SWITCHGEAR / MCC SIZING CALCULATION FOR:

STANDARD TIER STANDARD TIER


RQD. TOTAL RQD. TOTAL
ITEM NO.OF MODULES MODULES ITEM NO.OF MODULES MODULES
DESCRIPTION ITEMS PER ITEM REQUIRED DESCRIPTION ITEMS PER ITEM REQUIRED
DOL <= 15kW 1 0 400/230v DISBOARD 5 0
DOL >15kW<=55kW 2 0 110v DISBOARD 2 0
DOL >55kW<=110kW 3 0 110 VOLT Tx 3 0
DOL >110kW<=250kW 5 0 PLC 0
S/D <= 15kW 2 0 SPARE MODULES 0
S/D >15kW<=55kW 4 0 0
S/D >55kW<=110kW 6 0 0
S/D >110kW<=250kW 10 0 0
VSD <= 15kW 5 0 0
VSD >15kW <= 75 kW 10 0 0
S-STR >15kW <= 75 kW 10 0 0
F/SW TO 63A 1 0 0
F/SW 100A 2 0 0
F/SW 100A-400A 3 0 0
F/SW 400A-800A 5 0 0
TOTAL (A)= 0 TOTAL (B)= 0

TOTAL NUMBER OF MODULES REQUIRED SO FAR (A+B)= 0


THE NUMBER OF MODULES PER TIER = 10
NUMBER OF COMPLETE TIERS REQUIRED FOR THESE MODULES = 0
WIDTH OF A TYPICAL STANDARD TIER (mm) =
(say 600mm for front and rear access; 800mm for front only access)

FULL HEIGHT PANELS FULL HEIGHT PANELS


RQD. RQD. TOTAL RQD. RQD. TOTAL
PANEL NO.OF PANEL RQD. PANEL NO.OF PANEL RQD.
DESCRIPTION PANELS WIDTH(mm) WIDTH(mm) DESCRIPTION PANELS WIDTH(mm) WIDTH(mm)
VSD >75kW<=125kW 800 0 COMMON CONTROLS 800 0
VSD >125kW 1000 0 PLC 1200 0
S-STR >75kW<=125kW 800 0 TELEMETRY 1200 0
S-STR >125kW 1000 0 INSTRUMENTATION 800 0
ACB 1000 0 0
METERING 1000 0 0
TOTAL(C)= 0 TOTAL(D)= 0

RESULTS:

THE ESTIMATED TOTAL OVERALL WIDTH OF THIS SWITCHGEAR / MCC = 0 mm


FOR AN AVERAGE HEAT LOSS PER TIER OR PANEL OF 300 watts
THE ESTIMATED TOTAL HEAT LOSS FOR THIS SWITCHGEAR / MCC = 0.00 kW

NOTES
1. THE MCC WILL BE FRONT AND REAR ACCESS / FRONT ACCESS ONLY / BACK TO BACK
2. LINEUP HEIGHT WILL BE 2200mm OR AS VENDOR
3. LINEUP DEPTH WILL BE 550mm (PLUS 250 FOR CABLE BOXES; 350 FOR S/D CABLE BOXES)
4. CABLE ENTRY WILL BE FROM ABOVE / BELOW
5. MINIMUM CLEARANCE OF 1000mm WILL BE REQUIRED IN FRONT
6. MINIMUM CLEARANCE OF 500mm WILL BE REQUIRED TO REAR
7. THE MCC WILL BE EXTENSIBLE AT BOTH ENDS