Project Job Ref.

Structure Sheet no.


Page 1/1
Calc. by Date Chk'd by Date App'd by Date
asus 28/11/2021 26/11/2021 26/11/2021

SB 1/G/1-1/H/1

Restraints
Source Distance / LTB Top / LTB LTB Btm / LTB Strut Major Strut Strut Minor Strut
Length Sub-Beam Top Sub-Beam Btm / Sub- Major / Sub-Beam Minor
[m] Factor Factor Beam Factor Factor
support 0.000 ● ● ● ●
sub-beam 9.250 ● 1.000 1.000 1.000 1.000
support 9.250 ● ● ● ●
Static
Summary W 530x66
Design Condition # Design Value Design Capacity Units U.R. Status
Axial Classification Unknown - - - Not required
Flexural Classification 7 Compact - - -
Pass
Shear Major 7 107.7 967.2 kN 0.111
Pass
Shear Minor No Significant Forces kN - Not required
Flexure Major 7 322.1 484.0 kNm 0.666
Pass
Flexure Minor No Significant Forces kNm - Not required
Axial Tension No Significant Forces kN - Not required
Axial Compression No Significant Forces kN - Not required
Combined Forces No Significant Forces - - Not required
Torsion No Significant Forces - - Not required
Deflection Self weight 7 0.9 - mm - -
Deflection Slab 7 17.4 38.5 mm 0.452
Pass
Deflection Dead 7 3.6 25.7 mm 0.141
Pass
Deflection Live 7 9.0 25.7 mm 0.352
Pass
Deflection Total 7 31.0 38.5 mm 0.803
Pass

Tekla Structural Designer, version: 21.3.0.72 (mt)