Professional Documents
Culture Documents
unielon
On
27/11/2021
Digest
Paul Blackmore
LR = 8.4 m
H = 8.0 m
Licensed copy from CIS: unielon, University of East London, 27/11/2021, Uncontrolled Copy.
45°
Lw = 8.0 m
α = 22.5° 10 m
20 m
H = 6.3 m
30 m
Building height, 8 m (when considering wind loads on the side walls, a building height of 6.3 m may be used)
h (m)
Direction (˚N) 0 30 60 90 120 150 180 210 240 270 300 330 360
Directional factor, 0.78 0.73 0.73 0.74 0.73 0.80 0.85 0.93 1.00 0.99 0.91 0.82 0.78
cdir
Distance to shore 200 128 110 110 200 200 200 200 200 200 112 200 200
(km)
Distance to town 15.5 12.5 9.5 3.5 4.5 1.5 1.6 3.5 2.5 2.5 1.6 5.5 15.5
(km)
Displacement 3.6 3.6 3.6 3.6 6.4 6.4 5.6 5.6 5.6 5.6 6.4 3.6 3.6
height,
hdis (m)
Effective height, 4.4 4.4 4.4 4.4 3.2 3.2 3.2 3.2 3.2 3.2 3.2 4.4 4.4
h – hdis (m)
Basic wind 19.2 18.0 18.0 18.2 18.0 19.7 20.9 22.9 24.6 24.4 22.4 20.2 19.2
velocity, vb (m/s)
Basic velocity 226.4 198.3 198.3 203.8 198.3 238.2 268.9 321.9 372.2 364.8 308.2 250.2 226.4
pressure, qb (Pa)
Exposure factor, 1.833 1.833 1.833 1.833 1.654 1.654 1.654 1.654 1.654 1.654 1.654 1.833 1.833
ce (z)
Exposure 0.692 0.699 0.709 0.749 0.698 0.749 0.745 0.708 0.723 0.723 0.745 0.730 0.692
correction factor,
ce,T
Zone C C C C C C C C C C C C C
(for size factor)
Peak velocity 287.2 254.1 257.7 279.8 229.0 295.1 331.3 376.9 445.1 436.2 379.8 334.9 287.2 Op.
pressure, 1
qp(z) (Pa)
The choices made for determining peak velocity pressure qp(z) for Quadrant SW.
The choices made for determining peak velocity pressure qp(z) for the single worst case.
4 Part 2: Worked examples – wind loads on a two-storey house and 128 m tower DG 436-2
For Option 2 the shortest distance to the shore and to the edge
of the town and values of have and x are determined for each 90º
Determining pressure coefficients
sector. This option gives a good compromise between simplicity
In this example the peak velocity pressures calculated using
and conservatism.
Option 2 will be used for the two orthogonal axes (Figure 3).
These are:
For Option 3 the worst combination of parameters is taken
irrespective of wind direction. This is the most conservative • wind parallel to the ridge (SW and NE wind directions)
option but can be useful when initially assessing the wind loads. • wind perpendicular to the ridge (NW and SE wind
directions).
Licensed copy from CIS: unielon, University of East London, 27/11/2021, Uncontrolled Copy.
Wall parameters
Roof parameters
where the distance x to the faces of surrounding buildings The EN gives both positive and negative pressure coefficients
measured perpendicular to the wind direction is < e/4 or > e for most roof zones. The negative values will generally represent
(e is given in Table 2). For the NW direction x = 20 m so the worst-case roof cladding loads. The negative values should
funnelling can be disregarded. For the SW direction x = 4 m so be used when considering uplift loads on the roof and both the
funnelling will occur and the external pressure coefficients have positive and negative values should be used when considering
been taken as -1.6 (for Zone A) and -0.9 (for Zones B and C) from the overall alongwind loads acting on the building. The positive
NA Clause NA.2.27 Note e. values are likely to give the most onerous design case when
considering load combinations of wind + snow, wind + dead
load.
External pressure coefficients
Licensed copy from CIS: unielon, University of East London, 27/11/2021, Uncontrolled Copy.
The values of the pressure coefficients on the house walls are In practice it is not easy to determine the area of openings or
shown in Figures 4 and 5 (using NA Table NA.4) and on the roof permeability in a building. For that reason it is simpler to
in Figure 6 (using NA Tables NA.7a and NA.7b). The EN allows consider the area of the faces where the pressures are positive or
division by parts (EN Figure 7.4) based on the h/b ratio. For negative. The equation for μ then becomes:
h/b ≤ 1 no division is allowed, for 1 < h/b ≤ 2 the building may
be subdivided into two parts and for h/b > 2 the building may ∑ areas where cpe is negative or -0.0
μ=
be divided into two or more parts. In this example h/b < 1 for
∑ sum of all openings
both orthogonal directions, therefore division by parts is not
applicable. Note that in this example the effective height for
determining wall pressure coefficients has been taken as the In this example it is assumed that the walls and roof of the
ridge height for SW wind and as the eaves height for NW wind. house have similar permeability; this is a reasonable assumption
1.6 m
Leeward face (h/d = 0.79) Side face (isolated) Windward face (h/d = 0.79)
1.6 m
Windward face (h/d = 1.0) Side face (max funnelling) Leeward face (h/d = 1.0)
Figure 5: Wall pressure coefficients (cpe) for SW wind direction including funnelling
6 Part 2: Worked examples – wind loads on a two-storey house and 128 m tower DG 436-2
-0.8/+0.5
-0.45/+0.2 -0.45/+0.2
-0.65/+0.35
Ridge
Ridge
-0.3/+0.3 -1.1 -0.5
Licensed copy from CIS: unielon, University of East London, 27/11/2021, Uncontrolled Copy.
NW
wind
-0.6/+0.25 -0.6/+0.25
4.0 m
-0.8/+0.5
2.1 m
0.8 m
for modern airtight buildings. Where a face has more or less NW wind
permeability (perhaps a higher or lower number of opening
doors and windows), then the relative area of that face can be Case 1: Considering negative coefficients on roof
increased or reduced to give a larger or smaller effective area for
the calculation of μ; see Part 1 of this Digest for more details of Areas where cpe is negative = 50.4 (leeward wall) + 57.2 × 2
this approach. Because the roof has both positive and negative (gables) + 36.5 × 2 (roof slopes) = 237.8 m2
pressure coefficients on some zones, both sets of pressure
coefficients must be considered when calculating the internal Total area = 50.4 × 2 (side walls) + 57.2 × 2 (gables) + 36.5 × 2
pressure in the building. (roof) = 288 m2
The relative areas of each wall and roof element of the house 237.8
are: µ= = 0.83 (From EN Figure 7.13 cpi = -0.32 (h/d = 1.0))
288
• Side walls: 8 m × 6.3 m = 50.4 m2
• Gable ends: 8 m × 6.3 m + (8 m × (8 – 6.3)/2) = 57.2 m2
Case 2: Considering positive coefficients on roof
• Roof (per slope): 8.4 m × 4.35 m = 36.5 m2 (true area of
each roof slope).
Areas where cpe is negative = 50.4 (leeward wall) + 57.2
× 2 (gables) + 36.5 (leeward roof slope) = 201.3 m2
Areas where cpe is negative = 50.4 × 2 (side walls) + 57.2 For overall loads on the house the scaling length b + h = 16 m
(leeward gable) + 0.0 (roof) = 158 m2 (8 m + 8 m). The effective height h – hdis is < 6 m for all directions
(Table 1) and cs = 0.856 (from NA Table NA.3 for Zone C).
Total area = 50.4 × 2 (side walls) + 57.2 × 2 (gables) + 36.5 × 2
(roof) = 288 m2 For buildings < 20 m in height (such as the house) and
for cladding, the dynamic factor cd may be taken as 1.0
158 (NA Clause NA.2.20 Note 4).
µ= = 0.55 (From EN Figure 7.13 cpi = +0.05 (h/d = 1.0))
288
DG 436-2 Part 2: Worked examples – wind loads on a two-storey house and 128 m tower 7
The EN does not give an equation for net wind force on Wall loads for SW wind
Licensed copy from CIS: unielon, University of East London, 27/11/2021, Uncontrolled Copy.
In this example the overall loads have been determined for For NW wind (ie wind perpendicular to the ridge), the positive
the two worst-case orthogonal directions of SW and NW. The windward roof slope coefficients and the negative leeward roof
overall load on the house can be determined by summing the slope coefficients should be considered. The effective pressure
external pressure coefficients given in Figures 4–6. However, coefficient acting on the roof can be obtained by summing the
significant benefit will be obtained from using the net pressure area-weighted load contribution acting over each roof zone, F
coefficients given in NA Clause NA.2.27 Note f. The net to I (EN Figure 7.8b).
pressure coefficients only apply to the walls. The EN does
not give net pressure coefficients for roofs so these will need The overall loads acting on the house for wind perpendicular to
to be determined using vectorial summation of the external the ridge are given by summing the wall and roof loads:
pressure coefficients given in Figure 6. When considering overall
wind loads determined from external pressure coefficients, 15.71 kN + 2.61 kN = 18.32 kN
a reduction factor accounting for the lack of correlation
between wind gusts on the windward and leeward faces may For roof pitches ≤ 25º it will be conservative to ignore the
be included. This factor does not have a symbol in the EN so contribution to overall load from the roof pressures and consider
is referred to as factor in these calculations. This factor varies the wall height to be equal to the ridge height. For this example,
from 0.85 for h/d ≤ 1.0 to 1.0 for h/d ≥ 5.0 (EN Clause EN 7.2.2 ignoring the roof loads and assuming the wall to be equal to the
Note 3). This factor can be applied when summing windward ridge height gives an overall load of 24.7 kN.
Table 3: Cladding wind loads on the gable wall for SW wind direction
Wind loads on gable wall (SW wind) Notes
cpi = -0.3 or +0.05 As calculated in previous section, use worst-case value of -0.3
we = 458.6 × 0.8 = 366.9 Pa External wind pressure, we = qp(ze) ⋅ cpe (EN Expression 5.1)
wi = 458.6 × -0.3 = -137.6 Pa Internal wind pressure, wi = qp(zi) ⋅ cpi (using cpi = -0.3) (EN Expression 5.2)
8 Part 2: Worked examples – wind loads on a two-storey house and 128 m tower DG 436-2
Table 4: Overall wind loads on the walls for SW wind (ie wind parallel to the ridge)
Wind loads on walls (SW wind) Notes
factor = 0.85 Lack of correlation factor for h/d = 1.0 (EN Expression 7.2.2 Note 3)
e = 8.0 m e = smaller of b or 2 h
cp,net,walls = 1.1 Net cp on walls for h/d = 1.1 (NA Clause NA.2.27 Note f)
we,net = 458.6 × 1.1 × 0.85 = 428.8 Pa Net wind pressure, we,net = qp(z) ⋅ cp,net ⋅ factor
F = 0.856 × 1.0 × 428.8 × 57.2 = 21.0 kN Overall wind force F = cscd ⋅ we,net ⋅ Aref
Table 5: Overall wind loads on the walls for NW wind (ie wind perpendicular to the ridge)
Wind loads on walls (NW wind) Notes
factor = 0.85 Lack of correlation factor for h/d ≤ 1.0 (EN Expression 7.2.2 Note 3)
e = 8.0 m e = smaller of b or 2 h
cp,net,walls = 1.05 Net cp on walls for h/d = 0.79 (NA Clause NA.2.27 Note f)
we,net = 404.8 × 1.05 × 0.85 = 361.3 Pa Net wind pressure, we,net = qp(z) ⋅ cp,net ⋅ factor
F = 0.863 × 1.0 × 361.3 × 50.4 = 15.71 kN Overall wind force F = cscd ⋅ we,net ⋅ Aref
DG 436-2 Part 2: Worked examples – wind loads on a two-storey house and 128 m tower 9
Table 6: Overall wind loads on the roof for NW wind (ie wind perpendicular to the ridge)
Wind loads on roof (NW wind) Notes
factor = 0.85 Lack of correlation factor for roof (EN Expression 7.2.2 Note 3)
e = 8.4 m e = smaller of b or 2 h
cp,zone F = 0.012 × 2 (two zone Fs) Example calculation of cp contribution from Zone J:
cp,zone G = 0.019 cpe for Zone J = -1.1, Area of Zone J = 8.4 m × 8.4/10 = 7.06 m2
cp,zone H = 0.128 Total roof area = 8.4 m × 4.35 × 2 = 73.08 m2 (true area of both slopes)
cp,zone I = -0.214 Weighted roof area = 7.06/73.08 = 0.097
cp,zone J = -0.106 Weighted coefficient = -1.1 × 0.097 = -0.106
cp,net,roof = 0.491 Net cp for roof (windward slope cp – leeward slope cp)
cs = 0.88 From NA Table NA.3 for h – hdis < 6 m, Zone C
Aref = 14.28 m2 Projected horizontal roof area for NW wind (1.7 × 8.4)
we,net = 498.1 × 0.491 × 0.85 = 207.9 Pa Net wind pressure, we,net = qp(z) ⋅ cp,net ⋅ factor
F = 0.88 × 1.0 × 207.9 × 14.28 = 2.61 kN Overall wind force F = cscd ⋅ we,net ⋅ Aref
podium
Assumptions for this example are:
• the site is in open country on the outskirts of Glasgow
• the site altitude A is 173 m
120 m
• the site is flat so orography is not significant
• the map wind speed vb,map (NA Figure NA.1) for the site is
25.3 m/s
• factors cseason and cprob = 1.0
• logarithmic decrement of damping δs = 0.05 for a steel
building (from EN Table F.2)
• the principal building axes are aligned SW to NE and SE to 8m
NW.
44 m 54 m
54 m
This example is a residential tower 120 m tall on an 8 m podium.
The tower storey height is 3 m and the podium storey height is 30 m
4 m. The dimensions of the building are shown in Figure 7, the
scaling parameters are given in Table 7 and the values of peak
20 m
44 m
e/2 = 15.0 m e/2 = 10.0 m The width of the zone of influence is based on
the height and breadth of the tower
-1.2 -1.2
NW elevation SW elevation
Direction (˚N) 0 30 60 90 120 150 180 210 240 270 300 330 360
Directional factor, cdir 0.78 0.73 0.73 0.74 0.73 0.80 0.85 0.93 1.00 0.99 0.91 0.82 0.78
Distance to shore 200 200 114 150 200 200 100 200 36 90 142 200 200
(km)
Basic wind velocity, 23.15 21.66 21.66 21.96 21.66 23.74 25.23 27.60 29.68 29.38 27.01 24.34 23.15
vb (m/s)
Basic velocity 328.5 287.7 287.7 295.6 287.7 345.5 390.1 466.9 539.9 529.1 447.1 363.0 328.5
pressure, qb (Pa)
Exposure factor, ce (z) 2.189 2.189 2.189 2.189 2.189 2.189 2.189 2.189 2.249 2.194 2.189 2.189 2.189
qp(z) (Pa) worst case 719.0 (Quadrant NE) 1214.1 (Quadrant SW)
by quadrant
853.8 (Quadrant SE) 1160.9 (Quadrant NW)
120 m tower (effective height ze = h = 128 m)
Basic wind velocity, 21.78 20.39 20.39 20.67 20.39 22.34 23.74 25.97 27.93 27.65 25.42 22.90 21.78
vb (m/s)
Basic velocity 290.9 254.8 254.8 261.8 254.8 306.0 345.5 413.5 478.1 468.6 396.0 321.5 290.9
pressure, qb (Pa)
Exposure factor, ce (z) 3.949 3.949 3.949 3.949 3.949 3.949 3.950 3.949 4.059 3.960 3.949 3.949 3.949
qp(z) (Pa) worst case 1149.3 (Quadrant NE) 1943.0 (Quadrant NW)
by quadrant
1365.7 (Quadrant SE) 1854.3 (Quadrant NW)
The pressure coefficients on the roof of the tower and podium of the tower completely envelopes the podium and the local
are shown in Figure 9. The presence of the tower will affect high negative pressure coefficients have been replaced with a
the wind pressures on the roof of the podium. In this case positive pressure coefficient of +0.8. It is recommended that
the tower should be treated like an inset storey according the design of the podium roof in windward edge zones F and G
to PD Clause 3.4. The roof pressure coefficients within the is assessed for the roof pressure coefficients determined from
zone of influence of the tower are taken as the adjacent wall both NA Table NA.5 and PD Clause 3.4.
pressure coefficients on the tower. In this example, for NW
wind there is a narrow strip on the windward edge of the Cladding pressures on the tower and podium walls and roofs
podium where the normal roof edge coefficients of -2.0 and are determined using EN Expressions 5.1 and 5.2 as shown in
-1.4 exist (NA Table NA.5). For SW wind the zone of influence Example 1. These calculations are not included for this example.
12 Part 2: Worked examples – wind loads on a two-storey house and 128 m tower DG 436-2
-1.4 -2.0
-1.2 -0.8 -0.5 -0.7
-2.0 -2.0/+0.2
-0.8 -0.7 -0.8
-1.4 +0.8 -0.7 -2.0/+0.2 -0.7
NW wind -2.0 -1.4 -2.0
-2.0
-1.2 -1.2
Licensed copy from CIS: unielon, University of East London, 27/11/2021, Uncontrolled Copy.
SW wind
Figure 9: Pressure coefficients on the roof of the podium and the tower (tower roof shaded)
Calculating overall wind force on the cd = 1.185 (from NA Figure NA.9 for: δs = 0.05,
h/b = 4.0, h = 120 m)
tower above the podium
For tall buildings with h/d > 5, the overall wind force (base shear cf = cf,0 ⋅ ψr ⋅ ψλ (EN Expression 7.9)
force) Fw is determined from EN Expression 5.3, which uses force
coefficients (cf): cf,0 = 2.38 (from EN Figure 7.23 for d/b = 0.67)
Fw = cscd ⋅ cf ⋅ qp(z) ⋅ Aref (EN Expression 5.3 – use when h/d > 5)
ψr = 1.0 (from EN Figure 7.24 for r/b = 0)
Ffr = cfr qp(z) ⋅ Aref (EN Expression 5.7 – use when h/d ≤ 5)
Base shear force for wind onto the narrow face of the
tower (h/d = 4) for NW wind (EN Expression 5.5)
Where: cfr is the friction coefficient from EN Clause 7.5
Fw = cscd ⋅ ∑ we ⋅ Aref
Afr is the area of external surface parallel to the wind as
surfaces
defined in EN Figure 7.22.
When using EN Expression 5.5 there are three calculation
The effects of friction can be disregarded when the total area of options, not all of which will be appropriate in every case:
all surfaces parallel to or at a small angle to the wind is ≤ 4 times
• sum the wind pressures on the windward and leeward faces
the total area of all external surfaces perpendicular to the wind.
of the building using cpe pressure coefficients
In practice this means that friction only needs to be considered
• use the cp,net pressure coefficients from NA Clause NA.2.27
when the plan aspect ratio of the building is greater than about
Note f
4:1 (EN Clause 5.3 Note 4).
• use division by parts for windward cpe pressure coefficients
from EN Clause 7.2.2.
In the example calculations given below, the overall wind loads
are determined for the podium and tower for the two principal
wind directions using the largest peak velocity pressure qp(z) for Each of these options is considered below. Note that friction
the SW and NW quadrants from Table 7. forces can be disregarded for this example because the sum of
surface areas parallel to the wind is < 4 times the sum of surface
The overall force on the tower should be determined using areas perpendicular to the wind (EN Clause 5.3 Note 4).
EN Expression 5.3 for wind onto the narrow face (h/d >5) and
EN Expressions 5.5 and 5.7 (h/d ≤5) for wind onto the wide face.
Option 1: Summing windward and leeward cpe pressure
coefficients
Base shear force for wind onto the wide face of the tower
(h/d = 6) for SW wind (EN Expression 5.3) Where available, cp,net pressure coefficients would normally be
used in the calculation of overall wind loads. However, for some
Fw = cscd ⋅ cf ⋅ qp(z) ⋅ Aref building forms, such as non-rectangular buildings or buildings
with pitched roofs, cp,net pressure coefficients are not given in the
Where: cs = 0.874 (from NA Table NA.3 for: z – hdis = 120 m, EN, NA or PD. In these cases, summing windward and leeward
b + h = 150 m, Zone = B) face pressures is the only option. This approach is included here
to demonstrate the procedure:
DG 436-2 Part 2: Worked examples – wind loads on a two-storey house and 128 m tower 13
Fw = cscd ⋅ ∑ we ⋅ Aref
surfaces 48 m
28 m
Option 2: Using cp,net pressure coefficients
b
This is the option that is recommended by BRE for rectangular
buildings because it requires the least calculation effort and 8m
generally gives the lowest wind loads:
cs, cd, qp(z), Aref and lack of correlation factors are the same as for
Option 1. Figure 10: Subdivision of the tower used for division-by-parts calculation
This represents a reduction of about 14% over the result Fw = 0.88 × 1.22 × 0.8 × 0.85 × 1854.3 × 400 = 541.5 kN
obtained by summing windward and leeward face pressures.
Windward face loads: Part 2 (h = 108 m)
Option 3: Using division by parts qp(z) = 1821.0, calt = 1.107, Aref = 400 m2, cpe = +0.8
Division by parts is only applicable to the windward face Fw = 0.88 × 1.22 × 0.8 × 0.85 × 1821 × 400 = 531.8 kN
pressure coefficients and only where h/b ≥ 1.0 (EN Figure 7.4).
In this example (Figure 10), the tower has been divided into Windward face loads: Part 3 (h = 88 m)
six equal parts in order to demonstrate the approach. Peak
velocity pressure qp (z) is determined for the top of each part. qp(z) = 1787.6, calt = 1.112, Aref = 400 m2, cpe = +0.8
The horizontal shear force at any level is due to the wind force
above that level. It might therefore be expected that the size Fw = 0.88 × 1.22 × 0.8 × 0.85 × 1787.6 × 400 = 522.0 kN
factor cs would be based on the size of the loaded area being
considered. However, in EN Expression 5.5 the structural factor Windward face loads: Part 4 (h = 68 m)
cscd is outside of the summation sign. This means that cs based
on the dimensions of the whole building must be used to qp(z) = 1724.5, calt = 1.118, Aref = 400 m2, cpe = +0.8
calculate the forces on each part of the building. The size factor
cs and dynamic factor cd are therefore the same as those given Fw = 0.88 × 1.22 × 0.8 × 0.85 × 1724.5 × 400 = 503.6 kN
in Option 1, ie 0.88 and 1.22 respectively. The values of the
altitude factor calt and the peak velocity pressure qp (z), which Windward face loads: Part 5 (h = 48 m)
depend on calt , are calculated at the top of each part being
considered. The full calculation of qp (z) and calt at each height is qp(z) = 1643.0, calt = 1.126, Aref = 400 m2, cpe = +0.8
not given here.
Fw = 0.88 × 1.22 × 0.8 × 0.85 × 1643 × 400 = 479.8 kN
The factor accounting for the lack of correlation between
windward and leeward faces (EN Clause 7.2.2 Note 3) should Windward face loads: Part 6 (bottom part, h = 28m)
be determined for each individual part considered. In this case
h/d = 20/30 = 0.67 and the factor = 0.85 for wind loads on the qp(z) = 1506.7, calt = 1.141, Aref = 400 m2, cpe = +0.8
windward face of each part considered. For the wind loads on
the leeward face the building is not divided by parts and the Fw = 0.88 × 1.22 × 0.8 × 0.85 × 1506.7 × 400 = 440.0 kN
factor = 0.963.
Total windward face load = 541.5 + 531.8 + 522.0 + 503.6 +
479.8 + 440.0 = 3.02 x 103 kN
14 Part 2: Worked examples – wind loads on a two-storey house and 128 m tower DG 436-2
Base shear force for wind onto the wide face of the
podium (h/d = 0.18) for SW wind (EN Expression 5.5)
cp,net = 0.8 (from NA Clause NA.2.27 Note f for h/d < 0.25)
Aref = 8 × 54 = 432 m2
Base shear force for wind onto the narrow face of the
podium (h/d = 0.15) for NW wind (EN Expression 5.5)
Aref = 8 × 44 = 352 m2
Online
700 Books, Reports
and Guides
Research, innovation, best
practice and case studies,
including best-sellers:
Spending hours searching
250 Digests
for construction information? Authoritative state-of-the-art
BRE Connect Online gives you instant and 150 Good Building and
unlimited access to over 1700 authoritative Repair Guides
BRE publications. Illustrated practical guides to
good building and repair work
View our demo to find out what BRE Connect
Online can do for you. And much more...
Wind loads on roof-mounted PV Wind microclimate around buildings Wind loads on unclad structures
and solar thermal systems
Acknowledgements
BRE Group (BRE) is a world-leading centre of built environment expertise, Any views expressed in this publication are not necessarily those of BRE or
research and training, and includes a third-party approvals organisation IHS. BRE and IHS have made every effort to ensure that the information and
offering certification of products and services to international markets. guidance presented here were accurate when published, but can take no
BRE, Garston, Watford WD25 9XX responsibility for the subsequent use of this information, nor for any errors
Tel: +44 (0) 333 321 8811 or omissions it may contain. To the extent permitted by law, BRE and IHS
Email: enquiries@bre.co.uk, www.bre.co.uk. shall not be liable for any loss, damage or expense incurred by reliance on the
information or any statement contained herein.
BRE is owned by BRE Trust, the largest UK charity dedicated specifically
to research and education in the built environment. BRE Trust uses the Digests are authoritative summaries of the state of the art on specific topics
profits made by BRE to fund new research and education programmes that in construction design and technology. They draw on BRE’s expertise in these
advance knowledge, innovation and communication for public benefit. areas and provide essential support for all involved in design, specification,
construction and maintenance.
IHS (NYSE: IHS) is the leading source of information, insight and analytics
in critical areas that shape today’s business landscape. Businesses and BRE publications are available from www.brebookshop.com or IHS BRE Press,
governments in more than 165 countries around the globe rely on the Willoughby Road, Bracknell, Berkshire RG12 8FB. Tel: +44 (0) 1344 328038,
comprehensive content, expert independent analysis and flexible delivery Fax: +44 (0) 1344 328005, Email: brepress@ihs.com.
methods of IHS to make high-impact decisions and develop strategies with
speed and confidence. IHS is the exclusive publisher of BRE publications. © IHS 2015. No part of this publication may be reproduced or transmitted, in
any form or by any means, electronic, mechanical, photocopying, recording
IHS Global Ltd is a private limited company registered in England and Wales or otherwise, or be stored in any retrieval system of any nature, without
(no. 00788737). Registered office: Willoughby Road, Bracknell, Berkshire prior written permission of IHS. Requests to copy any part of this publication
RG12 8FB. www.ihs.com. should be made to: The Publisher, IHS, Verulam Point, Station Way, St Albans,
Herts AL1 5HE. Tel: +44 (0) 1727 733810, Email: brepress@ihs.com.
Any third-party URLs are given for information and reference purposes
only and BRE and IHS do not control or warrant the accuracy, relevance, DG 436-2, August 2015
availability, timeliness or completeness of the information contained on
any third-party website. Inclusion of any third-party details or website
ISBN 978-1-84806-424-9 (Part 2)
is not intended to reflect their importance, nor is it intended to endorse ISBN 978-1-84806-426-3 (3-part set)
any views expressed, products or services offered, nor the companies or
organisations in question.