1,2-3,6 4,5-7,8 1,2-3,6 MHz MHz
ACR-N (dB) 14.9 14.3 31.9 36.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 15.5 13.3 430.0 468.0
Limite (dB) 47.9 49.5 -11.3 -14.5 80 80

Pire paire 1,2 1,2 4,5 3,6


40 40
PS ACR-N (dB) 15.0 15.1 37.5 38.7
Fréq. (MHz) 15.4 14.9 483.0 495.0 0 0
Limite (dB) 45.7 46.0 -18.6 -19.6
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 4,5 3,6 4,5 MHz MHz
RL (dB) 9.7 8.6 10.3 8.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 118.5 483.0 422.0 483.0 60 100
Limite (dB) 13.3 8.0 8.0 8.0 50 80
Conforme aux normes de réseaux: 40
60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 34
ID Câble: R.5 H1-B/14 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:53:49 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.8 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 30.1 30.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 138
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 11
Résistance (ohms) [Paire 3,6] 4.35
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 30.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.8 5.0 4.9 7.2
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 260.0 288.0 478.0 483.0 100 100
Limite (dB) 35.1 34.3 27.3 27.1 80 80
Pire paire 7,8 7,8 7,8 4,5
60 60
PS NEXT (dB) 6.1 7.0 7.2 8.3
Fréq. (MHz) 260.0 288.0 484.0 484.0 40 40

Limite (dB) 32.4 31.7 24.2 24.2 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.4 13.5 13.6 13.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 302.0 299.0 500.0 497.0 100 100
Limite (dB) 14.6 14.7 10.2 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.4 15.4 15.4 15.4
40 40
Fréq. (MHz) 500.0 497.0 500.0 497.0
Limite (dB) 7.2 7.3 7.2 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 15.9 14.9 35.8 38.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.9 3.6 478.0 483.0
Limite (dB) 60.8 61.4 -15.3 -15.7 80 80

Pire paire 3,6 3,6 4,5 4,5


40 40
PS ACR-N (dB) 15.1 14.0 37.7 38.8
Fréq. (MHz) 4.0 4.8 478.0 484.0 0 0
Limite (dB) 58.3 56.8 -18.2 -18.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 4,5 3,6 4,5 MHz MHz
RL (dB) 8.9 8.6 9.2 8.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 136.0 471.0 486.0 471.0 100 100
Limite (dB) 12.7 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 35
ID Câble: R.5 H1-B/15 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 17:53:14 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.5 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 31.3 31.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 142
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 10
Résistance (ohms) [Paire 3,6] 4.46
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 30.7 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.5 5.8 6.9 7.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 219.5 333.0 453.0 440.0 100 100
Limite (dB) 36.3 32.5 28.1 28.5 80 80
Pire paire 4,5 7,8 3,6 4,5
60 60
PS NEXT (dB) 6.0 7.3 9.0 8.4
Fréq. (MHz) 244.5 333.0 499.0 440.0 40 40

Limite (dB) 32.9 29.8 23.8 25.7 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 11.9 12.9 11.9 12.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 475.0 469.0 475.0 475.0 100 100
Limite (dB) 10.7 10.8 10.7 10.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 13.9 14.4 13.9 14.4
40 40
Fréq. (MHz) 475.0 469.0 475.0 469.0
Limite (dB) 7.7 7.8 7.7 7.8 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 17.5 16.7 38.8 39.9 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 9.0 4.3 490.0 480.0
Limite (dB) 53.3 60.0 -16.3 -15.5 80 80

Pire paire 4,5 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.0 17.2 39.6 39.8
Fréq. (MHz) 9.0 4.8 499.0 479.0 0 0
Limite (dB) 51.0 56.8 -19.9 -18.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 4,5 4,5 4,5 MHz MHz
RL (dB) 7.2 9.0 8.2 9.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 203.5 470.0 429.0 470.0 100 100
Limite (dB) 10.9 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 36
ID Câble: R.5 H1-B/16 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:00:45 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.9 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 27.2 27.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 125
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 10
Résistance (ohms) [Paire 4,5] 3.97
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 31.7 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 2.9 5.5 3.3 7.0
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 433.0 360.0 458.0 500.0 100 100
Limite (dB) 28.7 31.4 27.9 26.7 80 80
Pire paire 4,5 4,5 4,5 7,8
60 60
PS NEXT (dB) 4.7 7.1 6.3 8.9
Fréq. (MHz) 433.0 360.0 497.0 500.0 40 40

Limite (dB) 25.9 28.7 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.1 14.8 15.5 14.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 335.0 443.0 438.0 443.0 100 100
Limite (dB) 13.7 11.3 11.4 11.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.3 16.5 18.1 17.7
40 40
Fréq. (MHz) 331.0 1.1 438.0 442.0
Limite (dB) 10.8 60.2 8.4 8.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 14.3 16.2 37.5 39.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 6.4 7.1 498.0 500.0
Limite (dB) 56.5 55.5 -16.9 -17.1 80 80

Pire paire 4,5 4,5 4,5 7,8


40 40
PS ACR-N (dB) 14.9 15.4 38.0 41.5
Fréq. (MHz) 6.4 8.6 497.0 500.0 0 0
Limite (dB) 54.2 51.4 -19.7 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 4,5 3,6 4,5 MHz MHz
RL (dB) 7.0 7.6 8.8 8.8 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 53.0 42.0 416.0 474.0 100 100
Limite (dB) 16.8 17.8 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 37
ID Câble: R.5 H1-B/17 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:02:03 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.5 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 25.8 25.8 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 118
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 9
Résistance (ohms) [Paire 3,6] 3.74
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 32.5 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.6 2.5 7.2 8.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 219.0 219.0 444.0 497.0 100 100
Limite (dB) 36.3 36.3 28.4 26.7 80 80
Pire paire 7,8 4,5 4,5 4,5
60 60
PS NEXT (dB) 5.9 4.6 8.0 8.4
Fréq. (MHz) 219.0 219.0 444.0 454.0 40 40

Limite (dB) 33.7 33.7 25.5 25.2 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.7 13.8 14.1 14.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 342.0 345.0 468.0 465.0 100 100
Limite (dB) 13.5 13.4 10.8 10.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.3 16.4 16.7 16.8
40 40
Fréq. (MHz) 341.0 344.0 480.0 466.0
Limite (dB) 10.5 10.5 7.6 7.8 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 14.3 14.4 40.6 41.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.6 8.8 479.0 497.0
Limite (dB) 59.3 53.6 -15.4 -16.9 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 14.4 15.1 41.8 42.1
Fréq. (MHz) 4.0 9.0 494.0 493.0 0 0
Limite (dB) 58.3 51.0 -19.5 -19.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 3,6 4,5 3,6 MHz MHz
RL (dB) 8.0 9.3 8.0 9.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 492.0 487.0 492.0 487.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 38
ID Câble: R.5 H1-B/19 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:08:31 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.1 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 29.8 29.8 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 136
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 10
Résistance (ohms) [Paire 3,6] 4.28
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 30.5 40
Fréquence (MHz) [Paire 3,6] 498.0
30
Limite (dB) [Paire 3,6] 43.6
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 4.2 2.1 6.0 10.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 307.0 196.5 460.0 487.0 100 100
Limite (dB) 33.7 37.1 27.8 27.0 80 80
Pire paire 4,5 7,8 3,6 4,5
60 60
PS NEXT (dB) 6.0 4.4 6.4 10.0
Fréq. (MHz) 307.0 196.5 493.0 471.0 40 40

Limite (dB) 31.1 34.4 24.0 24.7 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 3,6-1,2 1,2-3,6 MHz MHz
ACR-F (dB) 14.5 14.5 15.9 14.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 302.0 299.0 500.0 500.0 100 100
Limite (dB) 14.6 14.7 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.7 16.7 17.4 16.9
40 40
Fréq. (MHz) 1.0 1.5 500.0 500.0
Limite (dB) 61.2 57.7 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 14.9 16.4 37.0 41.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.6 19.0 483.0 487.0
Limite (dB) 61.4 45.8 -15.7 -16.1 80 80

Pire paire 3,6 3,6 3,6 4,5


40 40
PS ACR-N (dB) 15.4 16.0 36.8 40.1
Fréq. (MHz) 14.5 4.3 493.0 471.0 0 0
Limite (dB) 46.3 57.7 -19.4 -17.6
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 3,6 3,6 3,6 MHz MHz
RL (dB) 7.4 8.1 9.3 8.1 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 113.5 493.0 498.0 493.0 60 100
Limite (dB) 13.5 8.0 8.0 8.0 50 80
Conforme aux normes de réseaux: 40
60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 39
ID Câble: R.5 H1-B/20 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:07:08 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.8 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 30.1 30.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 137
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 10
Résistance (ohms) [Paire 3,6] 4.35
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 30.7 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 1,2-4,5 MHz


NEXT (dB) 4.8 4.8 5.9 6.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 291.0 426.0 451.0 469.0 100 100
Limite (dB) 34.2 29.0 28.1 27.6 80 80
Pire paire 7,8 4,5 3,6 4,5
60 60
PS NEXT (dB) 6.4 6.1 8.2 6.7
Fréq. (MHz) 291.0 257.0 500.0 468.0 40 40

Limite (dB) 31.6 32.5 23.8 24.7 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.3 13.9 14.3 14.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 500.0 394.0 500.0 488.0 100 100
Limite (dB) 10.2 12.3 10.2 10.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 14.9 15.8 14.9 15.8
40 40
Fréq. (MHz) 500.0 490.0 500.0 490.0
Limite (dB) 7.2 7.4 7.2 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-4,5 1,2-4,5 1,2-3,6 1,2-4,5 MHz MHz
ACR-N (dB) 14.8 14.9 39.1 36.0 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 16.5 16.0 500.0 469.0
Limite (dB) 47.3 47.6 -17.1 -14.6 80 80

Pire paire 4,5 4,5 3,6 4,5


40 40
PS ACR-N (dB) 16.5 16.1 38.9 36.4
Fréq. (MHz) 16.9 15.6 500.0 468.0 0 0
Limite (dB) 44.7 45.5 -20.0 -17.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 4,5 3,6 MHz MHz
RL (dB) 6.2 7.7 8.2 9.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 80.3 195.5 441.0 470.0 100 100
Limite (dB) 15.0 11.1 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 40
ID Câble: R.5 H1-B/21 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:12:36 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.9 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 24.4 24.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 111
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 8
Résistance (ohms) [Paire 4,5] 3.53
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 33.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 4.9 5.2 4.9 7.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 424.0 299.0 424.0 423.0 100 100
Limite (dB) 29.0 34.1 29.0 29.1 80 80
Pire paire 7,8 7,8 3,6 4,5
60 60
PS NEXT (dB) 7.2 7.4 8.3 10.6
Fréq. (MHz) 424.0 299.0 476.0 467.0 40 40

Limite (dB) 26.2 31.4 24.5 24.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.0 14.6 14.5 14.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 360.0 497.0 494.0 498.0 100 100
Limite (dB) 13.1 10.3 10.3 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.1 16.5 16.8 16.6
40 40
Fréq. (MHz) 360.0 497.0 500.0 499.0
Limite (dB) 10.1 7.3 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 15.7 15.9 39.3 41.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.9 6.5 471.0 470.0
Limite (dB) 60.8 56.3 -14.7 -14.7 80 80

Pire paire 3,6 4,5 3,6 4,5


40 40
PS ACR-N (dB) 15.8 16.6 40.2 44.8
Fréq. (MHz) 3.9 6.4 476.0 499.0 0 0
Limite (dB) 58.5 54.2 -18.0 -19.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 4,5 4,5 3,6 MHz MHz
RL (dB) 7.0 8.4 7.0 8.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 447.0 127.0 447.0 475.0 100 100
Limite (dB) 8.0 13.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 41
ID Câble: R.5 H1-B/22 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:13:25 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.0 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 24.4 24.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 111
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 8
Résistance (ohms) [Paire 4,5] 3.50
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 32.8 40
Fréquence (MHz) [Paire 3,6] 494.0
30
Limite (dB) [Paire 3,6] 43.4
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 5.1 4.0 5.9 8.6
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 293.0 305.0 484.0 454.0 100 100
Limite (dB) 34.2 33.8 27.1 28.0 80 80
Pire paire 3,6 7,8 3,6 7,8
60 60
PS NEXT (dB) 6.7 6.2 7.2 10.5
Fréq. (MHz) 443.0 305.0 485.0 468.0 40 40

Limite (dB) 25.6 31.2 24.2 24.7 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.2 13.4 13.7 13.4
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 355.0 471.0 472.0 471.0 100 100
Limite (dB) 13.2 10.7 10.7 10.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.7 15.7 16.4 16.1
40 40
Fréq. (MHz) 355.0 355.0 494.0 471.0
Limite (dB) 10.2 10.2 7.3 7.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 4,5-7,8 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 15.5 17.1 39.2 40.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.5 8.8 494.0 454.0
Limite (dB) 59.5 53.6 -16.6 -13.3 80 80

Pire paire 1,2 3,6 3,6 4,5


40 40
PS ACR-N (dB) 16.6 17.5 39.7 43.4
Fréq. (MHz) 4.6 6.0 485.0 478.0 0 0
Limite (dB) 57.0 54.7 -18.8 -18.2
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 1,2 3,6 3,6 MHz MHz
RL (dB) 6.6 6.7 6.6 8.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 495.0 70.5 495.0 494.0 100 100
Limite (dB) 8.0 15.5 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 42
ID Câble: R.5 H1-B/23 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:11:45 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.1 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 21.1 21.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 97
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 8
Résistance (ohms) [Paire 4,5] 3.10
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 34.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.1 5.5 3.1 7.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 455.0 297.0 455.0 457.0 100 100
Limite (dB) 28.0 34.1 28.0 27.9 80 80
Pire paire 4,5 4,5 4,5 3,6
60 60
PS NEXT (dB) 5.3 7.5 5.3 8.7
Fréq. (MHz) 456.0 171.5 456.0 480.0 40 40

Limite (dB) 25.1 35.4 25.1 24.4 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.5 14.3 14.6 14.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 286.0 270.0 425.0 425.0 100 100
Limite (dB) 15.1 15.6 11.6 11.6 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.9 16.9 17.0 17.1
40 40
Fréq. (MHz) 413.0 270.0 425.0 432.0
Limite (dB) 8.9 12.6 8.6 8.5 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 4,5-7,8 1,2-3,6 MHz MHz
ACR-N (dB) 15.4 15.6 36.1 42.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 5.1 5.1 455.0 484.0
Limite (dB) 58.4 58.4 -13.4 -15.8 80 80

Pire paire 3,6 3,6 4,5 3,6


40 40
PS ACR-N (dB) 14.7 14.6 37.6 42.1
Fréq. (MHz) 5.1 5.3 456.0 480.0 0 0
Limite (dB) 56.1 55.9 -16.3 -18.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 4,5 4,5 4,5 MHz MHz
RL (dB) 5.8 8.9 5.8 8.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 464.0 494.0 464.0 494.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 43
ID Câble: R.5 H1-B/24 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:10:34 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.1 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 22.5 22.5 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 102
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 7
Résistance (ohms) [Paire 4,5] 3.21
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 33.8 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 4.1 6.6 5.1 6.6
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 286.0 497.0 487.0 497.0 100 100
Limite (dB) 34.4 26.7 27.0 26.7 80 80
Pire paire 7,8 4,5 7,8 7,8
60 60
PS NEXT (dB) 6.0 8.2 7.0 8.4
Fréq. (MHz) 286.0 168.0 487.0 497.0 40 40

Limite (dB) 31.7 35.6 24.2 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.2 15.0 15.1 15.2
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 385.0 396.0 494.0 499.0 100 100
Limite (dB) 12.5 12.2 10.3 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.5 16.4 17.3 18.0
40 40
Fréq. (MHz) 385.0 397.0 492.0 499.0
Limite (dB) 9.5 9.2 7.4 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 16.3 17.4 39.0 40.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 5.3 3.5 487.0 497.0
Limite (dB) 58.2 61.7 -16.1 -16.9 80 80

Pire paire 3,6 3,6 4,5 4,5


40 40
PS ACR-N (dB) 16.6 17.5 40.8 42.2
Fréq. (MHz) 4.0 4.9 487.0 497.0 0 0
Limite (dB) 58.3 56.6 -18.9 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 7,8 4,5 MHz MHz
RL (dB) 6.6 8.5 6.6 8.8 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 499.0 220.0 499.0 436.0 100 100
Limite (dB) 8.0 10.6 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 44
ID Câble: R.5 H1-C/01 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:14:18 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.8 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 25.1 25.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 115
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 9
Résistance (ohms) [Paire 3,6] 3.56
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 32.6 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 4.8 5.1 4.8 5.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 472.0 460.0 472.0 499.0 100 100
Limite (dB) 27.5 27.8 27.5 26.7 80 80
Pire paire 7,8 4,5 4,5 4,5
60 60
PS NEXT (dB) 6.2 7.5 6.7 7.8
Fréq. (MHz) 316.0 460.0 472.0 498.0 40 40

Limite (dB) 30.6 25.0 24.6 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.6 15.1 15.5 15.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 359.0 479.0 481.0 479.0 100 100
Limite (dB) 13.1 10.6 10.5 10.6 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.1 17.8 18.5 17.9
40 40
Fréq. (MHz) 359.0 479.0 496.0 491.0
Limite (dB) 10.1 7.6 7.3 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 4,5-7,8 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 16.4 15.7 37.1 38.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 9.0 3.5 472.0 499.0
Limite (dB) 53.3 61.7 -14.8 -17.0 80 80

Pire paire 1,2 4,5 4,5 4,5


40 40
PS ACR-N (dB) 15.9 16.9 38.5 40.5
Fréq. (MHz) 4.0 2.9 472.0 498.0 0 0
Limite (dB) 58.3 59.0 -17.7 -19.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 4,5 3,6 3,6 MHz MHz
RL (dB) 7.6 9.1 9.8 9.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 66.5 67.8 421.0 470.0 100 100
Limite (dB) 15.8 15.7 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 45
ID Câble: R.5 H1-C/02 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:15:48 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.8 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 26.3 26.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 120
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 9
Résistance (ohms) [Paire 3,6] 3.81
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 32.3 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 4.8 5.6 4.8 5.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 476.0 253.0 476.0 436.0 100 100
Limite (dB) 27.4 35.3 27.4 28.6 80 80
Pire paire 7,8 4,5 3,6 4,5
60 60
PS NEXT (dB) 6.5 7.6 7.2 7.6
Fréq. (MHz) 476.0 435.0 500.0 435.0 40 40

Limite (dB) 24.5 25.8 23.8 25.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.2 13.4 13.2 13.4
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 441.0 444.0 441.0 444.0 100 100
Limite (dB) 11.3 11.2 11.3 11.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.1 16.3 16.1 16.3
40 40
Fréq. (MHz) 441.0 444.0 441.0 444.0
Limite (dB) 8.3 8.2 8.3 8.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 15.9 17.3 38.5 37.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.8 6.4 492.0 453.0
Limite (dB) 59.1 56.5 -16.5 -13.2 80 80

Pire paire 3,6 3,6 3,6 4,5


40 40
PS ACR-N (dB) 16.6 17.1 39.5 39.0
Fréq. (MHz) 5.0 4.9 500.0 453.0 0 0
Limite (dB) 56.3 56.6 -20.0 -16.1
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 4,5 MHz MHz
RL (dB) 5.7 6.9 7.6 7.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 72.5 72.0 461.0 478.0 100 100
Limite (dB) 15.4 15.4 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 46
ID Câble: R.5 H1-C/03 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:16:28 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.5 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 26.5 26.5 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 121
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 9
Résistance (ohms) [Paire 3,6] 3.85
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 32.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.5 5.8 5.5 6.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 179.0 259.0 421.0 488.0 100 100
Limite (dB) 37.7 35.1 29.1 27.0 80 80
Pire paire 4,5 4,5 3,6 4,5
60 60
PS NEXT (dB) 5.9 8.1 7.5 9.0
Fréq. (MHz) 179.0 259.0 491.0 488.0 40 40

Limite (dB) 35.1 32.4 24.0 24.1 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.2 14.7 14.2 14.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 436.0 439.0 436.0 439.0 100 100
Limite (dB) 11.4 11.3 11.4 11.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.0 17.1 17.0 17.1
40 40
Fréq. (MHz) 448.0 439.0 448.0 439.0
Limite (dB) 8.2 8.3 8.2 8.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 13.4 14.8 39.4 39.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 17.1 17.0 490.0 488.0
Limite (dB) 46.9 47.0 -16.3 -16.1 80 80

Pire paire 3,6 3,6 3,6 4,5


40 40
PS ACR-N (dB) 14.9 15.9 39.2 41.1
Fréq. (MHz) 4.0 17.0 491.0 488.0 0 0
Limite (dB) 58.3 44.6 -19.3 -19.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 4,5 7,8 4,5 MHz MHz
RL (dB) 5.8 6.5 5.8 6.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 326.0 498.0 326.0 498.0 100 100
Limite (dB) 8.9 8.0 8.9 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 47
ID Câble: R.5 H1-C/07 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:20:05 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.3 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 20.6 20.6 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 93
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 6
Résistance (ohms) [Paire 3,6] 2.98
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 34.5 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 3.3 4.4 5.4 4.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 235.5 459.0 440.0 460.0 100 100
Limite (dB) 35.8 27.9 28.5 27.8 80 80
Pire paire 4,5 7,8 7,8 7,8
60 60
PS NEXT (dB) 5.3 6.8 8.9 6.8
Fréq. (MHz) 235.5 460.0 500.0 460.0 40 40

Limite (dB) 33.1 25.0 23.8 25.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.6 14.7 14.8 15.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 303.0 303.0 450.0 451.0 100 100
Limite (dB) 14.6 14.6 11.1 11.1 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.9 17.4 17.0 17.6
40 40
Fréq. (MHz) 448.0 303.0 450.0 450.0
Limite (dB) 8.2 11.6 8.1 8.1 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 3,6-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 14.0 15.8 37.4 37.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.5 7.4 440.0 460.0
Limite (dB) 61.7 55.2 -12.1 -13.8 80 80

Pire paire 4,5 3,6 7,8 4,5


40 40
PS ACR-N (dB) 15.3 16.3 43.7 40.0
Fréq. (MHz) 3.8 6.4 500.0 460.0 0 0
Limite (dB) 58.6 54.2 -20.0 -16.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 3,6 4,5 3,6 MHz MHz
RL (dB) 5.2 7.2 5.2 7.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 483.0 464.0 483.0 464.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 48
ID Câble: R.5 H1-C/09 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:24:58 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.2 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 26.3 26.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 120
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 9
Résistance (ohms) [Paire 4,5] 3.86
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 32.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 4.2 3.2 6.9 4.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 215.5 215.0 499.0 386.0 100 100
Limite (dB) 36.4 36.4 26.7 30.4 80 80
Pire paire 4,5 4,5 3,6 7,8
60 60
PS NEXT (dB) 6.1 5.5 7.9 9.9
Fréq. (MHz) 215.5 215.0 498.0 497.0 40 40

Limite (dB) 33.8 33.8 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.2 14.6 14.7 15.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 346.0 333.0 455.0 449.0 100 100
Limite (dB) 13.4 13.7 11.0 11.1 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.9 17.2 17.3 18.0
40 40
Fréq. (MHz) 346.0 333.0 476.0 473.0
Limite (dB) 10.4 10.7 7.6 7.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 13.9 14.9 39.0 42.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 8.3 9.0 499.0 497.0
Limite (dB) 54.1 53.3 -17.0 -16.9 80 80

Pire paire 1,2 1,2 3,6 3,6


40 40
PS ACR-N (dB) 14.4 14.7 39.9 42.4
Fréq. (MHz) 8.6 9.4 498.0 496.0 0 0
Limite (dB) 51.4 50.6 -19.8 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 7,8 4,5 3,6 MHz MHz
RL (dB) 8.1 8.3 8.2 8.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 362.0 138.0 453.0 477.0 100 100
Limite (dB) 8.4 12.6 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 49
ID Câble: R.5 H1-C/11 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:29:29 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.1 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 34.1 34.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 156
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 12
Résistance (ohms) [Paire 3,6] 4.93
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 29.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 3,6-4,5 4,5-7,8 MHz


NEXT (dB) 3.1 3.9 8.1 5.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 168.0 170.5 495.0 467.0 100 100
Limite (dB) 38.2 38.1 26.8 27.6 80 80
Pire paire 4,5 4,5 3,6 7,8
60 60
PS NEXT (dB) 5.3 6.2 8.5 7.6
Fréq. (MHz) 168.0 171.0 500.0 467.0 40 40

Limite (dB) 35.6 35.5 23.8 24.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-1,2 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 12.5 13.5 13.4 14.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 402.0 334.0 498.0 499.0 100 100
Limite (dB) 12.1 13.7 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 14.9 16.3 14.9 16.8
40 40
Fréq. (MHz) 500.0 409.0 500.0 493.0
Limite (dB) 7.2 9.0 7.2 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 3,6-4,5 4,5-7,8 MHz MHz
ACR-N (dB) 11.3 12.3 37.9 34.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 19.5 19.8 500.0 467.0
Limite (dB) 45.5 45.4 -17.1 -14.4 80 80

Pire paire 7,8 4,5 3,6 4,5


40 40
PS ACR-N (dB) 13.3 14.1 37.6 36.1
Fréq. (MHz) 19.6 19.6 500.0 467.0 0 0
Limite (dB) 43.1 43.1 -20.0 -17.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 3,6 1,2 3,6 MHz MHz
RL (dB) 6.4 8.4 6.7 8.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 187.0 471.0 444.0 471.0 100 100
Limite (dB) 11.3 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 50
ID Câble: R.5 H1-F/05 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:38:40 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.9 dB (NEXT 3,6-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 25.3 25.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 109
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 2
Résistance (ohms) [Paire 4,5] 3.78
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 30.9 40
Fréquence (MHz) [Paire 3,6] 491.0
30
Limite (dB) [Paire 3,6] 43.3
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-4,5 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 9.9 13.0 10.4 14.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 460.0 407.0 493.0 489.0 100 100
Limite (dB) 27.8 29.6 26.9 27.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 9.8 13.3 9.8 13.3
Fréq. (MHz) 498.0 489.0 498.0 489.0 40 40

Limite (dB) 23.8 24.1 23.8 24.1 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-1,2 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 13.7 14.1 13.7 14.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 435.0 435.0 435.0 435.0 100 100
Limite (dB) 11.4 11.4 11.4 11.4 80 80
Pire paire 3,6 1,2 3,6 1,2
60 60
PS ACR-F (dB) 16.4 17.0 17.2 17.0
40 40
Fréq. (MHz) 435.0 435.0 498.0 435.0
Limite (dB) 8.4 8.4 7.2 8.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 18.0 17.6 41.5 44.9 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.4 5.3 493.0 489.0
Limite (dB) 59.8 58.2 -16.5 -16.2 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.4 17.9 41.1 44.1
Fréq. (MHz) 4.0 5.3 498.0 489.0 0 0
Limite (dB) 58.3 55.9 -19.8 -19.1
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 4,5 4,5 MHz MHz
RL (dB) 4.8 7.4 6.8 7.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 113.5 402.0 488.0 402.0 100 60
Limite (dB) 13.5 8.0 8.0 8.0 80 50

Conforme aux normes de réseaux: 40


60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 51
ID Câble: R.5 H1-F/06 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:40:42 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 7.5 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 24.9 24.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 107
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 2
Résistance (ohms) [Paire 7,8] 3.67
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 32.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 7.5 12.4 7.6 12.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 479.0 500.0 483.0 500.0 100 100
Limite (dB) 27.3 26.7 27.1 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 8.9 12.7 8.9 12.7
Fréq. (MHz) 482.0 500.0 482.0 500.0 40 40

Limite (dB) 24.3 23.8 24.3 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-1,2 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 14.2 14.5 14.9 15.4
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 402.0 402.0 469.0 469.0 100 100
Limite (dB) 12.1 12.1 10.8 10.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.3 16.9 16.4 17.6
40 40
Fréq. (MHz) 469.0 418.0 470.0 487.0
Limite (dB) 7.8 8.8 7.7 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 19.6 19.8 38.7 44.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.5 5.1 483.0 500.0
Limite (dB) 59.5 58.4 -15.7 -17.1 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 19.2 19.8 40.0 44.7
Fréq. (MHz) 3.8 5.3 482.0 500.0 0 0
Limite (dB) 58.6 55.9 -18.5 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 3,6 3,6 3,6 MHz MHz
RL (dB) 4.5 7.7 4.5 7.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 479.0 465.0 479.0 465.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 52
ID Câble: R.5 H1-F/07 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:39:37 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.3 dB (NEXT 3,6-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 25.3 25.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 109
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 2
Résistance (ohms) [Paire 7,8] 3.71
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 31.4 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-4,5 1,2-3,6 3,6-4,5 1,2-3,6 MHz


NEXT (dB) 10.3 11.7 10.3 12.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 497.0 445.0 497.0 488.0 100 100
Limite (dB) 26.7 28.3 26.7 27.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.5 11.4 10.5 11.4
Fréq. (MHz) 497.0 488.0 497.0 488.0 40 40

Limite (dB) 23.8 24.1 23.8 24.1 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 14.7 14.9 15.2 15.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 409.0 397.0 452.0 450.0 100 100
Limite (dB) 12.0 12.2 11.1 11.1 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.8 17.5 16.8 18.8
40 40
Fréq. (MHz) 496.0 397.0 496.0 489.0
Limite (dB) 7.3 9.2 7.3 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 3,6-4,5 1,2-3,6 MHz MHz
ACR-N (dB) 17.0 17.9 41.8 43.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.9 5.0 497.0 493.0
Limite (dB) 58.8 58.6 -16.9 -16.5 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.0 17.6 41.6 42.3
Fréq. (MHz) 4.0 5.0 497.0 488.0 0 0
Limite (dB) 58.3 56.3 -19.7 -19.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 3,6 3,6 MHz MHz
RL (dB) 7.3 7.5 7.3 8.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 360.0 215.0 360.0 454.0 100 100
Limite (dB) 8.4 10.7 8.4 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 53
ID Câble: R.5 H1-F/08 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:41:28 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.6 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 24.6 24.6 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 106
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 2
Résistance (ohms) [Paire 4,5] 3.64
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 32.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 3,6-4,5 3,6-4,5 MHz


NEXT (dB) 10.6 11.4 11.6 12.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 389.0 429.0 495.0 500.0 100 100
Limite (dB) 30.3 28.9 26.8 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 11.1 12.0 11.4 12.0
Fréq. (MHz) 461.0 500.0 486.0 500.0 40 40

Limite (dB) 25.0 23.8 24.2 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 15.0 14.8 15.2 15.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 406.0 395.0 455.0 455.0 100 100
Limite (dB) 12.0 12.3 11.0 11.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.8 17.4 17.0 17.9
40 40
Fréq. (MHz) 456.0 395.0 471.0 474.0
Limite (dB) 8.0 9.3 7.7 7.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 3,6-4,5 1,2-3,6 MHz MHz
ACR-N (dB) 19.2 19.0 43.7 44.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.8 2.5 495.0 500.0
Limite (dB) 59.1 62.0 -16.7 -17.1 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.9 19.0 42.9 44.1
Fréq. (MHz) 4.0 5.0 486.0 500.0 0 0
Limite (dB) 58.3 56.3 -18.8 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 3,6 3,6 3,6 MHz MHz
RL (dB) 5.5 8.5 5.5 8.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 474.0 456.0 474.0 456.0 60 100
Limite (dB) 8.0 8.0 8.0 8.0 50 80
Conforme aux normes de réseaux: 40
60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 54
ID Câble: R.5 H1-F/09 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:43:27 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.5 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 14.2 14.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 61
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 1
Résistance (ohms) [Paire 4,5] 2.20
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 36.1 40
Fréquence (MHz) [Paire 3,6] 499.0
30
Limite (dB) [Paire 3,6] 43.7
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 3,6-4,5 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 9.5 11.4 11.1 11.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 249.0 496.0 497.0 496.0 100 100
Limite (dB) 35.4 26.8 26.7 26.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.1 11.8 10.7 11.9
Fréq. (MHz) 471.0 488.0 497.0 496.0 40 40

Limite (dB) 24.7 24.1 23.8 23.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 15.8 15.8 19.0 19.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 39.5 34.8 496.0 496.0 100 100
Limite (dB) 32.3 33.4 10.3 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.7 17.8 19.9 20.1
40 40
Fréq. (MHz) 1.0 1.0 497.0 479.0
Limite (dB) 61.2 61.2 7.3 7.6 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 3,6-4,5 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 16.5 17.5 47.1 47.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.4 3.5 497.0 496.0
Limite (dB) 59.8 61.7 -16.9 -16.8 80 80

Pire paire 4,5 4,5 3,6 3,6


40 40
PS ACR-N (dB) 16.9 18.2 46.6 47.9
Fréq. (MHz) 4.4 3.9 497.0 496.0 0 0
Limite (dB) 57.5 58.5 -19.7 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 3,6 4,5 3,6 MHz MHz
RL (dB) 7.2 7.1 7.2 7.1 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 435.0 476.0 435.0 476.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 55
ID Câble: R.5 H1-F/10 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:52:14 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 11.6 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 44.5 44.5 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 193
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 5
Résistance (ohms) [Paire 4,5] 6.56
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 23.8 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 3,6-4,5 1,2-3,6 MHz


NEXT (dB) 11.6 12.9 11.7 13.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 468.0 96.8 485.0 489.0 100 100
Limite (dB) 27.6 42.1 27.1 27.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.9 13.0 11.1 13.2
Fréq. (MHz) 470.0 493.0 486.0 500.0 40 40

Limite (dB) 24.7 24.0 24.2 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 13.4 14.2 13.5 14.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 469.0 459.0 474.0 497.0 100 100
Limite (dB) 10.8 11.0 10.7 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.9 16.4 16.0 16.4
40 40
Fréq. (MHz) 469.0 459.0 472.0 459.0
Limite (dB) 7.8 8.0 7.7 8.0 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 19.5 17.4 34.8 37.1 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.1 3.6 481.0 494.0
Limite (dB) 60.3 61.4 -15.6 -16.6 80 80

Pire paire 4,5 4,5 3,6 3,6


40 40
PS ACR-N (dB) 19.5 18.5 35.5 37.0
Fréq. (MHz) 4.4 3.3 500.0 500.0 0 0
Limite (dB) 57.5 58.8 -20.0 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 3,6 3,6 MHz MHz
RL (dB) 7.9 8.0 7.9 8.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 360.0 28.5 360.0 458.0 100 100
Limite (dB) 8.4 18.7 8.4 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 56
ID Câble: R.5 H1-F/11 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:55:40 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.5 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 44.5 44.5 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 192
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 4
Résistance (ohms) [Paire 4,5] 6.52
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 23.8 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 9.5 12.6 9.6 13.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 429.0 434.0 486.0 499.0 100 100
Limite (dB) 28.9 28.7 27.1 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 9.1 12.7 9.3 12.7
Fréq. (MHz) 477.0 480.0 485.0 480.0 40 40

Limite (dB) 24.5 24.4 24.2 24.4 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.6 14.8 15.1 14.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 471.0 468.0 499.0 468.0 100 100
Limite (dB) 10.7 10.8 10.2 10.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.9 17.3 17.1 17.3
40 40
Fréq. (MHz) 445.0 468.0 471.0 468.0
Limite (dB) 8.2 7.8 7.7 7.8 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 17.6 16.3 33.8 37.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 5.0 3.6 497.0 499.0
Limite (dB) 58.6 61.4 -16.9 -17.0 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.7 18.1 33.3 37.2
Fréq. (MHz) 5.0 3.6 496.0 500.0 0 0
Limite (dB) 56.3 58.6 -19.7 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 3,6 4,5 MHz MHz
RL (dB) 7.5 7.2 7.5 7.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 379.0 418.0 379.0 418.0 100 100
Limite (dB) 8.2 8.0 8.2 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 57
ID Câble: R.5 H1-F/12 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:56:53 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.2 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 44.8 44.8 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 193
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 4
Résistance (ohms) [Paire 3,6] 6.62
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 23.7 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 9.2 10.9 9.9 12.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 426.0 402.0 495.0 498.0 100 100
Limite (dB) 29.0 29.8 26.8 26.7 80 80
Pire paire 3,6 3,6 3,6 4,5
60 60
PS NEXT (dB) 10.4 11.2 10.5 12.1
Fréq. (MHz) 423.0 432.0 499.0 499.0 40 40

Limite (dB) 26.3 25.9 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 14.9 15.7 15.1 15.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 471.0 478.0 490.0 498.0 100 100
Limite (dB) 10.7 10.6 10.4 10.2 80 80
Pire paire 3,6 3,6 3,6 1,2
60 60
PS ACR-F (dB) 17.4 18.0 17.4 18.7
40 40
Fréq. (MHz) 471.0 1.1 471.0 498.0
Limite (dB) 7.7 60.2 7.7 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 17.1 17.9 33.5 36.3 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 5.0 5.3 495.0 499.0
Limite (dB) 58.6 58.2 -16.7 -17.0 80 80

Pire paire 1,2 1,2 3,6 4,5


40 40
PS ACR-N (dB) 17.0 18.6 34.3 35.7
Fréq. (MHz) 5.0 5.1 499.0 499.0 0 0
Limite (dB) 56.3 56.1 -19.9 -19.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 3,6 3,6 3,6 MHz MHz
RL (dB) 8.7 8.0 8.7 8.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 480.0 441.0 480.0 441.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 58
ID Câble: R.5 H1-F/13 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:54:11 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.0 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 44.5 44.5 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 193
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 5
Résistance (ohms) [Paire 4,5] 6.52
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 23.8 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 10.0 11.8 10.5 12.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 419.0 460.0 500.0 495.0 100 100
Limite (dB) 29.2 27.8 26.7 26.8 80 80
Pire paire 3,6 4,5 3,6 4,5
60 60
PS NEXT (dB) 10.8 12.6 10.8 12.6
Fréq. (MHz) 500.0 497.0 500.0 497.0 40 40

Limite (dB) 23.8 23.8 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 13.9 14.7 13.9 14.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 477.0 459.0 477.0 477.0 100 100
Limite (dB) 10.6 11.0 10.6 10.6 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.6 17.1 16.6 17.1
40 40
Fréq. (MHz) 477.0 459.0 477.0 459.0
Limite (dB) 7.6 8.0 7.6 8.0 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 18.5 16.2 34.3 36.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.4 3.5 500.0 495.0
Limite (dB) 59.8 61.7 -17.1 -16.7 80 80

Pire paire 3,6 3,6 3,6 4,5


40 40
PS ACR-N (dB) 18.5 18.0 34.6 36.4
Fréq. (MHz) 4.6 5.3 500.0 497.0 0 0
Limite (dB) 57.0 55.9 -20.0 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 3,6 3,6 3,6 MHz MHz
RL (dB) 6.5 8.8 6.5 8.8 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 364.0 457.0 364.0 457.0 100 100
Limite (dB) 8.4 8.0 8.4 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 59
ID Câble: R.5 H1-F/14 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:50:09 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.8 dB (NEXT 3,6-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 45.2 45.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 195
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 4
Résistance (ohms) [Paire 3,6] 6.62
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 23.5 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-4,5 1,2-3,6 3,6-4,5 1,2-3,6 MHz


NEXT (dB) 10.8 11.7 10.8 12.2
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 496.0 424.0 496.0 481.0 100 100
Limite (dB) 26.8 29.0 26.8 27.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.4 12.0 10.4 12.2
Fréq. (MHz) 498.0 481.0 498.0 500.0 40 40

Limite (dB) 23.8 24.3 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 15.2 15.1 15.3 15.2
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 461.0 464.0 488.0 473.0 100 100
Limite (dB) 10.9 10.9 10.4 10.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.6 17.7 18.1 17.9
40 40
Fréq. (MHz) 461.0 464.0 488.0 473.0
Limite (dB) 7.9 7.9 7.4 7.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 3,6-4,5 1,2-3,6 MHz MHz
ACR-N (dB) 18.6 16.7 34.2 35.0 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.6 3.6 496.0 481.0
Limite (dB) 61.4 61.4 -16.8 -15.6 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 19.4 18.1 33.9 35.7
Fréq. (MHz) 5.0 3.4 499.0 500.0 0 0
Limite (dB) 56.3 58.7 -19.9 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 3,6 3,6 4,5 MHz MHz
RL (dB) 7.4 8.4 7.4 8.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 489.0 122.5 489.0 472.0 100 100
Limite (dB) 8.0 13.1 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 60
ID Câble: R.5 H1-F/15 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:00:01 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 11.0 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 46.9 46.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 203
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 5
Résistance (ohms) [Paire 3,6] 6.87
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 22.7 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 4,5-7,8 3,6-4,5 3,6-4,5 MHz


NEXT (dB) 11.0 12.8 11.4 13.2
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 391.0 407.0 500.0 500.0 100 100
Limite (dB) 30.2 29.6 26.7 26.7 80 80
Pire paire 3,6 4,5 3,6 4,5
60 60
PS NEXT (dB) 11.8 12.8 11.8 12.8
Fréq. (MHz) 486.0 500.0 486.0 500.0 40 40

Limite (dB) 24.2 23.8 24.2 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.9 14.8 15.4 15.2
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 435.0 423.0 467.0 447.0 100 100
Limite (dB) 11.4 11.7 10.8 11.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.2 16.8 17.4 17.1
40 40
Fréq. (MHz) 428.0 1.1 441.0 424.0
Limite (dB) 8.6 60.2 8.3 8.6 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 3,6-4,5 3,6-4,5 MHz MHz
ACR-N (dB) 18.5 17.3 34.1 35.9 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.3 5.1 500.0 500.0
Limite (dB) 60.0 58.4 -17.1 -17.1 80 80

Pire paire 3,6 3,6 3,6 4,5


40 40
PS ACR-N (dB) 20.0 18.3 34.8 35.5
Fréq. (MHz) 4.5 5.1 497.0 500.0 0 0
Limite (dB) 57.2 56.1 -19.7 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 3,6 4,5 3,6 MHz MHz
RL (dB) 6.5 5.9 6.5 5.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 395.0 393.0 395.0 393.0 100 100
Limite (dB) 8.0 8.1 8.0 8.1 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 61
ID Câble: R.5 H1-F/16 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:04:29 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.4 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 46.4 46.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 201
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 5
Résistance (ohms) [Paire 4,5] 6.77
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 23.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 9.4 10.0 10.3 10.0
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 397.0 426.0 493.0 426.0 100 100
Limite (dB) 30.0 29.0 26.9 29.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.8 11.2 11.1 12.6
Fréq. (MHz) 480.0 426.0 500.0 499.0 40 40

Limite (dB) 24.4 26.2 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.2 14.7 14.3 14.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 448.0 464.0 464.0 464.0 100 100
Limite (dB) 11.2 10.9 10.9 10.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.9 17.1 17.2 17.4
40 40
Fréq. (MHz) 448.0 1.3 464.0 464.0
Limite (dB) 8.2 59.3 7.9 7.9 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-7,8 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 19.9 18.9 33.1 36.3 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 2.9 3.5 493.0 499.0
Limite (dB) 62.0 61.7 -16.5 -17.0 80 80

Pire paire 1,2 1,2 3,6 3,6


40 40
PS ACR-N (dB) 19.4 19.3 34.2 35.6
Fréq. (MHz) 5.0 5.0 500.0 499.0 0 0
Limite (dB) 56.3 56.3 -20.0 -19.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 3,6 4,5 MHz MHz
RL (dB) 5.5 5.6 5.5 5.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 397.0 384.0 397.0 384.0 60 100
Limite (dB) 8.0 8.2 8.0 8.2 50 80
Conforme aux normes de réseaux: 40
60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 62
ID Câble: R.5 H1-F/17 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:01:51 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.3 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 46.2 46.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 200
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 5
Résistance (ohms) [Paire 4,5] 6.77
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 22.8 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 10.3 12.4 10.6 14.0
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 316.0 274.0 489.0 495.0 100 100
Limite (dB) 33.3 34.7 27.0 26.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.9 13.5 11.0 14.4
Fréq. (MHz) 489.0 298.0 500.0 494.0 40 40

Limite (dB) 24.1 31.4 23.8 23.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 3,6-1,2 1,2-3,6 MHz MHz
ACR-F (dB) 15.3 14.5 15.4 14.5
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 236.0 467.0 467.0 467.0 100 100
Limite (dB) 16.7 10.8 10.8 10.8 80 80
Pire paire 3,6 3,6 1,2 3,6
60 60
PS ACR-F (dB) 17.5 16.9 18.2 17.1
40 40
Fréq. (MHz) 1.5 428.0 467.0 467.0
Limite (dB) 57.7 8.6 7.8 7.8 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 18.0 17.6 33.0 36.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.4 3.4 489.0 495.0
Limite (dB) 59.8 61.7 -16.2 -16.7 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.8 17.9 33.9 37.0
Fréq. (MHz) 4.8 5.3 500.0 494.0 0 0
Limite (dB) 56.8 55.9 -20.0 -19.5
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 3,6 4,5 MHz MHz
RL (dB) 9.1 7.5 9.9 7.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 139.0 17.4 467.0 414.0 100 100
Limite (dB) 12.6 19.8 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 63
ID Câble: R.5 H1-F/18 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:05:35 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.1 dB (NEXT 3,6-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 47.1 47.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 203
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 4
Résistance (ohms) [Paire 4,5] 6.84
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 22.8 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-4,5 3,6-4,5 3,6-4,5 3,6-4,5 MHz


NEXT (dB) 10.1 11.5 10.8 13.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 438.0 57.0 489.0 488.0 100 100
Limite (dB) 28.6 45.8 27.0 27.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.4 13.1 10.5 13.1
Fréq. (MHz) 453.0 496.0 500.0 496.0 40 40

Limite (dB) 25.2 23.9 23.8 23.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-1,2 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 13.6 14.1 13.6 14.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 432.0 432.0 432.0 432.0 100 100
Limite (dB) 11.5 11.5 11.5 11.5 80 80
Pire paire 3,6 3,6 3,6 1,2
60 60
PS ACR-F (dB) 16.2 16.8 16.2 17.0
40 40
Fréq. (MHz) 432.0 1.3 432.0 432.0
Limite (dB) 8.5 59.3 8.5 8.5 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 3,6-4,5 3,6-4,5 MHz MHz
ACR-N (dB) 15.5 13.4 34.2 36.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.5 3.6 500.0 500.0
Limite (dB) 61.7 61.4 -17.1 -17.1 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.0 16.1 33.3 35.8
Fréq. (MHz) 4.0 3.6 500.0 496.0 0 0
Limite (dB) 58.3 58.6 -20.0 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 3,6 3,6 3,6 MHz MHz
RL (dB) 6.9 8.5 7.3 8.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 276.0 400.0 413.0 400.0 100 100
Limite (dB) 9.6 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 64
ID Câble: R.5 H1-F/20 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:12:10 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.2 dB (NEXT 3,6-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 54.2 54.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 234
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 5
Résistance (ohms) [Paire 3,6] 7.91
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 19.7 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-7,8 1,2-3,6 3,6-7,8 MHz


NEXT (dB) 10.2 4.2 10.3 5.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 485.0 303.0 487.0 475.0 100 100
Limite (dB) 27.1 33.9 27.0 27.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.8 5.9 10.8 7.5
Fréq. (MHz) 484.0 303.0 484.0 493.0 40 40

Limite (dB) 24.2 31.3 24.2 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-1,2 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.7 13.8 14.3 14.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 4.8 4.8 391.0 401.0 100 100
Limite (dB) 50.7 50.7 12.3 12.1 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.0 15.0 16.2 16.4
40 40
Fréq. (MHz) 2.4 2.1 391.0 401.0
Limite (dB) 53.7 54.6 9.3 9.1 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 3,6-7,8 1,2-3,6 3,6-7,8 MHz MHz
ACR-N (dB) 16.6 12.9 29.6 26.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 5.5 25.3 487.0 500.0
Limite (dB) 57.8 42.7 -16.1 -17.1 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.0 14.4 31.2 27.5
Fréq. (MHz) 3.8 25.9 500.0 500.0 0 0
Limite (dB) 58.6 40.0 -20.0 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 4,5 3,6 3,6 MHz MHz
RL (dB) 8.0 7.5 8.3 8.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 146.0 17.0 357.0 430.0 100 100
Limite (dB) 12.4 19.8 8.5 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 65
ID Câble: R.5 H1-F/21 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:16:01 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.8 dB (NEXT 3,6-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 52.6 52.6 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 228
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 6
Résistance (ohms) [Paire 3,6] 7.70
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 20.4 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-4,5 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 10.8 11.8 11.6 12.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 405.0 421.0 495.0 488.0 100 100
Limite (dB) 29.7 29.1 26.8 27.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.7 12.2 10.7 12.2
Fréq. (MHz) 495.0 500.0 495.0 500.0 40 40

Limite (dB) 23.9 23.8 23.9 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.6 14.6 15.7 15.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 7.9 7.3 403.0 407.0 100 100
Limite (dB) 46.3 47.0 12.1 12.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.7 16.7 17.9 17.7
40 40
Fréq. (MHz) 1.5 1.1 393.0 406.0
Limite (dB) 57.7 60.2 9.3 9.0 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-7,8 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 20.4 19.5 31.8 33.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.5 3.0 495.0 500.0
Limite (dB) 59.5 61.9 -16.7 -17.1 80 80

Pire paire 7,8 3,6 3,6 3,6


40 40
PS ACR-N (dB) 19.5 19.5 30.9 32.6
Fréq. (MHz) 4.0 4.6 495.0 500.0 0 0
Limite (dB) 58.3 57.0 -19.6 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 3,6 4,5 MHz MHz
RL (dB) 6.2 8.3 6.2 8.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 472.0 452.0 472.0 452.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 66
ID Câble: R.5 H1-F/22 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:13:09 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.4 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 54.2 54.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 234
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 5
Résistance (ohms) [Paire 4,5] 7.85
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 19.6 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 4,5-7,8 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 9.4 12.3 9.6 12.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 444.0 302.0 488.0 485.0 100 100
Limite (dB) 28.4 33.9 27.0 27.1 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.4 12.4 10.5 12.4
Fréq. (MHz) 487.0 491.0 488.0 491.0 40 40

Limite (dB) 24.2 24.0 24.1 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.6 14.6 15.4 15.0
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 6.4 5.4 403.0 394.0 100 100
Limite (dB) 48.1 49.6 12.1 12.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.4 16.5 17.5 17.7
40 40
Fréq. (MHz) 1.5 2.0 383.0 397.0
Limite (dB) 57.7 55.2 9.5 9.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-7,8 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 19.9 19.9 28.6 32.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.5 2.9 488.0 492.0
Limite (dB) 59.5 62.0 -16.1 -16.5 80 80

Pire paire 7,8 4,5 3,6 3,6


40 40
PS ACR-N (dB) 19.9 21.2 29.8 31.5
Fréq. (MHz) 4.0 4.9 491.0 491.0 0 0
Limite (dB) 58.3 56.6 -19.3 -19.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 3,6 4,5 3,6 MHz MHz
RL (dB) 6.3 7.3 6.3 7.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 481.0 493.0 481.0 493.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 67
ID Câble: R.5 H1-F/23 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:17:15 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 11.0 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 50.2 50.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 217
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 5
Résistance (ohms) [Paire 4,5] 7.38
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 21.4 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 3,6-4,5 3,6-4,5 MHz


NEXT (dB) 11.0 12.5 11.8 12.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 372.0 499.0 497.0 499.0 100 100
Limite (dB) 30.9 26.7 26.7 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.9 13.0 11.0 13.0
Fréq. (MHz) 474.0 499.0 498.0 499.0 40 40

Limite (dB) 24.6 23.8 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 15.3 14.6 15.6 14.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 6.8 418.0 426.0 418.0 100 100
Limite (dB) 47.6 11.8 11.6 11.8 80 80
Pire paire 3,6 3,6 1,2 3,6
60 60
PS ACR-F (dB) 17.3 17.1 18.3 17.2
40 40
Fréq. (MHz) 1.3 412.0 418.0 418.0
Limite (dB) 59.3 8.9 8.8 8.8 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-7,8 1,2-7,8 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 21.0 20.7 33.3 34.1 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.6 2.1 499.0 499.0
Limite (dB) 59.3 62.0 -17.0 -17.0 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 21.1 20.2 32.2 34.3
Fréq. (MHz) 4.5 5.0 498.0 499.0 0 0
Limite (dB) 57.2 56.3 -19.8 -19.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 3,6 3,6 3,6 MHz MHz
RL (dB) 5.3 8.8 5.3 8.8 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 174.0 472.0 174.0 472.0 100 100
Limite (dB) 11.6 8.0 11.6 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 68
ID Câble: R.5 H1-F/24 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:14:13 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.3 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 54.2 54.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 234
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 5
Résistance (ohms) [Paire 4,5] 7.92
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 19.5 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 9.3 12.0 9.3 12.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 478.0 493.0 478.0 494.0 100 100
Limite (dB) 27.3 26.9 27.3 26.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.0 12.4 10.1 12.6
Fréq. (MHz) 478.0 482.0 499.0 498.0 40 40

Limite (dB) 24.4 24.3 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 15.5 15.4 15.9 15.4
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 375.0 394.0 404.0 394.0 100 100
Limite (dB) 12.7 12.3 12.1 12.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.7 17.9 18.4 18.2
40 40
Fréq. (MHz) 2.0 5.1 391.0 394.0
Limite (dB) 55.2 47.0 9.3 9.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 21.5 20.3 29.7 32.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.4 3.1 500.0 500.0
Limite (dB) 59.8 61.8 -17.1 -17.1 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 21.9 21.6 29.5 31.9
Fréq. (MHz) 3.9 4.5 499.0 498.0 0 0
Limite (dB) 58.5 57.2 -19.9 -19.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 4,5 3,6 4,5 MHz MHz
RL (dB) 6.7 7.7 9.4 7.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 13.0 474.0 494.0 474.0 100 100
Limite (dB) 20.4 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 69
ID Câble: R.5 H1-G/01 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:24:44 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.6 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 56.6 56.6 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 244
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 5
Résistance (ohms) [Paire 4,5] 8.36
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 18.7 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 10.6 11.9 11.4 12.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 375.0 400.0 487.0 494.0 100 100
Limite (dB) 30.8 29.9 27.0 26.8 80 80
Pire paire 3,6 3,6 3,6 4,5
60 60
PS NEXT (dB) 11.3 12.8 11.6 13.5
Fréq. (MHz) 487.0 470.0 498.0 500.0 40 40

Limite (dB) 24.2 24.7 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.9 15.4 15.0 17.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 373.0 354.0 387.0 500.0 100 100
Limite (dB) 12.8 13.2 12.4 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.1 17.3 18.9 19.3
40 40
Fréq. (MHz) 373.0 1.1 500.0 500.0
Limite (dB) 9.8 60.2 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 18.7 16.5 29.7 31.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.9 4.8 487.0 494.0
Limite (dB) 60.8 59.1 -16.1 -16.6 80 80

Pire paire 3,6 3,6 3,6 4,5


40 40
PS ACR-N (dB) 17.8 17.5 30.1 32.3
Fréq. (MHz) 3.9 4.4 498.0 500.0 0 0
Limite (dB) 58.5 57.5 -19.8 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 1,2 3,6 3,6 MHz MHz
RL (dB) 8.3 6.6 8.3 8.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 409.0 14.6 409.0 481.0 100 100
Limite (dB) 8.0 20.2 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 70
ID Câble: R.5 H1-G/02 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:25:45 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.2 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 56.4 56.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 244
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 6
Résistance (ohms) [Paire 3,6] 8.35
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 18.8 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 9.2 10.0 9.2 13.6
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 490.0 44.3 490.0 490.0 100 100
Limite (dB) 26.9 47.6 26.9 26.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 9.6 12.4 9.6 13.6
Fréq. (MHz) 500.0 44.3 500.0 490.0 40 40

Limite (dB) 23.8 45.1 23.8 24.1 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.7 14.1 13.8 14.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 390.0 377.0 391.0 396.0 100 100
Limite (dB) 12.4 12.7 12.3 12.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.3 16.0 16.4 16.4
40 40
Fréq. (MHz) 390.0 1.1 391.0 377.0
Limite (dB) 9.4 60.2 9.3 9.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 17.4 13.9 27.5 31.9 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.6 4.8 490.0 490.0
Limite (dB) 61.4 59.1 -16.3 -16.3 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.3 15.7 28.4 32.5
Fréq. (MHz) 3.9 4.6 500.0 497.0 0 0
Limite (dB) 58.5 57.0 -20.0 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 4,5 4,5 3,6 MHz MHz
RL (dB) 8.4 8.7 8.4 8.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 481.0 8.6 481.0 495.0 100 100
Limite (dB) 8.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 71
ID Câble: R.5 H1-G/03 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:26:47 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 11.4 dB (NEXT 3,6-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 56.4 56.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 243
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 5
Résistance (ohms) [Paire 3,6] 8.38
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 18.7 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-4,5 3,6-4,5 3,6-4,5 3,6-4,5 MHz


NEXT (dB) 11.4 11.8 11.9 11.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 478.0 497.0 497.0 497.0 100 100
Limite (dB) 27.3 26.7 26.7 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.9 12.2 11.0 12.2
Fréq. (MHz) 496.0 497.0 497.0 497.0 40 40

Limite (dB) 23.9 23.8 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.5 14.2 13.5 14.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 386.0 360.0 386.0 390.0 100 100
Limite (dB) 12.5 13.1 12.5 12.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.9 16.5 16.0 18.7
40 40
Fréq. (MHz) 386.0 360.0 388.0 500.0
Limite (dB) 9.5 10.1 9.4 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 18.4 16.1 30.6 30.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.8 4.4 497.0 497.0
Limite (dB) 61.1 59.8 -16.9 -16.9 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.2 17.7 29.5 30.8
Fréq. (MHz) 3.9 4.4 497.0 498.0 0 0
Limite (dB) 58.5 57.5 -19.7 -19.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 3,6 3,6 3,6 MHz MHz
RL (dB) 5.5 8.0 8.4 8.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 10.4 490.0 493.0 490.0 100 100
Limite (dB) 20.9 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 72
ID Câble: R.5 H1-G/05 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:21:31 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 11.2 dB (NEXT 3,6-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 53.3 53.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 231
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 6
Résistance (ohms) [Paire 3,6] 7.95
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 19.6 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-4,5 3,6-4,5 3,6-4,5 1,2-3,6 MHz


NEXT (dB) 11.2 11.8 11.7 14.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 443.0 49.0 500.0 481.0 100 100
Limite (dB) 28.4 46.8 26.7 27.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.9 13.8 11.0 13.8
Fréq. (MHz) 443.0 481.0 499.0 481.0 40 40

Limite (dB) 25.6 24.3 23.8 24.3 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.1 14.1 14.3 14.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 404.0 399.0 422.0 399.0 100 100
Limite (dB) 12.1 12.2 11.7 12.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.5 16.1 16.6 16.1
40 40
Fréq. (MHz) 404.0 399.0 408.0 399.0
Limite (dB) 9.1 9.2 9.0 9.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 3,6-4,5 1,2-3,6 MHz MHz
ACR-N (dB) 15.8 14.9 31.3 33.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.0 4.9 500.0 481.0
Limite (dB) 60.5 58.8 -17.1 -15.6 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 16.4 16.6 30.8 34.1
Fréq. (MHz) 4.0 4.8 499.0 494.0 0 0
Limite (dB) 58.3 56.8 -19.9 -19.5
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 7,8 3,6 3,6 MHz MHz
RL (dB) 8.3 8.1 8.6 9.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 13.1 11.1 492.0 484.0 100 100
Limite (dB) 20.4 20.8 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 73
ID Câble: R.5 H1-G/06 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:36:00 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 8.0 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 60.4 60.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 261
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 6
Résistance (ohms) [Paire 3,6] 8.96
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 16.8 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 8.0 13.0 8.7 13.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 476.0 428.0 500.0 500.0 100 100
Limite (dB) 27.4 28.9 26.7 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 8.9 13.1 9.4 13.5
Fréq. (MHz) 477.0 461.0 500.0 500.0 40 40

Limite (dB) 24.5 25.0 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.6 14.9 15.6 15.5
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 352.0 352.0 500.0 500.0 100 100
Limite (dB) 13.3 13.3 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.9 17.5 17.9 18.0
40 40
Fréq. (MHz) 347.0 352.0 500.0 500.0
Limite (dB) 10.4 10.3 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 16.2 16.0 25.8 30.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.6 4.3 500.0 500.0
Limite (dB) 61.4 60.0 -17.1 -17.1 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 15.6 16.8 26.5 30.6
Fréq. (MHz) 3.9 4.1 500.0 500.0 0 0
Limite (dB) 58.5 58.0 -20.0 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 3,6 3,6 MHz MHz
RL (dB) 7.4 6.8 7.5 8.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 9.6 8.1 492.0 479.0 100 100
Limite (dB) 21.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 74
ID Câble: R.5 H1-G/08 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:30:08 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.4 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 57.8 57.8 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 249
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 5
Résistance (ohms) [Paire 3,6] 8.56
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 18.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 9.4 12.1 9.8 13.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 342.0 378.0 496.0 476.0 100 100
Limite (dB) 32.1 30.7 26.8 27.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.6 13.2 10.7 13.6
Fréq. (MHz) 477.0 471.0 496.0 483.0 40 40

Limite (dB) 24.5 24.7 23.9 24.3 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-1,2 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 14.6 15.3 15.9 16.5
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 343.0 344.0 500.0 500.0 100 100
Limite (dB) 13.5 13.5 10.2 10.2 80 80
Pire paire 3,6 1,2 3,6 3,6
60 60
PS ACR-F (dB) 17.1 17.7 18.0 19.0
40 40
Fréq. (MHz) 343.0 1.1 500.0 500.0
Limite (dB) 10.5 60.2 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 16.8 17.4 27.8 30.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.9 4.6 496.0 476.0
Limite (dB) 60.8 59.3 -16.8 -15.2 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.3 17.6 28.7 32.5
Fréq. (MHz) 3.9 4.3 496.0 500.0 0 0
Limite (dB) 58.5 57.7 -19.7 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 4,5 4,5 3,6 MHz MHz
RL (dB) 8.5 7.5 8.6 8.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 34.5 8.3 488.0 478.0 100 100
Limite (dB) 18.3 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 75
ID Câble: R.5 H1-G/09 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:32:12 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.3 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 57.1 57.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 246
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 5
Résistance (ohms) [Paire 4,5] 8.46
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 18.4 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 9.3 13.1 9.3 13.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 489.0 56.3 489.0 500.0 100 100
Limite (dB) 27.0 45.9 27.0 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 9.2 14.0 9.2 14.0
Fréq. (MHz) 490.0 500.0 490.0 500.0 40 40

Limite (dB) 24.1 23.8 24.1 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.1 13.6 13.1 14.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 377.0 356.0 377.0 390.0 100 100
Limite (dB) 12.7 13.2 12.7 12.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.8 15.8 18.2 18.2
40 40
Fréq. (MHz) 377.0 369.0 500.0 500.0
Limite (dB) 9.7 9.8 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 18.4 15.8 27.3 32.0 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.5 4.3 489.0 500.0
Limite (dB) 61.7 60.0 -16.2 -17.1 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 19.4 17.7 28.1 32.4
Fréq. (MHz) 3.9 10.8 500.0 500.0 0 0
Limite (dB) 58.5 49.3 -20.0 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 1,2 4,5 3,6 MHz MHz
RL (dB) 7.1 6.2 7.1 9.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 461.0 8.8 461.0 440.0 100 100
Limite (dB) 8.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 76
ID Câble: R.5 H1-G/10 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:37:10 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.4 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 60.4 60.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 261
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 6
Résistance (ohms) [Paire 4,5] 8.86
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 17.0 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 10.4 13.3 10.5 13.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 490.0 500.0 495.0 500.0 100 100
Limite (dB) 26.9 26.7 26.8 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.1 13.4 10.2 13.4
Fréq. (MHz) 490.0 500.0 491.0 500.0 40 40

Limite (dB) 24.1 23.8 24.0 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.4 14.5 14.4 14.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 490.0 477.0 490.0 498.0 100 100
Limite (dB) 10.4 10.6 10.4 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.9 16.9 16.9 17.1
40 40
Fréq. (MHz) 490.0 477.0 490.0 498.0
Limite (dB) 7.4 7.6 7.4 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 18.4 17.6 27.4 30.3 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.5 4.3 495.0 500.0
Limite (dB) 61.7 60.0 -16.7 -17.1 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 19.4 19.0 26.9 30.5
Fréq. (MHz) 3.8 4.3 491.0 500.0 0 0
Limite (dB) 58.6 57.7 -19.3 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 3,6 4,5 3,6 MHz MHz
RL (dB) 7.6 9.4 8.9 9.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 8.0 457.0 459.0 457.0 100 100
Limite (dB) 21.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 77
ID Câble: R.5 H1-G/11 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:51:56 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.4 dB (NEXT 3,6-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 61.1 61.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 264
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 6
Résistance (ohms) [Paire 3,6] 9.06
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 16.7 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-4,5 1,2-3,6 3,6-4,5 1,2-3,6 MHz


NEXT (dB) 10.4 11.8 11.0 12.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 463.0 437.0 500.0 495.0 100 100
Limite (dB) 27.8 28.6 26.7 26.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 11.0 11.8 11.0 11.8
Fréq. (MHz) 492.0 464.0 492.0 464.0 40 40

Limite (dB) 24.0 24.9 24.0 24.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 15.0 14.3 15.4 14.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 168.0 348.0 500.0 487.0 100 100
Limite (dB) 19.7 13.4 10.2 10.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.3 16.8 17.4 17.1
40 40
Fréq. (MHz) 497.0 348.0 499.0 488.0
Limite (dB) 7.3 10.4 7.2 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 3,6-4,5 1,2-3,6 MHz MHz
ACR-N (dB) 16.7 16.2 27.7 29.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.6 4.4 500.0 500.0
Limite (dB) 61.4 59.8 -17.1 -17.1 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.3 16.9 27.5 29.9
Fréq. (MHz) 3.9 4.1 492.0 495.0 0 0
Limite (dB) 58.5 58.0 -19.3 -19.6
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 3,6 3,6 MHz MHz
RL (dB) 7.5 7.1 7.7 9.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 19.0 8.0 373.0 487.0 100 100
Limite (dB) 19.6 21.0 8.3 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 78
ID Câble: R.5 H1-G/12 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:46:27 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.2 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 60.4 60.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 261
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 6
Résistance (ohms) [Paire 3,6] 8.96
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 17.1 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 3,6-4,5 1,2-3,6 MHz


NEXT (dB) 10.2 13.5 10.9 14.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 436.0 33.5 499.0 486.0 100 100
Limite (dB) 28.6 49.5 26.7 27.1 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.1 13.8 10.1 13.8
Fréq. (MHz) 499.0 481.0 499.0 481.0 40 40

Limite (dB) 23.8 24.3 23.8 24.3 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 15.3 14.8 16.0 15.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 340.0 352.0 500.0 500.0 100 100
Limite (dB) 13.6 13.3 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.7 17.3 18.1 17.9
40 40
Fréq. (MHz) 340.0 352.0 500.0 500.0
Limite (dB) 10.6 10.3 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 3,6-4,5 3,6-4,5 MHz MHz
ACR-N (dB) 16.3 15.2 27.9 32.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.8 4.1 499.0 500.0
Limite (dB) 61.1 60.3 -17.0 -17.1 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 16.4 16.6 27.4 30.4
Fréq. (MHz) 3.8 4.0 499.0 481.0 0 0
Limite (dB) 58.6 58.3 -19.9 -18.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 7,8 4,5 MHz MHz
RL (dB) 5.9 5.1 5.9 9.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 189.5 8.0 189.5 479.0 100 100
Limite (dB) 11.2 21.0 11.2 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 79
ID Câble: R.5 H1-G/13 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:49:23 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.3 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 60.6 60.6 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 261
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 5
Résistance (ohms) [Paire 3,6] 8.92
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 17.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 10.3 12.8 10.4 12.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 434.0 477.0 493.0 477.0 100 100
Limite (dB) 28.7 27.3 26.9 27.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.6 12.9 10.6 12.9
Fréq. (MHz) 493.0 486.0 493.0 486.0 40 40

Limite (dB) 24.0 24.2 24.0 24.2 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 15.2 15.2 17.4 17.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 344.0 348.0 500.0 500.0 100 100
Limite (dB) 13.5 13.4 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.6 17.5 18.9 20.2
40 40
Fréq. (MHz) 350.0 347.0 500.0 500.0
Limite (dB) 10.3 10.4 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 17.4 17.1 27.2 29.0 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.8 3.8 493.0 477.0
Limite (dB) 61.1 61.1 -16.5 -15.2 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.4 17.6 27.4 30.4
Fréq. (MHz) 3.6 3.9 493.0 500.0 0 0
Limite (dB) 58.6 58.5 -19.4 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 7,8 3,6 4,5 MHz MHz
RL (dB) 6.5 6.6 9.4 9.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 8.0 24.9 435.0 444.0 100 100
Limite (dB) 21.0 19.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 80
ID Câble: R.5 H1-G/14 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:40:53 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.2 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 59.2 59.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 256
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 6
Résistance (ohms) [Paire 4,5] 8.75
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 17.6 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 9.2 12.9 9.7 12.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 426.0 466.0 496.0 466.0 100 100
Limite (dB) 29.0 27.7 26.8 27.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.4 13.4 10.4 14.4
Fréq. (MHz) 494.0 465.0 494.0 500.0 40 40

Limite (dB) 23.9 24.8 23.9 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.6 13.9 13.6 13.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 357.0 363.0 357.0 363.0 100 100
Limite (dB) 13.1 13.0 13.1 13.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.0 16.2 18.0 18.5
40 40
Fréq. (MHz) 357.0 1.1 500.0 500.0
Limite (dB) 10.1 60.2 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 17.9 16.1 27.3 29.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.5 4.4 497.0 466.0
Limite (dB) 61.7 59.8 -16.9 -14.3 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.2 17.6 27.7 32.0
Fréq. (MHz) 3.8 4.3 494.0 500.0 0 0
Limite (dB) 58.6 57.7 -19.5 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 1,2 3,6 4,5 MHz MHz
RL (dB) 7.4 6.1 7.8 9.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 210.0 8.3 472.0 479.0 100 100
Limite (dB) 10.8 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 81
ID Câble: R.5 H1-G/17 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:56:44 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.5 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 63.0 63.0 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 272
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 6
Résistance (ohms) [Paire 3,6] 9.39
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 15.9 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 9.5 12.3 9.5 12.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 488.0 494.0 488.0 494.0 100 100
Limite (dB) 27.0 26.8 27.0 26.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.7 12.8 10.7 12.8
Fréq. (MHz) 487.0 495.0 487.0 495.0 40 40

Limite (dB) 24.2 23.9 24.2 23.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.5 14.9 14.8 15.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 339.0 347.0 480.0 491.0 100 100
Limite (dB) 13.6 13.4 10.6 10.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.1 17.1 17.7 18.3
40 40
Fréq. (MHz) 339.0 1.0 499.0 491.0
Limite (dB) 10.6 61.2 7.2 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 15.0 15.0 25.1 28.1 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.5 3.8 488.0 494.0
Limite (dB) 61.7 61.1 -16.1 -16.6 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 16.8 16.8 26.3 28.8
Fréq. (MHz) 3.5 3.8 487.0 496.0 0 0
Limite (dB) 58.7 58.6 -18.9 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 4,5 3,6 3,6 MHz MHz
RL (dB) 5.0 8.6 8.5 8.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 7.6 119.0 457.0 498.0 60 100
Limite (dB) 21.0 13.2 8.0 8.0 50 80
Conforme aux normes de réseaux: 40
60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 82
ID Câble: R.5 H1-G/18 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 19:59:54 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.5 dB (NEXT 3,6-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 66.1 66.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 285
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 6
Résistance (ohms) [Paire 4,5] 9.65
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 14.6 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-4,5 1,2-7,8 3,6-4,5 3,6-4,5 MHz


NEXT (dB) 10.5 12.4 10.7 13.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 489.0 403.0 500.0 498.0 100 100
Limite (dB) 27.0 29.8 26.7 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.9 12.8 10.9 12.8
Fréq. (MHz) 500.0 498.0 500.0 498.0 40 40

Limite (dB) 23.8 23.8 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.8 15.1 15.3 15.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 336.0 337.0 492.0 479.0 100 100
Limite (dB) 13.7 13.6 10.4 10.6 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.6 17.7 17.6 17.7
40 40
Fréq. (MHz) 492.0 479.0 492.0 479.0
Limite (dB) 7.4 7.6 7.4 7.6 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-7,8 3,6-4,5 3,6-4,5 1,2-3,6 MHz MHz
ACR-N (dB) 15.7 17.0 25.8 28.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.8 3.5 500.0 498.0
Limite (dB) 61.1 61.7 -17.1 -16.9 80 80

Pire paire 1,2 4,5 3,6 3,6


40 40
PS ACR-N (dB) 15.8 17.7 25.5 27.2
Fréq. (MHz) 3.6 5.1 500.0 498.0 0 0
Limite (dB) 58.6 56.1 -20.0 -19.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 4,5 3,6 4,5 MHz MHz
RL (dB) 5.6 8.0 8.6 8.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 9.1 494.0 441.0 494.0 100 100
Limite (dB) 21.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 83
ID Câble: R.5 H1-I/21 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:44:16 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.7 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 81.2 81.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 350
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 7
Résistance (ohms) [Paire 3,6] 11.91
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 7.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 9.7 12.1 9.7 12.2
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 480.0 486.0 480.0 487.0 100 100
Limite (dB) 27.2 27.1 27.2 27.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.3 12.9 10.4 12.9
Fréq. (MHz) 467.0 500.0 480.0 500.0 40 40

Limite (dB) 24.8 23.8 24.4 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.2 13.7 13.2 13.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 498.0 497.0 498.0 498.0 100 100
Limite (dB) 10.2 10.3 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.9 16.2 15.9 16.2
40 40
Fréq. (MHz) 500.0 498.0 500.0 498.0
Limite (dB) 7.2 7.2 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 16.8 14.1 19.0 20.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 288.0 7.4 500.0 487.0
Limite (dB) 2.4 55.2 -17.1 -16.1 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.9 16.3 19.1 20.8
Fréq. (MHz) 288.0 7.5 500.0 500.0 0 0
Limite (dB) -0.2 52.7 -20.0 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 7,8 3,6 4,5 MHz MHz
RL (dB) 4.1 6.2 8.2 7.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 4.6 195.0 486.0 377.0 100 100
Limite (dB) 21.0 11.1 8.0 8.2 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 84
ID Câble: R.5 H1-I/22 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:48:01 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.7 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 81.5 81.5 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 352
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 8
Résistance (ohms) [Paire 3,6] 11.98
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 7.6 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 10.7 11.6 10.7 11.6
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 476.0 475.0 476.0 475.0 100 100
Limite (dB) 27.4 27.4 27.4 27.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 11.3 11.6 11.8 11.6
Fréq. (MHz) 476.0 476.0 495.0 476.0 40 40

Limite (dB) 24.5 24.5 23.9 24.5 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.3 15.1 14.3 15.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 495.0 491.0 495.0 491.0 100 100
Limite (dB) 10.3 10.4 10.3 10.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.0 17.3 17.0 17.4
40 40
Fréq. (MHz) 496.0 1.0 496.0 490.0
Limite (dB) 7.3 61.2 7.3 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 16.0 14.9 19.3 20.9 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 283.0 4.6 495.0 500.0
Limite (dB) 2.8 59.3 -16.7 -17.1 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.2 16.2 19.9 20.8
Fréq. (MHz) 4.0 7.4 500.0 500.0 0 0
Limite (dB) 58.3 52.8 -20.0 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 3,6 3,6 3,6 MHz MHz
RL (dB) 3.4 6.6 9.9 7.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 4.6 293.0 494.0 489.0 60 100
Limite (dB) 21.0 9.3 8.0 8.0 50 80
Conforme aux normes de réseaux: 40
60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 85
ID Câble: R.5 H1-I/23 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:38:14 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.9 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 75.1 75.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 324
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 7
Résistance (ohms) [Paire 3,6] 11.01
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 10.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 9.9 10.6 10.1 10.6
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 484.0 487.0 492.0 487.0 100 100
Limite (dB) 27.1 27.0 26.9 27.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.4 11.7 10.6 11.7
Fréq. (MHz) 483.0 487.0 494.0 487.0 40 40

Limite (dB) 24.3 24.2 23.9 24.2 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.6 14.2 14.7 14.2
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 400.0 409.0 408.0 409.0 100 100
Limite (dB) 12.1 12.0 12.0 12.0 80 80
Pire paire 3,6 1,2 3,6 3,6
60 60
PS ACR-F (dB) 16.3 16.6 17.3 16.9
40 40
Fréq. (MHz) 1.0 1.0 424.0 410.0
Limite (dB) 61.2 61.2 8.6 8.9 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 16.8 13.4 20.7 21.1 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 2.9 3.5 492.0 487.0
Limite (dB) 62.0 61.7 -16.5 -16.1 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 19.2 15.8 21.2 22.2
Fréq. (MHz) 4.4 5.0 494.0 487.0 0 0
Limite (dB) 57.5 56.3 -19.5 -18.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 4,5 4,5 3,6 MHz MHz
RL (dB) 4.5 8.1 7.7 8.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 5.1 161.0 493.0 462.0 100 100
Limite (dB) 21.0 11.9 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 86
ID Câble: R.5 H1-I/24 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:41:54 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.7 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 76.3 76.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 330
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 8
Résistance (ohms) [Paire 3,6] 11.22
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 10.2 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 9.7 12.7 9.7 13.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 491.0 466.0 491.0 492.0 100 100
Limite (dB) 26.9 27.7 26.9 26.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.0 13.3 10.0 13.8
Fréq. (MHz) 492.0 466.0 492.0 495.0 40 40

Limite (dB) 24.0 24.8 24.0 23.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 15.5 15.8 15.8 16.4
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 395.0 384.0 500.0 500.0 100 100
Limite (dB) 12.3 12.5 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 1,2
60 60
PS ACR-F (dB) 17.8 18.3 18.1 19.1
40 40
Fréq. (MHz) 395.0 397.0 500.0 500.0
Limite (dB) 9.3 9.2 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 16.1 13.8 20.0 23.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.5 3.5 492.0 492.0
Limite (dB) 59.5 61.7 -16.5 -16.5 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 16.3 15.2 20.7 24.0
Fréq. (MHz) 4.4 4.9 500.0 495.0 0 0
Limite (dB) 57.5 56.6 -20.0 -19.6
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 3,6 3,6 MHz MHz
RL (dB) 5.1 6.0 11.6 9.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 5.0 5.1 470.0 466.0 100 100
Limite (dB) 21.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 87
ID Câble: R.5 H1-J/01 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:46:20 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 11.6 dB (NEXT 3,6-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 80.5 80.5 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 348
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 8
Résistance (ohms) [Paire 3,6] 11.84
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 8.2 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-4,5 1,2-3,6 3,6-4,5 1,2-3,6 MHz


NEXT (dB) 11.6 11.8 11.9 11.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 411.0 487.0 500.0 487.0 100 100
Limite (dB) 29.5 27.0 26.7 27.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 11.3 12.5 11.3 12.5
Fréq. (MHz) 495.0 487.0 495.0 487.0 40 40

Limite (dB) 23.9 24.2 23.9 24.2 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.8 15.1 14.9 15.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 495.0 500.0 500.0 500.0 100 100
Limite (dB) 10.3 10.2 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.1 17.1 17.1 17.1
40 40
Fréq. (MHz) 500.0 500.0 500.0 500.0
Limite (dB) 7.2 7.2 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 3,6-4,5 1,2-3,6 MHz MHz
ACR-N (dB) 18.0 15.3 20.2 19.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.9 4.6 500.0 487.0
Limite (dB) 60.8 59.3 -17.1 -16.1 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.6 17.2 19.7 20.3
Fréq. (MHz) 410.0 4.6 500.0 487.0 0 0
Limite (dB) -12.3 57.0 -20.0 -18.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 7,8 4,5 3,6 MHz MHz
RL (dB) 4.5 6.3 8.8 6.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 4.6 14.5 500.0 488.0 100 100
Limite (dB) 21.0 20.2 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 88
ID Câble: R.5 H1-J/02 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:35:38 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.8 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 75.3 75.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 325
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 7
Résistance (ohms) [Paire 3,6] 11.08
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 10.6 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 4,5-7,8 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 9.8 12.5 9.8 12.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 490.0 345.0 490.0 498.0 100 100
Limite (dB) 26.9 32.0 26.9 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.4 12.5 10.4 12.5
Fréq. (MHz) 490.0 497.0 490.0 497.0 40 40

Limite (dB) 24.1 23.8 24.1 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 14.7 15.1 15.3 16.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 291.0 291.0 429.0 429.0 100 100
Limite (dB) 14.9 14.9 11.5 11.5 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.2 16.8 17.2 18.3
40 40
Fréq. (MHz) 429.0 1.0 429.0 441.0
Limite (dB) 8.5 61.2 8.5 8.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 17.6 13.9 20.2 23.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.3 3.5 490.0 498.0
Limite (dB) 60.0 61.7 -16.3 -16.9 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.8 15.5 20.9 23.0
Fréq. (MHz) 4.5 4.9 490.0 497.0 0 0
Limite (dB) 57.2 56.6 -19.2 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 3,6 3,6 4,5 MHz MHz
RL (dB) 3.9 6.6 9.3 7.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 4.9 114.5 495.0 491.0 100 100
Limite (dB) 21.0 13.4 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 89
ID Câble: R.5 H1-J/03 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:32:35 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.5 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 75.3 75.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 325
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 7
Résistance (ohms) [Paire 3,6] 11.12
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 10.4 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 10.8 10.5 10.8 10.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 495.0 493.0 495.0 493.0 100 100
Limite (dB) 26.8 26.9 26.8 26.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 11.7 11.3 11.8 11.3
Fréq. (MHz) 496.0 493.0 500.0 493.0 40 40

Limite (dB) 23.9 24.0 23.8 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.3 14.2 15.3 14.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 287.0 289.0 412.0 403.0 100 100
Limite (dB) 15.0 15.0 11.9 12.1 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.6 16.8 17.8 17.9
40 40
Fréq. (MHz) 1.0 1.1 421.0 437.0
Limite (dB) 61.2 60.2 8.7 8.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-7,8 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 18.0 15.3 21.5 21.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 6.1 5.0 495.0 496.0
Limite (dB) 56.8 58.6 -16.7 -16.8 80 80

Pire paire 1,2 4,5 3,6 3,6


40 40
PS ACR-N (dB) 18.1 16.4 22.6 22.0
Fréq. (MHz) 4.5 5.0 500.0 493.0 0 0
Limite (dB) 57.2 56.3 -20.0 -19.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 7,8 3,6 3,6 MHz MHz
RL (dB) 3.3 6.5 8.4 7.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 5.0 8.1 497.0 499.0 100 100
Limite (dB) 21.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 90
ID Câble: R.5 H1-J/04 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:34:16 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 8.9 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 75.3 75.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 325
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 7
Résistance (ohms) [Paire 3,6] 10.94
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 10.7 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 8.9 12.4 9.3 12.6
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 435.0 438.0 474.0 495.0 100 100
Limite (dB) 28.7 28.6 27.4 26.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.1 13.2 10.2 13.2
Fréq. (MHz) 463.0 495.0 474.0 495.0 40 40

Limite (dB) 24.9 23.9 24.6 23.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.3 14.6 15.3 15.0
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 283.0 279.0 440.0 431.0 100 100
Limite (dB) 15.2 15.3 11.3 11.5 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.7 16.9 17.1 16.9
40 40
Fréq. (MHz) 283.0 416.0 418.0 416.0
Limite (dB) 12.2 8.8 8.8 8.8 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 17.2 15.1 20.1 23.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.3 3.5 474.0 496.0
Limite (dB) 60.0 61.7 -15.0 -16.8 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.0 16.7 22.2 24.4
Fréq. (MHz) 4.4 4.9 500.0 496.0 0 0
Limite (dB) 57.5 56.6 -20.0 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 3,6 3,6 3,6 MHz MHz
RL (dB) 5.0 6.5 7.9 6.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 5.0 500.0 464.0 500.0 100 100
Limite (dB) 21.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 91
ID Câble: R.5 H1-J/05 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:26:26 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 12.1 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 72.0 72.0 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 311
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 7
Résistance (ohms) [Paire 3,6] 10.61
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 12.2 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 12.1 12.7 12.4 14.2
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 475.0 21.5 496.0 499.0 100 100
Limite (dB) 27.4 52.6 26.8 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 11.7 13.8 11.9 14.4
Fréq. (MHz) 476.0 474.0 496.0 498.0 40 40

Limite (dB) 24.5 24.6 23.9 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.3 14.7 15.7 15.2
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 289.0 291.0 454.0 427.0 100 100
Limite (dB) 15.0 14.9 11.0 11.6 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.5 17.1 17.2 17.6
40 40
Fréq. (MHz) 285.0 288.0 459.0 452.0
Limite (dB) 12.1 12.0 8.0 8.1 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-7,8 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 17.5 13.6 24.8 26.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.3 3.6 497.0 499.0
Limite (dB) 61.8 61.4 -16.9 -17.0 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.6 15.8 24.2 26.6
Fréq. (MHz) 3.4 8.4 497.0 498.0 0 0
Limite (dB) 58.7 51.7 -19.7 -19.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 7,8 3,6 7,8 MHz MHz
RL (dB) 3.8 3.3 9.7 5.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 5.3 6.9 490.0 168.5 100 100
Limite (dB) 21.0 21.0 8.0 11.7 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 92
ID Câble: R.5 H1-J/06 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:29:59 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.4 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 69.9 69.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 301
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 6
Résistance (ohms) [Paire 3,6] 10.14
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 13.2 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 10.4 12.1 10.4 12.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 488.0 489.0 488.0 489.0 100 100
Limite (dB) 27.0 27.0 27.0 27.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.7 13.0 11.2 13.0
Fréq. (MHz) 434.0 490.0 491.0 490.0 40 40

Limite (dB) 25.9 24.1 24.0 24.1 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.6 14.0 13.8 14.0
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 458.0 475.0 470.0 475.0 100 100
Limite (dB) 11.0 10.7 10.7 10.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.8 16.4 15.9 16.5
40 40
Fréq. (MHz) 469.0 475.0 471.0 477.0
Limite (dB) 7.8 7.7 7.7 7.6 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 17.7 14.9 23.7 25.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.4 3.6 488.0 490.0
Limite (dB) 59.8 61.4 -16.1 -16.3 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.9 16.6 24.6 27.0
Fréq. (MHz) 4.6 5.3 492.0 500.0 0 0
Limite (dB) 57.0 55.9 -19.3 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 3,6 4,5 3,6 MHz MHz
RL (dB) 4.4 3.7 9.6 3.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 5.8 165.5 500.0 165.5 100 100
Limite (dB) 21.0 11.8 8.0 11.8 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 93
ID Câble: R.5 H1-J/07 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:14:42 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 11.0 dB (NEXT 3,6-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 68.9 68.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 298
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 7
Résistance (ohms) [Paire 4,5] 10.19
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 13.5 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-4,5 1,2-3,6 3,6-4,5 3,6-4,5 MHz


NEXT (dB) 11.0 13.2 11.0 13.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 484.0 456.0 484.0 481.0 100 100
Limite (dB) 27.1 28.0 27.1 27.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.7 13.2 10.7 13.3
Fréq. (MHz) 482.0 480.0 482.0 481.0 40 40

Limite (dB) 24.3 24.4 24.3 24.3 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 14.5 14.9 14.6 15.4
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 464.0 306.0 466.0 465.0 100 100
Limite (dB) 10.9 14.5 10.8 10.8 80 80
Pire paire 3,6 3,6 3,6 1,2
60 60
PS ACR-F (dB) 16.4 17.5 16.5 17.9
40 40
Fréq. (MHz) 464.0 298.0 466.0 466.0
Limite (dB) 7.9 11.7 7.8 7.8 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 3,6-4,5 3,6-4,5 MHz MHz
ACR-N (dB) 18.7 14.4 24.3 27.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.0 3.9 484.0 498.0
Limite (dB) 61.9 60.8 -15.8 -16.9 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 19.5 16.2 23.6 27.5
Fréq. (MHz) 5.0 5.4 482.0 500.0 0 0
Limite (dB) 56.3 55.7 -18.5 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 7,8 3,6 3,6 MHz MHz
RL (dB) 6.7 7.4 6.7 8.8 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 262.0 5.9 262.0 458.0 100 100
Limite (dB) 9.8 21.0 9.8 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 94
ID Câble: R.5 H1-J/08 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:19:35 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.9 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 76.7 76.7 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 331
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 7
Résistance (ohms) [Paire 3,6] 11.12
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 10.4 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 9.9 12.6 10.2 12.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 478.0 496.0 500.0 500.0 100 100
Limite (dB) 27.3 26.8 26.7 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 9.8 12.9 10.2 12.9
Fréq. (MHz) 478.0 500.0 499.0 500.0 40 40

Limite (dB) 24.4 23.8 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.1 14.1 14.2 14.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 418.0 418.0 419.0 430.0 100 100
Limite (dB) 11.8 11.8 11.7 11.5 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.6 16.3 16.8 16.3
40 40
Fréq. (MHz) 418.0 430.0 430.0 430.0
Limite (dB) 8.8 8.5 8.5 8.5 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 16.7 16.2 20.6 23.1 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.5 3.6 500.0 500.0
Limite (dB) 59.5 61.4 -17.1 -17.1 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.0 17.6 20.5 23.3
Fréq. (MHz) 4.5 4.6 499.0 500.0 0 0
Limite (dB) 57.2 57.0 -19.9 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 7,8 3,6 4,5 MHz MHz
RL (dB) 5.8 5.7 8.0 8.1 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 5.1 5.0 500.0 492.0 60 60
Limite (dB) 21.0 21.0 8.0 8.0 50 50

Conforme aux normes de réseaux: 40 40


10BASE-T 100BASE-TX 100BASE-T4 30 30
1000BASE-T 2.5GBASE-T 5GBASE-T 20 20
10GBASE-T ATM-25 ATM-51
ATM-155 100VG-AnyLan TR-4 10 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 95
ID Câble: R.5 H1-J/09 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:22:12 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.2 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 76.5 76.5 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 331
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 8
Résistance (ohms) [Paire 3,6] 11.30
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 10.2 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 10.2 13.0 10.2 13.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 485.0 373.0 485.0 499.0 100 100
Limite (dB) 27.1 30.9 27.1 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.0 13.3 10.0 13.4
Fréq. (MHz) 485.0 471.0 485.0 500.0 40 40

Limite (dB) 24.2 24.7 24.2 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 15.1 15.4 15.1 15.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 421.0 283.0 421.0 411.0 100 100
Limite (dB) 11.7 15.2 11.7 11.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.4 17.8 17.4 17.8
40 40
Fréq. (MHz) 421.0 411.0 421.0 411.0
Limite (dB) 8.7 8.9 8.7 8.9 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 3,6-4,5 1,2-3,6 MHz MHz
ACR-N (dB) 18.0 14.6 21.1 23.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.5 5.1 500.0 499.0
Limite (dB) 59.5 58.4 -17.1 -17.0 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.5 16.2 21.0 23.8
Fréq. (MHz) 4.5 4.9 500.0 500.0 0 0
Limite (dB) 57.2 56.6 -20.0 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 3,6 3,6 MHz MHz
RL (dB) 5.9 6.2 8.4 9.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 5.0 5.0 493.0 499.0 60 100
Limite (dB) 21.0 21.0 8.0 8.0 50 80
Conforme aux normes de réseaux: 40
60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 96
ID Câble: R.5 H1-J/10 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:16:58 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.4 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 76.7 76.7 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 332
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 8
Résistance (ohms) [Paire 4,5] 11.16
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 10.3 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 10.4 11.9 10.6 11.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 472.0 498.0 500.0 498.0 100 100
Limite (dB) 27.5 26.7 26.7 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 9.8 11.5 9.8 11.5
Fréq. (MHz) 500.0 498.0 500.0 498.0 40 40

Limite (dB) 23.8 23.8 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-1,2 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 13.4 14.4 13.4 14.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 417.0 404.0 417.0 419.0 100 100
Limite (dB) 11.8 12.1 11.8 11.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.0 17.0 16.0 17.5
40 40
Fréq. (MHz) 417.0 267.0 417.0 421.0
Limite (dB) 8.8 12.7 8.8 8.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 18.1 15.5 21.0 22.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 276.0 3.5 500.0 498.0
Limite (dB) 3.5 61.7 -17.1 -16.9 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.9 17.7 20.2 21.8
Fréq. (MHz) 4.5 3.5 500.0 498.0 0 0
Limite (dB) 57.2 58.7 -20.0 -19.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 7,8 3,6 3,6 MHz MHz
RL (dB) 5.2 4.8 7.6 6.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 5.0 5.1 475.0 492.0 60 100
Limite (dB) 21.0 21.0 8.0 8.0 50 80
Conforme aux normes de réseaux: 40
60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 97
ID Câble: R.5 H1-J/11 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:24:01 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.7 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 70.6 70.6 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 305
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 7
Résistance (ohms) [Paire 3,6] 10.40
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 12.8 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 10.7 13.9 10.7 14.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 498.0 4.0 498.0 497.0 100 100
Limite (dB) 26.7 64.1 26.7 26.7 80 80
Pire paire 3,6 3,6 3,6 4,5
60 60
PS NEXT (dB) 10.0 13.8 10.0 14.0
Fréq. (MHz) 500.0 476.0 500.0 497.0 40 40

Limite (dB) 23.8 24.5 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.8 15.1 14.9 15.2
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 302.0 293.0 460.0 452.0 100 100
Limite (dB) 14.6 14.9 10.9 11.1 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.9 17.2 16.9 17.6
40 40
Fréq. (MHz) 460.0 1.0 460.0 460.0
Limite (dB) 7.9 61.2 7.9 7.9 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 3,6-4,5 3,6-4,5 MHz MHz
ACR-N (dB) 18.4 14.9 23.5 26.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.4 4.0 500.0 497.0
Limite (dB) 61.7 60.5 -17.1 -16.9 80 80

Pire paire 1,2 3,6 3,6 4,5


40 40
PS ACR-N (dB) 18.3 16.6 23.2 26.5
Fréq. (MHz) 4.6 3.9 500.0 497.0 0 0
Limite (dB) 57.0 58.5 -20.0 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 4,5 4,5 4,5 MHz MHz
RL (dB) 6.1 6.4 7.6 8.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 6.9 5.4 435.0 500.0 100 60
Limite (dB) 21.0 21.0 8.0 8.0 80 50

Conforme aux normes de réseaux: 40


60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 98
ID Câble: R.5 H1-J/12 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:10:35 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.6 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 68.4 68.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 295
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 6
Résistance (ohms) [Paire 4,5] 9.98
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 14.0 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 10.6 12.1 10.7 12.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 445.0 480.0 482.0 498.0 100 100
Limite (dB) 28.3 27.2 27.2 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.9 11.9 10.9 12.0
Fréq. (MHz) 473.0 492.0 473.0 498.0 40 40

Limite (dB) 24.6 24.0 24.6 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.0 14.5 14.3 14.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 469.0 471.0 483.0 476.0 100 100
Limite (dB) 10.8 10.7 10.5 10.6 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.4 16.6 16.4 16.6
40 40
Fréq. (MHz) 471.0 477.0 471.0 477.0
Limite (dB) 7.7 7.6 7.7 7.6 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 18.3 15.6 24.4 26.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 5.0 3.5 482.0 499.0
Limite (dB) 58.6 61.7 -15.6 -17.0 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.0 16.9 26.0 26.2
Fréq. (MHz) 5.0 3.5 497.0 499.0 0 0
Limite (dB) 56.3 58.7 -19.7 -19.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 3,6 3,6 MHz MHz
RL (dB) 7.2 7.2 7.3 8.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 7.1 8.8 500.0 500.0 60 100
Limite (dB) 21.0 21.0 8.0 8.0 50 80
Conforme aux normes de réseaux: 40
60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 99
ID Câble: R.5 H1-J/13 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:04:19 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.4 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 65.1 65.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 281
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 6
Résistance (ohms) [Paire 3,6] 9.64
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 14.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 3,6-4,5 1,2-3,6 MHz


NEXT (dB) 10.4 12.9 10.5 12.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 471.0 481.0 500.0 481.0 100 100
Limite (dB) 27.5 27.2 26.7 27.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.1 12.5 10.6 12.6
Fréq. (MHz) 463.0 480.0 500.0 481.0 40 40

Limite (dB) 24.9 24.4 23.8 24.3 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.7 15.1 14.7 15.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 500.0 161.0 500.0 484.0 100 100
Limite (dB) 10.2 20.1 10.2 10.5 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.1 17.3 17.1 17.4
40 40
Fréq. (MHz) 500.0 474.0 500.0 484.0
Limite (dB) 7.2 7.7 7.2 7.5 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 3,6-4,5 1,2-3,6 MHz MHz
ACR-N (dB) 17.6 15.1 25.5 27.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.5 3.9 500.0 481.0
Limite (dB) 61.7 60.8 -17.1 -15.6 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.8 16.5 25.5 28.3
Fréq. (MHz) 3.5 3.9 500.0 497.0 0 0
Limite (dB) 58.7 58.5 -20.0 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 7,8 3,6 MHz MHz
RL (dB) 7.2 6.3 9.8 9.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 26.9 7.6 473.0 434.0 100 100
Limite (dB) 18.9 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 100
ID Câble: R.5 H1-J/14 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:08:58 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.3 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 67.7 67.7 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 292
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 6
Résistance (ohms) [Paire 4,5] 9.83
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 14.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 9.3 12.3 9.3 12.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 482.0 500.0 482.0 500.0 100 100
Limite (dB) 27.2 26.7 27.2 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.7 12.6 11.0 12.6
Fréq. (MHz) 482.0 500.0 500.0 500.0 40 40

Limite (dB) 24.3 23.8 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-1,2 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 12.3 12.7 12.4 12.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 480.0 480.0 481.0 481.0 100 100
Limite (dB) 10.6 10.6 10.5 10.5 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 14.7 15.5 14.9 15.7
40 40
Fréq. (MHz) 473.0 491.0 481.0 498.0
Limite (dB) 7.7 7.4 7.5 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 17.4 14.6 23.1 26.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.0 3.6 482.0 500.0
Limite (dB) 61.9 61.4 -15.6 -17.1 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 19.2 16.4 25.1 26.7
Fréq. (MHz) 4.6 3.8 500.0 500.0 0 0
Limite (dB) 57.0 58.6 -20.0 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 1,2 3,6 4,5 MHz MHz
RL (dB) 7.7 5.3 8.7 8.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 10.4 7.3 485.0 481.0 100 100
Limite (dB) 20.9 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 101
ID Câble: R.5 H1-J/15 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:06:59 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.3 dB (NEXT 3,6-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 63.2 63.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 273
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 6
Résistance (ohms) [Paire 3,6] 9.35
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 15.4 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-4,5 1,2-3,6 3,6-4,5 1,2-3,6 MHz


NEXT (dB) 9.3 12.8 9.5 13.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 460.0 426.0 500.0 496.0 100 100
Limite (dB) 27.8 29.0 26.7 26.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 9.3 13.2 9.3 13.5
Fréq. (MHz) 500.0 474.0 500.0 500.0 40 40

Limite (dB) 23.8 24.6 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.1 14.9 16.7 17.2
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 352.0 344.0 500.0 496.0 100 100
Limite (dB) 13.3 13.5 10.2 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.8 17.3 18.8 19.1
40 40
Fréq. (MHz) 352.0 344.0 500.0 484.0
Limite (dB) 10.3 10.5 7.2 7.5 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 3,6-4,5 1,2-3,6 MHz MHz
ACR-N (dB) 16.0 14.8 24.9 29.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.5 4.4 500.0 500.0
Limite (dB) 61.7 59.8 -17.1 -17.1 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 16.6 16.3 24.9 29.1
Fréq. (MHz) 3.6 4.0 500.0 500.0 0 0
Limite (dB) 58.6 58.3 -20.0 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 3,6 4,5 MHz MHz
RL (dB) 8.3 7.7 10.5 7.8 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 7.9 9.5 499.0 493.0 100 100
Limite (dB) 21.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 102
ID Câble: R.5 H1-J/16 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 20:11:53 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.3 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 67.5 67.5 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 291
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 6
Résistance (ohms) [Paire 4,5] 9.87
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 14.5 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 9.3 12.7 10.3 12.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 295.0 478.0 495.0 478.0 100 100
Limite (dB) 34.2 27.3 26.8 27.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.9 13.0 10.9 13.0
Fréq. (MHz) 479.0 489.0 479.0 489.0 40 40

Limite (dB) 24.4 24.1 24.4 24.1 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-1,2 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 14.2 14.4 14.5 14.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 478.0 477.0 496.0 497.0 100 100
Limite (dB) 10.6 10.6 10.3 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.5 17.2 16.6 17.3
40 40
Fréq. (MHz) 492.0 495.0 493.0 498.0
Limite (dB) 7.4 7.3 7.3 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-7,8 3,6-4,5 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 17.6 16.7 25.3 28.3 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.5 3.6 500.0 500.0
Limite (dB) 61.7 61.4 -17.1 -17.1 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.7 18.0 26.7 27.4
Fréq. (MHz) 3.6 3.6 500.0 489.0 0 0
Limite (dB) 58.6 58.6 -20.0 -19.1
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 3,6 3,6 4,5 MHz MHz
RL (dB) 6.2 7.1 6.2 8.8 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 500.0 8.8 500.0 494.0 100 100
Limite (dB) 8.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 103
ID Câble: R.5 H1-J/18 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:23:00 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.7 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 23.0 23.0 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 99
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 2
Résistance (ohms) [Paire 4,5] 3.50
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 32.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 9.7 11.4 9.8 11.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 446.0 461.0 492.0 461.0 100 100
Limite (dB) 28.3 27.8 26.9 27.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.5 12.3 10.5 12.3
Fréq. (MHz) 493.0 498.0 493.0 498.0 40 40

Limite (dB) 24.0 23.8 24.0 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.5 14.3 14.8 14.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 445.0 450.0 480.0 471.0 100 100
Limite (dB) 11.2 11.1 10.6 10.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.1 16.9 17.2 17.4
40 40
Fréq. (MHz) 444.0 453.0 480.0 497.0
Limite (dB) 8.2 8.1 7.6 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 16.4 17.0 42.4 45.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.1 5.1 492.0 498.0
Limite (dB) 60.3 58.4 -16.5 -16.9 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 16.7 16.9 43.1 45.0
Fréq. (MHz) 4.4 5.1 493.0 498.0 0 0
Limite (dB) 57.5 56.1 -19.4 -19.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 3,6 3,6 3,6 MHz MHz
RL (dB) 7.4 8.8 7.4 9.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 461.0 66.8 461.0 462.0 100 100
Limite (dB) 8.0 15.8 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 104
ID Câble: R.5 H1-J/19 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 18:26:01 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.3 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 23.4 23.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 101
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 2
Résistance (ohms) [Paire 4,5] 3.53
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 32.7 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 9.3 11.9 9.3 12.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 487.0 433.0 487.0 492.0 100 100
Limite (dB) 27.0 28.7 27.0 26.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 9.7 12.1 9.7 12.1
Fréq. (MHz) 487.0 492.0 487.0 492.0 40 40

Limite (dB) 24.2 24.0 24.2 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-1,2 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.8 14.2 13.9 14.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 453.0 453.0 454.0 500.0 100 100
Limite (dB) 11.1 11.1 11.0 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.4 16.8 17.3 17.0
40 40
Fréq. (MHz) 453.0 451.0 498.0 500.0
Limite (dB) 8.1 8.1 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 17.6 18.3 41.4 44.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.9 5.4 487.0 492.0
Limite (dB) 58.8 58.0 -16.1 -16.5 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.6 17.7 41.8 44.4
Fréq. (MHz) 4.0 5.1 487.0 492.0 0 0
Limite (dB) 58.3 56.1 -18.9 -19.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 3,6 4,5 3,6 MHz MHz
RL (dB) 8.7 9.3 8.7 9.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 436.0 415.0 436.0 415.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 105
ID Câble: R.5 H2-A/01 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:07:02 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.8 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 78.9 78.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 360
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 27
Résistance (ohms) [Paire 3,6] 11.33
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 12.2 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-4,5 4,5-7,8 MHz


NEXT (dB) 2.8 3.7 3.4 5.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 241.5 379.0 364.0 481.0 100 100
Limite (dB) 35.6 30.6 31.2 27.2 80 80
Pire paire 4,5 7,8 3,6 4,5
60 60
PS NEXT (dB) 4.4 5.9 8.4 8.3
Fréq. (MHz) 238.5 379.0 489.0 481.0 40 40

Limite (dB) 33.0 27.9 24.1 24.3 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.4 13.1 12.7 14.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 188.0 340.0 455.0 497.0 100 100
Limite (dB) 18.7 13.6 11.0 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.3 15.8 15.3 16.6
40 40
Fréq. (MHz) 451.0 340.0 451.0 497.0
Limite (dB) 8.1 10.6 8.1 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 3,6-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 10.7 13.5 20.0 19.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 43.8 3.6 489.0 481.0
Limite (dB) 36.0 61.4 -16.2 -15.6 80 80

Pire paire 4,5 3,6 3,6 4,5


40 40
PS ACR-N (dB) 12.7 14.2 20.5 20.8
Fréq. (MHz) 238.5 5.6 489.0 481.0 0 0
Limite (dB) 4.3 55.3 -19.1 -18.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 1,2 3,6 MHz MHz
RL (dB) 3.8 7.6 5.2 9.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 136.0 21.0 488.0 475.0 100 100
Limite (dB) 12.7 19.4 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 106
ID Câble: R.5 H2-A/02 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:07:37 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.4 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 78.9 78.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 360
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 27
Résistance (ohms) [Paire 3,6] 11.30
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 12.3 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 4.4 6.8 7.0 6.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 178.0 440.0 495.0 440.0 100 100
Limite (dB) 37.8 28.5 26.8 28.5 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 5.9 8.8 7.7 8.8
Fréq. (MHz) 177.5 440.0 495.0 440.0 40 40

Limite (dB) 35.2 25.7 23.9 25.7 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.1 13.4 13.9 14.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 149.0 261.0 448.0 490.0 100 100
Limite (dB) 20.7 15.9 11.2 10.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.8 16.3 16.4 16.7
40 40
Fréq. (MHz) 149.0 187.5 490.0 490.0
Limite (dB) 17.7 15.7 7.4 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 11.3 9.8 20.5 20.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 9.3 9.4 495.0 444.0
Limite (dB) 53.0 52.9 -16.7 -12.5 80 80

Pire paire 4,5 7,8 3,6 4,5


40 40
PS ACR-N (dB) 12.9 11.7 20.3 23.8
Fréq. (MHz) 9.3 9.3 498.0 486.0 0 0
Limite (dB) 50.7 50.7 -19.8 -18.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 3,6 3,6 MHz MHz
RL (dB) 4.8 5.5 4.8 9.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 466.0 5.9 466.0 480.0 100 100
Limite (dB) 8.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 107
ID Câble: R.5 H2-A/05 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:10:16 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.6 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 83.1 83.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 379
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 28
Résistance (ohms) [Paire 3,6] 11.94
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 10.5 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-4,5 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 4.6 6.6 6.9 7.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 163.0 300.0 494.0 499.0 100 100
Limite (dB) 38.4 34.0 26.8 26.7 80 80
Pire paire 4,5 4,5 3,6 4,5
60 60
PS NEXT (dB) 5.6 7.7 6.6 8.6
Fréq. (MHz) 237.5 249.5 493.0 499.0 40 40

Limite (dB) 33.1 32.7 24.0 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.5 13.0 14.9 14.5
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 390.0 394.0 469.0 466.0 100 100
Limite (dB) 12.4 12.3 10.8 10.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.0 15.6 17.1 17.1
40 40
Fréq. (MHz) 390.0 394.0 470.0 473.0
Limite (dB) 9.4 9.3 7.7 7.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-4,5 1,2-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 9.0 11.3 17.3 19.3 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 18.3 14.9 494.0 499.0
Limite (dB) 46.2 48.4 -16.6 -17.0 80 80

Pire paire 4,5 4,5 3,6 4,5


40 40
PS ACR-N (dB) 8.8 12.4 17.0 19.7
Fréq. (MHz) 18.4 14.8 493.0 499.0 0 0
Limite (dB) 43.8 46.1 -19.4 -19.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 4,5 MHz MHz
RL (dB) 2.4 4.1 3.3 9.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 92.3 7.3 341.0 499.0 100 100
Limite (dB) 14.4 21.0 8.7 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 108
ID Câble: R.5 H2-A/06 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:10:44 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.0 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 83.1 83.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 380
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 29
Résistance (ohms) [Paire 3,6] 11.91
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 10.6 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 5.0 4.0 7.7 4.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 286.0 272.0 495.0 399.0 100 100
Limite (dB) 34.4 34.7 26.8 29.9 80 80
Pire paire 4,5 4,5 3,6 4,5
60 60
PS NEXT (dB) 6.6 5.6 8.6 5.6
Fréq. (MHz) 271.0 403.0 495.0 403.0 40 40

Limite (dB) 32.1 27.0 23.9 27.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 13.4 13.9 14.0 15.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 427.0 178.5 499.0 499.0 100 100
Limite (dB) 11.6 19.2 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.1 16.0 16.1 17.1
40 40
Fréq. (MHz) 499.0 178.5 499.0 459.0
Limite (dB) 7.2 16.2 7.2 8.0 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 12.0 12.4 18.1 22.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 42.0 3.3 495.0 496.0
Limite (dB) 36.5 61.8 -16.7 -16.8 80 80

Pire paire 4,5 3,6 3,6 3,6


40 40
PS ACR-N (dB) 13.4 13.1 19.0 23.0
Fréq. (MHz) 61.0 4.3 495.0 496.0 0 0
Limite (dB) 29.0 57.7 -19.6 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 7,8 4,5 MHz MHz
RL (dB) 4.8 5.9 4.8 9.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 480.0 8.4 480.0 496.0 100 100
Limite (dB) 8.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 109
ID Câble: R.5 H2-A/07 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:13:04 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.6 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 81.0 81.0 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 369
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 27
Résistance (ohms) [Paire 3,6] 11.55
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 11.7 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-4,5 1,2-4,5 4,5-7,8 1,2-4,5 MHz


NEXT (dB) 3.6 6.0 5.9 7.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 285.0 389.0 478.0 427.0 100 100
Limite (dB) 34.4 30.3 27.3 28.9 80 80
Pire paire 4,5 4,5 4,5 3,6
60 60
PS NEXT (dB) 5.1 7.1 5.8 10.5
Fréq. (MHz) 233.5 389.0 452.0 500.0 40 40

Limite (dB) 33.2 27.5 25.3 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.3 13.6 13.3 14.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 441.0 365.0 441.0 478.0 100 100
Limite (dB) 11.3 12.9 11.3 10.6 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.9 16.1 16.5 17.3
40 40
Fréq. (MHz) 442.0 365.0 477.0 479.0
Limite (dB) 8.3 9.9 7.6 7.6 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-4,5 3,6-4,5 4,5-7,8 3,6-4,5 MHz MHz
ACR-N (dB) 10.0 10.7 18.5 23.1 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 8.1 5.0 478.0 500.0
Limite (dB) 54.3 58.6 -15.3 -17.1 80 80

Pire paire 4,5 4,5 4,5 3,6


40 40
PS ACR-N (dB) 9.5 9.6 20.4 22.2
Fréq. (MHz) 6.3 8.0 499.0 500.0 0 0
Limite (dB) 54.3 52.1 -19.9 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 4,5 3,6 MHz MHz
RL (dB) 2.8 5.7 4.2 10.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 72.5 7.4 437.0 488.0 100 100
Limite (dB) 15.4 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 110
ID Câble: R.5 H2-A/08 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:12:28 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.3 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 80.8 80.8 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 368
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 27
Résistance (ohms) [Paire 3,6] 11.62
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 11.8 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-3,6 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.3 6.2 5.1 7.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 392.0 303.0 491.0 500.0 100 100
Limite (dB) 30.2 33.9 26.9 26.7 80 80
Pire paire 1,2 3,6 7,8 4,5
60 60
PS NEXT (dB) 5.1 7.0 6.7 9.2
Fréq. (MHz) 280.0 303.0 489.0 499.0 40 40

Limite (dB) 31.9 31.3 24.1 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.4 13.0 13.3 14.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 328.0 293.0 444.0 479.0 100 100
Limite (dB) 13.9 14.9 11.2 10.6 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 14.8 14.9 16.0 15.9
40 40
Fréq. (MHz) 330.0 405.0 482.0 479.0
Limite (dB) 10.8 9.0 7.5 7.6 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 11.4 10.8 18.2 20.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 6.8 11.8 491.0 500.0
Limite (dB) 56.0 50.7 -16.4 -17.1 80 80

Pire paire 3,6 3,6 4,5 4,5


40 40
PS ACR-N (dB) 12.9 11.5 19.4 21.1
Fréq. (MHz) 11.5 11.6 491.0 499.0 0 0
Limite (dB) 48.6 48.5 -19.3 -19.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 7,8 3,6 MHz MHz
RL (dB) 3.2 5.9 3.2 9.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 262.0 7.3 262.0 491.0 100 100
Limite (dB) 9.8 21.0 9.8 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 111
ID Câble: R.5 H2-A/09 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:18:38 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.7 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 77.2 77.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 352
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 26
Résistance (ohms) [Paire 3,6] 11.08
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 13.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 4.1 2.7 6.2 2.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 64.5 458.0 458.0 458.0 100 100
Limite (dB) 44.9 27.9 27.9 27.9 80 80
Pire paire 1,2 7,8 4,5 7,8
60 60
PS NEXT (dB) 5.7 5.1 8.3 5.1
Fréq. (MHz) 293.0 458.0 481.0 458.0 40 40

Limite (dB) 31.6 25.1 24.3 25.1 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.0 13.6 14.0 14.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 463.0 350.0 463.0 428.0 100 100
Limite (dB) 10.9 13.3 10.9 11.6 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.8 16.1 16.8 16.2
40 40
Fréq. (MHz) 463.0 349.0 463.0 428.0
Limite (dB) 7.9 10.3 7.9 8.6 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 1,2-3,6 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 8.6 10.4 21.2 16.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 64.5 7.5 481.0 458.0
Limite (dB) 30.7 55.0 -15.6 -13.7 80 80

Pire paire 7,8 3,6 4,5 4,5


40 40
PS ACR-N (dB) 10.6 11.6 21.6 18.2
Fréq. (MHz) 4.9 7.5 481.0 458.0 0 0
Limite (dB) 56.6 52.7 -18.4 -16.5
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 7,8 4,5 MHz MHz
RL (dB) 4.5 5.4 6.0 8.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 6.6 7.5 436.0 447.0 100 100
Limite (dB) 21.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 112
ID Câble: R.5 H2-A/12 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:17:00 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.2 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 77.4 77.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 353
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 26
Résistance (ohms) [Paire 3,6] 11.12
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 12.7 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.2 6.7 5.8 8.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 241.5 417.0 448.0 476.0 100 100
Limite (dB) 35.6 29.3 28.2 27.4 80 80
Pire paire 7,8 7,8 4,5 4,5
60 60
PS NEXT (dB) 4.6 8.4 8.6 10.2
Fréq. (MHz) 241.5 417.0 489.0 477.0 40 40

Limite (dB) 33.0 26.5 24.1 24.5 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.0 13.4 13.7 13.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 421.0 462.0 496.0 499.0 100 100
Limite (dB) 11.7 10.9 10.3 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.7 15.7 16.1 15.7
40 40
Fréq. (MHz) 421.0 499.0 496.0 499.0
Limite (dB) 8.7 7.2 7.3 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 3,6-4,5 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 11.2 11.6 18.9 22.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 122.0 4.8 448.0 476.0
Limite (dB) 20.5 59.1 -12.8 -15.2 80 80

Pire paire 7,8 3,6 4,5 4,5


40 40
PS ACR-N (dB) 12.5 12.0 21.5 23.0
Fréq. (MHz) 122.0 7.5 489.0 477.0 0 0
Limite (dB) 17.9 52.7 -19.1 -18.1
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 3,6 MHz MHz
RL (dB) 5.8 4.8 5.8 9.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 452.0 6.3 452.0 499.0 60 100
Limite (dB) 8.0 21.0 8.0 8.0 50 80
Conforme aux normes de réseaux: 40
60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 113
ID Câble: R.5 H2-A/13 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:20:29 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.6 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 77.7 77.7 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 355
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 27
Résistance (ohms) [Paire 3,6] 11.19
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 12.6 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 1,2-3,6 MHz


NEXT (dB) 3.6 6.8 5.9 9.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 163.0 254.0 471.0 482.0 100 100
Limite (dB) 38.4 35.2 27.5 27.2 80 80
Pire paire 4,5 4,5 4,5 3,6
60 60
PS NEXT (dB) 5.9 8.3 6.5 10.5
Fréq. (MHz) 163.0 202.5 471.0 493.0 40 40

Limite (dB) 35.8 34.2 24.7 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.6 12.8 12.7 13.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 457.0 459.0 496.0 498.0 100 100
Limite (dB) 11.0 11.0 10.3 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 14.8 15.0 14.9 15.0
40 40
Fréq. (MHz) 497.0 459.0 498.0 459.0
Limite (dB) 7.3 8.0 7.2 8.0 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 1,2-3,6 4,5-7,8 1,2-3,6 MHz MHz
ACR-N (dB) 10.1 12.2 19.5 21.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 9.4 4.5 471.0 482.0
Limite (dB) 52.9 59.5 -14.7 -15.6 80 80

Pire paire 4,5 4,5 4,5 3,6


40 40
PS ACR-N (dB) 11.2 12.9 19.4 23.0
Fréq. (MHz) 9.3 6.9 471.0 493.0 0 0
Limite (dB) 50.7 53.5 -17.6 -19.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 7,8 3,6 7,8 MHz MHz
RL (dB) 4.1 6.0 8.4 9.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 6.3 34.3 450.0 489.0 100 100
Limite (dB) 21.0 18.3 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 114
ID Câble: R.5 H2-A/14 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:20:59 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 6.5 dB (NEXT 3,6-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 77.7 77.7 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 355
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 27
Résistance (ohms) [Paire 3,6] 11.15
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 12.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 6.5 7.3 7.8 7.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 216.0 457.0 489.0 457.0 100 100
Limite (dB) 36.4 27.9 27.0 27.9 80 80
Pire paire 7,8 4,5 3,6 7,8
60 60
PS NEXT (dB) 7.0 7.9 8.9 8.2
Fréq. (MHz) 196.0 411.0 487.0 469.0 40 40

Limite (dB) 34.5 26.7 24.2 24.7 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.1 12.8 13.1 12.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 500.0 456.0 500.0 456.0 100 100
Limite (dB) 10.2 11.0 10.2 11.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.4 15.5 15.4 16.1
40 40
Fréq. (MHz) 495.0 456.0 495.0 497.0
Limite (dB) 7.3 8.0 7.3 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-4,5 1,2-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 11.4 12.3 20.7 21.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 22.9 44.5 491.0 468.0
Limite (dB) 43.8 35.7 -16.4 -14.5 80 80

Pire paire 1,2 4,5 3,6 3,6


40 40
PS ACR-N (dB) 12.6 14.2 21.5 22.6
Fréq. (MHz) 23.0 44.8 487.0 497.0 0 0
Limite (dB) 41.3 33.2 -18.9 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 3,6 3,6 MHz MHz
RL (dB) 5.8 5.3 6.6 8.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 13.4 6.3 415.0 500.0 100 100
Limite (dB) 20.4 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 115
ID Câble: R.5 H2-A/15 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:19:29 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.0 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 77.7 77.7 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 354
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 26
Résistance (ohms) [Paire 3,6] 11.15
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 12.8 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.0 6.0 4.4 7.2
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 127.0 243.0 457.0 443.0 100 100
Limite (dB) 40.2 35.5 27.9 28.4 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 5.3 6.9 6.2 8.9
Fréq. (MHz) 260.0 348.0 457.0 453.0 40 40

Limite (dB) 32.4 29.2 25.1 25.2 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.5 13.3 12.5 13.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 457.0 457.0 457.0 457.0 100 100
Limite (dB) 11.0 11.0 11.0 11.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.0 15.4 15.0 15.4
40 40
Fréq. (MHz) 457.0 457.0 457.0 457.0
Limite (dB) 8.0 8.0 8.0 8.0 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 1,2-3,6 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 9.6 11.8 20.6 23.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 127.0 27.6 495.0 486.0
Limite (dB) 19.7 41.6 -16.7 -16.0 80 80

Pire paire 4,5 4,5 4,5 3,6


40 40
PS ACR-N (dB) 11.3 13.3 21.0 23.9
Fréq. (MHz) 127.0 19.6 495.0 496.0 0 0
Limite (dB) 17.2 43.1 -19.6 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 1,2 4,5 MHz MHz
RL (dB) 5.7 5.7 6.8 7.8 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 6.3 24.3 363.0 466.0 100 100
Limite (dB) 21.0 19.1 8.4 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 116
ID Câble: R.5 H2-A/16 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:19:57 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.6 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 77.7 77.7 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 355
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 27
Résistance (ohms) [Paire 3,6] 11.12
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 12.6 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-4,5 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 5.0 4.6 8.5 4.6
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 303.0 416.0 497.0 416.0 100 100
Limite (dB) 33.9 29.3 26.7 29.3 80 80
Pire paire 1,2 4,5 3,6 4,5
60 60
PS NEXT (dB) 6.7 5.7 9.1 5.7
Fréq. (MHz) 302.0 422.0 493.0 422.0 40 40

Limite (dB) 31.3 26.3 24.0 26.3 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.8 13.5 13.8 13.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 490.0 492.0 490.0 493.0 100 100
Limite (dB) 10.4 10.4 10.4 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.1 15.8 16.1 15.8
40 40
Fréq. (MHz) 492.0 495.0 492.0 495.0
Limite (dB) 7.4 7.3 7.4 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 11.2 11.1 21.9 21.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 27.4 27.8 500.0 493.0
Limite (dB) 41.7 41.6 -17.1 -16.5 80 80

Pire paire 4,5 3,6 3,6 4,5


40 40
PS ACR-N (dB) 11.6 11.7 21.5 23.1
Fréq. (MHz) 27.0 4.1 493.0 493.0 0 0
Limite (dB) 39.5 58.0 -19.4 -19.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 1,2 4,5 MHz MHz
RL (dB) 7.1 4.6 7.2 9.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 80.8 25.9 317.0 478.0 100 100
Limite (dB) 14.9 18.9 9.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 117
ID Câble: R.5 H2-A/17 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:22:31 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.2 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 68.9 68.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 314
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 23
Résistance (ohms) [Paire 3,6] 9.89
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 16.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 4.2 4.8 6.6 4.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 258.0 418.0 483.0 418.0 100 100
Limite (dB) 35.1 29.2 27.1 29.2 80 80
Pire paire 1,2 4,5 3,6 4,5
60 60
PS NEXT (dB) 6.3 6.2 8.8 6.2
Fréq. (MHz) 297.0 412.0 490.0 412.0 40 40

Limite (dB) 31.5 26.7 24.1 26.7 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.9 12.7 13.3 13.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 341.0 346.0 433.0 430.0 100 100
Limite (dB) 13.5 13.4 11.5 11.5 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.6 15.6 16.3 16.6
40 40
Fréq. (MHz) 341.0 346.0 475.0 472.0
Limite (dB) 10.5 10.4 7.7 7.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 8.4 12.9 22.0 24.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 17.5 3.6 483.0 495.0
Limite (dB) 46.7 61.4 -15.7 -16.7 80 80

Pire paire 3,6 4,5 3,6 4,5


40 40
PS ACR-N (dB) 10.4 12.9 24.8 25.4
Fréq. (MHz) 17.5 5.9 492.0 494.0 0 0
Limite (dB) 44.3 54.9 -19.3 -19.5
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 4,5 MHz MHz
RL (dB) 5.0 5.0 8.1 9.1 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 27.3 8.8 335.0 463.0 100 100
Limite (dB) 18.8 21.0 8.7 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 118
ID Câble: R.5 H2-A/18 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:23:10 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 5.3 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 68.9 68.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 314
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 23
Résistance (ohms) [Paire 3,6] 9.89
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 16.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-4,5 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 5.3 6.1 6.1 6.2
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 357.0 247.0 475.0 470.0 100 100
Limite (dB) 31.5 35.4 27.4 27.5 80 80
Pire paire 1,2 7,8 7,8 7,8
60 60
PS NEXT (dB) 7.2 7.8 7.8 7.8
Fréq. (MHz) 357.0 470.0 475.0 470.0 40 40

Limite (dB) 28.8 24.7 24.5 24.7 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.7 14.3 13.7 14.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 477.0 303.0 477.0 479.0 100 100
Limite (dB) 10.6 14.6 10.6 10.6 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.1 16.6 16.1 16.6
40 40
Fréq. (MHz) 477.0 470.0 477.0 470.0
Limite (dB) 7.6 7.7 7.6 7.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-7,8 1,2-3,6 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 13.1 13.5 25.2 23.0 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 6.8 19.5 500.0 470.0
Limite (dB) 56.0 45.5 -17.1 -14.7 80 80

Pire paire 1,2 1,2 4,5 3,6


40 40
PS ACR-N (dB) 14.7 14.0 26.0 25.6
Fréq. (MHz) 6.9 6.6 499.0 489.0 0 0
Limite (dB) 53.5 53.8 -19.9 -19.1
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 4,5 MHz MHz
RL (dB) 4.4 5.5 5.8 9.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 36.0 36.0 364.0 500.0 100 100
Limite (dB) 18.2 18.2 8.4 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 119
ID Câble: R.5 H2-A/20 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:22:01 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.9 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 68.9 68.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 315
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 24
Résistance (ohms) [Paire 3,6] 9.89
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 16.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.9 6.0 7.3 6.0
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 275.0 470.0 469.0 470.0 100 100
Limite (dB) 34.7 27.5 27.6 27.5 80 80
Pire paire 4,5 4,5 4,5 7,8
60 60
PS NEXT (dB) 6.2 7.6 8.8 7.6
Fréq. (MHz) 270.0 338.0 469.0 470.0 40 40

Limite (dB) 32.1 29.6 24.7 24.7 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 12.2 13.5 12.2 14.0
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 467.0 425.0 467.0 468.0 100 100
Limite (dB) 10.8 11.6 10.8 10.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 14.8 15.9 14.8 16.4
40 40
Fréq. (MHz) 467.0 213.5 467.0 468.0
Limite (dB) 7.8 14.6 7.8 7.8 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 14.4 15.0 26.0 22.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 5.1 5.3 494.0 470.0
Limite (dB) 58.4 58.2 -16.6 -14.7 80 80

Pire paire 1,2 1,2 3,6 4,5


40 40
PS ACR-N (dB) 14.6 15.0 26.3 25.7
Fréq. (MHz) 5.3 4.9 494.0 485.0 0 0
Limite (dB) 55.9 56.6 -19.5 -18.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 7,8 4,5 3,6 MHz MHz
RL (dB) 5.7 7.1 6.9 9.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 27.1 33.3 451.0 500.0 100 100
Limite (dB) 18.8 18.4 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 120
ID Câble: R.5 H2-A/21 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:23:59 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.5 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 66.8 66.8 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 305
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 23
Résistance (ohms) [Paire 3,6] 9.60
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 16.8 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 2.5 5.6 4.2 7.0
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 269.0 246.5 485.0 423.0 100 100
Limite (dB) 34.8 35.4 27.1 29.1 80 80
Pire paire 4,5 4,5 4,5 3,6
60 60
PS NEXT (dB) 4.6 7.7 5.8 9.9
Fréq. (MHz) 269.0 246.5 485.0 490.0 40 40

Limite (dB) 32.2 32.8 24.2 24.1 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.0 13.2 14.4 15.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 306.0 305.0 479.0 441.0 100 100
Limite (dB) 14.5 14.5 10.6 11.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.4 15.8 16.9 18.3
40 40
Fréq. (MHz) 306.0 257.0 482.0 489.0
Limite (dB) 11.5 13.0 7.5 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 1,2-3,6 MHz MHz
ACR-N (dB) 9.1 11.0 22.3 26.0 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 12.4 12.4 485.0 491.0
Limite (dB) 50.2 50.2 -15.9 -16.4 80 80

Pire paire 7,8 7,8 4,5 3,6


40 40
PS ACR-N (dB) 10.4 12.0 23.1 26.6
Fréq. (MHz) 12.3 12.4 485.0 491.0 0 0
Limite (dB) 48.0 47.9 -18.8 -19.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 7,8 1,2 3,6 MHz MHz
RL (dB) 4.5 6.2 4.5 9.1 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 352.0 27.6 352.0 474.0 100 100
Limite (dB) 8.5 18.8 8.5 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 121
ID Câble: R.5 H2-A/22 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:24:27 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 6.2 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 66.8 66.8 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 305
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 23
Résistance (ohms) [Paire 3,6] 9.57
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 16.8 40
Fréquence (MHz) [Paire 3,6] 497.0
30
Limite (dB) [Paire 3,6] 43.6
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 3,6-7,8 1,2-3,6 3,6-7,8 MHz


NEXT (dB) 6.2 6.6 6.8 10.6
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 339.0 244.0 481.0 492.0 100 100
Limite (dB) 32.2 35.5 27.2 26.9 80 80
Pire paire 7,8 7,8 3,6 3,6
60 60
PS NEXT (dB) 7.6 8.5 7.8 10.5
Fréq. (MHz) 301.0 240.5 481.0 491.0 40 40

Limite (dB) 31.4 33.0 24.3 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.2 13.2 13.3 14.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 218.5 395.0 484.0 492.0 100 100
Limite (dB) 17.4 12.3 10.5 10.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.6 15.7 15.7 16.7
40 40
Fréq. (MHz) 218.5 395.0 484.0 492.0
Limite (dB) 14.4 9.3 7.5 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 11.2 10.9 23.1 28.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 12.6 12.8 481.0 491.0
Limite (dB) 50.0 49.9 -15.6 -16.4 80 80

Pire paire 4,5 4,5 3,6 3,6


40 40
PS ACR-N (dB) 13.2 12.4 24.0 27.0
Fréq. (MHz) 12.6 12.8 481.0 491.0 0 0
Limite (dB) 47.7 47.6 -18.4 -19.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 1,2 3,6 1,2 MHz MHz
RL (dB) 5.3 7.1 5.3 9.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 492.0 19.4 492.0 494.0 100 100
Limite (dB) 8.0 19.6 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 122
ID Câble: R.5 H2-A/23 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:25:35 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.7 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 60.2 60.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 274
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 20
Résistance (ohms) [Paire 3,6] 8.63
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 19.5 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-4,5 4,5-7,8 1,2-4,5 MHz


NEXT (dB) 2.7 3.5 4.1 3.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 135.5 350.0 499.0 350.0 100 100
Limite (dB) 39.7 31.8 26.7 31.8 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 5.1 5.2 6.7 5.2
Fréq. (MHz) 348.0 350.0 499.0 350.0 40 40

Limite (dB) 29.2 29.1 23.8 29.1 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.0 13.1 14.7 13.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 347.0 393.0 500.0 497.0 100 100
Limite (dB) 13.4 12.3 10.2 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.2 15.3 16.7 16.1
40 40
Fréq. (MHz) 401.0 393.0 493.0 497.0
Limite (dB) 9.1 9.3 7.3 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 1,2-3,6 4,5-7,8 1,2-3,6 MHz MHz
ACR-N (dB) 12.5 12.6 24.9 27.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 110.5 9.9 499.0 486.0
Limite (dB) 22.2 52.4 -17.0 -16.0 80 80

Pire paire 1,2 1,2 4,5 3,6


40 40
PS ACR-N (dB) 13.3 13.6 26.8 30.7
Fréq. (MHz) 9.6 9.9 499.0 499.0 0 0
Limite (dB) 50.3 50.1 -19.9 -19.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 3,6 MHz MHz
RL (dB) 5.8 7.4 5.8 8.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 317.0 47.8 317.0 466.0 100 100
Limite (dB) 9.0 17.2 9.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 123
ID Câble: R.5 H2-A/24 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:25:03 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 5.6 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 59.9 59.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 274
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 21
Résistance (ohms) [Paire 3,6] 8.67
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 19.5 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 5.6 6.9 5.6 8.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 467.0 403.0 467.0 476.0 100 100
Limite (dB) 27.6 29.8 27.6 27.4 80 80
Pire paire 1,2 4,5 1,2 4,5
60 60
PS NEXT (dB) 6.6 8.1 7.4 10.1
Fréq. (MHz) 318.0 402.0 467.0 476.0 40 40

Limite (dB) 30.5 27.0 24.8 24.5 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.7 14.2 14.6 14.5
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 293.0 251.0 497.0 488.0 100 100
Limite (dB) 14.9 16.2 10.3 10.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.8 15.9 15.9 17.0
40 40
Fréq. (MHz) 291.0 252.0 500.0 488.0
Limite (dB) 11.9 13.2 7.2 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 13.9 15.0 24.3 28.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 22.0 29.4 467.0 476.0
Limite (dB) 44.2 40.9 -14.4 -15.2 80 80

Pire paire 1,2 1,2 3,6 3,6


40 40
PS ACR-N (dB) 14.6 16.0 28.9 31.3
Fréq. (MHz) 22.3 12.0 496.0 500.0 0 0
Limite (dB) 41.7 48.2 -19.7 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 1,2 3,6 MHz MHz
RL (dB) 5.3 6.6 6.2 9.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 288.0 33.3 396.0 489.0 100 100
Limite (dB) 9.4 18.4 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 124
ID Câble: R.5 H2-B/02 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:27:17 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.1 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 59.9 59.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 273
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 20
Résistance (ohms) [Paire 3,6] 8.63
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 19.4 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-3,6 4,5-7,8 1,2-3,6 MHz


NEXT (dB) 3.1 7.1 3.1 7.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 385.0 383.0 385.0 497.0 100 100
Limite (dB) 30.4 30.5 30.4 26.7 80 80
Pire paire 4,5 4,5 4,5 3,6
60 60
PS NEXT (dB) 3.5 9.1 3.5 9.5
Fréq. (MHz) 385.0 379.0 385.0 494.0 40 40

Limite (dB) 27.7 27.9 27.7 23.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.1 12.6 14.7 12.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 342.0 346.0 499.0 346.0 100 100
Limite (dB) 13.5 13.4 10.2 13.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 14.9 14.4 16.6 17.4
40 40
Fréq. (MHz) 341.0 346.0 489.0 489.0
Limite (dB) 10.5 10.4 7.4 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 12.5 14.2 27.9 27.0 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 19.8 2.8 500.0 497.0
Limite (dB) 45.4 62.0 -17.1 -16.9 80 80

Pire paire 4,5 4,5 4,5 3,6


40 40
PS ACR-N (dB) 13.6 14.1 29.3 29.1
Fréq. (MHz) 19.9 5.3 491.0 500.0 0 0
Limite (dB) 42.9 55.9 -19.3 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 4,5 7,8 4,5 MHz MHz
RL (dB) 5.2 7.4 5.2 8.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 448.0 39.3 448.0 484.0 100 100
Limite (dB) 8.0 18.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 125
ID Câble: R.5 H2-B/03 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:28:00 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.6 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 59.9 59.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 274
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 21
Résistance (ohms) [Paire 3,6] 8.63
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 19.4 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-4,5 4,5-7,8 1,2-4,5 4,5-7,8 MHz


NEXT (dB) 3.6 6.8 7.0 7.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 199.5 315.0 474.0 488.0 100 100
Limite (dB) 36.9 33.3 27.4 27.0 80 80
Pire paire 1,2 4,5 1,2 4,5
60 60
PS NEXT (dB) 5.8 8.5 6.4 9.0
Fréq. (MHz) 200.0 315.0 445.0 479.0 40 40

Limite (dB) 34.3 30.7 25.5 24.4 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.6 13.7 13.6 13.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 491.0 438.0 491.0 495.0 100 100
Limite (dB) 10.4 11.4 10.4 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.7 15.3 16.3 15.3
40 40
Fréq. (MHz) 443.0 440.0 490.0 440.0
Limite (dB) 8.3 8.3 7.4 8.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 3,6-4,5 1,2-4,5 4,5-7,8 MHz MHz
ACR-N (dB) 12.5 14.0 26.1 27.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 5.5 13.0 474.0 488.0
Limite (dB) 57.8 49.7 -15.0 -16.1 80 80

Pire paire 4,5 4,5 4,5 4,5


40 40
PS ACR-N (dB) 12.9 14.7 26.7 28.3
Fréq. (MHz) 9.1 13.1 474.0 480.0 0 0
Limite (dB) 50.8 47.3 -17.9 -18.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 3,6 MHz MHz
RL (dB) 2.7 5.0 4.6 9.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 91.3 19.8 461.0 470.0 100 100
Limite (dB) 14.4 19.5 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 126
ID Câble: R.5 H2-B/04 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:29:11 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.7 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 60.9 60.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 278
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 21
Résistance (ohms) [Paire 3,6] 8.78
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 18.4 40
Fréquence (MHz) [Paire 3,6] 489.0
30
Limite (dB) [Paire 3,6] 43.2
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-4,5 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 5.2 4.7 6.0 6.2
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 98.3 344.0 485.0 434.0 100 100
Limite (dB) 42.0 32.0 27.1 28.7 80 80
Pire paire 3,6 4,5 3,6 4,5
60 60
PS NEXT (dB) 7.4 6.3 8.1 7.8
Fréq. (MHz) 285.0 325.0 485.0 434.0 40 40

Limite (dB) 31.8 30.2 24.2 25.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.8 13.6 13.9 14.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 384.0 388.0 484.0 487.0 100 100
Limite (dB) 12.5 12.4 10.5 10.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.5 15.8 16.5 16.8
40 40
Fréq. (MHz) 383.0 380.0 484.0 487.0
Limite (dB) 9.5 9.6 7.5 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 12.6 13.4 24.3 27.0 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 41.8 41.5 485.0 458.0
Limite (dB) 36.6 36.6 -15.9 -13.7 80 80

Pire paire 4,5 4,5 3,6 4,5


40 40
PS ACR-N (dB) 13.7 14.3 26.4 25.9
Fréq. (MHz) 5.0 5.1 485.0 434.0 0 0
Limite (dB) 56.3 56.1 -18.8 -14.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 1,2 4,5 3,6 MHz MHz
RL (dB) 5.4 3.8 5.4 8.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 500.0 13.9 500.0 427.0 100 100
Limite (dB) 8.0 20.3 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 127
ID Câble: R.5 H2-B/05 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:30:06 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 5.6 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 60.9 60.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 278
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 21
Résistance (ohms) [Paire 3,6] 8.78
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 19.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-4,5 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 5.6 6.7 5.9 8.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 409.0 413.0 498.0 472.0 100 100
Limite (dB) 29.5 29.4 26.7 27.5 80 80
Pire paire 3,6 4,5 3,6 4,5
60 60
PS NEXT (dB) 7.0 8.2 7.0 10.0
Fréq. (MHz) 498.0 412.0 498.0 472.0 40 40

Limite (dB) 23.8 26.7 23.8 24.6 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.5 13.7 13.9 13.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 433.0 192.5 484.0 486.0 100 100
Limite (dB) 11.5 18.5 10.5 10.5 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.0 16.3 16.4 16.3
40 40
Fréq. (MHz) 433.0 490.0 484.0 490.0
Limite (dB) 8.5 7.4 7.5 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 15.1 13.4 24.7 28.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.6 5.1 498.0 472.0
Limite (dB) 59.3 58.4 -16.9 -14.8 80 80

Pire paire 3,6 4,5 3,6 4,5


40 40
PS ACR-N (dB) 15.1 13.7 25.8 31.0
Fréq. (MHz) 3.9 5.0 498.0 500.0 0 0
Limite (dB) 58.5 56.3 -19.8 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 4,5 MHz MHz
RL (dB) 5.8 6.3 5.8 8.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 499.0 13.6 499.0 498.0 100 100
Limite (dB) 8.0 20.3 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 128
ID Câble: R.5 H2-B/06 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:30:47 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 0.7 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 57.1 57.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 260
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 19
Résistance (ohms) [Paire 3,6] 8.27
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 20.5 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 0.7 * 5.1 5.9 7.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 276.0 298.0 483.0 459.0 100 100
Limite (dB) 34.6 34.1 27.1 27.9 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 2.9 6.6 7.4 9.2
Fréq. (MHz) 276.0 298.0 483.0 460.0 40 40

Limite (dB) 32.0 31.4 24.3 25.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.9 13.2 15.0 15.0
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 155.0 360.0 465.0 468.0 100 100
Limite (dB) 20.4 13.1 10.8 10.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.7 15.2 16.6 16.6
40 40
Fréq. (MHz) 155.0 360.0 465.0 468.0
Limite (dB) 17.4 10.1 7.8 7.8 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-4,5 1,2-3,6 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 11.0 12.6 27.0 31.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 9.9 8.1 483.0 498.0
Limite (dB) 52.4 54.3 -15.7 -16.9 80 80

Pire paire 1,2 4,5 4,5 3,6


40 40
PS ACR-N (dB) 11.6 13.3 28.0 32.2
Fréq. (MHz) 9.9 5.9 483.0 499.0 0 0
Limite (dB) 50.1 54.9 -18.6 -19.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 1,2 MHz MHz
RL (dB) 5.6 5.0 6.5 8.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 291.0 12.6 408.0 473.0 100 100
Limite (dB) 9.4 20.5 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

* La marge est dans les limites de précision de l'instrument.

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 129
ID Câble: R.5 H2-B/07 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:31:21 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 5.1 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 57.1 57.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 260
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 19
Résistance (ohms) [Paire 3,6] 8.20
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 20.5 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 3,6-7,8 1,2-4,5 1,2-3,6 MHz


NEXT (dB) 5.1 5.2 8.4 7.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 284.0 206.0 493.0 412.0 100 100
Limite (dB) 34.4 36.7 26.9 29.4 80 80
Pire paire 7,8 3,6 3,6 4,5
60 60
PS NEXT (dB) 6.7 7.4 8.1 10.7
Fréq. (MHz) 296.0 205.5 500.0 498.0 40 40

Limite (dB) 31.5 34.1 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.0 13.6 14.5 14.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 357.0 359.0 462.0 463.0 100 100
Limite (dB) 13.1 13.1 10.9 10.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.8 16.1 17.0 16.7
40 40
Fréq. (MHz) 359.0 359.0 500.0 457.0
Limite (dB) 10.1 10.1 7.2 8.0 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 13.0 12.9 29.1 31.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.6 7.9 498.0 497.0
Limite (dB) 61.4 54.6 -16.9 -16.9 80 80

Pire paire 3,6 4,5 3,6 4,5


40 40
PS ACR-N (dB) 13.6 13.2 28.6 31.5
Fréq. (MHz) 9.6 4.0 500.0 498.0 0 0
Limite (dB) 50.3 58.3 -20.0 -19.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 4,5 MHz MHz
RL (dB) 4.7 7.1 4.7 10.1 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 254.0 12.4 254.0 402.0 100 100
Limite (dB) 10.0 20.5 10.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 130
ID Câble: R.5 H2-B/08 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:32:06 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.7 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 57.1 57.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 259
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 18
Résistance (ohms) [Paire 3,6] 8.13
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 20.9 40
Fréquence (MHz) [Paire 3,6] 495.0
30
Limite (dB) [Paire 3,6] 43.5
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 3.7 6.7 7.1 7.0
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 361.0 318.0 493.0 474.0 100 100
Limite (dB) 31.3 33.2 26.9 27.4 80 80
Pire paire 4,5 7,8 3,6 4,5
60 60
PS NEXT (dB) 5.6 8.0 7.6 8.6
Fréq. (MHz) 361.0 226.5 491.0 474.0 40 40

Limite (dB) 28.6 33.4 24.0 24.6 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.3 13.7 14.8 13.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 222.0 444.0 451.0 444.0 100 100
Limite (dB) 17.3 11.2 11.1 11.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.5 16.4 16.5 16.5
40 40
Fréq. (MHz) 451.0 446.0 451.0 450.0
Limite (dB) 8.1 8.2 8.1 8.1 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 12.6 11.9 27.9 28.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 9.4 9.6 493.0 474.0
Limite (dB) 52.9 52.7 -16.5 -15.0 80 80

Pire paire 7,8 4,5 3,6 4,5


40 40
PS ACR-N (dB) 12.5 13.0 28.4 29.7
Fréq. (MHz) 10.0 23.5 491.0 474.0 0 0
Limite (dB) 50.0 41.1 -19.3 -17.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 1,2 MHz MHz
RL (dB) 3.1 6.0 3.1 6.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 391.0 429.0 391.0 429.0 100 100
Limite (dB) 8.1 8.0 8.1 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 131
ID Câble: R.5 H2-B/09 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:32:28 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.5 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 57.3 57.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 260
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 18
Résistance (ohms) [Paire 3,6] 8.20
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 20.8 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 3,6-7,8 4,5-7,8 1,2-3,6 MHz


NEXT (dB) 3.5 3.9 4.5 7.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 142.0 68.8 483.0 498.0 100 100
Limite (dB) 39.4 44.5 27.1 26.7 80 80
Pire paire 7,8 7,8 4,5 3,6
60 60
PS NEXT (dB) 4.0 4.3 6.5 9.0
Fréq. (MHz) 142.5 68.8 483.0 498.0 40 40

Limite (dB) 36.8 42.0 24.3 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.2 13.7 15.3 14.0
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 389.0 276.0 496.0 452.0 100 100
Limite (dB) 12.4 15.4 10.3 11.1 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.4 15.8 15.8 16.3
40 40
Fréq. (MHz) 390.0 278.0 441.0 453.0
Limite (dB) 9.4 12.3 8.3 8.1 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 3,6-7,8 4,5-7,8 1,2-3,6 MHz MHz
ACR-N (dB) 11.4 10.9 26.1 28.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 13.6 60.0 483.0 498.0
Limite (dB) 49.3 31.7 -15.7 -16.9 80 80

Pire paire 7,8 7,8 4,5 3,6


40 40
PS ACR-N (dB) 12.2 11.6 27.5 29.7
Fréq. (MHz) 23.9 68.5 483.0 498.0 0 0
Limite (dB) 40.9 27.3 -18.6 -19.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 4,5 MHz MHz
RL (dB) 4.5 5.4 4.5 8.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 449.0 44.0 449.0 376.0 100 100
Limite (dB) 8.0 17.6 8.0 8.2 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 132
ID Câble: R.5 H2-B/10 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:35:52 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.4 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 53.1 53.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 243
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 19
Résistance (ohms) [Paire 3,6] 7.73
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 22.2 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 4.4 5.2 8.1 6.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 368.0 317.0 482.0 476.0 100 100
Limite (dB) 31.1 33.2 27.2 27.4 80 80
Pire paire 4,5 4,5 3,6 4,5
60 60
PS NEXT (dB) 5.6 6.5 9.2 7.9
Fréq. (MHz) 368.0 317.0 482.0 477.0 40 40

Limite (dB) 28.3 30.6 24.3 24.5 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.5 14.3 13.5 14.4
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 385.0 487.0 385.0 496.0 100 100
Limite (dB) 12.5 10.4 12.5 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.6 16.4 15.6 17.2
40 40
Fréq. (MHz) 385.0 438.0 385.0 496.0
Limite (dB) 9.5 8.4 9.5 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 1,2-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 14.1 13.0 29.5 29.9 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 38.8 21.9 482.0 476.0
Limite (dB) 37.5 44.3 -15.6 -15.2 80 80

Pire paire 3,6 4,5 3,6 4,5


40 40
PS ACR-N (dB) 15.1 13.7 30.6 30.1
Fréq. (MHz) 4.0 14.8 482.0 477.0 0 0
Limite (dB) 58.3 46.1 -18.5 -18.1
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 3,6 1,2 MHz MHz
RL (dB) 3.3 5.8 8.3 9.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 30.4 30.5 433.0 429.0 100 100
Limite (dB) 18.6 18.6 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 133
ID Câble: R.5 H2-B/11 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:36:27 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 6.1 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 53.3 53.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 243
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 18
Résistance (ohms) [Paire 3,6] 7.66
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 22.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-4,5 3,6-7,8 4,5-7,8 MHz


NEXT (dB) 6.1 7.4 7.7 8.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 354.0 416.0 478.0 453.0 100 100
Limite (dB) 31.6 29.3 27.3 28.1 80 80
Pire paire 7,8 4,5 7,8 4,5
60 60
PS NEXT (dB) 7.6 9.0 9.1 9.4
Fréq. (MHz) 362.0 442.0 478.0 453.0 40 40

Limite (dB) 28.6 25.6 24.4 25.2 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.9 14.9 15.8 15.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 55.8 387.0 448.0 498.0 100 100
Limite (dB) 29.3 12.4 11.2 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.0 16.6 17.4 17.2
40 40
Fréq. (MHz) 278.0 281.0 446.0 496.0
Limite (dB) 12.3 12.2 8.2 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 14.9 15.5 31.4 30.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 6.5 6.9 492.0 453.0
Limite (dB) 56.3 55.8 -16.5 -13.2 80 80

Pire paire 3,6 4,5 3,6 3,6


40 40
PS ACR-N (dB) 16.3 15.5 31.6 32.7
Fréq. (MHz) 6.5 5.6 492.0 491.0 0 0
Limite (dB) 54.0 55.3 -19.3 -19.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 7,8 4,5 MHz MHz
RL (dB) 5.7 4.7 8.6 9.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 24.1 13.5 488.0 494.0 100 100
Limite (dB) 19.1 20.3 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 134
ID Câble: R.5 H2-B/12 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:38:08 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.7 dB (NEXT 3,6-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 50.0 50.0 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 227
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 16
Résistance (ohms) [Paire 3,6] 7.19
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 23.7 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-7,8 3,6-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 2.7 5.3 7.6 5.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 56.8 56.8 499.0 474.0 100 100
Limite (dB) 45.8 45.8 26.7 27.4 80 80
Pire paire 7,8 3,6 3,6 4,5
60 60
PS NEXT (dB) 4.8 6.5 6.3 7.4
Fréq. (MHz) 56.8 56.8 451.0 475.0 40 40

Limite (dB) 43.3 43.3 25.3 24.5 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-1,2 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 13.0 14.1 13.0 14.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 453.0 453.0 453.0 453.0 100 100
Limite (dB) 11.1 11.1 11.1 11.1 80 80
Pire paire 3,6 3,6 3,6 1,2
60 60
PS ACR-F (dB) 15.7 16.5 15.7 16.9
40 40
Fréq. (MHz) 453.0 383.0 453.0 453.0
Limite (dB) 8.1 9.5 8.1 8.1 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 1,2-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 10.1 11.1 31.5 29.9 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 56.8 3.5 498.0 481.0
Limite (dB) 32.5 61.7 -16.9 -15.6 80 80

Pire paire 4,5 4,5 3,6 4,5


40 40
PS ACR-N (dB) 11.1 11.2 31.5 30.7
Fréq. (MHz) 3.9 3.9 498.0 475.0 0 0
Limite (dB) 58.5 58.5 -19.8 -17.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 1,2 MHz MHz
RL (dB) 4.3 5.6 4.3 7.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 274.0 41.0 274.0 454.0 60 100
Limite (dB) 9.6 17.9 9.6 8.0 50 80
Conforme aux normes de réseaux: 40
60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 135
ID Câble: R.5 H2-B/13 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:37:30 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.7 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 51.4 51.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 234
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 17
Résistance (ohms) [Paire 3,6] 7.37
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 22.4 40
Fréquence (MHz) [Paire 3,6] 489.0
30
Limite (dB) [Paire 3,6] 43.2
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.7 5.3 5.8 6.6
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 165.0 286.0 406.0 491.0 100 100
Limite (dB) 38.3 34.4 29.6 26.9 80 80
Pire paire 4,5 4,5 3,6 4,5
60 60
PS NEXT (dB) 5.4 7.4 8.1 9.2
Fréq. (MHz) 339.0 286.0 471.0 491.0 40 40

Limite (dB) 29.6 31.7 24.7 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.2 13.2 14.3 13.2
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 497.0 500.0 500.0 500.0 100 100
Limite (dB) 10.3 10.2 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.9 15.7 16.5 15.8
40 40
Fréq. (MHz) 310.0 487.0 500.0 500.0
Limite (dB) 11.4 7.4 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 3,6-7,8 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 10.7 11.1 28.7 30.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.8 8.4 444.0 491.0
Limite (dB) 59.1 54.0 -12.5 -16.4 80 80

Pire paire 3,6 3,6 3,6 4,5


40 40
PS ACR-N (dB) 10.4 10.5 30.6 32.5
Fréq. (MHz) 4.8 4.9 471.0 491.0 0 0
Limite (dB) 56.8 56.6 -17.6 -19.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 4,5 1,2 1,2 MHz MHz
RL (dB) 5.8 6.8 7.0 7.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 61.3 46.5 411.0 411.0 100 100
Limite (dB) 16.1 17.3 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 136
ID Câble: R.5 H2-B/14 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:34:52 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.7 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 50.4 50.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 230
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 17
Résistance (ohms) [Paire 3,6] 7.34
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 23.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.7 4.3 4.0 4.6
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 273.0 390.0 427.0 495.0 100 100
Limite (dB) 34.7 30.2 28.9 26.8 80 80
Pire paire 4,5 4,5 7,8 7,8
60 60
PS NEXT (dB) 5.6 5.6 5.9 6.8
Fréq. (MHz) 273.0 390.0 427.0 495.0 40 40

Limite (dB) 32.1 27.5 26.1 23.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 11.9 12.8 12.9 13.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 349.0 347.0 463.0 466.0 100 100
Limite (dB) 13.3 13.4 10.9 10.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 14.7 15.4 15.4 16.4
40 40
Fréq. (MHz) 349.0 406.0 463.0 466.0
Limite (dB) 10.3 9.0 7.9 7.8 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 13.3 13.2 30.8 28.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 46.0 7.9 484.0 495.0
Limite (dB) 35.3 54.6 -15.8 -16.7 80 80

Pire paire 4,5 3,6 4,5 4,5


40 40
PS ACR-N (dB) 15.1 14.2 32.3 30.6
Fréq. (MHz) 46.0 8.4 497.0 500.0 0 0
Limite (dB) 32.8 51.7 -19.7 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 3,6 4,5 MHz MHz
RL (dB) 6.9 5.0 8.3 8.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 15.4 21.1 495.0 470.0 100 100
Limite (dB) 20.1 19.4 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 137
ID Câble: R.5 H2-B/15 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:33:22 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 1.7 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 48.8 48.8 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 223
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 17
Résistance (ohms) [Paire 3,6] 7.08
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 23.6 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 3,6-7,8 4,5-7,8 3,6-7,8 MHz


NEXT (dB) 1.7 7.6 7.1 9.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 231.5 178.0 490.0 473.0 100 100
Limite (dB) 35.9 37.8 26.9 27.4 80 80
Pire paire 7,8 4,5 4,5 3,6
60 60
PS NEXT (dB) 3.3 8.9 9.0 9.7
Fréq. (MHz) 218.5 70.5 490.0 473.0 40 40

Limite (dB) 33.7 41.8 24.1 24.6 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.7 14.1 13.7 14.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 491.0 489.0 491.0 489.0 100 100
Limite (dB) 10.4 10.4 10.4 10.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.3 16.4 16.3 16.4
40 40
Fréq. (MHz) 491.0 489.0 491.0 489.0
Limite (dB) 7.4 7.4 7.4 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 14.7 13.3 31.4 34.9 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.5 16.3 490.0 498.0
Limite (dB) 61.7 47.5 -16.3 -16.9 80 80

Pire paire 4,5 4,5 4,5 4,5


40 40
PS ACR-N (dB) 13.7 14.1 32.9 34.5
Fréq. (MHz) 5.8 11.3 490.0 497.0 0 0
Limite (dB) 55.1 48.8 -19.2 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 7,8 4,5 MHz MHz
RL (dB) 6.4 9.4 6.4 9.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 444.0 21.6 444.0 419.0 100 100
Limite (dB) 8.0 19.3 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 138
ID Câble: R.5 H2-B/16 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:38:34 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.8 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 41.9 41.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 192
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 15
Résistance (ohms) [Paire 3,6] 6.15
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 26.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 5.7 3.8 7.1 6.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 211.0 230.0 493.0 448.0 100 100
Limite (dB) 36.5 35.9 26.9 28.2 80 80
Pire paire 1,2 4,5 1,2 4,5
60 60
PS NEXT (dB) 5.7 6.0 8.6 8.9
Fréq. (MHz) 217.5 230.0 493.0 448.0 40 40

Limite (dB) 33.7 33.3 24.0 25.4 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.8 14.7 13.8 14.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 417.0 344.0 417.0 496.0 100 100
Limite (dB) 11.8 13.5 11.8 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.2 16.7 16.2 16.8
40 40
Fréq. (MHz) 417.0 350.0 417.0 495.0
Limite (dB) 8.8 10.3 8.8 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 11.3 14.0 32.9 32.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 10.5 10.4 493.0 448.0
Limite (dB) 51.8 52.0 -16.5 -12.8 80 80

Pire paire 7,8 4,5 3,6 4,5


40 40
PS ACR-N (dB) 12.7 15.0 34.2 33.8
Fréq. (MHz) 10.6 10.5 487.0 448.0 0 0
Limite (dB) 49.4 49.5 -18.9 -15.6
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 3,6 3,6 MHz MHz
RL (dB) 5.7 6.7 7.2 9.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 45.8 23.0 433.0 393.0 100 100
Limite (dB) 17.4 19.2 8.0 8.1 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 139
ID Câble: R.5 H2-B/17 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:36:58 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.2 dB (NEXT 3,6-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 42.2 42.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 192
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 14
Résistance (ohms) [Paire 3,6] 6.04
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 26.3 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-7,8 3,6-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 4.2 5.7 7.9 5.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 20.9 20.9 444.0 415.0 100 100
Limite (dB) 52.8 52.8 28.4 29.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 6.4 7.2 9.1 9.9
Fréq. (MHz) 21.0 21.1 500.0 490.0 40 40

Limite (dB) 50.3 50.3 23.8 24.1 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 15.0 15.6 16.2 17.5
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 140.0 138.5 494.0 494.0 100 100
Limite (dB) 21.3 21.4 10.3 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.5 18.1 18.6 19.3
40 40
Fréq. (MHz) 417.0 281.0 494.0 490.0
Limite (dB) 8.8 12.2 7.3 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 3,6-7,8 3,6-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 9.2 10.7 36.5 30.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 20.9 20.9 494.0 416.0
Limite (dB) 44.8 44.8 -16.6 -10.0 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 11.2 12.0 35.4 35.9
Fréq. (MHz) 21.0 20.9 500.0 490.0 0 0
Limite (dB) 42.3 42.4 -20.0 -19.2
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 4,5 MHz MHz
RL (dB) 7.1 8.1 9.1 9.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 44.0 57.3 500.0 419.0 100 100
Limite (dB) 17.6 16.4 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 140
ID Câble: R.5 H2-B/18 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:39:19 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.2 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 51.9 51.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 235
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 16
Résistance (ohms) [Paire 3,6] 7.41
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 23.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-3,6 4,5-7,8 1,2-3,6 MHz


NEXT (dB) 2.2 6.4 6.3 8.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 281.0 310.0 482.0 476.0 100 100
Limite (dB) 34.5 33.5 27.2 27.4 80 80
Pire paire 4,5 1,2 4,5 3,6
60 60
PS NEXT (dB) 4.1 8.3 7.6 9.7
Fréq. (MHz) 281.0 311.0 482.0 480.0 40 40

Limite (dB) 31.9 30.9 24.3 24.4 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 13.3 13.8 13.3 14.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 489.0 357.0 489.0 490.0 100 100
Limite (dB) 10.4 13.1 10.4 10.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.1 15.8 15.2 15.8
40 40
Fréq. (MHz) 481.0 479.0 489.0 479.0
Limite (dB) 7.5 7.6 7.4 7.6 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 3,6-7,8 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 11.9 12.2 29.2 30.9 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 14.0 20.6 489.0 476.0
Limite (dB) 49.0 44.9 -16.2 -15.2 80 80

Pire paire 7,8 7,8 4,5 3,6


40 40
PS ACR-N (dB) 11.3 12.2 30.3 32.0
Fréq. (MHz) 13.9 13.9 482.0 480.0 0 0
Limite (dB) 46.7 46.7 -18.5 -18.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 1,2 MHz MHz
RL (dB) 6.0 5.5 6.0 5.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 435.0 428.0 435.0 428.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 141
ID Câble: R.5 H2-B/19 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:29:10 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.9 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 37.9 37.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 172
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 12
Résistance (ohms) [Paire 3,6] 5.50
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 28.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 4.2 3.9 5.4 3.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 258.0 416.0 437.0 416.0 100 100
Limite (dB) 35.1 29.3 28.6 29.3 80 80
Pire paire 7,8 7,8 4,5 7,8
60 60
PS NEXT (dB) 5.6 6.1 7.1 8.3
Fréq. (MHz) 258.0 417.0 454.0 485.0 40 40

Limite (dB) 32.5 26.5 25.2 24.2 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.0 13.7 14.1 14.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 334.0 412.0 495.0 488.0 100 100
Limite (dB) 13.7 11.9 10.3 10.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.5 16.1 15.5 16.8
40 40
Fréq. (MHz) 495.0 412.0 495.0 489.0
Limite (dB) 7.3 8.9 7.3 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 3,6-7,8 3,6-4,5 4,5-7,8 MHz MHz
ACR-N (dB) 12.0 11.8 35.2 30.1 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 22.1 3.3 477.0 416.0
Limite (dB) 44.1 61.8 -15.2 -10.0 80 80

Pire paire 7,8 3,6 4,5 7,8


40 40
PS ACR-N (dB) 12.9 13.0 33.9 36.7
Fréq. (MHz) 28.8 3.6 454.0 485.0 0 0
Limite (dB) 38.7 58.6 -16.2 -18.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 1,2 3,6 1,2 MHz MHz
RL (dB) 5.1 6.7 5.1 6.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 482.0 411.0 482.0 411.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 142
ID Câble: R.5 H2-B/20 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:32:27 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.4 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 37.9 37.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 172
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 12
Résistance (ohms) [Paire 3,6] 5.47
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 28.3 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-4,5 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.4 4.5 3.4 6.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 394.0 404.0 394.0 496.0 100 100
Limite (dB) 30.1 29.7 30.1 26.8 80 80
Pire paire 4,5 4,5 1,2 4,5
60 60
PS NEXT (dB) 5.5 6.4 7.2 8.7
Fréq. (MHz) 296.0 295.0 475.0 497.0 40 40

Limite (dB) 31.5 31.5 24.5 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.7 14.4 14.0 14.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 329.0 414.0 489.0 498.0 100 100
Limite (dB) 13.8 11.8 10.4 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.0 16.3 16.0 16.3
40 40
Fréq. (MHz) 496.0 498.0 496.0 498.0
Limite (dB) 7.3 7.2 7.3 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-4,5 1,2-4,5 1,2-4,5 4,5-7,8 MHz MHz
ACR-N (dB) 10.9 11.5 34.5 35.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 13.8 13.8 476.0 496.0
Limite (dB) 49.2 49.2 -15.2 -16.8 80 80

Pire paire 4,5 4,5 4,5 4,5


40 40
PS ACR-N (dB) 12.5 13.5 37.1 37.3
Fréq. (MHz) 29.6 13.9 496.0 497.0 0 0
Limite (dB) 38.4 46.7 -19.7 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 1,2 MHz MHz
RL (dB) 4.8 6.8 5.0 7.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 224.5 31.5 443.0 409.0 100 100
Limite (dB) 10.5 18.5 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 143
ID Câble: R.5 H2-B/21 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:33:03 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.2 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 31.3 31.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 143
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 11
Résistance (ohms) [Paire 3,6] 4.60
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 30.4 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 2.2 5.2 2.2 8.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 443.0 363.0 443.0 484.0 100 100
Limite (dB) 28.4 31.3 28.4 27.1 80 80
Pire paire 7,8 4,5 7,8 7,8
60 60
PS NEXT (dB) 4.4 6.7 4.4 9.3
Fréq. (MHz) 443.0 309.0 443.0 484.0 40 40

Limite (dB) 25.6 31.0 25.6 24.2 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.5 14.7 14.8 15.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 283.0 93.5 471.0 471.0 100 100
Limite (dB) 15.2 24.8 10.7 10.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.6 16.8 16.9 16.9
40 40
Fréq. (MHz) 1.3 1.6 470.0 471.0
Limite (dB) 59.3 57.0 7.7 7.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 14.1 16.5 31.4 38.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 16.0 16.9 443.0 484.0
Limite (dB) 47.6 47.1 -12.4 -15.8 80 80

Pire paire 4,5 1,2 4,5 7,8


40 40
PS ACR-N (dB) 16.0 17.1 33.9 39.8
Fréq. (MHz) 16.0 7.0 450.0 484.0 0 0
Limite (dB) 45.2 53.3 -15.8 -18.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 7,8 7,8 3,6 MHz MHz
RL (dB) 6.1 7.8 6.1 9.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 481.0 55.5 481.0 458.0 100 100
Limite (dB) 8.0 16.6 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 144
ID Câble: R.5 H2-B/22 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:33:29 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 6.5 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 31.3 31.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 143
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 11
Résistance (ohms) [Paire 3,6] 4.53
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 30.2 40
Fréquence (MHz) [Paire 3,6] 498.0
30
Limite (dB) [Paire 3,6] 43.6
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 6.6 6.5 8.0 6.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 139.5 391.0 486.0 391.0 100 100
Limite (dB) 39.5 30.2 27.1 30.2 80 80
Pire paire 3,6 7,8 3,6 7,8
60 60
PS NEXT (dB) 8.4 7.6 8.4 7.6
Fréq. (MHz) 479.0 391.0 479.0 391.0 40 40

Limite (dB) 24.4 27.4 24.4 27.4 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 15.6 16.0 15.8 16.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 377.0 459.0 464.0 461.0 100 100
Limite (dB) 12.7 11.0 10.9 10.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.6 17.2 17.7 17.2
40 40
Fréq. (MHz) 464.0 479.0 469.0 479.0
Limite (dB) 7.9 7.6 7.8 7.6 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 14.9 14.9 37.8 41.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 16.4 12.1 486.0 497.0
Limite (dB) 47.4 50.4 -16.0 -16.9 80 80

Pire paire 1,2 3,6 3,6 4,5


40 40
PS ACR-N (dB) 16.7 15.0 38.0 41.9
Fréq. (MHz) 16.3 8.0 479.0 498.0 0 0
Limite (dB) 45.1 52.1 -18.3 -19.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 4,5 MHz MHz
RL (dB) 4.9 8.1 7.4 8.8 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 84.0 123.5 446.0 483.0 60 100
Limite (dB) 14.8 13.1 8.0 8.0 50 80
Conforme aux normes de réseaux: 40
60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 145
ID Câble: R.5 H2-B/23 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:34:13 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.3 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 40.0 40.0 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 182
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 13
Résistance (ohms) [Paire 3,6] 5.75
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 27.1 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 4.3 5.7 6.7 6.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 79.0 167.5 479.0 476.0 100 100
Limite (dB) 43.5 38.2 27.3 27.4 80 80
Pire paire 4,5 4,5 3,6 4,5
60 60
PS NEXT (dB) 6.5 7.2 8.4 8.8
Fréq. (MHz) 79.3 203.5 499.0 476.0 40 40

Limite (dB) 41.0 34.2 23.8 24.5 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.4 13.0 14.4 13.0
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 404.0 403.0 486.0 403.0 100 100
Limite (dB) 12.1 12.1 10.5 12.1 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.3 15.1 16.5 16.5
40 40
Fréq. (MHz) 404.0 402.0 473.0 471.0
Limite (dB) 9.1 9.1 7.7 7.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 11.2 13.4 33.3 34.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 5.8 5.8 479.0 476.0
Limite (dB) 57.4 57.4 -15.4 -15.2 80 80

Pire paire 4,5 4,5 3,6 4,5


40 40
PS ACR-N (dB) 12.5 13.8 35.7 35.8
Fréq. (MHz) 5.5 5.8 499.0 476.0 0 0
Limite (dB) 55.5 55.1 -19.9 -18.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 1,2 MHz MHz
RL (dB) 4.8 7.0 5.0 7.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 115.0 47.8 409.0 411.0 100 100
Limite (dB) 13.4 17.2 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 146
ID Câble: R.5 H2-B/24 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:34:39 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.0 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 39.8 39.8 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 181
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 13
Résistance (ohms) [Paire 3,6] 5.75
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 26.8 40
Fréquence (MHz) [Paire 3,6] 491.0
30
Limite (dB) [Paire 3,6] 43.3
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-4,5 3,6-4,5 1,2-4,5 MHz


NEXT (dB) 3.0 5.4 7.6 5.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 299.0 408.0 461.0 409.0 100 100
Limite (dB) 34.1 29.6 27.8 29.5 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 4.8 6.8 6.8 9.4
Fréq. (MHz) 299.0 407.0 429.0 495.0 40 40

Limite (dB) 31.4 26.8 26.1 23.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.4 13.9 14.8 15.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 311.0 231.0 472.0 471.0 100 100
Limite (dB) 14.3 16.9 10.7 10.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.2 15.8 16.5 15.8
40 40
Fréq. (MHz) 315.0 469.0 470.0 469.0
Limite (dB) 11.2 7.8 7.7 7.8 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 3,6-7,8 3,6-4,5 1,2-3,6 MHz MHz
ACR-N (dB) 9.0 9.5 34.0 36.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 6.9 7.1 461.0 494.0
Limite (dB) 55.8 55.5 -13.9 -16.6 80 80

Pire paire 3,6 7,8 4,5 4,5


40 40
PS ACR-N (dB) 10.0 10.5 36.9 36.7
Fréq. (MHz) 6.5 6.6 499.0 495.0 0 0
Limite (dB) 54.0 53.8 -19.9 -19.6
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 1,2 3,6 3,6 MHz MHz
RL (dB) 5.9 5.9 6.0 8.1 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 369.0 30.8 380.0 500.0 100 100
Limite (dB) 8.3 18.6 8.2 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 147
ID Câble: R.5 H2-C/01 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:35:11 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.5 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 40.0 40.0 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 182
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 13
Résistance (ohms) [Paire 3,6] 5.83
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 27.2 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.1 2.5 8.7 9.2
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 289.0 191.0 477.0 477.0 100 100
Limite (dB) 34.3 37.3 27.3 27.3 80 80
Pire paire 4,5 7,8 3,6 4,5
60 60
PS NEXT (dB) 5.3 4.3 9.5 9.0
Fréq. (MHz) 289.0 191.5 486.0 470.0 40 40

Limite (dB) 31.7 34.6 24.2 24.7 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.9 14.8 15.2 15.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 390.0 392.0 481.0 473.0 100 100
Limite (dB) 12.4 12.3 10.5 10.7 80 80
Pire paire 3,6 4,5 3,6 4,5
60 60
PS ACR-F (dB) 16.6 16.1 16.7 16.1
40 40
Fréq. (MHz) 408.0 423.0 481.0 423.0
Limite (dB) 9.0 8.7 7.5 8.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 3,6-7,8 3,6-4,5 4,5-7,8 MHz MHz
ACR-N (dB) 10.7 9.6 36.8 36.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 17.1 29.1 495.0 477.0
Limite (dB) 46.9 41.0 -16.7 -15.2 80 80

Pire paire 3,6 7,8 3,6 4,5


40 40
PS ACR-N (dB) 12.3 11.4 36.2 36.9
Fréq. (MHz) 10.8 29.1 486.0 486.0 0 0
Limite (dB) 49.3 38.6 -18.8 -18.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 1,2 4,5 1,2 MHz MHz
RL (dB) 4.4 6.7 4.4 6.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 437.0 439.0 437.0 439.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 148
ID Câble: R.5 H2-C/02 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:35:44 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.6 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 40.0 40.0 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 182
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 13
Résistance (ohms) [Paire 3,6] 5.75
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 27.2 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 3,6-4,5 4,5-7,8 MHz


NEXT (dB) 4.6 5.7 7.0 8.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 46.8 231.5 492.0 485.0 100 100
Limite (dB) 47.2 35.9 26.9 27.1 80 80
Pire paire 7,8 4,5 4,5 4,5
60 60
PS NEXT (dB) 5.9 6.9 7.3 10.4
Fréq. (MHz) 46.8 47.0 479.0 499.0 40 40

Limite (dB) 44.7 44.7 24.4 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.7 14.4 13.7 14.4
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 472.0 470.0 472.0 470.0 100 100
Limite (dB) 10.7 10.7 10.7 10.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.6 16.3 15.6 16.5
40 40
Fréq. (MHz) 472.0 1.0 472.0 471.0
Limite (dB) 7.7 61.2 7.7 7.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 3,6-4,5 4,5-7,8 MHz MHz
ACR-N (dB) 11.3 11.8 34.1 36.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 7.9 7.9 492.0 485.0
Limite (dB) 54.6 54.6 -16.5 -15.9 80 80

Pire paire 7,8 7,8 3,6 4,5


40 40
PS ACR-N (dB) 12.0 11.7 34.5 37.7
Fréq. (MHz) 7.9 7.8 488.0 500.0 0 0
Limite (dB) 52.2 52.4 -19.0 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 1,2 MHz MHz
RL (dB) 5.4 6.8 5.7 7.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 121.0 63.0 449.0 418.0 100 100
Limite (dB) 13.2 16.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 149
ID Câble: R.5 H2-C/07 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:27:05 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.7 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 28.9 28.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 132
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 10
Résistance (ohms) [Paire 3,6] 4.17
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 31.3 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 4,5-7,8 3,6-4,5 4,5-7,8 MHz


NEXT (dB) 3.7 5.3 7.2 5.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 297.0 410.0 495.0 472.0 100 100
Limite (dB) 34.1 29.5 26.8 27.5 80 80
Pire paire 1,2 4,5 3,6 4,5
60 60
PS NEXT (dB) 5.0 7.3 8.4 7.3
Fréq. (MHz) 330.0 471.0 490.0 471.0 40 40

Limite (dB) 30.0 24.7 24.1 24.7 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 13.6 13.7 14.4 15.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 4.8 217.0 437.0 436.0 100 100
Limite (dB) 50.7 17.5 11.4 11.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.0 16.1 16.0 17.9
40 40
Fréq. (MHz) 437.0 3.3 437.0 433.0
Limite (dB) 8.4 51.0 8.4 8.5 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 3,6-4,5 4,5-7,8 MHz MHz
ACR-N (dB) 11.1 11.9 38.5 36.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 8.1 7.6 495.0 472.0
Limite (dB) 54.3 54.9 -16.7 -14.8 80 80

Pire paire 4,5 7,8 3,6 4,5


40 40
PS ACR-N (dB) 12.4 12.5 39.8 37.8
Fréq. (MHz) 7.8 7.1 495.0 471.0 0 0
Limite (dB) 52.4 53.2 -19.6 -17.6
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 1,2 MHz MHz
RL (dB) 5.4 8.0 5.4 8.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 411.0 446.0 411.0 446.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 150
ID Câble: R.5 H2-C/08 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:27:49 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.9 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 28.7 28.7 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 131
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 10
Résistance (ohms) [Paire 3,6] 4.21
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 31.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 3,6-4,5 1,2-4,5 MHz


NEXT (dB) 2.9 4.6 6.8 6.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 267.0 266.0 495.0 420.0 100 100
Limite (dB) 34.9 34.9 26.8 29.2 80 80
Pire paire 4,5 7,8 3,6 7,8
60 60
PS NEXT (dB) 5.0 6.6 7.8 9.6
Fréq. (MHz) 267.0 266.0 495.0 500.0 40 40

Limite (dB) 32.2 32.3 23.9 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.4 15.1 14.4 15.4
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 428.0 212.0 428.0 432.0 100 100
Limite (dB) 11.6 17.7 11.6 11.5 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.6 17.1 16.6 17.7
40 40
Fréq. (MHz) 498.0 2.6 498.0 432.0
Limite (dB) 7.2 52.8 7.2 8.5 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 3,6-7,8 3,6-4,5 4,5-7,8 MHz MHz
ACR-N (dB) 13.3 13.9 38.0 40.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 22.4 9.6 495.0 500.0
Limite (dB) 44.0 52.7 -16.7 -17.1 80 80

Pire paire 7,8 7,8 3,6 7,8


40 40
PS ACR-N (dB) 14.2 14.4 38.7 41.3
Fréq. (MHz) 9.0 9.5 495.0 500.0 0 0
Limite (dB) 51.0 50.5 -19.6 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 4,5 MHz MHz
RL (dB) 6.2 7.4 7.4 8.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 63.0 62.5 368.0 446.0 100 100
Limite (dB) 16.0 16.0 8.3 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 151
ID Câble: R.5 H2-C/09 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:28:15 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.4 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 28.4 28.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 130
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 10
Résistance (ohms) [Paire 3,6] 4.13
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 31.4 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-4,5 1,2-3,6 1,2-4,5 MHz


NEXT (dB) 4.4 7.1 4.4 7.2
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 447.0 208.0 447.0 394.0 100 100
Limite (dB) 28.3 36.6 28.3 30.1 80 80
Pire paire 3,6 1,2 3,6 1,2
60 60
PS NEXT (dB) 5.8 7.1 8.0 7.1
Fréq. (MHz) 289.0 394.0 497.0 394.0 40 40

Limite (dB) 31.7 27.3 23.8 27.3 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.9 14.2 15.8 15.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 334.0 107.5 447.0 418.0 100 100
Limite (dB) 13.7 23.6 11.2 11.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.3 16.5 18.0 18.8
40 40
Fréq. (MHz) 334.0 1.0 447.0 458.0
Limite (dB) 10.7 61.2 8.2 8.0 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 1,2-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 13.2 13.6 33.7 40.0 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 8.1 3.5 447.0 468.0
Limite (dB) 54.3 61.7 -12.7 -14.5 80 80

Pire paire 4,5 4,5 3,6 3,6


40 40
PS ACR-N (dB) 13.2 12.8 39.1 39.6
Fréq. (MHz) 8.0 8.0 497.0 456.0 0 0
Limite (dB) 52.1 52.1 -19.7 -16.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 3,6 3,6 MHz MHz
RL (dB) 4.3 7.9 4.3 8.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 455.0 72.3 455.0 473.0 100 100
Limite (dB) 8.0 15.4 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 152
ID Câble: R.5 H2-C/10 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:01:54 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.6 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 78.4 78.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 356
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 25
Résistance (ohms) [Paire 3,6] 11.12
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 12.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 2.6 4.0 3.3 5.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 289.0 28.5 468.0 475.0 100 100
Limite (dB) 34.3 50.6 27.6 27.4 80 80
Pire paire 7,8 7,8 7,8 7,8
60 60
PS NEXT (dB) 4.1 5.7 5.2 7.2
Fréq. (MHz) 305.0 28.5 468.0 475.0 40 40

Limite (dB) 31.2 48.2 24.7 24.5 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-1,2 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 11.5 13.2 11.6 13.2
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 453.0 456.0 454.0 456.0 100 100
Limite (dB) 11.1 11.0 11.0 11.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 14.0 15.9 14.0 15.9
40 40
Fréq. (MHz) 453.0 497.0 453.0 497.0
Limite (dB) 8.1 7.3 8.1 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 8.2 6.9 19.1 19.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 28.3 28.5 499.0 475.0
Limite (dB) 41.4 41.3 -17.0 -15.1 80 80

Pire paire 7,8 7,8 4,5 4,5


40 40
PS ACR-N (dB) 10.1 8.6 20.5 20.4
Fréq. (MHz) 28.4 28.4 499.0 475.0 0 0
Limite (dB) 38.9 38.9 -19.9 -17.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 1,2 MHz MHz
RL (dB) 4.6 6.2 7.2 6.8 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 7.9 9.0 493.0 458.0 100 100
Limite (dB) 21.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 153
ID Câble: R.5 H2-C/11 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:54:32 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 5.3 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 68.2 68.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 310
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 22
Résistance (ohms) [Paire 3,6] 9.71
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 16.6 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 3,6-7,8 1,2-4,5 MHz


NEXT (dB) 5.9 5.3 6.9 6.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 38.0 236.0 490.0 443.0 100 100
Limite (dB) 48.6 35.7 26.9 28.4 80 80
Pire paire 7,8 4,5 3,6 4,5
60 60
PS NEXT (dB) 6.7 6.4 7.9 7.9
Fréq. (MHz) 15.4 236.0 490.0 443.0 40 40

Limite (dB) 52.5 33.1 24.1 25.6 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.3 14.4 13.3 14.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 456.0 366.0 456.0 453.0 100 100
Limite (dB) 11.0 12.9 11.0 11.1 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.4 16.3 15.4 16.3
40 40
Fréq. (MHz) 456.0 453.0 456.0 453.0
Limite (dB) 8.0 8.1 8.0 8.1 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 3,6-7,8 1,2-4,5 MHz MHz
ACR-N (dB) 8.6 9.2 24.6 22.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 15.4 15.4 490.0 443.0
Limite (dB) 48.0 48.0 -16.3 -12.4 80 80

Pire paire 7,8 4,5 3,6 3,6


40 40
PS ACR-N (dB) 9.3 10.5 24.2 27.3
Fréq. (MHz) 15.4 15.3 490.0 498.0 0 0
Limite (dB) 45.7 45.7 -19.2 -19.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 4,5 MHz MHz
RL (dB) 3.6 5.8 7.5 9.1 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 8.6 15.6 492.0 477.0 100 100
Limite (dB) 21.0 20.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 154
ID Câble: R.5 H2-C/13 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:49:14 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 1.1 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 76.3 76.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 346
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 24
Résistance (ohms) [Paire 3,6] 10.90
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 13.2 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-4,5 1,2-4,5 1,2-4,5 MHz


NEXT (dB) 2.9 1.1 * 3.0 1.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 334.0 400.0 405.0 400.0 100 100
Limite (dB) 32.5 29.9 29.7 29.9 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 4.3 3.4 4.3 3.4
Fréq. (MHz) 405.0 400.0 405.0 400.0 40 40

Limite (dB) 26.9 27.1 26.9 27.1 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 7,8-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.2 13.4 13.2 14.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 447.0 414.0 447.0 497.0 100 100
Limite (dB) 11.2 11.8 11.2 10.3 80 80
Pire paire 3,6 4,5 3,6 3,6
60 60
PS ACR-F (dB) 15.4 14.4 15.5 15.7
40 40
Fréq. (MHz) 492.0 414.0 493.0 497.0
Limite (dB) 7.4 8.8 7.3 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 1,2-4,5 4,5-7,8 1,2-4,5 MHz MHz
ACR-N (dB) 9.6 13.0 20.6 13.0 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 100.5 400.0 476.0 400.0
Limite (dB) 23.8 -8.6 -15.2 -8.6 80 80

Pire paire 4,5 3,6 3,6 3,6


40 40
PS ACR-N (dB) 11.6 14.0 22.4 23.3
Fréq. (MHz) 116.0 6.0 484.0 497.0 0 0
Limite (dB) 18.8 54.7 -18.7 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 1,2 4,5 4,5 MHz MHz
RL (dB) 5.4 6.8 5.4 9.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 306.0 11.0 306.0 498.0 100 100
Limite (dB) 9.1 20.8 9.1 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

* La marge est dans les limites de précision de l'instrument.

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 155
ID Câble: R.5 H2-C/14 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:49:54 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 0.5 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 76.3 76.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 347
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 25
Résistance (ohms) [Paire 3,6] 10.83
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 13.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-4,5 4,5-7,8 1,2-4,5 MHz


NEXT (dB) 2.5 0.5 * 5.6 0.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 238.5 403.0 469.0 403.0 100 100
Limite (dB) 35.7 29.8 27.6 29.8 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 4.2 3.1 4.2 3.1
Fréq. (MHz) 410.0 403.0 410.0 403.0 40 40

Limite (dB) 26.7 27.0 26.7 27.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.5 12.8 12.6 13.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 448.0 407.0 449.0 449.0 100 100
Limite (dB) 11.2 12.0 11.1 11.1 80 80
Pire paire 3,6 4,5 3,6 4,5
60 60
PS ACR-F (dB) 15.0 13.5 15.0 13.5
40 40
Fréq. (MHz) 444.0 414.0 444.0 414.0
Limite (dB) 8.2 8.8 8.2 8.8 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 1,2-4,5 1,2-3,6 1,2-4,5 MHz MHz
ACR-N (dB) 9.9 12.4 20.7 12.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 93.0 403.0 494.0 411.0
Limite (dB) 25.1 -8.9 -16.6 -9.6 80 80

Pire paire 3,6 3,6 4,5 4,5


40 40
PS ACR-N (dB) 10.4 12.5 14.9 14.8
Fréq. (MHz) 4.1 4.3 410.0 411.0 0 0
Limite (dB) 58.0 57.7 -12.3 -12.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 1,2 4,5 3,6 MHz MHz
RL (dB) 5.8 6.3 5.8 8.8 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 498.0 6.4 498.0 495.0 100 100
Limite (dB) 8.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

* La marge est dans les limites de précision de l'instrument.

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 156
ID Câble: R.5 H2-C/15 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:53:30 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 1.9 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 74.6 74.6 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 339
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 24
Résistance (ohms) [Paire 3,6] 10.68
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 13.8 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 4.3 1.9 6.6 5.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 281.0 127.0 496.0 407.0 100 100
Limite (dB) 34.5 40.2 26.8 29.6 80 80
Pire paire 7,8 4,5 4,5 4,5
60 60
PS NEXT (dB) 6.4 4.4 8.0 6.9
Fréq. (MHz) 281.0 127.0 496.0 423.0 40 40

Limite (dB) 31.9 37.6 23.9 26.3 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.5 12.5 13.8 13.5
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 254.0 255.0 468.0 424.0 100 100
Limite (dB) 16.1 16.1 10.8 11.6 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.0 14.8 15.8 16.3
40 40
Fréq. (MHz) 253.0 255.0 471.0 472.0
Limite (dB) 13.1 13.1 7.7 7.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 10.6 9.0 22.1 22.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 64.8 127.0 496.0 464.0
Limite (dB) 30.6 19.7 -16.8 -14.2 80 80

Pire paire 3,6 3,6 4,5 4,5


40 40
PS ACR-N (dB) 10.2 10.5 22.7 23.1
Fréq. (MHz) 11.4 11.3 500.0 479.0 0 0
Limite (dB) 48.7 48.8 -20.0 -18.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 3,6 MHz MHz
RL (dB) 2.5 2.6 2.5 10.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 268.0 6.6 268.0 497.0 60 100
Limite (dB) 9.7 21.0 9.7 8.0 50 80
Conforme aux normes de réseaux: 40
60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 157
ID Câble: R.5 H2-C/20 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:46:36 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.1 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 74.4 74.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 339
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 25
Résistance (ohms) [Paire 3,6] 10.61
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 13.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 6.9 4.1 8.2 6.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 195.0 133.0 478.0 488.0 100 100
Limite (dB) 37.1 39.8 27.3 27.0 80 80
Pire paire 4,5 1,2 3,6 4,5
60 60
PS NEXT (dB) 7.5 6.1 8.1 8.3
Fréq. (MHz) 204.0 405.0 479.0 487.0 40 40

Limite (dB) 34.2 26.9 24.4 24.2 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.0 12.0 14.2 12.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 335.0 452.0 462.0 454.0 100 100
Limite (dB) 13.7 11.1 10.9 11.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.3 14.4 17.3 14.4
40 40
Fréq. (MHz) 335.0 452.0 500.0 452.0
Limite (dB) 10.7 8.1 7.2 8.1 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 3,6-7,8 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 10.4 11.2 21.4 21.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 6.8 24.8 478.0 488.0
Limite (dB) 56.0 42.9 -15.3 -16.1 80 80

Pire paire 7,8 7,8 3,6 4,5


40 40
PS ACR-N (dB) 10.3 11.5 21.3 22.8
Fréq. (MHz) 6.8 6.9 479.0 487.0 0 0
Limite (dB) 53.6 53.5 -18.3 -18.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 1,2 3,6 3,6 MHz MHz
RL (dB) 5.3 6.2 7.6 10.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 6.5 7.9 498.0 486.0 100 100
Limite (dB) 21.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 158
ID Câble: R.5 H2-C/21 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:47:21 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.1 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 74.6 74.6 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 339
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 24
Résistance (ohms) [Paire 3,6] 10.61
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 13.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-4,5 1,2-4,5 1,2-4,5 1,2-4,5 MHz


NEXT (dB) 3.1 2.1 3.1 2.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 403.0 404.0 403.0 404.0 100 100
Limite (dB) 29.8 29.7 29.8 29.7 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 4.8 3.9 4.8 3.9
Fréq. (MHz) 403.0 404.0 403.0 404.0 40 40

Limite (dB) 27.0 26.9 27.0 26.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.4 13.5 12.4 14.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 454.0 245.5 454.0 499.0 100 100
Limite (dB) 11.0 16.4 11.0 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 14.8 15.3 14.8 15.8
40 40
Fréq. (MHz) 454.0 332.0 454.0 457.0
Limite (dB) 8.0 10.8 8.0 8.0 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 3,6-7,8 1,2-4,5 1,2-4,5 MHz MHz
ACR-N (dB) 9.9 10.2 14.6 14.1 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 88.8 12.8 415.0 404.0
Limite (dB) 25.8 49.9 -9.9 -8.9 80 80

Pire paire 7,8 3,6 3,6 4,5


40 40
PS ACR-N (dB) 10.7 11.7 21.7 15.9
Fréq. (MHz) 20.1 7.8 479.0 404.0 0 0
Limite (dB) 42.8 52.4 -18.3 -11.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 4,5 MHz MHz
RL (dB) 5.8 6.7 7.3 9.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 78.5 6.5 426.0 489.0 100 100
Limite (dB) 15.1 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 159
ID Câble: R.5 H2-C/22 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:47:49 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.0 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 73.4 73.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 334
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 24
Résistance (ohms) [Paire 3,6] 10.50
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 14.4 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-4,5 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.0 3.8 3.0 5.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 452.0 409.0 452.0 495.0 100 100
Limite (dB) 28.1 29.5 28.1 26.8 80 80
Pire paire 4,5 4,5 4,5 7,8
60 60
PS NEXT (dB) 4.9 5.6 4.9 7.1
Fréq. (MHz) 452.0 409.0 452.0 495.0 40 40

Limite (dB) 25.3 26.8 25.3 23.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.6 14.2 15.4 15.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 419.0 292.0 468.0 460.0 100 100
Limite (dB) 11.7 14.9 10.8 10.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.0 16.7 17.5 17.5
40 40
Fréq. (MHz) 375.0 374.0 458.0 459.0
Limite (dB) 9.7 9.7 8.0 8.0 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 9.5 11.3 20.7 20.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 37.3 40.5 492.0 495.0
Limite (dB) 38.0 37.0 -16.5 -16.7 80 80

Pire paire 7,8 3,6 4,5 7,8


40 40
PS ACR-N (dB) 11.0 12.4 21.7 22.3
Fréq. (MHz) 40.5 4.9 492.0 495.0 0 0
Limite (dB) 34.5 56.6 -19.3 -19.6
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 1,2 4,5 3,6 MHz MHz
RL (dB) 7.7 5.1 8.7 9.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 274.0 8.3 397.0 493.0 100 100
Limite (dB) 9.6 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 160
ID Câble: R.5 H2-C/23 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:48:20 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 1.3 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 73.9 73.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 336
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 24
Résistance (ohms) [Paire 3,6] 10.54
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 14.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-4,5 1,2-4,5 1,2-4,5 1,2-4,5 MHz


NEXT (dB) 1.3 * 1.7 1.3 1.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 404.0 404.0 404.0 404.0 100 100
Limite (dB) 29.7 29.7 29.7 29.7 80 80
Pire paire 1,2 4,5 1,2 4,5
60 60
PS NEXT (dB) 3.3 4.0 3.3 4.0
Fréq. (MHz) 404.0 404.0 404.0 404.0 40 40

Limite (dB) 26.9 26.9 26.9 26.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 15.3 15.0 16.0 16.2
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 249.0 246.5 500.0 460.0 100 100
Limite (dB) 16.3 16.4 10.2 10.9 80 80
Pire paire 4,5 4,5 3,6 3,6
60 60
PS ACR-F (dB) 17.4 17.2 17.8 17.9
40 40
Fréq. (MHz) 416.0 416.0 500.0 500.0
Limite (dB) 8.8 8.8 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 1,2-4,5 1,2-4,5 MHz MHz
ACR-N (dB) 9.2 12.4 14.0 14.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 16.3 16.3 404.0 404.0
Limite (dB) 47.5 47.5 -8.9 -8.9 80 80

Pire paire 7,8 7,8 3,6 4,5


40 40
PS ACR-N (dB) 10.6 13.6 23.5 21.9
Fréq. (MHz) 16.1 8.5 500.0 475.0 0 0
Limite (dB) 45.2 51.5 -20.0 -17.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 1,2 4,5 3,6 MHz MHz
RL (dB) 7.6 4.9 7.6 10.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 415.0 8.1 415.0 500.0 100 60
Limite (dB) 8.0 21.0 8.0 8.0 80 50

Conforme aux normes de réseaux: 40


60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

* La marge est dans les limites de précision de l'instrument.

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 161
ID Câble: R.5 H2-D/02 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:40:14 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.4 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 32.0 32.0 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 146
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 11
Résistance (ohms) [Paire 4,5] 4.61
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 30.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 4.4 5.7 5.5 7.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 300.0 257.0 500.0 500.0 100 100
Limite (dB) 34.0 35.1 26.7 26.7 80 80
Pire paire 3,6 7,8 3,6 4,5
60 60
PS NEXT (dB) 6.4 7.4 7.0 9.3
Fréq. (MHz) 389.0 257.0 500.0 500.0 40 40

Limite (dB) 27.5 32.5 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 15.2 15.4 15.2 15.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 472.0 286.0 472.0 480.0 100 100
Limite (dB) 10.7 15.1 10.7 10.6 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.1 16.1 16.1 16.1
40 40
Fréq. (MHz) 471.0 470.0 471.0 470.0
Limite (dB) 7.7 7.7 7.7 7.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 3,6-7,8 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 11.9 12.0 35.6 38.3 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 17.4 17.5 500.0 500.0
Limite (dB) 46.8 46.7 -17.1 -17.1 80 80

Pire paire 3,6 3,6 3,6 4,5


40 40
PS ACR-N (dB) 13.4 13.5 37.1 39.5
Fréq. (MHz) 10.8 17.9 500.0 500.0 0 0
Limite (dB) 49.3 44.1 -20.0 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 1,2 MHz MHz
RL (dB) 6.3 7.2 7.1 7.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 44.8 474.0 463.0 474.0 100 100
Limite (dB) 17.5 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 162
ID Câble: R.5 H2-D/03 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:47:09 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.0 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 33.9 33.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 154
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 11
Résistance (ohms) [Paire 3,6] 4.89
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 29.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 1,2-4,5 MHz


NEXT (dB) 4.0 5.2 6.3 9.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 278.0 297.0 499.0 480.0 100 100
Limite (dB) 34.6 34.1 26.7 27.2 80 80
Pire paire 7,8 4,5 3,6 4,5
60 60
PS NEXT (dB) 5.7 7.0 7.4 9.4
Fréq. (MHz) 278.0 297.0 499.0 480.0 40 40

Limite (dB) 31.9 31.5 23.8 24.4 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.4 13.3 13.4 13.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 453.0 456.0 453.0 456.0 100 100
Limite (dB) 11.1 11.0 11.1 11.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.0 15.6 16.0 15.6
40 40
Fréq. (MHz) 453.0 446.0 453.0 446.0
Limite (dB) 8.1 8.2 8.1 8.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 1,2-4,5 MHz MHz
ACR-N (dB) 13.5 14.6 35.3 38.1 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 23.1 22.6 499.0 480.0
Limite (dB) 43.6 43.9 -17.0 -15.5 80 80

Pire paire 4,5 4,5 3,6 4,5


40 40
PS ACR-N (dB) 14.7 15.2 36.4 38.3
Fréq. (MHz) 22.9 22.6 499.0 480.0 0 0
Limite (dB) 41.4 41.5 -19.9 -18.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 4,5 1,2 4,5 MHz MHz
RL (dB) 3.2 7.2 5.7 7.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 216.0 493.0 493.0 493.0 100 100
Limite (dB) 10.7 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 163
ID Câble: R.5 H2-D/05 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:38:34 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 0.7 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 71.1 71.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 323
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 23
Résistance (ohms) [Paire 3,6] 10.18
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 15.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-4,5 4,5-7,8 1,2-4,5 4,5-7,8 MHz


NEXT (dB) 0.7 * 3.5 0.7 4.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 405.0 169.5 405.0 410.0 100 100
Limite (dB) 29.7 38.1 29.7 29.5 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 3.0 5.3 3.0 5.3
Fréq. (MHz) 405.0 402.0 405.0 402.0 40 40

Limite (dB) 26.9 27.0 26.9 27.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.3 13.2 12.4 13.2
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 438.0 481.0 483.0 481.0 100 100
Limite (dB) 11.4 10.5 10.5 10.5 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 14.6 15.0 14.6 15.1
40 40
Fréq. (MHz) 477.0 480.0 477.0 481.0
Limite (dB) 7.6 7.6 7.6 7.5 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 4,5-7,8 1,2-4,5 1,2-4,5 MHz MHz
ACR-N (dB) 9.0 12.3 13.8 18.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 31.5 169.5 405.0 402.0
Limite (dB) 40.1 14.3 -9.0 -8.8 80 80

Pire paire 7,8 3,6 3,6 4,5


40 40
PS ACR-N (dB) 10.3 13.7 23.1 18.7
Fréq. (MHz) 31.5 31.3 493.0 407.0 0 0
Limite (dB) 37.6 37.7 -19.4 -12.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 1,2 7,8 4,5 MHz MHz
RL (dB) 5.8 8.0 7.6 9.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 6.6 28.5 425.0 483.0 100 100
Limite (dB) 21.0 18.7 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

* La marge est dans les limites de précision de l'instrument.

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 164
ID Câble: R.5 H2-D/06 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:44:49 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.1 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 71.3 71.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 324
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 23
Résistance (ohms) [Paire 3,6] 10.18
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 14.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 3.1 3.1 6.6 7.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 121.5 248.5 499.0 487.0 100 100
Limite (dB) 40.5 35.4 26.7 27.0 80 80
Pire paire 4,5 4,5 3,6 4,5
60 60
PS NEXT (dB) 5.0 5.1 8.1 9.4
Fréq. (MHz) 278.0 180.5 498.0 487.0 40 40

Limite (dB) 31.9 35.1 23.8 24.2 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 13.0 13.7 13.0 14.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 500.0 407.0 500.0 500.0 100 100
Limite (dB) 10.2 12.0 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.9 15.5 15.9 16.8
40 40
Fréq. (MHz) 500.0 407.0 500.0 497.0
Limite (dB) 7.2 9.0 7.2 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 3,6-7,8 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 9.1 10.4 21.4 23.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 58.0 5.4 499.0 487.0
Limite (dB) 32.2 58.0 -17.0 -16.1 80 80

Pire paire 7,8 3,6 3,6 4,5


40 40
PS ACR-N (dB) 10.6 11.1 22.8 24.6
Fréq. (MHz) 58.3 5.4 498.0 487.0 0 0
Limite (dB) 29.6 55.7 -19.8 -18.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 4,5 4,5 3,6 MHz MHz
RL (dB) 4.0 3.6 7.6 9.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 8.0 7.0 470.0 471.0 100 100
Limite (dB) 21.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 165
ID Câble: R.5 H2-D/07 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:45:25 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.7 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 71.3 71.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 324
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 23
Résistance (ohms) [Paire 3,6] 10.15
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 14.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-4,5 4,5-7,8 1,2-4,5 4,5-7,8 MHz


NEXT (dB) 4.7 6.0 4.7 7.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 400.0 447.0 400.0 494.0 100 100
Limite (dB) 29.9 28.3 29.9 26.8 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 6.5 8.1 6.5 9.6
Fréq. (MHz) 408.0 417.0 408.0 494.0 40 40

Limite (dB) 26.8 26.5 26.8 23.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-4,5 1,2-3,6 1,2-4,5 MHz MHz
ACR-F (dB) 13.6 10.8 14.6 10.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 391.0 413.0 477.0 414.0 100 100
Limite (dB) 12.3 11.9 10.6 11.8 80 80
Pire paire 3,6 4,5 3,6 4,5
60 60
PS ACR-F (dB) 15.6 12.2 17.3 12.2
40 40
Fréq. (MHz) 391.0 413.0 476.0 413.0
Limite (dB) 9.3 8.9 7.6 8.9 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 1,2-3,6 1,2-4,5 4,5-7,8 MHz MHz
ACR-N (dB) 10.9 11.1 18.2 23.3 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 25.4 6.4 409.0 494.0
Limite (dB) 42.6 56.5 -9.4 -16.6 80 80

Pire paire 3,6 3,6 3,6 4,5


40 40
PS ACR-N (dB) 11.2 11.4 26.7 25.0
Fréq. (MHz) 6.4 6.4 498.0 494.0 0 0
Limite (dB) 54.2 54.2 -19.8 -19.5
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 1,2 4,5 3,6 MHz MHz
RL (dB) 8.2 6.1 8.2 10.1 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 452.0 7.1 452.0 499.0 100 100
Limite (dB) 8.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 166
ID Câble: R.5 H2-D/08 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:39:15 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.3 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 70.8 70.8 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 322
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 23
Résistance (ohms) [Paire 3,6] 9.96
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 15.3 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.3 4.3 6.2 4.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 208.0 474.0 425.0 474.0 100 100
Limite (dB) 36.6 27.4 29.0 27.4 80 80
Pire paire 4,5 4,5 3,6 4,5
60 60
PS NEXT (dB) 5.6 6.4 9.5 6.4
Fréq. (MHz) 208.0 473.0 492.0 473.0 40 40

Limite (dB) 34.0 24.6 24.0 24.6 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.8 13.7 13.7 13.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 433.0 438.0 478.0 438.0 100 100
Limite (dB) 11.5 11.4 10.6 11.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.2 15.6 15.2 15.6
40 40
Fréq. (MHz) 478.0 433.0 478.0 433.0
Limite (dB) 7.6 8.5 7.6 8.5 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 3,6-4,5 4,5-7,8 MHz MHz
ACR-N (dB) 12.6 12.5 24.3 20.3 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 66.8 3.5 492.0 474.0
Limite (dB) 30.2 61.7 -16.5 -15.0 80 80

Pire paire 3,6 4,5 3,6 4,5


40 40
PS ACR-N (dB) 13.8 12.6 24.7 21.6
Fréq. (MHz) 66.3 7.3 493.0 473.0 0 0
Limite (dB) 27.8 53.0 -19.4 -17.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 3,6 3,6 MHz MHz
RL (dB) 6.8 5.0 7.0 7.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 6.8 6.8 435.0 493.0 100 100
Limite (dB) 21.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 167
ID Câble: R.5 H2-D/09 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:36:38 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 1.3 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 68.7 68.7 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 312
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 22
Résistance (ohms) [Paire 3,6] 9.78
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 15.8 40
Fréquence (MHz) [Paire 3,6] 498.0
30
Limite (dB) [Paire 3,6] 43.6
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-4,5 1,2-4,5 1,2-4,5 1,2-4,5 MHz


NEXT (dB) 3.4 1.3 * 3.5 1.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 408.0 404.0 409.0 404.0 100 100
Limite (dB) 29.6 29.7 29.5 29.7 80 80
Pire paire 1,2 1,2 1,2 1,2
60 60
PS NEXT (dB) 5.5 3.8 5.5 3.8
Fréq. (MHz) 409.0 404.0 409.0 404.0 40 40

Limite (dB) 26.8 26.9 26.8 26.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.0 13.3 14.8 13.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 229.0 228.0 498.0 459.0 100 100
Limite (dB) 17.0 17.0 10.2 11.0 80 80
Pire paire 3,6 4,5 3,6 4,5
60 60
PS ACR-F (dB) 16.0 14.9 16.1 14.9
40 40
Fréq. (MHz) 2.6 414.0 497.0 414.0
Limite (dB) 52.8 8.8 7.3 8.8 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 4,5-7,8 1,2-4,5 1,2-4,5 MHz MHz
ACR-N (dB) 13.1 12.9 16.8 15.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 28.0 13.4 409.0 405.0
Limite (dB) 41.5 49.4 -9.4 -9.0 80 80

Pire paire 7,8 4,5 3,6 7,8


40 40
PS ACR-N (dB) 13.3 13.6 24.6 25.7
Fréq. (MHz) 6.9 13.4 489.0 499.0 0 0
Limite (dB) 53.5 47.1 -19.1 -19.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 1,2 1,2 3,6 MHz MHz
RL (dB) 6.7 6.1 7.4 10.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 7.0 8.8 347.0 487.0 100 100
Limite (dB) 21.0 21.0 8.6 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

* La marge est dans les limites de précision de l'instrument.

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 168
ID Câble: R.5 H2-D/10 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:37:16 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 1.8 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 69.2 69.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 315
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 23
Résistance (ohms) [Paire 3,6] 9.86
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 16.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-4,5 1,2-4,5 1,2-4,5 1,2-4,5 MHz


NEXT (dB) 1.8 2.5 1.8 2.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 396.0 402.0 396.0 402.0 100 100
Limite (dB) 30.0 29.8 30.0 29.8 80 80
Pire paire 4,5 1,2 4,5 1,2
60 60
PS NEXT (dB) 4.1 5.0 4.1 5.0
Fréq. (MHz) 409.0 402.0 409.0 402.0 40 40

Limite (dB) 26.8 27.0 26.8 27.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.7 13.0 13.7 13.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 500.0 453.0 500.0 495.0 100 100
Limite (dB) 10.2 11.1 10.2 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.3 15.4 15.3 16.2
40 40
Fréq. (MHz) 493.0 453.0 493.0 495.0
Limite (dB) 7.3 8.1 7.3 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 3,6-7,8 1,2-4,5 1,2-4,5 MHz MHz
ACR-N (dB) 9.0 10.8 16.8 16.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 19.3 5.1 409.0 402.0
Limite (dB) 45.7 58.4 -9.4 -8.8 80 80

Pire paire 7,8 3,6 4,5 4,5


40 40
PS ACR-N (dB) 11.0 11.2 17.4 19.1
Fréq. (MHz) 24.8 5.1 409.0 402.0 0 0
Limite (dB) 40.5 56.1 -12.2 -11.5
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 7,8 1,2 3,6 MHz MHz
RL (dB) 6.2 7.7 7.3 8.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 144.5 7.1 443.0 471.0 100 100
Limite (dB) 12.4 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 169
ID Câble: R.5 H2-D/11 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:35:38 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.4 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 69.2 69.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 314
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 22
Résistance (ohms) [Paire 3,6] 9.89
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 15.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 3,6-7,8 1,2-3,6 1,2-4,5 MHz


NEXT (dB) 3.4 3.6 5.8 6.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 383.0 34.0 475.0 410.0 100 100
Limite (dB) 30.5 49.4 27.4 29.5 80 80
Pire paire 7,8 7,8 3,6 3,6
60 60
PS NEXT (dB) 5.2 4.8 7.2 8.7
Fréq. (MHz) 382.0 34.0 475.0 469.0 40 40

Limite (dB) 27.8 47.0 24.5 24.7 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.7 14.2 13.7 15.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 463.0 326.0 463.0 464.0 100 100
Limite (dB) 10.9 13.9 10.9 10.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.9 16.2 15.9 16.8
40 40
Fréq. (MHz) 461.0 326.0 461.0 460.0
Limite (dB) 7.9 10.9 7.9 7.9 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 3,6-7,8 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 9.5 7.4 21.0 25.9 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 63.0 31.0 475.0 477.0
Limite (dB) 31.0 40.3 -15.1 -15.2 80 80

Pire paire 7,8 3,6 3,6 3,6


40 40
PS ACR-N (dB) 11.1 8.8 22.3 23.8
Fréq. (MHz) 25.0 34.0 475.0 469.0 0 0
Limite (dB) 40.4 36.7 -17.9 -17.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 3,6 1,2 3,6 MHz MHz
RL (dB) 5.1 7.2 5.1 7.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 469.0 26.0 469.0 471.0 100 100
Limite (dB) 8.0 18.9 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 170
ID Câble: R.5 H2-D/12 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:36:07 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.7 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 68.2 68.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 310
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 22
Résistance (ohms) [Paire 3,6] 9.68
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 16.2 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 2.7 3.5 3.7 6.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 265.0 327.0 459.0 497.0 100 100
Limite (dB) 34.9 32.8 27.9 26.7 80 80
Pire paire 4,5 7,8 7,8 4,5
60 60
PS NEXT (dB) 5.1 5.8 5.9 8.2
Fréq. (MHz) 265.0 327.0 459.0 497.0 40 40

Limite (dB) 32.3 30.1 25.0 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.0 13.9 13.0 13.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 461.0 460.0 461.0 460.0 100 100
Limite (dB) 10.9 10.9 10.9 10.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.4 16.6 15.5 16.6
40 40
Fréq. (MHz) 459.0 460.0 461.0 460.0
Limite (dB) 8.0 7.9 7.9 7.9 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 4,5-7,8 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 11.1 11.4 20.2 23.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 38.0 8.0 459.0 497.0
Limite (dB) 37.8 54.4 -13.7 -16.9 80 80

Pire paire 1,2 4,5 4,5 4,5


40 40
PS ACR-N (dB) 13.2 12.9 22.0 24.7
Fréq. (MHz) 38.0 8.3 459.0 497.0 0 0
Limite (dB) 35.3 51.8 -16.6 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 7,8 4,5 MHz MHz
RL (dB) 6.9 7.1 7.1 10.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 173.0 12.1 468.0 491.0 100 100
Limite (dB) 11.6 20.6 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 171
ID Câble: R.5 H2-D/13 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:34:02 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.3 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 66.3 66.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 301
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 21
Résistance (ohms) [Paire 3,6] 9.42
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 17.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-4,5 1,2-3,6 1,2-4,5 MHz


NEXT (dB) 4.3 2.3 6.2 2.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 236.5 403.0 482.0 403.0 100 100
Limite (dB) 35.7 29.8 27.2 29.8 80 80
Pire paire 4,5 1,2 3,6 1,2
60 60
PS NEXT (dB) 6.4 4.7 7.3 4.7
Fréq. (MHz) 408.0 403.0 482.0 403.0 40 40

Limite (dB) 26.8 27.0 24.3 27.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.5 13.8 13.5 13.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 472.0 471.0 472.0 471.0 100 100
Limite (dB) 10.7 10.7 10.7 10.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 14.8 16.0 14.8 16.4
40 40
Fréq. (MHz) 417.0 420.0 417.0 471.0
Limite (dB) 8.8 8.7 8.8 7.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 3,6-7,8 1,2-3,6 1,2-4,5 MHz MHz
ACR-N (dB) 11.1 12.3 22.5 17.5 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 10.0 6.3 482.0 403.0
Limite (dB) 52.3 56.7 -15.6 -8.9 80 80

Pire paire 3,6 3,6 3,6 4,5


40 40
PS ACR-N (dB) 10.8 11.4 23.6 20.2
Fréq. (MHz) 6.5 6.5 482.0 404.0 0 0
Limite (dB) 54.0 54.0 -18.5 -11.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 4,5 3,6 4,5 MHz MHz
RL (dB) 7.6 5.7 7.7 10.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 262.0 7.3 483.0 489.0 100 100
Limite (dB) 9.8 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 172
ID Câble: R.5 H2-D/14 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:34:32 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 0.2 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 66.3 66.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 301
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 21
Résistance (ohms) [Paire 3,6] 9.42
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 17.2 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-4,5 3,6-4,5 1,2-4,5 MHz


NEXT (dB) 5.3 0.2 * 6.1 0.2
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 163.5 402.0 410.0 402.0 100 100
Limite (dB) 38.4 29.8 29.5 29.8 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 6.2 2.8 6.3 2.8
Fréq. (MHz) 406.0 402.0 407.0 402.0 40 40

Limite (dB) 26.9 27.0 26.8 27.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.5 13.8 13.5 13.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 426.0 424.0 426.0 424.0 100 100
Limite (dB) 11.6 11.6 11.6 11.6 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.4 16.0 15.4 16.1
40 40
Fréq. (MHz) 426.0 421.0 426.0 424.0
Limite (dB) 8.6 8.7 8.6 8.6 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-7,8 1,2-3,6 1,2-4,5 MHz MHz
ACR-N (dB) 10.5 10.2 26.6 15.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.5 5.5 499.0 402.0
Limite (dB) 61.7 57.8 -17.0 -8.8 80 80

Pire paire 3,6 3,6 3,6 4,5


40 40
PS ACR-N (dB) 11.3 10.9 26.8 17.7
Fréq. (MHz) 3.4 5.5 498.0 402.0 0 0
Limite (dB) 58.7 55.5 -19.8 -11.5
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 1,2 4,5 MHz MHz
RL (dB) 6.6 6.9 6.6 10.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 416.0 9.0 416.0 472.0 100 100
Limite (dB) 8.0 21.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

* La marge est dans les limites de précision de l'instrument.

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 173
ID Câble: R.5 H2-D/15 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:32:54 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.1 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 66.3 66.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 302
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 22
Résistance (ohms) [Paire 3,6] 9.42
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 17.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-4,5 4,5-7,8 1,2-4,5 4,5-7,8 MHz


NEXT (dB) 4.1 5.5 4.1 5.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 404.0 481.0 404.0 489.0 100 100
Limite (dB) 29.7 27.2 29.7 27.0 80 80
Pire paire 4,5 7,8 4,5 7,8
60 60
PS NEXT (dB) 5.4 7.0 5.4 7.0
Fréq. (MHz) 404.0 481.0 404.0 481.0 40 40

Limite (dB) 26.9 24.3 26.9 24.3 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.1 13.5 14.1 14.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 423.0 422.0 473.0 469.0 100 100
Limite (dB) 11.7 11.7 10.7 10.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.6 15.1 16.0 15.1
40 40
Fréq. (MHz) 417.0 420.0 473.0 420.0
Limite (dB) 8.8 8.7 7.7 8.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 1,2-4,5 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 11.0 12.4 25.3 23.3 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 7.4 7.9 498.0 489.0
Limite (dB) 55.2 54.6 -16.9 -16.2 80 80

Pire paire 4,5 4,5 3,6 4,5


40 40
PS ACR-N (dB) 10.3 11.9 25.3 24.6
Fréq. (MHz) 7.6 7.6 494.0 489.0 0 0
Limite (dB) 52.5 52.5 -19.5 -19.1
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 4,5 MHz MHz
RL (dB) 6.8 7.5 6.9 10.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 34.5 32.5 475.0 489.0 100 100
Limite (dB) 18.3 18.4 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 174
ID Câble: R.5 H2-D/16 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:33:28 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.8 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 66.3 66.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 301
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 21
Résistance (ohms) [Paire 3,6] 9.42
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 17.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.8 5.1 5.5 6.6
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 255.0 327.0 445.0 490.0 100 100
Limite (dB) 35.2 32.8 28.3 26.9 80 80
Pire paire 7,8 4,5 3,6 4,5
60 60
PS NEXT (dB) 6.2 6.6 7.7 8.7
Fréq. (MHz) 255.0 400.0 473.0 490.0 40 40

Limite (dB) 32.6 27.1 24.6 24.1 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.7 14.8 13.7 15.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 474.0 189.0 474.0 469.0 100 100
Limite (dB) 10.7 18.7 10.7 10.8 80 80
Pire paire 4,5 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.1 17.1 16.1 17.1
40 40
Fréq. (MHz) 410.0 478.0 474.0 478.0
Limite (dB) 8.9 7.6 7.7 7.6 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 12.4 14.2 23.3 24.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 26.1 10.0 475.0 490.0
Limite (dB) 42.3 52.3 -15.1 -16.3 80 80

Pire paire 3,6 3,6 3,6 4,5


40 40
PS ACR-N (dB) 13.3 13.9 24.1 26.2
Fréq. (MHz) 10.1 10.3 474.0 490.0 0 0
Limite (dB) 49.8 49.7 -17.9 -19.2
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 7,8 3,6 3,6 MHz MHz
RL (dB) 5.5 8.8 5.5 9.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 431.0 31.5 431.0 469.0 100 100
Limite (dB) 8.0 18.5 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 175
ID Câble: R.5 H2-E/09 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:30:45 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.1 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 56.1 56.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 256
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 19
Résistance (ohms) [Paire 3,6] 8.06
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 21.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-4,5 1,2-3,6 1,2-4,5 MHz


NEXT (dB) 3.1 4.9 7.3 4.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 149.5 407.0 473.0 407.0 100 100
Limite (dB) 39.0 29.6 27.4 29.6 80 80
Pire paire 4,5 4,5 3,6 4,5
60 60
PS NEXT (dB) 5.1 6.5 9.0 6.5
Fréq. (MHz) 149.0 406.0 500.0 406.0 40 40

Limite (dB) 36.4 26.9 23.8 26.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.5 14.1 13.5 14.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 492.0 495.0 492.0 495.0 100 100
Limite (dB) 10.4 10.3 10.4 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.5 16.6 15.5 16.7
40 40
Fréq. (MHz) 492.0 495.0 492.0 500.0
Limite (dB) 7.4 7.3 7.4 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 1,2-4,5 1,2-3,6 1,2-4,5 MHz MHz
ACR-N (dB) 12.5 13.4 27.4 23.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 23.0 3.5 473.0 407.0
Limite (dB) 43.7 61.7 -14.9 -9.2 80 80

Pire paire 4,5 4,5 3,6 4,5


40 40
PS ACR-N (dB) 12.6 13.9 30.0 24.5
Fréq. (MHz) 26.8 12.0 500.0 419.0 0 0
Limite (dB) 39.6 48.2 -20.0 -13.1
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 4,5 7,8 4,5 MHz MHz
RL (dB) 5.5 7.1 5.6 7.8 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 155.5 10.6 351.0 499.0 100 100
Limite (dB) 12.1 20.9 8.5 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 176
ID Câble: R.5 H2-E/10 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:31:21 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 5.1 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 55.4 55.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 253
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 19
Résistance (ohms) [Paire 3,6] 8.02
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 21.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 5.2 5.1 7.4 7.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 35.3 168.5 468.0 464.0 100 100
Limite (dB) 49.1 38.1 27.6 27.7 80 80
Pire paire 7,8 7,8 3,6 7,8
60 60
PS NEXT (dB) 6.1 6.8 8.9 8.8
Fréq. (MHz) 22.1 22.3 483.0 464.0 40 40

Limite (dB) 50.0 49.9 24.3 24.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.9 14.0 14.9 14.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 327.0 271.0 498.0 494.0 100 100
Limite (dB) 13.9 15.5 10.2 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 14.9 15.8 16.7 16.4
40 40
Fréq. (MHz) 272.0 270.0 495.0 495.0
Limite (dB) 12.5 12.6 7.3 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 3,6-7,8 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 10.1 10.1 27.6 29.1 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 21.8 22.6 468.0 464.0
Limite (dB) 44.3 43.9 -14.5 -14.2 80 80

Pire paire 7,8 7,8 3,6 4,5


40 40
PS ACR-N (dB) 10.2 10.9 29.5 29.9
Fréq. (MHz) 22.0 22.3 483.0 464.0 0 0
Limite (dB) 41.8 41.7 -18.6 -17.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 4,5 1,2 1,2 MHz MHz
RL (dB) 2.3 7.3 2.3 7.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 386.0 30.9 386.0 418.0 100 100
Limite (dB) 8.1 18.6 8.1 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 177
ID Câble: R.5 H2-E/11 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:26:53 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.2 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 54.0 54.0 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 246
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 18
Résistance (ohms) [Paire 3,6] 7.70
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 21.7 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-4,5 3,6-7,8 1,2-4,5 MHz


NEXT (dB) 4.2 5.8 7.2 5.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 217.5 407.0 497.0 407.0 100 100
Limite (dB) 36.3 29.6 26.7 29.6 80 80
Pire paire 7,8 4,5 3,6 4,5
60 60
PS NEXT (dB) 5.8 7.7 7.6 7.7
Fréq. (MHz) 217.0 407.0 497.0 407.0 40 40

Limite (dB) 33.7 26.8 23.8 26.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.2 13.3 13.9 14.2
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 406.0 404.0 461.0 464.0 100 100
Limite (dB) 12.0 12.1 10.9 10.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.0 15.2 16.5 16.3
40 40
Fréq. (MHz) 407.0 402.0 461.0 464.0
Limite (dB) 9.0 9.1 7.9 7.9 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-4,5 1,2-4,5 3,6-7,8 1,2-4,5 MHz MHz
ACR-N (dB) 13.5 12.8 29.5 24.9 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 19.4 18.9 497.0 407.0
Limite (dB) 45.6 45.9 -16.9 -9.2 80 80

Pire paire 4,5 1,2 3,6 4,5


40 40
PS ACR-N (dB) 13.1 13.9 29.1 32.4
Fréq. (MHz) 19.4 6.4 497.0 485.0 0 0
Limite (dB) 43.2 54.2 -19.7 -18.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 1,2 1,2 MHz MHz
RL (dB) 6.6 9.5 7.2 9.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 274.0 13.4 432.0 462.0 100 100
Limite (dB) 9.6 20.4 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 178
ID Câble: R.5 H2-E/12 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:25:54 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.2 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 53.1 53.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 242
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 18
Résistance (ohms) [Paire 3,6] 7.59
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 21.3 40
Fréquence (MHz) [Paire 3,6] 496.0
30
Limite (dB) [Paire 3,6] 43.5
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-3,6 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 3.2 7.5 5.3 7.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 244.0 165.0 458.0 492.0 100 100
Limite (dB) 35.5 38.3 27.9 26.9 80 80
Pire paire 7,8 4,5 4,5 4,5
60 60
PS NEXT (dB) 5.3 8.6 7.4 8.6
Fréq. (MHz) 243.5 492.0 458.0 492.0 40 40

Limite (dB) 32.9 24.0 25.1 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.9 13.6 14.0 14.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 344.0 346.0 460.0 455.0 100 100
Limite (dB) 13.5 13.4 10.9 11.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.2 15.7 15.8 16.5
40 40
Fréq. (MHz) 351.0 286.0 460.0 455.0
Limite (dB) 10.3 12.1 7.9 8.0 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-4,5 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 12.1 12.0 26.8 30.3 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 10.3 7.9 458.0 492.0
Limite (dB) 52.1 54.6 -13.7 -16.5 80 80

Pire paire 1,2 1,2 4,5 4,5


40 40
PS ACR-N (dB) 12.7 12.6 28.3 30.9
Fréq. (MHz) 10.4 10.1 458.0 500.0 0 0
Limite (dB) 49.6 49.8 -16.5 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 3,6 7,8 4,5 MHz MHz
RL (dB) 4.3 7.1 4.3 9.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 449.0 11.4 449.0 499.0 100 100
Limite (dB) 8.0 20.7 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 179
ID Câble: R.5 H2-E/13 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:26:21 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.1 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 53.1 53.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 241
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 17
Résistance (ohms) [Paire 3,6] 7.55
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 21.5 40
Fréquence (MHz) [Paire 3,6] 497.0
30
Limite (dB) [Paire 3,6] 43.6
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 4.1 4.4 4.1 8.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 491.0 336.0 491.0 499.0 100 100
Limite (dB) 26.9 32.4 26.9 26.7 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 6.1 6.6 6.1 9.7
Fréq. (MHz) 491.0 336.0 491.0 499.0 40 40

Limite (dB) 24.0 29.7 24.0 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.7 14.5 14.9 14.5
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 351.0 458.0 466.0 458.0 100 100
Limite (dB) 13.3 11.0 10.8 11.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.2 16.6 17.4 16.6
40 40
Fréq. (MHz) 351.0 458.0 465.0 458.0
Limite (dB) 10.3 8.0 7.8 8.0 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-4,5 1,2-4,5 4,5-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 12.2 13.7 26.7 31.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 14.1 13.9 491.0 499.0
Limite (dB) 48.9 49.1 -16.4 -17.0 80 80

Pire paire 1,2 1,2 4,5 4,5


40 40
PS ACR-N (dB) 13.7 14.4 28.1 31.8
Fréq. (MHz) 13.6 13.3 491.0 499.0 0 0
Limite (dB) 46.9 47.2 -19.3 -19.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 1,2 3,6 3,6 MHz MHz
RL (dB) 5.4 7.6 5.4 10.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 430.0 193.5 430.0 420.0 100 100
Limite (dB) 8.0 11.1 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 180
ID Câble: R.5 H2-E/14 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:27:31 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 5.5 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 53.1 53.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 242
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 18
Résistance (ohms) [Paire 3,6] 7.62
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 21.7 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 5.5 6.3 6.6 6.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 188.0 475.0 415.0 475.0 100 100
Limite (dB) 37.4 27.4 29.3 27.4 80 80
Pire paire 3,6 4,5 3,6 4,5
60 60
PS NEXT (dB) 6.2 7.7 8.5 7.7
Fréq. (MHz) 302.0 474.0 472.0 474.0 40 40

Limite (dB) 31.3 24.6 24.6 24.6 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.3 14.8 14.4 14.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 459.0 459.0 460.0 460.0 100 100
Limite (dB) 11.0 11.0 10.9 10.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.8 16.9 16.9 17.6
40 40
Fréq. (MHz) 459.0 1.0 460.0 460.0
Limite (dB) 8.0 61.2 7.9 7.9 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 12.6 11.0 31.2 28.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 5.1 5.3 485.0 475.0
Limite (dB) 58.4 58.2 -15.9 -15.1 80 80

Pire paire 3,6 4,5 3,6 4,5


40 40
PS ACR-N (dB) 13.4 12.1 29.5 29.1
Fréq. (MHz) 19.3 5.3 473.0 474.0 0 0
Limite (dB) 43.3 55.9 -17.8 -17.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 3,6 3,6 4,5 MHz MHz
RL (dB) 5.1 8.1 6.0 9.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 151.5 11.1 488.0 499.0 100 100
Limite (dB) 12.2 20.8 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 181
ID Câble: R.5 H2-E/15 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:13:48 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.5 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 45.9 45.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 209
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 15
Résistance (ohms) [Paire 3,6] 6.62
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 24.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-4,5 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 4.1 3.5 4.5 3.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 404.0 404.0 440.0 404.0 100 100
Limite (dB) 29.7 29.7 28.5 29.7 80 80
Pire paire 7,8 4,5 7,8 4,5
60 60
PS NEXT (dB) 5.9 5.2 7.7 5.2
Fréq. (MHz) 236.0 404.0 500.0 404.0 40 40

Limite (dB) 33.1 26.9 23.8 26.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.9 13.2 14.0 14.5
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 477.0 336.0 485.0 482.0 100 100
Limite (dB) 10.6 13.7 10.5 10.5 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.5 15.5 16.5 17.0
40 40
Fréq. (MHz) 485.0 336.0 485.0 482.0
Limite (dB) 7.5 10.7 7.5 7.5 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 3,6-7,8 3,6-7,8 4,5-7,8 MHz MHz
ACR-N (dB) 9.6 9.9 33.1 30.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 6.8 6.5 500.0 467.0
Limite (dB) 56.0 56.3 -17.1 -14.4 80 80

Pire paire 3,6 3,6 3,6 4,5


40 40
PS ACR-N (dB) 10.6 11.7 32.7 26.8
Fréq. (MHz) 6.9 6.1 500.0 404.0 0 0
Limite (dB) 53.5 54.5 -20.0 -11.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 4,5 4,5 3,6 MHz MHz
RL (dB) 6.1 9.6 7.6 9.7 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 88.8 39.8 477.0 475.0 100 100
Limite (dB) 14.5 18.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 182
ID Câble: R.5 H2-E/16 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:18:50 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 3.8 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 48.8 48.8 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 222
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 16
Résistance (ohms) [Paire 3,6] 7.01
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 23.6 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 4.0 3.8 6.9 5.6
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 218.5 291.0 480.0 496.0 100 100
Limite (dB) 36.3 34.2 27.2 26.8 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 5.4 6.0 7.6 7.9
Fréq. (MHz) 218.0 291.0 477.0 496.0 40 40

Limite (dB) 33.7 31.6 24.5 23.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.5 12.9 14.2 12.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 449.0 442.0 499.0 442.0 100 100
Limite (dB) 11.1 11.3 10.2 11.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.0 15.7 16.5 15.8
40 40
Fréq. (MHz) 449.0 443.0 498.0 444.0
Limite (dB) 8.1 8.3 7.2 8.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 14.1 12.4 29.7 29.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.8 3.3 480.0 496.0
Limite (dB) 59.1 61.8 -15.5 -16.8 80 80

Pire paire 3,6 3,6 3,6 4,5


40 40
PS ACR-N (dB) 13.9 12.8 30.5 31.9
Fréq. (MHz) 4.8 4.8 477.0 496.0 0 0
Limite (dB) 56.8 56.8 -18.1 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 1,2 3,6 4,5 MHz MHz
RL (dB) 5.1 9.0 6.7 9.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 155.0 24.5 478.0 410.0 100 100
Limite (dB) 12.1 19.1 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 183
ID Câble: R.5 H2-E/17 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:16:28 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 0.7 dB (NEXT 1,2-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 49.0 49.0 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 223
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 16
Résistance (ohms) [Paire 3,6] 7.05
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 23.7 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 1,2-4,5 1,2-4,5 1,2-4,5 MHz


NEXT (dB) 1.3 0.7 * 2.1 0.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 169.0 408.0 407.0 408.0 100 100
Limite (dB) 38.1 29.6 29.6 29.6 80 80
Pire paire 4,5 4,5 4,5 4,5
60 60
PS NEXT (dB) 3.7 3.1 4.0 3.1
Fréq. (MHz) 169.0 408.0 407.0 408.0 40 40

Limite (dB) 35.5 26.8 26.8 26.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.6 14.3 15.7 14.4
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 310.0 443.0 500.0 444.0 100 100
Limite (dB) 14.4 11.3 10.2 11.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.4 16.9 18.0 17.3
40 40
Fréq. (MHz) 306.0 442.0 500.0 500.0
Limite (dB) 11.5 8.3 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-7,8 3,6-7,8 1,2-4,5 1,2-4,5 MHz MHz
ACR-N (dB) 10.8 9.6 23.1 21.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 44.5 4.1 407.0 408.0
Limite (dB) 35.7 60.3 -9.2 -9.3 80 80

Pire paire 3,6 3,6 4,5 4,5


40 40
PS ACR-N (dB) 12.4 10.9 25.0 24.1
Fréq. (MHz) 4.1 4.0 407.0 408.0 0 0
Limite (dB) 58.0 58.3 -12.0 -12.1
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 3,6 4,5 MHz MHz
RL (dB) 6.3 7.6 7.7 10.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 19.6 19.4 421.0 413.0 100 100
Limite (dB) 19.5 19.6 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

* La marge est dans les limites de précision de l'instrument.

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 184
ID Câble: R.5 H2-E/18 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:12:38 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.3 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 49.7 49.7 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 226
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 16
Résistance (ohms) [Paire 3,6] 7.08
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 23.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 5.1 4.3 6.2 5.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 232.0 300.0 487.0 477.0 100 100
Limite (dB) 35.9 34.0 27.0 27.3 80 80
Pire paire 3,6 4,5 3,6 4,5
60 60
PS NEXT (dB) 6.9 6.4 7.8 7.4
Fréq. (MHz) 334.0 300.0 487.0 486.0 40 40

Limite (dB) 29.8 31.4 24.2 24.2 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.8 14.2 14.8 14.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 492.0 497.0 492.0 498.0 100 100
Limite (dB) 10.4 10.3 10.4 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.2 15.9 17.3 16.9
40 40
Fréq. (MHz) 307.0 304.0 491.0 498.0
Limite (dB) 11.4 11.5 7.4 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 11.7 12.1 28.7 28.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 21.6 21.6 487.0 477.0
Limite (dB) 44.4 44.4 -16.1 -15.2 80 80

Pire paire 4,5 4,5 3,6 4,5


40 40
PS ACR-N (dB) 13.3 13.2 30.3 30.1
Fréq. (MHz) 21.6 21.6 487.0 486.0 0 0
Limite (dB) 42.0 42.0 -18.9 -18.8
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 4,5 7,8 4,5 MHz MHz
RL (dB) 5.7 6.6 5.7 6.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 420.0 497.0 420.0 497.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 185
ID Câble: R.5 H2-E/19 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:21:42 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.3 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 50.2 50.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 228
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 16
Résistance (ohms) [Paire 3,6] 7.30
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 23.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 4.3 5.7 7.2 8.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 201.5 224.5 464.0 500.0 100 100
Limite (dB) 36.9 36.1 27.7 26.7 80 80
Pire paire 7,8 1,2 3,6 4,5
60 60
PS NEXT (dB) 6.2 8.0 8.7 10.2
Fréq. (MHz) 201.5 405.0 500.0 500.0 40 40

Limite (dB) 34.3 26.9 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.3 14.0 13.4 14.0
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 480.0 484.0 481.0 484.0 100 100
Limite (dB) 10.6 10.5 10.5 10.5 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.9 16.5 15.9 16.5
40 40
Fréq. (MHz) 480.0 484.0 480.0 484.0
Limite (dB) 7.6 7.5 7.6 7.5 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 10.3 11.4 31.4 32.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.5 4.6 500.0 500.0
Limite (dB) 59.5 59.3 -17.1 -17.1 80 80

Pire paire 1,2 1,2 3,6 4,5


40 40
PS ACR-N (dB) 11.6 12.9 31.7 33.3
Fréq. (MHz) 4.5 4.8 500.0 500.0 0 0
Limite (dB) 57.2 56.8 -20.0 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 3,6 1,2 3,6 MHz MHz
RL (dB) 5.6 7.0 6.5 11.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 231.0 12.3 326.0 500.0 100 100
Limite (dB) 10.4 20.6 8.9 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 186
ID Câble: R.5 H2-E/21 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:21:04 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 4.7 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 49.7 49.7 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 226
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 16
Résistance (ohms) [Paire 3,6] 7.12
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 23.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 4.7 5.6 5.3 5.6
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 270.0 488.0 419.0 488.0 100 100
Limite (dB) 34.8 27.0 29.2 27.0 80 80
Pire paire 4,5 4,5 3,6 4,5
60 60
PS NEXT (dB) 6.6 7.8 8.3 7.9
Fréq. (MHz) 270.0 487.0 480.0 488.0 40 40

Limite (dB) 32.1 24.2 24.4 24.1 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.3 14.5 13.4 14.5
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 496.0 496.0 500.0 496.0 100 100
Limite (dB) 10.3 10.3 10.2 10.3 80 80
Pire paire 3,6 1,2 3,6 3,6
60 60
PS ACR-F (dB) 15.9 16.4 16.0 17.2
40 40
Fréq. (MHz) 1.0 1.0 496.0 496.0
Limite (dB) 61.2 61.2 7.3 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 13.7 14.1 30.4 28.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.0 9.5 479.0 488.0
Limite (dB) 60.5 52.8 -15.4 -16.1 80 80

Pire paire 3,6 4,5 3,6 4,5


40 40
PS ACR-N (dB) 14.5 13.9 30.7 30.9
Fréq. (MHz) 4.0 10.4 480.0 488.0 0 0
Limite (dB) 58.3 49.6 -18.4 -19.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 1,2 4,5 4,5 MHz MHz
RL (dB) 6.4 8.0 6.4 9.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 463.0 50.3 463.0 474.0 100 100
Limite (dB) 8.0 17.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 187
ID Câble: R.5 H2-E/24 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:25:03 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 2.6 dB (NEXT 4,5-7,8) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 50.4 50.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 230
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 17
Résistance (ohms) [Paire 3,6] 7.26
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 22.8 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 4,5-7,8 4,5-7,8 4,5-7,8 4,5-7,8 MHz


NEXT (dB) 5.2 2.6 6.6 3.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 214.5 301.0 434.0 434.0 100 100
Limite (dB) 36.4 34.0 28.7 28.7 80 80
Pire paire 7,8 7,8 3,6 7,8
60 60
PS NEXT (dB) 6.8 4.6 8.5 5.8
Fréq. (MHz) 214.5 301.0 487.0 434.0 40 40

Limite (dB) 33.8 31.4 24.2 25.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 12.8 13.8 12.8 13.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 480.0 298.0 480.0 480.0 100 100
Limite (dB) 10.6 14.7 10.6 10.6 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 15.5 15.8 15.5 15.9
40 40
Fréq. (MHz) 480.0 475.0 480.0 476.0
Limite (dB) 7.6 7.7 7.6 7.6 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5-7,8 4,5-7,8 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 11.2 11.5 31.0 25.3 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 23.5 23.3 487.0 434.0
Limite (dB) 43.5 43.6 -16.1 -11.6 80 80

Pire paire 4,5 4,5 3,6 4,5


40 40
PS ACR-N (dB) 12.8 13.4 30.7 30.6
Fréq. (MHz) 23.5 23.5 487.0 492.0 0 0
Limite (dB) 41.1 41.1 -18.9 -19.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 4,5 3,6 MHz MHz
RL (dB) 6.1 9.0 6.3 9.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 58.0 26.5 494.0 497.0 100 100
Limite (dB) 16.4 18.9 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 188
ID Câble: R.5 H2-F/01 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:09:53 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 8.8 dB (NEXT 3,6-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 46.9 46.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 203
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 5
Résistance (ohms) [Paire 3,6] 6.94
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 22.2 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-4,5 3,6-4,5 3,6-4,5 1,2-3,6 MHz


NEXT (dB) 8.8 13.0 8.8 13.6
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 463.0 465.0 463.0 493.0 100 100
Limite (dB) 27.8 27.7 27.8 26.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 9.2 12.6 10.2 12.9
Fréq. (MHz) 463.0 473.0 494.0 493.0 40 40

Limite (dB) 24.9 24.6 23.9 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 13.7 14.3 13.8 14.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 464.0 449.0 465.0 449.0 100 100
Limite (dB) 10.9 11.1 10.8 11.1 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.0 16.4 16.0 16.4
40 40
Fréq. (MHz) 465.0 462.0 465.0 462.0
Limite (dB) 7.8 7.9 7.8 7.9 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 18.9 17.1 31.1 35.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.8 3.5 480.0 493.0
Limite (dB) 59.1 61.7 -15.5 -16.5 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 19.2 18.6 32.0 34.7
Fréq. (MHz) 4.8 5.6 494.0 493.0 0 0
Limite (dB) 56.8 55.3 -19.5 -19.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2 1,2 3,6 4,5 MHz MHz
RL (dB) 7.0 7.8 9.0 9.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 22.4 22.4 483.0 387.0 100 100
Limite (dB) 19.3 19.3 8.0 8.1 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 189
ID Câble: R.5 H2-F/03 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:07:26 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.8 dB (NEXT 3,6-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 47.6 47.6 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 206
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 5
Résistance (ohms) [Paire 3,6] 7.05
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 22.0 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-4,5 4,5-7,8 3,6-4,5 4,5-7,8 MHz


NEXT (dB) 10.8 11.4 11.3 12.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 459.0 449.0 499.0 499.0 100 100
Limite (dB) 27.9 28.2 26.7 26.7 80 80
Pire paire 3,6 3,6 3,6 4,5
60 60
PS NEXT (dB) 10.7 12.5 11.0 12.7
Fréq. (MHz) 460.0 483.0 499.0 491.0 40 40

Limite (dB) 25.0 24.3 23.8 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.3 15.0 14.4 15.0
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 453.0 459.0 454.0 459.0 100 100
Limite (dB) 11.1 11.0 11.0 11.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.8 16.9 16.9 16.9
40 40
Fréq. (MHz) 459.0 459.0 461.0 459.0
Limite (dB) 8.0 8.0 7.9 8.0 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 3,6-4,5 1,2-3,6 MHz MHz
ACR-N (dB) 18.8 16.3 33.2 33.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 7.3 3.6 499.0 483.0
Limite (dB) 55.3 61.4 -17.0 -15.7 80 80

Pire paire 3,6 3,6 3,6 4,5


40 40
PS ACR-N (dB) 19.6 17.3 32.9 34.4
Fréq. (MHz) 4.6 5.1 499.0 491.0 0 0
Limite (dB) 57.0 56.1 -19.9 -19.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 3,6 4,5 MHz MHz
RL (dB) 8.4 9.1 8.4 9.1 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 437.0 493.0 437.0 493.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 190
ID Câble: R.5 H2-F/04 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:10:22 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.6 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 47.1 47.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 203
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 4
Résistance (ohms) [Paire 3,6] 6.94
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 21.7 40
Fréquence (MHz) [Paire 4,5] 498.0
30
Limite (dB) [Paire 4,5] 43.6
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 9.6 11.9 9.6 13.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 479.0 435.0 479.0 499.0 100 100
Limite (dB) 27.3 28.7 27.3 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.2 12.3 10.2 12.6
Fréq. (MHz) 479.0 485.0 479.0 500.0 40 40

Limite (dB) 24.4 24.2 24.4 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.5 15.3 14.5 15.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 464.0 461.0 464.0 461.0 100 100
Limite (dB) 10.9 10.9 10.9 10.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.9 17.5 16.9 17.5
40 40
Fréq. (MHz) 464.0 462.0 464.0 462.0
Limite (dB) 7.9 7.9 7.9 7.9 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 18.2 16.7 30.7 35.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.9 3.5 479.0 499.0
Limite (dB) 58.8 61.7 -15.4 -17.0 80 80

Pire paire 1,2 1,2 3,6 3,6


40 40
PS ACR-N (dB) 17.7 17.6 31.3 34.7
Fréq. (MHz) 4.8 4.9 479.0 500.0 0 0
Limite (dB) 56.8 56.6 -18.3 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 4,5 4,5 MHz MHz
RL (dB) 6.0 8.2 6.9 8.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 280.0 498.0 498.0 498.0 100 100
Limite (dB) 9.5 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 191
ID Câble: R.5 H2-F/05 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:49:22 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.1 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 43.8 43.8 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 189
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 4
Résistance (ohms) [Paire 3,6] 6.47
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 23.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 10.1 11.3 11.6 12.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 397.0 432.0 496.0 500.0 100 100
Limite (dB) 30.0 28.8 26.8 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 11.0 12.0 11.0 12.1
Fréq. (MHz) 496.0 487.0 496.0 488.0 40 40

Limite (dB) 23.9 24.2 23.9 24.1 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.3 14.4 14.3 14.4
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 496.0 492.0 496.0 492.0 100 100
Limite (dB) 10.3 10.4 10.3 10.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.3 16.4 16.3 16.4
40 40
Fréq. (MHz) 497.0 492.0 497.0 492.0
Limite (dB) 7.3 7.4 7.3 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 17.5 17.7 34.6 35.9 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 5.4 3.4 496.0 500.0
Limite (dB) 58.0 61.7 -16.8 -17.1 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.3 17.9 34.0 35.8
Fréq. (MHz) 5.1 5.4 496.0 500.0 0 0
Limite (dB) 56.1 55.7 -19.7 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 3,6 4,5 MHz MHz
RL (dB) 6.9 8.0 6.9 8.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 414.0 313.0 414.0 313.0 100 100
Limite (dB) 8.0 9.0 8.0 9.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 192
ID Câble: R.5 H2-F/06 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:57:56 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.3 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 42.2 42.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 182
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 4
Résistance (ohms) [Paire 4,5] 6.27
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 24.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 10.3 11.2 10.5 12.4
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 458.0 450.0 467.0 493.0 100 100
Limite (dB) 27.9 28.2 27.6 26.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.9 11.5 11.4 11.5
Fréq. (MHz) 467.0 487.0 498.0 487.0 40 40

Limite (dB) 24.8 24.2 23.8 24.2 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.6 15.1 14.7 15.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 492.0 500.0 500.0 500.0 100 100
Limite (dB) 10.4 10.2 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.5 16.9 16.5 16.9
40 40
Fréq. (MHz) 492.0 500.0 492.0 500.0
Limite (dB) 7.4 7.2 7.4 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 15.5 15.5 35.4 36.1 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 5.1 3.1 494.0 487.0
Limite (dB) 58.4 61.8 -16.6 -16.1 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 16.8 17.3 35.3 35.2
Fréq. (MHz) 5.1 5.9 498.0 487.0 0 0
Limite (dB) 56.1 54.9 -19.8 -18.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 3,6 3,6 3,6 MHz MHz
RL (dB) 6.9 8.6 6.9 8.6 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 460.0 500.0 460.0 500.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 193
ID Câble: R.5 H2-F/07 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:01:46 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.9 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 41.9 41.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 181
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 4
Résistance (ohms) [Paire 4,5] 6.27
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 24.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 10.9 13.1 11.0 13.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 489.0 486.0 500.0 486.0 100 100
Limite (dB) 27.0 27.1 26.7 27.1 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.9 13.4 11.3 13.4
Fréq. (MHz) 444.0 492.0 499.0 492.0 40 40

Limite (dB) 25.5 24.0 23.8 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 15.6 15.7 15.6 15.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 500.0 240.0 500.0 500.0 100 100
Limite (dB) 10.2 16.6 10.2 10.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.5 17.7 17.6 17.7
40 40
Fréq. (MHz) 495.0 500.0 500.0 500.0
Limite (dB) 7.3 7.2 7.2 7.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 19.7 16.3 35.1 36.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 5.5 3.6 500.0 486.0
Limite (dB) 57.8 61.4 -17.1 -16.0 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 19.7 17.1 35.3 37.1
Fréq. (MHz) 5.5 3.6 499.0 492.0 0 0
Limite (dB) 55.5 58.6 -19.9 -19.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 3,6 4,5 3,6 MHz MHz
RL (dB) 7.0 9.0 7.0 9.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 499.0 359.0 499.0 359.0 100 100
Limite (dB) 8.0 8.4 8.0 8.4 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 194
ID Câble: R.5 H2-F/08 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:04:07 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 11.1 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 44.3 44.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 191
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 4
Résistance (ohms) [Paire 3,6] 6.55
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 22.9 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 3,6-4,5 1,2-3,6 MHz


NEXT (dB) 11.1 11.5 13.7 11.5
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 387.0 500.0 499.0 500.0 100 100
Limite (dB) 30.3 26.7 26.7 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 13.0 12.0 13.7 12.0
Fréq. (MHz) 378.0 500.0 500.0 500.0 40 40

Limite (dB) 27.9 23.8 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 15.1 14.9 15.4 14.9
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 238.0 487.0 474.0 487.0 100 100
Limite (dB) 16.7 10.4 10.7 10.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.3 17.2 17.4 17.2
40 40
Fréq. (MHz) 466.0 488.0 474.0 488.0
Limite (dB) 7.8 7.4 7.7 7.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 3,6-4,5 1,2-3,6 MHz MHz
ACR-N (dB) 17.4 16.9 37.1 34.4 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 4.6 5.5 499.0 500.0
Limite (dB) 59.3 57.8 -17.0 -17.1 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.5 17.6 36.6 34.9
Fréq. (MHz) 5.0 5.5 500.0 500.0 0 0
Limite (dB) 56.3 55.5 -20.0 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 3,6 4,5 MHz MHz
RL (dB) 7.0 7.5 7.0 7.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 379.0 382.0 379.0 382.0 100 100
Limite (dB) 8.2 8.2 8.2 8.2 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 195
ID Câble: R.5 H2-F/09 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 14:04:54 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.3 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 43.1 43.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 186
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 4
Résistance (ohms) [Paire 3,6] 6.44
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 23.3 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 9.3 12.0 9.3 12.2
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 488.0 438.0 488.0 499.0 100 100
Limite (dB) 27.0 28.6 27.0 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 9.5 11.8 9.5 12.1
Fréq. (MHz) 487.0 438.0 487.0 491.0 40 40

Limite (dB) 24.2 25.7 24.2 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 16.1 16.4 16.7 16.8
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 235.0 242.0 454.0 495.0 100 100
Limite (dB) 16.8 16.5 11.0 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 18.4 18.2 18.9 18.2
40 40
Fréq. (MHz) 454.0 471.0 500.0 471.0
Limite (dB) 8.0 7.7 7.2 7.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 16.4 17.9 33.1 35.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 5.3 5.4 499.0 500.0
Limite (dB) 58.2 58.0 -17.0 -17.1 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.6 18.5 32.4 35.8
Fréq. (MHz) 5.3 5.5 487.0 500.0 0 0
Limite (dB) 55.9 55.5 -18.9 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 3,6 3,6 3,6 MHz MHz
RL (dB) 6.8 5.4 6.8 5.4 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 406.0 450.0 406.0 450.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 196
ID Câble: R.5 H2-F/15 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 16:09:09 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 8.7 dB (NEXT 3,6-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 29.4 29.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 127
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 3
Résistance (ohms) [Paire 4,5] 4.40
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 29.6 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-4,5 3,6-4,5 3,6-4,5 1,2-3,6 MHz


NEXT (dB) 8.7 12.2 8.7 13.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 484.0 81.8 484.0 493.0 100 100
Limite (dB) 27.1 43.3 27.1 26.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 9.5 12.6 9.5 12.6
Fréq. (MHz) 500.0 493.0 500.0 493.0 40 40

Limite (dB) 23.8 24.0 23.8 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.9 14.8 15.8 15.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 348.0 345.0 406.0 389.0 100 100
Limite (dB) 13.4 13.4 12.0 12.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.7 17.6 17.7 18.6
40 40
Fréq. (MHz) 455.0 348.0 455.0 484.0
Limite (dB) 8.0 10.4 8.0 7.5 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 3,6-4,5 1,2-3,6 MHz MHz
ACR-N (dB) 16.4 15.5 39.4 42.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.6 5.0 500.0 493.0
Limite (dB) 61.4 58.6 -17.1 -16.5 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 16.1 16.3 39.1 42.0
Fréq. (MHz) 3.8 4.1 500.0 493.0 0 0
Limite (dB) 58.6 58.0 -20.0 -19.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 3,6 4,5 MHz MHz
RL (dB) 7.8 10.5 7.8 10.5 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 365.0 473.0 365.0 473.0 100 100
Limite (dB) 8.4 8.0 8.4 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 197
ID Câble: R.5 H2-F/16 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 16:08:00 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 8.7 dB (NEXT 3,6-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 29.4 29.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 127
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 3
Résistance (ohms) [Paire 4,5] 4.40
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 29.5 40
Fréquence (MHz) [Paire 3,6] 499.0
30
Limite (dB) [Paire 3,6] 43.7
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-4,5 1,2-3,6 3,6-4,5 1,2-3,6 MHz


NEXT (dB) 8.7 12.7 9.3 12.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 478.0 499.0 499.0 499.0 100 100
Limite (dB) 27.3 26.7 26.7 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 9.9 12.6 10.3 12.6
Fréq. (MHz) 429.0 500.0 498.0 500.0 40 40

Limite (dB) 26.1 23.8 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.8 15.0 15.2 15.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 347.0 355.0 388.0 404.0 100 100
Limite (dB) 13.4 13.2 12.4 12.1 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.5 17.1 18.1 17.1
40 40
Fréq. (MHz) 388.0 457.0 450.0 457.0
Limite (dB) 9.4 8.0 8.1 8.0 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 3,6-4,5 1,2-3,6 MHz MHz
ACR-N (dB) 18.4 17.4 39.3 42.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.0 5.1 499.0 499.0
Limite (dB) 61.9 58.4 -17.0 -17.0 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 19.6 18.9 39.7 42.1
Fréq. (MHz) 3.8 5.0 498.0 499.0 0 0
Limite (dB) 58.6 56.3 -19.8 -19.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 7,8 3,6 7,8 3,6 MHz MHz
RL (dB) 7.7 9.3 9.1 9.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 130.0 383.0 361.0 383.0 100 100
Limite (dB) 12.9 8.2 8.4 8.2 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 198
ID Câble: R.5 H2-F/17 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 16:08:37 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.8 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 30.3 30.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 131
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 3
Résistance (ohms) [Paire 4,5] 4.58
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 29.3 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 10.8 12.1 12.2 12.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 419.0 436.0 495.0 496.0 100 100
Limite (dB) 29.2 28.6 26.8 26.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 11.4 12.1 12.0 12.3
Fréq. (MHz) 456.0 484.0 499.0 499.0 40 40

Limite (dB) 25.1 24.2 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.2 14.4 15.2 16.6
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 344.0 348.0 395.0 444.0 100 100
Limite (dB) 13.5 13.4 12.3 11.2 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.0 17.2 18.4 18.1
40 40
Fréq. (MHz) 344.0 348.0 463.0 444.0
Limite (dB) 10.5 10.4 7.9 8.2 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 17.2 17.8 41.3 41.7 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.8 3.6 495.0 496.0
Limite (dB) 61.1 61.4 -16.7 -16.8 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.5 18.3 41.2 41.5
Fréq. (MHz) 3.9 4.1 499.0 499.0 0 0
Limite (dB) 58.5 58.0 -19.9 -19.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 7,8 4,5 3,6 MHz MHz
RL (dB) 7.8 8.6 7.8 9.1 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 385.0 35.0 385.0 499.0 100 100
Limite (dB) 8.1 18.3 8.1 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 199
ID Câble: R.5 H2-F/19 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:56:28 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.8 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 35.5 35.5 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 153
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 3
Résistance (ohms) [Paire 4,5] 5.22
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 26.9 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 4,5-7,8 1,2-3,6 4,5-7,8 MHz


NEXT (dB) 9.8 12.8 10.2 12.8
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 296.0 461.0 484.0 461.0 100 100
Limite (dB) 34.1 27.8 27.1 27.8 80 80
Pire paire 3,6 4,5 3,6 4,5
60 60
PS NEXT (dB) 11.0 12.9 11.1 15.1
Fréq. (MHz) 483.0 291.0 484.0 500.0 40 40

Limite (dB) 24.3 31.6 24.2 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-1,2 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 15.0 15.5 16.0 16.5
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 293.0 292.0 334.0 336.0 100 100
Limite (dB) 14.9 14.9 13.7 13.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.8 17.8 19.2 19.5
40 40
Fréq. (MHz) 299.0 1.0 366.0 360.0
Limite (dB) 11.7 61.2 9.9 10.1 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 17.1 17.6 36.4 41.1 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.6 4.3 484.0 494.0
Limite (dB) 61.4 60.0 -15.8 -16.6 80 80

Pire paire 3,6 3,6 3,6 4,5


40 40
PS ACR-N (dB) 18.1 18.6 37.3 42.0
Fréq. (MHz) 3.6 4.0 484.0 500.0 0 0
Limite (dB) 58.6 58.3 -18.7 -20.0
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 3,6 3,6 4,5 MHz MHz
RL (dB) 7.3 9.0 7.3 10.0 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 482.0 20.6 482.0 415.0 100 100
Limite (dB) 8.0 19.4 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 200
ID Câble: R.5 H2-F/20 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 16:52:51 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 8.3 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 32.9 32.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 142
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 3
Résistance (ohms) [Paire 3,6] 4.89
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 28.2 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 8.3 11.1 8.3 11.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 439.0 497.0 439.0 497.0 100 100
Limite (dB) 28.5 26.7 28.5 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 9.7 11.4 10.8 11.4
Fréq. (MHz) 439.0 499.0 483.0 499.0 40 40

Limite (dB) 25.7 23.8 24.3 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 15.3 15.1 15.4 15.2
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 299.0 340.0 355.0 341.0 100 100
Limite (dB) 14.7 13.6 13.2 13.5 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.8 17.8 18.4 19.2
40 40
Fréq. (MHz) 355.0 340.0 392.0 410.0
Limite (dB) 10.2 10.6 9.3 8.9 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 17.1 17.3 37.2 39.1 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.6 5.1 483.0 497.0
Limite (dB) 61.4 58.4 -15.7 -16.9 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.9 18.2 39.1 39.5
Fréq. (MHz) 3.9 4.3 493.0 499.0 0 0
Limite (dB) 58.5 57.7 -19.4 -19.9
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 3,6 3,6 3,6 MHz MHz
RL (dB) 6.2 8.8 6.2 8.8 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 329.0 500.0 329.0 500.0 100 100
Limite (dB) 8.8 8.0 8.8 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 201
ID Câble: R.5 H2-F/21 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:55:22 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.4 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 32.2 32.2 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 139
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 3
Résistance (ohms) [Paire 4,5] 4.79
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 28.4 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 10.4 11.3 11.4 12.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 439.0 440.0 492.0 496.0 100 100
Limite (dB) 28.5 28.5 26.9 26.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 11.1 12.2 12.0 12.2
Fréq. (MHz) 440.0 492.0 495.0 492.0 40 40

Limite (dB) 25.7 24.0 23.9 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 15.4 15.3 15.7 15.4
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 339.0 295.0 358.0 346.0 100 100
Limite (dB) 13.6 14.8 13.1 13.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.4 17.2 19.0 19.5
40 40
Fréq. (MHz) 1.1 1.0 441.0 421.0
Limite (dB) 60.2 61.2 8.3 8.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 18.1 20.7 39.4 40.9 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.9 7.6 492.0 496.0
Limite (dB) 60.8 54.9 -16.5 -16.8 80 80

Pire paire 1,2 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.9 20.2 40.1 40.1
Fréq. (MHz) 3.9 4.1 495.0 492.0 0 0
Limite (dB) 58.5 58.0 -19.6 -19.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 3,6 4,5 MHz MHz
RL (dB) 5.1 8.9 5.1 8.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 464.0 481.0 464.0 481.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 202
ID Câble: R.5 H2-F/23 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:51:59 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 8.4 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 28.4 28.4 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 123
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 3
Résistance (ohms) [Paire 3,6] 4.24
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 30.1 40
Fréquence (MHz) [Paire 3,6] 500.0
30
Limite (dB) [Paire 3,6] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 8.4 10.9 8.4 10.9
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 458.0 496.0 458.0 496.0 100 100
Limite (dB) 27.9 26.8 27.9 26.8 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 9.6 11.3 10.4 11.3
Fréq. (MHz) 454.0 496.0 487.0 496.0 40 40

Limite (dB) 25.2 23.9 24.2 23.9 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 3,6-1,2 1,2-3,6 MHz MHz
ACR-F (dB) 14.9 14.8 15.1 15.2
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 340.0 356.0 438.0 438.0 100 100
Limite (dB) 13.6 13.2 11.4 11.4 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.2 17.1 17.2 17.1
40 40
Fréq. (MHz) 440.0 438.0 440.0 438.0
Limite (dB) 8.3 8.4 8.3 8.4 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 14.0 15.1 39.0 41.1 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.9 3.8 486.0 496.0
Limite (dB) 60.8 61.1 -16.0 -16.8 80 80

Pire paire 1,2 1,2 3,6 3,6


40 40
PS ACR-N (dB) 15.3 16.4 40.0 41.3
Fréq. (MHz) 4.0 4.0 487.0 496.0 0 0
Limite (dB) 58.3 58.3 -18.9 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 4,5 4,5 4,5 MHz MHz
RL (dB) 3.7 8.3 3.7 8.3 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 437.0 438.0 437.0 438.0 60 100
Limite (dB) 8.0 8.0 8.0 8.0 50 80
Conforme aux normes de réseaux: 40
60
10BASE-T 100BASE-TX 100BASE-T4 30
1000BASE-T 2.5GBASE-T 5GBASE-T 40
20
10GBASE-T ATM-25 ATM-51 20
ATM-155 100VG-AnyLan TR-4 10
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 203
ID Câble: R.5 H2-F/24 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 15:54:03 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.4 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 29.6 29.6 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 127
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 2
Résistance (ohms) [Paire 4,5] 4.40
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 28.8 40
Fréquence (MHz) [Paire 3,6] 489.0
30
Limite (dB) [Paire 3,6] 43.2
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 9.4 12.8 9.8 13.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 435.0 473.0 497.0 497.0 100 100
Limite (dB) 28.7 27.4 26.7 26.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.0 13.2 10.0 13.3
Fréq. (MHz) 497.0 473.0 497.0 493.0 40 40

Limite (dB) 23.8 24.6 23.8 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.7 14.8 15.1 15.7
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 350.0 346.0 403.0 442.0 100 100
Limite (dB) 13.3 13.4 12.1 11.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.2 17.4 17.9 17.4
40 40
Fréq. (MHz) 403.0 442.0 449.0 442.0
Limite (dB) 9.1 8.3 8.1 8.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-N (dB) 14.8 16.9 39.1 42.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.9 3.8 497.0 497.0
Limite (dB) 60.8 61.1 -16.9 -16.9 80 80

Pire paire 1,2 1,2 3,6 3,6


40 40
PS ACR-N (dB) 15.7 17.0 39.2 42.4
Fréq. (MHz) 3.9 3.9 497.0 493.0 0 0
Limite (dB) 58.5 58.5 -19.7 -19.4
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 3,6 4,5 MHz MHz
RL (dB) 6.0 9.1 6.0 9.1 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 487.0 489.0 487.0 489.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 204
ID Câble: R.5 H2-G/01 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:21:47 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 9.7 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 21.3 21.3 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 92
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 2
Résistance (ohms) [Paire 4,5] 3.21
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 32.8 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 1,2-3,6 MHz


NEXT (dB) 9.7 11.8 9.7 12.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 490.0 79.3 490.0 435.0 100 100
Limite (dB) 26.9 43.5 26.9 28.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.1 12.9 10.2 14.3
Fréq. (MHz) 490.0 95.8 491.0 491.0 40 40

Limite (dB) 24.1 39.6 24.0 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-1,2 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 14.5 15.0 14.6 15.0
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 488.0 496.0 496.0 496.0 100 100
Limite (dB) 10.4 10.3 10.3 10.3 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 16.9 17.6 16.9 17.6
40 40
Fréq. (MHz) 496.0 497.0 496.0 497.0
Limite (dB) 7.3 7.3 7.3 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 4,5-7,8 MHz MHz
ACR-N (dB) 16.0 15.9 42.2 47.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.3 2.9 490.0 500.0
Limite (dB) 61.8 62.0 -16.3 -17.1 80 80

Pire paire 4,5 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.5 17.8 42.7 46.8
Fréq. (MHz) 3.3 3.5 491.0 491.0 0 0
Limite (dB) 58.8 58.7 -19.3 -19.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 4,5 3,6 4,5 3,6 MHz MHz
RL (dB) 8.3 8.1 8.6 8.1 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 83.5 417.0 440.0 417.0 100 100
Limite (dB) 14.8 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 205
ID Câble: R.5 H2-G/02 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:24:19 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.0 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 21.1 21.1 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 91
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 2
Résistance (ohms) [Paire 7,8] 3.20
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 3,6] 32.8 40
Fréquence (MHz) [Paire 3,6] 494.0
30
Limite (dB) [Paire 3,6] 43.4
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 10.0 11.0 10.0 13.1
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 496.0 85.0 496.0 486.0 100 100
Limite (dB) 26.8 43.0 26.8 27.1 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.1 12.9 10.4 13.4
Fréq. (MHz) 486.0 85.0 497.0 497.0 40 40

Limite (dB) 24.2 40.5 23.8 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 1,2-3,6 MHz MHz
ACR-F (dB) 14.4 14.3 14.5 14.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 446.0 472.0 500.0 472.0 100 100
Limite (dB) 11.2 10.7 10.2 10.7 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.0 16.8 17.0 16.8
40 40
Fréq. (MHz) 500.0 472.0 500.0 472.0
Limite (dB) 7.2 7.7 7.2 7.7 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 15.8 16.1 43.1 45.8 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.5 7.3 496.0 486.0
Limite (dB) 61.7 55.3 -16.8 -16.0 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 17.1 17.2 43.4 46.4
Fréq. (MHz) 4.6 6.1 497.0 497.0 0 0
Limite (dB) 57.0 54.5 -19.7 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 4,5 4,5 4,5 MHz MHz
RL (dB) 8.8 9.2 10.2 9.2 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 111.5 420.0 476.0 420.0 100 100
Limite (dB) 13.5 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 206
ID Câble: R.5 H2-G/03 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:25:02 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 11.6 dB (NEXT 3,6-4,5) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 23.9 23.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 103
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 2
Résistance (ohms) [Paire 4,5] 3.61
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 31.9 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 11.7 11.6 11.9 11.7
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 461.0 485.0 500.0 490.0 100 100
Limite (dB) 27.8 27.1 26.7 26.9 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 11.8 11.8 11.8 11.8
Fréq. (MHz) 500.0 491.0 500.0 491.0 40 40

Limite (dB) 23.8 24.0 23.8 24.0 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 3,6-1,2 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 13.6 13.9 13.8 14.1
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 459.0 459.0 495.0 495.0 100 100
Limite (dB) 11.0 11.0 10.3 10.3 80 80
Pire paire 3,6 1,2 3,6 1,2
60 60
PS ACR-F (dB) 16.0 16.8 16.0 17.0
40 40
Fréq. (MHz) 495.0 459.0 495.0 495.0
Limite (dB) 7.3 8.0 7.3 7.3 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 16.8 16.5 43.9 43.2 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.5 6.4 500.0 490.0
Limite (dB) 61.7 56.5 -17.1 -16.3 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.3 18.4 43.8 43.5
Fréq. (MHz) 4.0 5.6 500.0 491.0 0 0
Limite (dB) 58.3 55.3 -20.0 -19.3
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 3,6 3,6 3,6 MHz MHz
RL (dB) 7.2 6.8 8.1 6.8 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 192.5 375.0 375.0 375.0 100 100
Limite (dB) 11.2 8.3 8.3 8.3 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 207
ID Câble: R.5 H2-G/04 Résumé de test: CORRECT
Limite: TIA Cat 6A Perm. Link Unité principale: Versiv Unité distante: Versiv
Version des limites: V7.5 Num. Sér.: 3126162 Num. Sér.: 3122062
Date / Heure: 20/05/2023 13:25:36 Version du logiciel: V6.5 Build 5 Version du logiciel: V6.5 Build 5
Opérateur: MEE Date d'étalonnage: 15/06/2020 Date d'étalonnage: 15/06/2020
Marge de Sécurité 10.0 dB (NEXT 1,2-3,6) Adaptateur: DSX-5000 (DSX-PLA004) Adaptateur: DSX-5000R (DSX-PLA004)
Type de Câble: GGM CAT6A F/FTP LSZH-FR Num. Sér.: 20347674 Num. Sér.: 20347676
NVP: 79.0%

Longueur (m), Lim. 90.0 [Paire 1,2] 23.9 23.9 m


Délai de prop. (ns), Lim. 498 [Paire 3,6] 103
Ecart entre paires (ns), Lim. 44 [Paire 3,6] 2
Résistance (ohms) [Paire 4,5] 3.61
Schéma de câblage (T568B) Perte d'insertion (dB)
60
CORRECT
50
Perte d'insertion Marge (dB) [Paire 4,5] 31.9 40
Fréquence (MHz) [Paire 4,5] 500.0
30
Limite (dB) [Paire 4,5] 43.8
20

Pire marge Pire valeur 10


0
CORRECT MAIN SR MAIN SR 0 250 500

Pire paire 1,2-3,6 3,6-4,5 1,2-3,6 3,6-4,5 MHz


NEXT (dB) 10.0 13.1 10.3 13.3
NEXT (dB) NEXT @ Unité distante (dB)
Fréq. (MHz) 420.0 100.0 493.0 487.0 100 100
Limite (dB) 29.2 41.8 26.9 27.0 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS NEXT (dB) 10.8 13.7 10.8 14.0
Fréq. (MHz) 493.0 442.0 493.0 497.0 40 40

Limite (dB) 24.0 25.6 24.0 23.8 20 20

CORRECT MAIN SR MAIN SR 0 0


0 250 500 0 250 500
Pire paire 1,2-3,6 1,2-3,6 1,2-3,6 3,6-1,2 MHz MHz
ACR-F (dB) 14.5 14.6 14.8 15.3
ACR-F (dB) ACR-F @ Unité distante (dB)
Fréq. (MHz) 451.0 435.0 476.0 476.0 100 100
Limite (dB) 11.1 11.4 10.6 10.6 80 80
Pire paire 3,6 3,6 3,6 3,6
60 60
PS ACR-F (dB) 17.1 17.3 17.5 17.9
40 40
Fréq. (MHz) 453.0 435.0 491.0 479.0
Limite (dB) 8.1 8.4 7.4 7.6 20 20

0 0
N/V MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6-4,5 3,6-4,5 1,2-3,6 3,6-4,5 MHz MHz
ACR-N (dB) 17.4 17.6 42.1 45.6 ACR-N (dB) ACR-N @ Unité distante (dB)
Fréq. (MHz) 3.8 6.1 493.0 497.0
Limite (dB) 61.1 56.8 -16.5 -16.9 80 80

Pire paire 3,6 3,6 3,6 3,6


40 40
PS ACR-N (dB) 18.2 18.6 42.6 45.8
Fréq. (MHz) 4.5 5.5 493.0 497.0 0 0
Limite (dB) 57.2 55.5 -19.4 -19.7
-40 -40
CORRECT MAIN SR MAIN SR 0 250 500 0 250 500
Pire paire 3,6 3,6 3,6 3,6 MHz MHz
RL (dB) 8.4 8.9 8.4 8.9 RL (dB) RL @ Unité distante (dB)
Fréq. (MHz) 397.0 398.0 397.0 398.0 100 100
Limite (dB) 8.0 8.0 8.0 8.0 80 80
Conforme aux normes de réseaux: 60 60
10BASE-T 100BASE-TX 100BASE-T4
1000BASE-T 2.5GBASE-T 5GBASE-T 40 40
10GBASE-T ATM-25 ATM-51 20 20
ATM-155 100VG-AnyLan TR-4
TR-16 Active TR-16 Passive 0 0
0 250 500 0 250 500
MHz MHz

LinkWare™ PC Version 10.5

Projet: HOPITAL NECKER H6


HOPITAL NECKER H6 22 05 2023 correct.flw Page 208