You are on page 1of 4

INSTALLATION INSTRUCTIONS

Page 1 of 2 Analogue Meter Relays


Ref: IW244/077 – Rev 6 – Apr 05 Switchboard 077 Series &
DIN Panel Mounted 244 Series

Products Covered Maintenance


244-30* 077-30* * = Any letter or number All units are fully calibrated before despatch and therefore no
adjustments are required. During routine servicing and
inspection of equipment the unit should be inspected to normal
Installation
standards for this class of equipment. For example remove
Units should be mounted in a reasonably stable ambient
accumulations of dust and check connections for tightness and
temperature within the range 0 to 60°C.
corrosion. In the event of a fault occurring and repair being
The units should not be mounted where they will be
necessary, it is recommended that the instruments be returned
subjected to excessive sunlight and vibration should be kept the factory or to the nearest Crompton Instruments Sales and
to a minimum. Connection wires should be sized to comply
Service Centre.
with local regulations and preferably should be fitted with
tags for the terminals provided. Labels are fixed to the units
Electromagnetic Compatibility
and carry connection-input information. The fitting of
This unit has been designed to provide protection against EM
external fuses is recommended since there are no internal
(electro-magnetic) interference in line with requirements of EU
fuses.
and other regulations. Precautions necessary to provide
proper operation of this and adjacent equipment will be
Set Point Operation
installation dependent and so the following can only be general
To obtain optimum accuracy the red pointers must be
guidance:-
adjusted upscale to the desired scale value.
• Avoid routing wiring to this unit alongside cables and
Example on Meter Scaled 0/100%:- products that are, or could be, a source of interference.
• If the desired set point is 20%, adjust the red pointer • The auxiliary supply to the unit should not be subject to
below this level, eg: 15% excessive interference. In some cases, a supply line filter
• Adjust the red pointer clockwise (upscale) to 20% may be required.
• To protect the product against incorrect operation or
permanent damage, surge transients must be controlled. It
is good EMC practice to suppress differential surges to
2kV or less at the source. The unit has been designed to
automatically recover from typical transients, however in
extreme circumstances it may be necessary to temporarily
disconnect the auxiliary supply for a period of greater than
5 seconds to restore correct operation.
• Screened communication and small signal leads are
recommended and may be required. These and other
connecting leads may require the fitting of RF suppression
components, such as ferrite absorbers, line filters etc., if
RF fields cause problems.
It is good practice to install sensitive electronic instruments that
are performing critical functions in EMC enclosures that protect
Fusing and Connections against electrical interference causing a disturbance in function.
1. This unit must be fitted with external fuses in voltage
and auxiliary supply lines. Warning
2. Voltage input lines must be fused with a quick blow • During normal operation, voltages hazardous to life may
fuse 1A maximum. be present at some of the terminals of this unit.
3. Auxiliary supply lines must be fused with a slow blow Installation and servicing should be performed only by
fuse rated 1A maximum. qualified, properly trained personnel' abiding by local
4. Choose fuses of a type and with a breaking capacity regulations. Ensure all supplies are de-energised before
appropriate to the supply and in accordance with local attempting connection or other procedures.
regulations. • It is recommended adjustments be made with the supplies
5. Where fitted, CT secondaries must be grounded in de-energised, but if this is not possible, then extreme
accordance with local regulations. caution should be exercised.
• Terminals should not be user accessible after installation
Screw Torque and external installation provisions must be sufficient to
Main terminal screws should be tightened to 1.35Nm or 1.0 prevent hazards under fault conditions.
ft/lbf only. Detachable terminal connector screws should be • This unit is not intended to function as part of a system
tightened to 0.9Nm or 0.7 ft/lbf only. Where fitted, terminal providing the sole means of fault protection - good
covers are held in place by miniature self tapping screws into engineering practice dictates that any critical function be
plastic. These screws should be tightened by hand only, protected by at least two independent and diverse means.
sufficiently to secure the terminal cover and prevent it • Never open circuit the secondary winding of an energised
vibrating. current transformer.
Page 2 of 2 INSTALLATION INSTRUCTIONS
Ref: IW244/077 – Rev 6 – Apr 05 Analogue Meter Relays
Switchboard 077 Series &
DIN Panel Mounted 244 Series

077 Series Connections 244 Series Connections


L L
N 110V 230V

INPUT + DC -
+ -A Auxiliary

DC CURRENT INPUT ABOVE


100mA 8mm² M4 TERMINALS

077 Series Dimensions and Cut Out


3.38” (86mm) 1.19” (30mm)
4.31” (109.5mm)
3.38” (86mm)
4.31” (109.5mm)
3.79” (96mm)

3.38” (86mm)

1.69” (42.9mm)
3.38” 4.06”
(86mm) 103mm
)

4 fixing holes 0.31”


1/4 -28 UNF Terminals (7.9mm) Diamter
Fixing Studs 10-32 UNF

244 Series Dimensions and Cut Out

Panel cut-out
96mm
96mm sq.2 92mm
(3.78”)
(3.78” sq.)
Max panel thickness (3.61”)
10mm (0.39”)

110mm 96mm 92mm


(4.32”) (3.78”) (3.61”)

The Information contained in these installation instructions is for use only by installers trained to make electrical power installations and is intended to describe the
correct method of installation for this product. However, Tyco Electronics has no control over the field conditions, which influence product installation.
It is the user's responsibility to determine the suitability of the installation method in the user's field conditions. Tyco Electronics' only obligations are those in Tyco
Electronics' standard Conditions of Sale for this product and in no case will Tyco Electronics be liable for any other incidental, indirect or consequential damages
arising from the use or misuse of the products. Crompton is a trademark.

Tyco Electronics UK Limited


Crompton Instruments
Freebournes Road, Witham, Essex, CM8 3AH, UK
Phone: +44 1376 509 509 Fax: +44 1376 509 511 http://energy.tycoelectronics.com
INSTALLATION INSTRUCTIONS

Page 1 of 2 Analogue Meter Relays


Ref: IW239 – Rev 8 – Nov 04 Panel Mounted 239 Series

Products Covered ConnectionS


239-30* * = any letter or number

Installation
The 239 meter relay may be mounted in a panel of any
thickness up to a maximum of 10mm. For thicker panels an
accessory clamp band is available. Consideration should be
given to the space required behind the unit to allow for
connecting cables. Units should be mounted in a reasonably
stable ambient temperature and in any event where the
temperature is within the range 0 to 60°C. The unit should
not be mounted where it is subjected to excessive sunlight
and also vibration should be kept to a minimum. Connection
wires should be sized to comply with local regulations and
preferably should be terminated in tags for the terminals
provided. Labels are fixed to the unit and carry connection
information and data including input voltage, input current
and supply and application as appropriate. The delay circuits drive double pole double throw output relays.
These products do not have internal fuses therefore external LED’s mounted on the front fascia show the operational state
fuses must be used for safety protection under fault of the relays.
conditions.
Terminal 1 Signal N or -VE input
Set Point Operation
Terminal 2 Signal L or +VE input
To obtain optimum accuracy the red pointers must be Terminal 3,4 RTD or thermocouple input
adjusted upscale to the desired scale value.
Terminal 4 Tap for dual auxiliary supply models
Example on Meter Scaled 0/100%:- Terminal 5 Auxiliary Supply Neutral (-ve if D.C.)
• If the desired set point is 20%, adjust the red pointer Terminal 6 Auxiliary Supply Live (+ve if D.C.)
below this level, eg: 15%
• Adjust the red pointer clockwise (upscale) to 20%
One Setpoint Two Setpoints
Upscale Downscale Upscale Downscale
Input Signal Conditioning Setpoint Setpoint Setpoint Setpoint
AC current transformers, dc shunts, resistors and diodes are (16 NC NC NC
used as appropriate to provide an input signal of 20mV for (15 C C C
full-scale deflection. This is then amplified to supply a 1mA High (18 NO NO NO
signal to the analogue meter. Relay (36 NC NC NC
(35 C C C
(38 NO NO NO
Delays (26 NC NC NC
The comparator outputs are each passed to a time delay (25 C C C
Low (28 NO NO NO
circuit with a delay time that can be varied over the range of
Relay (46 NC NC NC
0.3 to 20 seconds. The purpose of these is to allow the user
(45 C C C
to arrange for a delay in relay operation should the
(48 NO NO NO
monitored signal spuriously drop or rise around the set point.
This avoids a false alarm being triggered.
Fusing and Connections
Power supply
1. This unit must be fitted with external fuses in voltage and
Normally provided by a multi-tapped transformer, which also auxiliary supply lines.
provides isolation of the input from ground or the supply. For 2. Voltage input lines must be fused with a quick blow fuse
dc power operation, either:- 1A maximum.
a) An inverter board is wired internally to provide the 3. Auxiliary supply lines must be fused with a slow blow fuse
supplies required, or rated 1A maximum.
b) A 12V-0V-12V ac or dc source may be used. This 4. Choose fuses of a type and with a breaking capacity
option uses no inverter and avoids any problems appropriate to the supply and in accordance with local
associated with the switching noise generated by it. It regulations.
should be noted that this option does not isolate the 5. Where fitted, CT secondaries must be grounded in
input from the external signal. accordance with local regulations.
Page 2 of 2 INSTALLATION INSTRUCTIONS
Ref: IW239 – Rev 8 – Nov 04 Analogue Meter Relays
Panel Mounted 239 Series

Screw Torque Dimensions and Panel Cut Out


Main terminal screws should be tightened to 1.35Nm or 1.0 ft/lbf only.
Detachable terminal connector screws should be tightened to 0.9Nm or 0.7
ft/lbf only. Where fitted, terminal covers are held in place by miniature self
tapping screws into plastic. These screws should be tightened by hand only,
sufficiently to secure the terminal cover and prevent it vibrating.

Maintenance
Unless a fault develops, the unit requires little attention. During routine
servicing and inspection of the associated equipment, the device should be
inspected to normal standards for this class of equipment. For example
remove accumulations of dust and check all connections for tightness and
corrosion.

Electromagnetic Compatibility
This unit has been designed to provide protection against EM (electro-
magnetic) interference in line with requirements of EU and other regulations.
Precautions necessary to provide proper operation of this and adjacent
equipment will be installation dependent and so the following can only be
general guidance:-
• Avoid routing wiring to this unit alongside cables and products that are, or
could be, a source of interference.
• The auxiliary supply to the unit should not be subject to excessive
interference. In some cases, a supply line filter may be required.
• To protect the product against incorrect operation or permanent damage,
surge transients must be controlled. It is good EMC practice to suppress
differential surges to 2kV or less at the source. The unit has been
designed to automatically recover from typical transients, however in
extreme circumstances it may be necessary to temporarily disconnect the
auxiliary supply for a period of greater than 5 seconds to restore correct
operation.
• Screened communication and small signal leads are recommended and
may be required. These and other connecting leads may require the fitting
of RF suppression components, such as ferrite absorbers, line filters etc.,
if RF fields cause problems.
• It is good practice to install sensitive electronic instruments that are
performing critical functions in EMC enclosures that protect against
electrical interference causing a disturbance in function.

Warning
• During normal operation, voltages hazardous to life may be present at
some of the terminals of this unit. Installation and servicing should be
performed only by qualified, properly trained personnel' abiding by local
regulations. Ensure all supplies are de-energised before attempting
connection or other procedures.
• It is recommended adjustments be made with the supplies de-energised,
but if this is not possible, then extreme caution should be exercised.
• Terminals should not be user accessible after installation and external
installation provisions must be sufficient to prevent hazards under fault
conditions.
• This unit is not intended to function as part of a system providing the sole
means of fault protection - good engineering practice dictates that any
critical function be protected by at least two independent and diverse
means.
• Never open circuit the secondary winding of an energised current
transformer.

The Information contained in these installation instructions is for use only by installers trained to make electrical power installations and is intended to describe the
correct method of installation for this product. However, Tyco Electronics has no control over the field conditions, which influence product installation.
It is the user's responsibility to determine the suitability of the installation method in the user's field conditions. Tyco Electronics' only obligations are those in Tyco
Electronics' standard Conditions of Sale for this product and in no case will Tyco Electronics be liable for any other incidental, indirect or consequential damages
arising from the use or misuse of the products. Crompton is a trademark.

Tyco Electronics UK Limited


Crompton Instruments
Freebournes Road, Witham, Essex, CM8 3AH, UK
Phone: +44 1376 509 509 Fax: +44 1376 509 511 http://energy.tycoelectronics.com

You might also like